BASTONE (dual) fancoil Units

Similar documents
TECHNICAL MANUAL SOFFIO Ducted units

Chiller, Close control and Water terminals. Air Conditioning. Light Commercial, Commercial and Industrial

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL. Centrifugal fan coil units

Chilled Water FCU. Horizontal Fan Coil 50hz CFM. A Series.

CENTRIFUGAL FAN COIL UNIT VCE

MAJOR 2 NCH. Ductable units. High pressure and high capacity ductable units RANGE NCH Y NCH NCH I COADIS COMBI. Motor optional

Product Catalogue ARMONIA Providing indoor climate comfort

Ductable Modular Fan Coil Unit VPX. Technical Brochure TM VPX-W.2GB Date : May 2004 Supersedes : TM VPX-W.1GB/08.03

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ

Total cooling capacity kw Total heating capacity kw Features

LOW STATIC FAN COIL UNITS District Cooling Chilled Water Application

Chiller Close Control Water terminals SYSCASSETTE. Water cassette units

V33B High Efficiency 360 Cassette Indoor Models - 60HZ

42GW. Hydronic Cassette Fan Coil Units PRODUCT SELECTION DATA INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS EASY INSTALLATION

CMTE. Tangential Fan Coil Series with Electronic Controlled Motor

HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL

The World Leading Air-conditioning Company

HRH. High efficiency heat recovery units. from 300 to m³/h >70 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR

42NL & 42NH. Hydronic Ducted Fan Coil Units PRODUCT SELECTION DATA. Modular Horizontal ducted unit. Extremely quiet operation. Low Energy Consumption

HRS. Very high efficiency heat recovery units. from 300 to m³/h >90 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR

BRIZA 22 HYBRID HEATING & COOLING

Fan coil units. HFCE, HFXE, VFCE, VFXE series Sizes 03 to to 3400 m3/h UNT-PRC007-E4

DAIKIN INDUSTRIES, LTD. Ceiling Concealed Chilled Water Fan Coil Unit (50Hz/60Hz)

D M S 760 C01 A A 1 1

42NL & 42NH. Hydronic Ducted Fan Coil Units PRODUCT SELECTION DATA. Modular Horizontal ducted unit. Extremely quiet operation

Fan coil units MAJOR 2 CV/CH

PHCD-Series. Catalog

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

CODE MODEL 1RC9020 REC PRO 90 S RC9021 REC PRO 90 S RC9022 REC PRO 90 S RC9023 REC PRO 90 S

Carisma The Ultra Quiet Fan Coil

NEW. Wall controls. YFCN Fan Coil Units. Technical Guide - for internal distribution only

Cert. n 0545 Carisma CRC Fan Coil Unit The Ultra Quiet Fan Coil TECHNICAL GUIDE

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A

Engineering Data Manual. New : available with EC motor. High Static Pressure Ductable Fan Coil Unit. Models 07 to to 4650 m 3 /h

Residential comfort unit OperatiOn 2 models. new builds or existing properties. 5 operating modes COnfOrmity COmpOnents

High Static Pressure Duct Fan Coil Unit

Commercial Blower Coil Air Handlers

Fan coil unit NBS 100/150

Fan Coil Units. Technical Data. Flexi type unit ECDEN FWD-AT/AF

Technical Catalogue. Cassette Fan Coils Climmy Comfort 3

CLOSE CONTROL UNITS WITH CHILLED WATER COIL

Midea 50Hz AC Fan Coil Unit 2-Pipe Floor-standing Series Technical Service Manual

NEW Acoustic In-Line Fans (ACQ)

50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS

TECHNICAL GUIDE GENERAL HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS

FCVC Series VERTICAL FAN COILS

WATER SOURCE HEAT PUMPS

Fan coil units. Why choose Daikin fan coil units? 540 Products overview 542. Options & accessories 560. Round flow cassette 544 FWC-BT/BF 544

TECHNICAL MANUAL ESTRO BLDC ESTRO BLDC FAN COILS - BRUSHLESS TECHNOLOGY. 1.5 kw kw

Water terminals From 360 to 1598 m 3 /h. From 1.3 to 9.6 kw. SysQuare. Chilled water cassettes. From 1.1 to 14.0 kw

PRODUCT CATALOGUE CHILLED WATER CASSETTE CWC

High Performance Fan Coils FCHG Genesis Series Horizontal

KLIMA Active Chilled Beams

TECHNICAL DOCUMENTATION WOLF AIR HEATERS LH-EC / LH. 30m 3 /h

Package Air Conditioners

FCX TECHNICAL BOOKLET

NH 3. Evaporator. Ammonia Applications Tons MANP

M-SERIES MHP4 MODEL NUMBER GUIDE 3 M HP F P 1 ELECTRIC HEAT PUMP PACKAGED UNITS REVISION CODE

Guide Specifications. General. Casing. Coil/Drain pan. Fan/Motor

Highline 260i EC Waterside Fan Coil Unit

42CET/ 42CED Series Chilled Water Fan Coil Unit Furred-in Ceiling Model 300 to 1400 cfm Electric heater option

SYSCOIL 2. Range of fan coil units. Chillers & Heat Pumps Water terminals Roof tops Close control Water source heat pumps Direct expansion

CFFWA Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 12,000-60,000 BTUH

GENERAL ELECTRIC CONCEALED CHILLED WATER FAN COIL UNITS

NEW Slimpak EC Box Fan (SLPT EC)

Fan Coil Units. Technical Data ECDEN FWL-DT/DF

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

Contents. Carrier China

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

Ceiling Concealed Chilled Water Fan Coil Unit

INTRODUCTION CP 06 F C - A 4 L - F GENERAL DESCRIPTION DESIGN PARAMETER DUCTED CONCEALED WITH PLENUM. F - c/w Filter

PA95 12 SEER FEATURES 2 THRU 4 TON SINGLE PACKAGE

Fan Coil Units. Technical Data. Conceiled ceiling unit ECDEN FWB-BT

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

Model METRIC SHAFT WT (LBS) mm mm mm mm mm mm mm 572

Address: VTS Clima L.L.C.

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

Modular Air Handling. Up to 3,500 Litres / sec. Low profile & Plant room application. Draft. Version. Second Edition A-. AirDesign 2015 AirDesign 2016

YFCN Fan Coil Unit centrifugal fan 2 & 4 pipe system A complete range from 1.0 kw to 7.6 kw

ULTRA LOW ENERGY. VHR Void Series W/I/s TOTAL SFP Typical. Made in the UK. VHR Void Mounted Heat Recovery Units VHR PERFORMANCE OVERVIEW:

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

SECTION AIR TERMINAL UNITS

1 AIR HANDLING UNIT TYPE AIR ACCESS 75

TECHNICAL GUIDE R410a SPLIT SYSTEM 1.5 to 5.0 NOMINAL TONS

CHILLED WATER DUCTED FAN COIL

MH1WC4W-08-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille.

PGK Rectangular duct coolers for cooled water

something new in the air Technical Bulletin

technical data air conditioning systems Round Flow Cassette FXFQ-P9VEB

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75.

42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application

Cassette 4 Ways FCU DC Service manual

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology

Product Data. FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 SLIM LINE DUCTED FAN COIL WITH PLENUM ON/OFF DISPLAY TEMP

BUILDING EFFICIENCY Energy Efficient Variable Speed EC Motor Fan Coil Unit Solutions Model YECFC

RBV Sales Guide FAN COIL UNITS FLOOR-MOUNTED, VERTICAL

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

Transcription:

BASTONE (dual) fancoil Units Technical information manual Western Airconditioning B.V. Tel. +31 (0) 33 247 78 00 www.western.nl

1-INTRODUCTION..3 2- WORKING CONDITION LIMITS...3 3- COANDA EFFECT 3 4- KEY READING CODES.4 5-TECHNICAL DETAILS.5 6-TECHNICAL DATA (AC motors)..7 6.1-Cassette with 3 rows coil...7 7-TECHNICAL DATA(eC motors) 8 7.1-Cassette with 3 rows coil...8 8- OPTIONAL COIL TECNICAL DATA(AC motors) 9 8.1- Cassette with 1 or 2 rows coil...9 9-TECHNICAL DATA OPTIONAL COILS (EC motor)..10 9.1- Cassette with1 or 2 rows coil...10 10-DIMENSIONAL & WEIGHT.. 11 11-ACCESSORIES 12 11.1- Valves (V) and auxiliary tray (ADPB)...12 11.2- Hose connecting valves (Flex2 and Flex4)...155 11.3- Condensate drain pump Auxiliary (PSCC-BI)...15 11.4- Speed motor control board..166 11.5- Flange for air delivery duct (FLMA).199 11.6- Flange for external air intake (FLAE-FLAE2)...20 12-Electrical wiring diagrams..221 12.1- Wiring diagram cassette with AC motor...221 12.2-Wiring diagram cassette with EC motor 233 Western Airconditioning B.V. reserves the right to alter specifications 2

1-INTRODUCTION The new Water Cassette Series units Bastone are designed for air conditioning in residential and commercial plants. The installation is indoor and not exposed to ice or extreme temperatures, dustfree environment and not explosive materials. The manufacturer is not responsible in case of incorrect use. The series Bastone is proposed with traditional AC motors with three speeds and which EC motors with low consumption. The table below shows the electric power saving that can be achieved with EC motors (at constant working point of the machine). 2- WORKING CONDITION LIMITS Electrical power supply 220 240V / 50Hz Inletcoil water temperature 5 70 C Return air temperature 10 50 C RH air intake 15 70% It is advisable to let work the Bastone Cassette at the above mentioned extremes limits of operation ONLY for short periods, because the operation for long periods can reduce normal components. 3- COANDA EFFECT New cassette Series Bastone has been developed to ensure a high comfort. In fact, the particular shape of the panel as per the COANDA effect, avoids the annoying cold drafts (since ever the problem of fan-coil cassettes). The COANDA effect is the tendency of a fluid jet to follow the contour of a nearby surface. So the air flow follows the ceiling, then fells nearly at the wall. Since the air speed at this point is very low, this does not create discomfort to people. Traditional Cassette Cassette with Coanda effect Western Airconditioning B.V. reserves the right to alter specifications 3

In case where the ceiling is higher than 3m, accordingly there is the need to channel down the air flow, Aertesi provides an accessory panel with adjustable flaps. So you can set manually, for each of the four turns, the orientation of the flow: horizontal (with Coanda effect), or in vertical position. Flaps on horizontal position (Coanda) Flaps on vertical position 4- KEY READING CODES The standard version is with 3-rows coil (for versions 2 pipes) or 1 + 2 ranks (for versions 4 pipes), with fixed blades in COANDA position. All other versions are optional. Western Airconditioning B.V. reserves the right to alter specifications 4

5-TECHNICAL DETAILS STRUCTURE: made on galvanized steel sheet, thickness 1.00mm. The robust design prevents the vibration and it includes mounting brackets to the ceiling. FRONTAL PANEL: painted plate thickness 0.8mm. The conformation of the baffles ensures a Coanda Effect to the air flow output. As an accessory, you can have the adjustable deflectors to have the Coanda effect or vertical airflow (or intermediate positions). The fresh design of the panel fits perfectly into any environment and type of ceiling. ACCESSIBILITY : the filter can be removed without any tools. The accessibility to internal components (fan and condensate pump) is guaranteed by removing the front panel. Water connections, valves and electrical panel are on the same side and thus you need only one inspection hatch in the ceiling. FILTER: Class G1 (EN779), 6 mm thickness, made in polypropylene mesh. FAN GROUP: The fan is made of reinforced plastic material (nylon PA6-25GF); it is backward curved blades, directly coupled to the motor. The motor and fans are balanced after assembly to ensure, vibrations absence. Motor is mounted on ball bearings without any maintenance. The AC motor has three speed, degree of protection IP44, insulation class "B". Thermal protection incorporated. The EC motor is controlled 0-10V, IP54 protection, insulation class "B", noise emissions according to EN 61000-6-3 (civil environment), thermal motor protection and electronics, protection locked rotor. COIL: made with copper pipe diameter 3/8 "and corrugated aluminum fins with high efficiency, with manual air vent valve at the top. Nominal pressure PN10. Western Airconditioning B.V. reserves the right to alter specifications 5

WATER TRAP: blower housing made of expanded polystyrene (EPP) with condensation molded plastic tray, which ensures no water leakage even after a long use. The shape of the pan facilitates the outflow and ensures minimum water stagnation. INSULATION: cassette body insulated with cross-linked polyethylene foam 10 mm thick, class B-BLs2d0 s1d0 according to EN13501-1. Front panel insulated with polyethylene thickness 3mm. ELECTRICAL BOARD: made of galvanized steel plate and positioned on the same side of water connections. CONDENSATE DRAIN PUMP: centrifugal type, equipped with a double level float (on-off pump and alarm) and check valve (to avoid the return of odors from the plughole and reduce the noise power). The maximum head of the pump is 650mm, measured from the edge of the panel. Western Airconditioning B.V. reserves the right to alter specifications 6

6-TECHNICAL DATA (AC motors) 6.1-Cassette with 3 rows coil 2 PIPES 4 PIPES 133 163 135 165 Speed min med max min med max min med max min med max Airflow mc/h 560 800 1140 860 1260 1470 560 800 1140 860 1260 1470 COOLING Air 27 C b.s., 19 C b.u. Input water temperature 7 C, output water temperature 12 C Total kw 4,11 5,51 7,46 5,88 8,10 9,16 3,52 4,75 6,23 5,00 6,69 7,47 capacity Sens. kw 2,94 4,00 5,30 4,25 5,72 6,44 2,57 3,37 4,36 3,58 4,68 5,20 capacity Water flow l/h 706 946 1279 1008 1389 1571 603 815 1069 859 1148 1281 Δp water kpa 3,3 5,6 9,8 6,3 11,3 14,1 3,8 6,4 10,5 7,0 12,0 14,6 HEATING Air 20 C inlet water temperature 50 C,same for cooling flow Capacity kw 4,79 6,50 8,71 6,91 9,44 10,66 - - - - - - Water flow l/h 706 946 1279 1008 1389 1571 - - - - - - Δp water kpa 3,1 5,3 9,2 6,0 10,7 13,4 - - - - - - HEATING Air 20 C - inlet water temperature 70 C, output water temperature 60 C Capacity kw - - - - - - 5,25 6,69 8,47 7,03 8,96 9,90 Water flow l/h - - - - - - 476 606 767 637 811 896 Δp wate kpa - - - - - - 3,5 5,5 8,3 6,0 9,2 11,2 ELECTRIC MOTOR ABSORTION Consumption W 60 76 100 108 144 174 60 76 100 108 144 174 Max absorption A 0,46 0,80 0,46 0,80 SOUND DATA Sound power db(a) 39 46 56 53 63 66 39 46 56 53 63 66 Sound pressure db(a) 30 37 57 44 54 57 30 37 57 44 54 57 Western Airconditioning B.V. reserves the right to alter specifications 7

7-TECHNICAL DATA(EC motors) 7.1-Cassette with 3 rows coil 2 PIPES 4 PIPES 133 163 135 165 Speed 4V 7V 10V 4V 7V 10V 4V 7V 10V 4V 7V 10V Airflow mc/h 410 760 1120 570 1050 1520 410 760 1120 570 1050 1520 COOLING Air 27 C d.b., 19 C w.b.. inlet water temperature 7 C, output water temperature 12 C Total capacity kw 3,11 5,28 7,35 4,17 6,96 9,42 2,61 4,56 6,13 3,58 5,83 7,66 Sens.capacity kw 2,19 3,85 5,22 2,99 4,95 6,60 1,98 3,25 4,29 2,61 4,09 5,35 Water flow l/h 534 905 1260 716 1195 1616 448 783 1052 614 1001 1315 Δp water kpa 2,1 5,3 9,4 3,5 8,6 14,8 2,2 6,0 10,1 3,9 9,3 15,3 HEATING Air 20 C inlet water temperature 50 C, same for cooling flow Capacity kw 3,60 6,24 8,57 4,87 8,12 10,95 - - - - - - Water flow l/h 534 905 1260 716 1195 1616 - - - - - - Δp water kpa 1,8 4,9 9,0 3,3 8,2 14,2 - - - - - - HEATING Air 20 C - inlet water temperature 70 C, output water temperature 60 C Capacity kw - - - - - - 4,16 6,47 8,29 5,32 7,96 10,16 Water flow l/h - - - - - - 377 586 751 481 721 919 Δp water kpa - - - - - - 2,2 5,1 8,1 3,5 7,4 11,7 ELECTRIC MOTOR ABSORTION Consumption W 6 18 42 10 36 97 6 18 42 10 36 97 Max absorption A 0,34 0,76 0,34 0,76 DATI SONORI Sound power db(a) 34 48 59 41 57 66 34 48 59 41 57 66 Sound pressure db(a) 25 39 50 32 48 57 25 39 50 32 48 57 ENERGY SAVING CLASS FCEER A A A A FCCOP A A A A Western Airconditioning B.V. reserves the right to alter specifications 8

8- OPTIONAL COIL TECNICAL DATA(AC motors) 8.1- Cassette with 1 or 2 rows coil Speed 2 PIPES 4 PIPES 132 162 134 164 min med max min med max min med max min med max Airflow mc/h 560 800 1140 860 1260 1470 560 800 1140 860 1260 1470 COOLING Air 27 C d.b., 19 C w.b.. inlet water temperature 7 C, output water temperature 12 C Total capacity kw 3,37 4,53 5,94 4,80 6,39 7,12 2,28 2,94 3,73 3,12 3,99 4,40 Sens.capacity kw 2,49 3,26 4,20 3,44 4,52 5,02 1,67 2,14 2,67 2,22 2,86 3,11 Water flow l/h 578 778 1019 824 1096 1221 391 504 640 535 684 754 Δp water kpa 3,2 5,5 9,0 6,1 10,2 12,4 2,9 4,5 6,9 4,9 7,8 9,3 HEATING Air 20 C inlet water temperature 50 C, same for cooling flow Capacity kw 4,12 5,45 7,10 5,76 7,63 8,53 - - - - - - Water flow l/h 578 778 1019 824 1096 1221 - - - - - - Δp water kpa 3,0 5,2 8,6 5,9 9,8 12,0 - - - - - - HEATING Air 20 C - inlet water temperature 70 C, output water temperature 60 C Capacity kw - - - - - - 5,25 6,69 8,47 7,03 8,96 9,90 Water flow l/h - - - - - - 476 606 767 637 811 896 Δp water kpa - - - - - - 3,5 5,5 8,3 6,0 9,2 11,2 ELECTRIC MOTOR ABSORTION Consumption W 60 76 100 108 144 174 60 76 100 108 144 174 Max absorption A 0,46 0,80 0,46 0,80 SOUND DATA Sound power db(a) 39 46 56 53 63 66 39 46 56 53 63 66 Sound pressure db(a) 30 37 57 44 54 57 30 37 57 44 54 57 Western Airconditioning B.V. reserves the right to alter specifications 9

9-TECHNICAL DATA OPTIONAL COILS (EC motor) 9.1- Cassette with1 or 2 rows coil 2 PIPES 4 PIPES 132 162 134 164 Speed 4V 7V 10V 4V 7V 10V 4V 7V 10V 4V 7V 10V Airflow mc/h 410 760 1120 570 1050 1520 410 760 1120 570 1050 1520 COOLING Air 27 C d.b., 19 C w.b.. inlet water temperature 7 C, output water temperature 12 C Total capacity kw 2,46 4,38 5,85 3,43 5,57 7,30 1,75 2,86 3,68 2,32 3,53 4,51 Sens.capacity kw 1,92 3,13 4,14 2,52 3,96 5,12 1,34 2,07 2,64 1,69 2,50 3,19 Water flow l/h 423 751 1004 588 956 1253 299 491 632 398 606 774 Δp water kpa 1,8 5,2 8,7 3,3 7,9 13,0 1,7 4,3 6,8 3,0 6,2 9,8 HEATING Air 20 C inlet water temperature 50 C, same for cooling flow Capacity kw 3,16 5,25 7,00 4,18 6,65 8,73 - - - - - - Water flow l/h 423 751 1004 588 956 1253 - - - - - - Δp water kpa 1,7 4,8 8,3 3,1 7,5 12,5 - - - - - - HEATING Air 20 C - inlet water temperature 70 C, output water temperature 60 C Capacity kw - - - - - - 4,16 6,47 8,29 5,32 7,96 10,16 Water flow l/h - - - - - - 377 586 751 481 721 919 Δp water kpa - - - - - - 2,2 5,1 8,1 3,5 7,4 11,7 ELECTRIC MOTOR ABSORTION Consumption W 6 18 42 10 36 97 6 18 42 10 36 97 Max absorption A 0,34 0,76 0,34 0,76 SOUND DATA Sound power db(a) 34 48 59 41 57 66 34 48 59 41 57 66 Sound pressure db(a) 25 39 50 32 48 57 25 39 50 32 48 57 ENERGY SAVING CLASS FCEER A A A B FCCOP A B A A Western Airconditioning B.V. reserves the right to alter specifications 10

10-DIMENSIONAL & DRAWINGS 1 Batteria principale IN 1/2" 2 Batteria principale OUT 1/2" 3 Batteria ausiliaria IN 1/2" 4 Batteria ausiliaria OUT 1/2" 5 Scarico condensa d.12 132/162 133/163 134/164 135/165 Unit gross Weight kg 56 60 56 60 Internal volume main coil litri 2,6 4,0 2,8 2,8 Internal volume auxiliary coil litri - - 1,2 1,2 Western Airconditioning B.V. reserves the right to alter specifications 11

11-ACCESSORIES Accessories available are: HYDRAULIC ACCESSORIES A/K/C V22 V22 2-way valve ON-OFF 230V A/K V42 V42 2-way valve ON-OFF for 4 pipe A/K V23 V23 3-way valve ON-OFF 230V A/K V43 V43 3-way valve ON-OFF 230V for 4 pipe A/K V22M V22M Valve 2-way modulating 0-10V A/K V42M V42M Valve 2-way modulating 0-10V for 4 pipe A/K V23M V23M valve 3 way modulating 0-10V A/K V43M V43M valve 3 way modulating 0-10V for 4 pipe A/K ADPB ADPB Water trap auxiliary (supplied as standard) K FLEX2 Hoses for parallel connection valves (2 pipes) K FLEX4 Hoses for parallel connection valves (4 pipes) K PSCC-BI PSCC-BI Auxiliary Condensate drain pump A ELETTRICAL ACCESSORIES TR24 Transformer 230Vac-24VAC, 20VA for modulating valve A SC3 3-speed motor control board (for EC motor) A AERAULIC ACCESSORIES FLMA Flange for discharge air duct B FLAE Flange for fresh air intake B A = accessory supplied mounted on the base; K = accessory kit supplied unassembled; B = accessory supplied assembled, but not mounted on the base 11.1- Valves (V) and auxiliary tray (ADPB) We recommend the use of motorized valves, to prevent the formation of condensation on the surface of the unit when the fan is stopped. Valves can be supplied to the unit assembled or in kit (disassembled parts). All codes kits include two valves, one for each battery in double cassette. The drain pan is supplied as standard with the cassette, without extra-price (ADPB) Western Airconditioning B.V. reserves the right to alter specifications 12

The cassette have two double 1200x600 kit valves, one for the right battery and one for the left battery. Both kits valves are connected in parallel, the aim is a kit consisting of hoses and TEE brass (see paragraph on accessory Flex2 - Flex4). Heating/cooling valve (2 pipes) Valve cooling (4 pipes) Hot valve (only 4 pipes) Heating/cooling valve (2 pipes) Valve cooling (4 pipes) Hot valve (only 4 pipes) Auxiliary drain pan OUT IN OUT IN 2 pipes (hot/cold) 2 pipes (not present) 4 pipes (cold) 4 pipes (hot) Valves group and auxiliary tray (cassette double 1200x600) Western Airconditioning B.V. reserves the right to alter specifications 13

VALVES FOR MAIN COILS --- 132-133-134-135-162-163- 164-165 VALVES FOR AUXILIARY COILS 134-135-164-165 --- GENERAL FEATURES Size connections 1/2" 3/4" Kv (valvola 2 vie) 1,7 2,5 Kv (valvola 3 vie, via diritta) 1,7 2,5 Kv (valvola 3 vie, by-pass) 1,2 1,6 Max differential pressure 2,0bar 1,0bar Nominal pressure Nominal pressure 16bar 4-110 C ON-OFF ACTUATOR Power supply 230V-50Hz (24V-50Hz on request) Power consumption 2,5W Running time Feature (valve + actuator) N.C. Protection 180s N.C. (usually closed) IP44 MODULAT ACTUATOR Electrical supply 24V-50Hz Power consumption 1,5W Travel time 8S Control signal 0-10V Impedance control signal Protection 100k IP43 Western Airconditioning B.V. reserves the right to alter specifications 14

11.2- Hose connecting valves (Flex2 and Flex4) To facilitate the parallel connection of the valves, described in the previous paragraph, you can use the accessory Flex2 (for 2-pipe systems) and Flex4 (for 4-pipe systems). The kit consists of hoses with braided stainless steel (with 3/4 "for the valve) and brass TEE to connect the pipes from 3/4". You can also directly connect the hoses to the battery, inserting a reduced nipple 1/2 "-3/4" (nipple not supplied). TEE OTTONE FLEX INOX Accessory for flexible double cassette 1200x600 11.3- Condensate drain pump Auxiliary (PSCC-BI) The condensate drain pump voltage is supplied assembled to the side of the box, at the side of the exhaust pipe. Then must provide for the possibility of inspection also on this side. Maximum water flow Maximum discharge height Sound pressure 1m Supply Micro switch alarm Thermal Protection Protection 20 l/h 10m (4l/h) 28dB(A) 230V 50/60Hz NC 8 resistivi 250V 90 C (riarmo automatico) IP54 Western Airconditioning B.V. reserves the right to alter specifications 15

14 12 10 MAX HEIGHT 8 6 4 2 0 0 4 8 12 16 20 11.4- Speed motor control board Accessory for flexible double cassette 1200x600 The 3-speed motor tab control allows you to control the EC motor with a traditional thermostat 3-speed or with a thermostat with 0-10V signal. With this accessory, it is also possible to control more than one unit with a single thermostat (not addressable master-slave). For each double cassette, you need two cards SC3 (to be considered as a slave of the other). Western Airconditioning B.V. reserves the right to alter specifications 16

CONTROL FROM EXTERNAL THERMOSTAT VH Contact on-off valve heating (4 tubes) VC Contact on-off valve cooling (2-4 tubes) MIN Minimum fan speed MED Minimum fan speed MAX Maximum speed fan GND Reference signal 0-10V 0-10V 0-10V signal for motor control ELECTRICAL CONNECTIONS FOR 3 SPEEDSCONTROL : you must close the jumpers J3 and J4; jumpers J1, J2, J5, J6 are reserved to factory settings and should not be changed. Model J1 J2 J3 J4 J5 J6 7x-13x opened closed closed closed closed closed 9x-16x closed opened closed closed closed closed Western Airconditioning B.V. reserves the right to alter specifications 17

ELECTRICAL CONNECTIONS FOR CONTROL SIGNAL 0-10V: you must open the jumpers J3 and J4; jumpers J1, J2, J5, J6 are reserved to factory settings and should not be changed. Model J1 J2 J3 J4 J5 J6 7x-13x closed closed opened opened opened opened 9x-16x closed closed opened opened closed opened Western Airconditioning B.V. reserves the right to alter specifications 18

11.5- Flange for air delivery duct (FLMA) You can connect up to 3 throws ducted through D.160 collars. The available prevalence is a function of the number of collars connected and the air flow rate. Collars positions are represented in the figure below. Western Airconditioning B.V. reserves the right to alter specifications 19

11.6- Flange for external air intake (FLAE-FLAE2) It is possible to connect an external air intake via a D.100 collar. The maximum flow of outside air is 100MC/h. The outside air has to be treated, filtered and must not be at a low temperature. The flange for fresh air intake has FLAE code or FLAE2 code. These have different installation points on the unit, as in the drawing below. Western Airconditioning B.V. reserves the right to alter specifications 20

12-Electrical wiring diagrams 12.1- Wiring diagram cassette with AC motor Western Airconditioning B.V. reserves the right to alter specifications 21

Western Airconditioning B.V. reserves the right to alter specifications 22

12.2-Wiring diagram cassette with EC motor Western Airconditioning B.V. reserves the right to alter specifications 23

CONTROL FROM EXTERNAL THERMOSTAT VH Contact on-off valve heating (4 tubes) VC Contact on-off valve cooling (2-4 tubes) MIN Minimum fan speed MED Minimum fan speed MAX Maximum speed fan GND Reference signal 0-10V 0-10V 0-10V signal for motor control Western Airconditioning B.V. reserves the right to alter specifications 24

NOTES: Western Airconditioning B.V. reserves the right to alter specifications 25

Western Airconditioning B.V. reserves the right to alter specifications 26

Bastone (dual) 29062015 Western Airconditioning B.V. De Wel 10, 3871 MV HOEVELAKEN Tel. +31 (0) 33 247 78 00 www.western.nl Western Airconditioning B.V. reserves the right to alter specifications 27