10V. the rack of the oil pump must be on the

Similar documents
ENGINE GOVERNING SYSTEMS

ESD5550 / 5570 Series Speed Control Units

ESD5500E Series Speed Control Unit

ESD-5550/5570 Speed Control Unit. Manual

ESD-5500E Series - Speed Control Unit

ESD-5550/5570 Series - Speed Control Unit

ESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)

EG3002. Electronic Engine Governor Controller User Manual

EDG5500 Electronic Digital Governor With Quikset Display

EG1069X. Generator Electronic Governor Controller Operation Manual

EDG6000 Electronic Digital Governor

ESC2301. Universal Electronic Governor Controller Operation Manual

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

IGA225 Integrated Governor & Actuator

EG3000. Generator Electronic Governor Controller Operation Manual

KT230 Series Caterpillar 3406 Governor System Installation Kit

KT145 Series John Deere 6076 with Nippondenso Inj. Pump

KT101 Series Governor System Installation Kit Cummins 4B(T) / 6B(T) With CAV/DPA Pump

with discrete output (Overspeed) with auxiliary input (Synchronizer and Load Sharing)

EEG6500 Enhanced Electronic Governor

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

PRODUCT SERIES: DPG-2100

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

Product Manual (Revision D, 5/2015) Original Instructions. 2301A Speed Control. Installation and Operation Manual

DYNA Power Control Manual For Plus 1, Plus 2, Plus 4 and Plus 6 Ft. Lb. Systems

PED 5000 ELECTRIC ACTUATOR

ATB Series - Integral Throttle Body Actuators

Load Sharing Module. Analog Output Installation, Operation, and Calibration Manual. Manual 26011

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

Product Manual (Revision B) Original Instructions. EPG Electrically Powered Governor Models 501 and Installation and Operation Manual

225 SERIES ELECTRIC ACTUATOR

MODEL 422 Submersible Pump Controller

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

EEG6550 Enhanced Electronic Governor

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual

Product Manual (Revision C) Original Instructions. EPG (Electric Powered Governor) with Position Feedback. Installation and Operation Manual

700 Series Troubleshooting Guide for C711/C712 Alternators

Reverse power relay and protection assemblies

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

INDEX Section Page Number Remarks

PEAKTRONICS DMC-101 ADDITIONAL FEATURES. DC Motor Controller, 5A DMC-101

Product Manual (Revision C) Original Instructions. Load Sharing Module. Analog Output Installation and Operation Manual

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (0-10VDC Input Version)

UG-5.7, UG-8, UG10 Governor

KL-8070D. Fully Digital Stepping Driver. Table of Contents 1. Introduction, Features and Applications...1 Introduction...1 Features...

4024 EPG (Electrically Powered Governor) Product Manual (Revision B, 3/2008) Original Instructions

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

Installation and Operation Manual. Load Sharing Module Vdc Output Manual (Revision B)

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

Continental Hydraulics Installation Manual CEM-AA-A

User s Manual. For DM860T. Fully Digital Stepper Drive. Version 1.0 Designed by StepperOnline All Rights Reserved

500 Series Troubleshooting Guide for C520 Alternators

Power Controller. (see note 1) 10 sec

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity.

Error codes Diagnostic plug Read-out Reset Signal Error codes

Series 20 Installation Instructions

REMOTE MOUNT SOLENOID DRIVER (0-5 VDC/0-20 ma/10k Potentiometer Input)

GENSET CONTROL MODULE A121A / A241A

LIPPERTCOMPONENTS, INC.

C.E. Niehoff & Co. N1601, N1602, N1603, and N1604 Alternator Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Series 44 Installation Instructions

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

Troubleshooting Guide

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

User s Manual. For DM542T. Full Digital Stepper Drive

INSTALLATION INSTRUCTIONS

5001TCP SPEED CONTROLLER

EPG Electrically Powered Governor. Installation and Troubleshooting Manual. Models 1712/1724 and 512/524 without Position Feedback

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

Operating Manual For Stepper Driver

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

Boston Gear Ratiotrol

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

PRODUCT INFORMATION BULLETIN

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

PROCESS ELECTRONICS CORPORATION

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

th Street, Surrey, B.C. Canada V3W 0A6 Telephone Fax July 2012

5001TCP SPEED CONTROLLER

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

DRB-1 Series Instruction Manual

OPERATOR TROUBLESHOOTING GUIDE

EVS RP6020. Instruction Manual

DKG-114 MANUAL AND REMOTE START UNIT

MondoStep 7.8. High Performance Microstepping Driver. User s Manual. Version PROBOTIX All Rights Reserved

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Functional Symbols and Application Notes

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates

DRV-1. Step Motor Drive. User Manual Mentor Avenue Cincinnati, Ohio Tel (513)

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

User Manual of 2MA2282

Some admonitions you must know before using DS600

Transcription:

P.E.D 20.. ESG2002 series ELECTRONIC GOVERNOR INSTRUCTION A1000C-W ELECTROMAGNETIC ACTUATOR Before inst al l el ectromag neti c, p lea se inspect that the rack of the oil pump shouldn' t be stuck in any case. Aft er insta lla tion, pl ease inspect that the rack of the oil pump must be on the stop-oil position. E LE CT ROMA GNET IC ACTUAT OR Dr awing No. Mfg. No. Model Mfg. Date! B A! CAUTION The power must be supplied by the battery and can't be supplied by the generator. Be careful the polarity of the power, when installing or servicing refer to product publication. STARTING FUEL SPEED RAMPING STABILITY DROOP IDLE GAIN C2002 SPEED CONTROLLER IDLE SPEED ACTUATOR PICK-UP BATTERY - + 1 2 3 4 5 6 7 8 DROOP AUX 10V 9 10 11 12 13 14

CATALOGUE 1 Principle 1 2 System Composing 2 2.1 Speed Control Unit 2 2.2 Electromagnetic Actuator 4 2.3 Speed Pick-up 9 3 Installing and Debugging 10 3.1 Installing Of The Electronic Governor 10 3.2 Connection Diagram 10 3.3 Adjustments before Starting Engine 11 3.4 Adjustment of the Controller after Starting 11 3.5 Speed Droop Operation 12 3.6 Accessory Input 12 3.7 Accessory Output 12 4 System Troubleshooting 13 4.1 Check-up the Fault 13 4.2 Insufficient Magnetic Speed Sensor Signal 14 4.3 Electromagnetic Compatibility (EMC) 14

1 The Principle Of The Electronic Governor System Electronic governor, with its simple structure, high reliability, convenient operation, easy function extension and high cost performance, applies to all kinds of diesel generating sets, vehicles and marine diesel engines. Its normal type is all-electronic single pulse speed and close loop position structure, provided with functions of non-corresponding or corresponding control, speed and rated speed during running maximum fuel supply control, emergency stop and etc. It is also capable of adding other control functions according to the customer s particular requirements. parameter adjusting setting protect or restrict speed setting calculation drive out speed pick up real speed drive of the generator fuel load Figure 1.1 Electronic governor system 1

2 The Structure Of The Electronic Governor System 2.1 Speed Control Unit 2.1.1 The basic electronic characteristics SUPPLY VOLTAGE : 12V or 24V DC SUPPLLY CONSUMPTION : < 0.1A (static state) SPEED FLUCTUATION RATIO : ±0.25% STEADY STATE SPEED DROOP : 0~5% AMBIENT TEMP. : -40 C ~ +85 C RELATIVE HUMIDITY : <95% 2.1.2 The outline and installing size of the C2002 speed control unit The speed control unit is installed on the control box or fixed other peripheral equipment in the engine. It should be installed in the place of air drying and temperature suitable. If it be installed in the place of more water and humidity, the speed control unit should be mounted vertically. Its outline and installing size refers to figure 2.1.! CAUTION The power must be supplied by the battery and can't be supplied by the generator. Be careful the polarity of the power, when installing or servicing refer to product publication. STARTING FUEL SPEED RAMPING STABILITY GAIN C2002 SPEED CONTROLLER IDLE DROOP IDLE SPEED Mfg. Date 20.. Rated Speed rpm Rated Voltage DC V Mfg. No. Drawing No. Model Tooth Number ACTUATOR PICK-UP BATTERY - + 1 2 3 4 5 6 7 8 9 DROOP AUX 10V 10 11 12 13 14 DEGSON DG36 Figure 2.1 : The outline and installing size of the C2002 speed control unit 2

2.1.3 Connection diagram of the C2002 speed control unit 2.1.3.1 C2002 speed control unit s connection diagram for normal generator set refers to figure 2.2. 14 13 12 11 10 9 8 7 6 5 4 3 2 1 + - Close for droop Shut down switch 12V or 24V DC Assistant power 10V Votage adjust speed input connect with distribute load set or adjust speed insynchronization set out side Remote potentiometer (4.7K) Speed pick up Electromagnetic Close for idle Figure 2.2 Connection diagram of the C2002 speed control unit for normal generator set The Electromagnetic Actuator connects to Terminals 1 and 2 and battery connections to Terminals 5 and 6. Terminals 1, 2, 5, and 6 should be #16 AWG (1.3 mm sq) or larger. Long cables require an increased wire size to minimize voltage drops. The battery positive (+) input, Terminal 6, should be fused for 15 amps as illustrated. Magnetic speed sensor connects to Terminal 3 and 4 MUST BE TWISTED AND/OR SHIELDED for their entire length. The speed sensor cable shield should only be connected to Terminal 4. The shield should be insulated to insure no other part of the shield comes in connect with engine ground, otherwise stray speed signals may be introduced into the speed control unit to stop the engine. The remote potentiometer connects to Terminal 7 and 9. If it resistance is 4.7K Ω, speed adjusting range is 2400HZ. Speed droop connects to Terminal 10 and 11. When the Terminal 10 and 11 is off, speed droop is 0; When the Terminal 10 and 11 is closed, speed droop range is 0-5%. Rated and idle speed switch connects to Terminal 7 and 12. The switch close for idle, the switch off for rated speed. 3

Terminal 13 receives input signal from load distribution device, automatic synchronizer device and other governor system auxiliary device. Terminal 14 output +10 volt regulated supply. 2.1.3.2 C2002 speed control unit s connection diagram for a wide range of speed adjusting refers to figure 2.3. Through connecting a potentiometer between the terminal 7.9.10(11), the wide range speed adjustment will be achieved just as the figure 2.3 show. Clockwise rotate, speed will rise. Otherwise, speed droop. The rotate speed adjusting range is decided by the resistance (50K) potentiometer. 14 13 12 11 10 9 8 7 6 5 4 3 2 1 + - Shut down switch 12V or 24V DC Assistant power 10V Votage adjust speed input connect with distribute load set or adjust speed insynchronization set out side (50K) Wide range adjusting speed Speed pick up Electromagnetic Figure 2.3 Connection diagram of the C2002 speed control unit for a wide range of speed adjusting 2.2 The Electromagnetic Actuator The Electromagnetic Actuator is the executive element of the electronic governor. ESG2002 series speed control unit that is single-loop control mode can matching all kinds of electromagnetic, such as A3A A3B A1000CW A2000CW A1AW A08A. The Electromagnetic Actuator has two types of installation. One is internal installation, and the other is external installation. Customers can select it according their requirements. 2.2.1 Internal installation Internal installation is the electromagnetic substitute the mechanical governor. Rack of the electromagnetic links rack of fuel pump. Handle of can adjust fuel and set maximum fuel. ESG2002 series speed control unit can matching A3A A1000CW A2000CW A08A. 4

2.2.1.1 A3A electromagnetic Main technical parameters WORKING VOLTAGE: 12V or 24V DC WORKING TORQUE: 0.8 N m WORKING STROKE: 19mm Figure 2.4 The outline and installing size of the A3A electromagnetic 2.2.1.2 A1000CW electromagnetic Main technical parameters WORKING VOLTAGE: 12V or 24V DC WORKING TORQUE: 1 N m WORKING STROKE: 22 mm 5

B ESG2002 SERIES ELECTRONIC GOVERNOR INSTRUCTION A1000C-W ELECTROMAGNETIC ACTUATOR! Before install electromagnetic, please inspect that the rack of the oil pump shouldn't be stuck in any case. After installation, please inspect that the rack of the oil pump must be on the stop-oil position. A Figure 2.5 The outline and installing size of the A1000CW electromagnetic 2.2.1.3 A2000CW electromagnetic Main technical parameters WORKING VOLTAGE: 24V DC WORKING TORQUE: 2 N m WORKING STROKE: 22 mm Figure 2.6 The outline and installing size of the A2000CW electromagnetic 6

2.2.1.4 A08A electromagnetic Main technical parameters WORKING VOLTAGE: 24V or 12V DC WORKING TORQUE: 0.8 N m WORKING STROKE: 18 mm 图 2.7 The outline and installing size of the A08A electromagnetic 2.2.2 External installation 7

External installation is fuel handle of connects handle of the mechanical governor by Linkage device. Different Working stroke and torque can be adjusted by hole of the fuel handle of. The type of installation is more suited to assembly the diesel engine sets and transform the governor. 2.2.2.1 A3B electromagnetic Main technical parameters WORKING VOLTAGE: 12V or 24V DC WORKING TORQUE: 0.8 N m WORKING STROKE: 25 Figure 2.8 The outline and installing size of the A3B electromagnetic 2.2.2.2 A1AW electromagnetic Main technical parameters WORKING VOLTAGE: 12V or 24V DC WORKING TORQUE: 1 N m WORKING STROKE: 21 mm 8

Figure 2.9 The outline and installing size of the A1AW electromagnetic 2.3 Speed Pick-up The Speed Pick-up of the Electromagnetic Governor is Speed Pick-up of magnetoelectricity, inner structure of which are made of sensor, loop, alnico and plug. Its structure refers to figure 2.9. The gap between the magnetic speed sensor and the ring gear teeth should not be any smaller than 0.02 in. (0.45 mm). Usually, backing out the speed sensor 3/4 turn after touching the ring gear tooth will achieve a satisfactory air gap. 2.3.1 The structure of the speed pick-up Sensor Loop Alnico Plug Figure 2.10 The structure picture of the speed pick-up 9

! B A 20 ESG2002 SERIES ELECTRONIC GOVERNOR INSTRUCTION 3 Installing and Debugging 3.1 Installing Of The Electronic Governor The C2002 speed control unit is rugged enough to be placed in a control cabinet or engine mounted enclosure with other dedicated control equipment. If water, mist, or condensation may be in contact with the controller, it should be mounted vertically. This will allow the fluid to drain away from the speed control unit. Warning! An overspeed shutdown device, independent of the governor system, should be provided to prevent loss of engine control which may cause personal injury or equipment damage. Do not rely exclusively on the governor system of electric to prevent overspeed. A secondary shut off device, such as a fuel solenoid, should be used. 3.2 Connection Diagram Of The ESG2002 Series Electronic Governor System! CAUTION The power must be supplied by the battery and can't be supplied by the generator. Be careful the polarity of the power, when installing or servicing refer to product publication. STARTING FUEL SPEED RAMPING STABILITY DROOP IDLE GAIN C2002 SPEED CONTROLLER IDLE SPEED ACTUATOR PICK-UP BATTERY DROOP AUX 10V - + 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Drawing No. Mfg. No. Model Mfg. Date pump shouldn't be stuck in any case. After installation, please inspect that the rack of the oil pump must be on the stop-oil position. please inspect that the rack of the oil Before install electromagnetic, A1000C-W ELECTROMAG NETIC ACTUATOR Close for Idle Accessory power supply(+10v) Accssory Input (connect with distribute load set or adjust speed insynchronization set out side) No. Commponent Name.. _ + Figure 3.1 Connection diagram of the ESG2002 series electronic governor system 10

3.3 Adjustments before Starting Engine Check to insure the GAIN and STABILITY adjustments, normally this value is set mid position by factory. Leave factory conditions of Red State Switch is, namely RSW-1, RSW-3 = OFF, RSW-2 = ON. Rated and idle speed of the speed control unit had been set by factory. Normally, this value is near from the user s engine working rotate speed value. In practice, after some adjustments, controller can achieve rated and idle speed, and the stability would be very well. 3.4 Adjustment of the Controller after Starting 3.4.1 Crank the engine with D.C. power applied to the governor system. Start fuel quantity varies with environmental temperature of engine start. Though adjusting start fuel quantity potentiometer; exhaust smoke from the engine can be adjusted to the best state. 3.4.2 The governor system should control the engine at low idle speed. If the engine is unstable after starting, turn the GAIN and STABILITY adjustments counterclockwise until the engine is stable. 3.4.3 The governed speed set point is increased by clockwise rotation of the SPEED adjustment control. Remote speed adjustment can be obtained with an optional Speed Trim Control. 3.4.4 Once the engine is at the operating speed and at no load, the following governor performance adjustments can be made. 3.4.4.1 Rotate the GAIN adjustment clockwise until instability develops. Gradually move the adjustment counterclockwise until stability returns. Move the adjustment one division further counterclockwise to insure stable performance. 3.4.4.2 Rotate the STABILITY adjustment clockwise until instability develops. Gradually move the adjustment counterclockwise until stability returns. Move the adjustment one division further counterclockwise to insure stable performance. 3.4.4.3 Gain and stability adjustments may require minor changes after engine load is applied. Normally, adjustments made at no load achieve satisfactory performance. A strip chart recorder can be used to further optimize the adjustments. 3.4.5 After the governor speed setting has been adjusted, place the optional external selector switch in the IDLE position. The idle speed set point is increased by clockwise rotation of the IDLE adjustment control. When the engine is at idle speed, the speed control unit applies droop to the governor system to insure stable operation. 11

3.4.6 Through the above adjustments engine still unable to stability, it needs to be adjusted Red State Switch now, figure 3.2 four cases (a: RSW-1, RSW-3 = ON, RSW-2 =. OFF; b: RSW-1, RSW-2 = OFF, RSW-3 =. ON; c: RSW-1, RSW-2 = ON, RSW-3 =. OFF; d: RSW-1, RSW-3 = OFF, RSW-2 = ON). After every adjusting Red State Switch go on the 3.4.4.1 and 3.4.4.2 adjusting procedure again. If it is still unable to stability, should inspect engine and fuel pump for service condition. And then, contact with manufacturer. 1 2 3 1 2 3 1 2 3 1 2 3 a b c d 3.5 Speed Droop Operation Figure 3.2 Red State Switch 3.5.1 Droop is typically used for the paralleling of engine driven generators. 3.5.2 Place the optional external selector switch in the DROOP position, that is connected Terminals 10 and 11. Droop is increased by clockwise rotation of the DROOP adjustment control. When in droop operation, the engine speed will decrease as engine load increases. The percentage of droop is based on current change from no load to full load of the. 3.5.3 After the droop level has been adjusted, the rated engine speed setting may need to be reset. Check the engine speed and adjust the speed setting accordingly. 3.6 Accessory Input 3.6.1 When the Auxiliary Terminal 13 accepts input signals from load sharing units, auto synchronizers and other governor system accessories are directly connected to this terminal. It is recommended that this connection form accessories should be shielded as it is a sensitive input terminal. 3.6.2 When an accessory is connected to Terminal 13, the speed will decrease and the speed adjustment must be reset. 3.7 Accessory Output The +10 volt regulated supply, Terminal 14, can be utilized to provide power to governor system accessories. Up to 20 ma of current can be drawn from this supply. Ground reference is Terminal 7. Caution - a short circuit on this terminal can damage the speed control unit. 12

4 System Troubleshooting 4.1 Check-up the Fault When any incorrect matter happens during installation testing or using, please clear the problem referring to following diagrams. Symptom Test Probable Fault Engine can not start Actuator does not energize fully Unsteady engine speed Battery Pick-up Actuator Battery Actuator Speed Control Unit voltage between Terminals 5 and 6 Should be 12±2 V or 24±2 V DC. 1 the setting of the speed pick up is not correct and the space is too big. 2 Impedance between Terminals 3 and 4 Should be 300 to 500 ohms. 1 Actuator or linkage binding. 2 impedance between Terminals 1 and 2 Should be 2±0.2ohms. If the voltage is less than 14V(9V) for a 24V(12V) system, replace the battery if it is weak or undersized. Actuator or linkage binding. 1 adjust the stability and the gain of the control unit according to 3.4. 2 voltage between Terminals 14 and 7 Should be 10±0.5V. Engine Overspeed Actuator Speed Control Unit Actuator Pick-up Check the and the oil pump s rack and make sure their connect is not loose. 1 the number of engine gear is wrong and the rate speed is high 2 the gain is set too low and sensitive degree is not enough, which bring about too high instant speed 3 Defective speed control unit. 1 Actuator or linkage binding. 2 if zero position of the is not according to of the oil pump, cannot cut up the oil to the oil pump after losing power If error speed sensor signal happens, please Check wiring. 13

4.2 Insufficient Magnetic Speed Sensor Signal A strong magnetic speed sensor signal will eliminate the possibility of external pulses. The speed control unit will govern well 0.5 volts RMS speed sensor signal. A speed sensor signal of 3 volts RMS or greater at governed speed is recommended. Measurement of the signal is made at Terminals 3 and 4. The amplitude of the speed sensor signal can be raised by reducing the gap between the speed sensor tip and the engine ring gear. The gap should be smaller than 0.45mm.When the engine is stopped, back the speed sensor out by 3/4 turn after touching the ring gear tooth to achieve a satisfactory air gap. 4.3 Electromagnetic Compatibility (EMC) EMI SUSCEPTIBILITY -The electronic governor system can be adversely affected by large interfering signals that are introduced through the cabling or through direct radiation into the control circuits. All speed control units contain filters and shielding designed to protect the sensitive circuits from moderate external interfering sources Although it is difficult to predict levels of interference, applications that include magnetos, solid state ignition systems, radio transmitters, voltage regulators or battery chargers should be considered possible interfering sources. If it is suspected that external fields are either radiated or conducted, they will affect the electronic governor system operation; it is recommended to use shielded cable for all external connections. Make sure that only one end of the shields including the speed sensor shield, is connected to a single point on the case of the speed control unit. Mount the speed control unit on a grounded metal back plate or place it in a sealed metal box. What is called radiation is when the interfering signal is radiated directly through space to the electronic governor system. A metal shield or a solid metal container is usually effective to isolate the electronic governor system from this type of interference source. What is called conduction is when the interfering signal is conducted through the interconnecting wiring to the electronic governor system. Shielded cables and filters are common preventive measures. 14