Special voltages: Voltage >500 V AC are only permissible with external control box. 3-phase AC Voltages/frequencies. 1-phase AC Voltages/frequencies

Similar documents
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

1 potential-free change-over contact (max. 24 V DC/1 A) for SIL collective failure signal SIL functions - safety functions Standard: Safe ESD

ELECTRIC MULTI-TURN ACTUATORS for valve automation in the oil & gas industry with high torque requirements

ELECTRIC ACTUATORS. for industrial applications and civil vessels ELEKTRISCHE STELLANTRIEBE

Factor 1) Modulating torque 4) [Nm] 200 F14 G1/2 GK : :

Valve attachment Gearbox Reduction ratio :1 5) : ,

Factor 1) Modulating torque 4) [Nm]

Electric part-turn actuators

1/4 turn electric actuators (irreversible reducer with multi -turn electric actuator AUMA generation.2)

Issue Abbreviated MSP numbering system AUMA MATIC Types AM. Uncontrolled copy! EWH-25 GB-10. Quality Management System AUMA-Group

Electric multi-turn actuators

Factor 3) Max. input torques Flange 38 GS : F ,000 F10 F ,000 F12 82:

GEARBOXES for operation of industrial valves

Reduction ratio. Factor 1)

Electronic Limit Switch Type

Factor 2) 160:1 6) /(30) FA10 (FA14) :1 6) /(30) FA10 (FA14) 27 86

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

sinamics SINAMICS G110 Variable Speed Drives 0.12 kw to 3 kw SINAMICS G110 Short Form 2004

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 with actuator controls AUMA MATIC AM 01.1

Technical Datasheet. Compact DC Energy Meter. Multi-Function DC Energy Meter

EM DC Multi-Function DC Energy Meter

Power consumption In operation At rest For wire sizing

Type Electronic Limit Switch

Electronic Ballast EVG 2000-T

Power consumption In operation At rest For wire sizing. Cable 1 m, 2 x 0.75 mm 2 Cable 1 m, 6 x 0.75 mm 2 Functional data Torque Motor Spring return


Multi-turn actuators. Product description

JUMO ecotrans Lf 01/02

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

AKM 105S, 115S: Rotary actuator with SAUTER Universal Technology (SUT) for ball valve

1/4 turn ACTELEC SG05.1 to SG12.1 (AUMA)

ecotrans Lf 01/02 Microprocessor Transmitter / Switching Device for Conductivity

RVS-DN Digital Reduced Voltage Motor Starter

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

See «Overview of types»

Alpha EM DC Multi-Function DC Energy Meter. Technical Datasheet. Compact DC Energy Meter

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

Technical Datasheet. Multi-channel support RTC with Data Storage RS485 Output Alarming & Protection Onsite Programmable Load Profile Analysis

JUMO MIDAS S05 Pressure transmitter Type

Pushing 1) force. Motor Spring [N] [kg]

Power consumption In operation At rest For wire sizing

Industrial Chargers and

Motor-drive mechanism, type BUL. Technical guide

SECTION MOTOR CONTROL

Power consumption In operation At rest For wire sizing

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 with local control unit AUMA SEMIPACT SEM 01.1/SEM 02.1

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

Recommended spare parts and often used accessories

Empty enclosures IEC 62208

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

SMARTRONIC MA. Type Series Booklet

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

AQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2

VALVE CONTROLLERS Controllers for Dust Extr 2010 / 2011 action Technology

825-P Modular Protection System for motors Specification Guide

Series description: Wilo-Stratos

General_technical_data Series

SAV Electronic Valve Actuator

LED Driver Linear / area fixed output industry. Driver LCI 100W 350mA 900mA TOP INDUSTRY sl TOP series

Material Specification PVC valves shall meet ASTM D1784 cell classification 124 standards. CPVC valves shall meet ASTM D1784 cell classification 23447

Integrated Control modules

Electric part-turn actuators

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems.

Positive displacement batch controller

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

Technical Data Electric double-motor-actuators

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

Type Electrically Actuated Ball Valve

Prism PI Intelligent features offer advanced performance

For Operation in the Control Cabinet 3RW Soft Starters

"INTEGRAL +" CONTROLS HANDBOOK WITH POSITIONER POSIGAM+ OR MODUGAM+

Part-turn actuators SQEx 05.2 SQEx 14.2 SQREx 05.2 SQREx 14.2 with local controls AUMA SEMIPACT SEMExC 01.1

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

Logic module. Brief description. Features. Block structure. Data Sheet Page 1/5

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

LED Driver Linear / area fixed output industry. Driver LCI 65W 150mA 400mA TOP INDUSTRY sl TOP series

SSW03 Soft Starter APG2009.indd 69 5/26/09 8:55 AM

AME. Rectifier - Battery charger. Industrial applications: Key features:

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

HIB Enclosed Inverter User Guide

Overview of types. Technical data

Power consumption In operation At rest For wire sizing

Actuators IC 20, IC 40

SAX Electronic Valve Actuator

Linear actuator. Product features. Overview. Wide range of force outputs. Wide selection of column adapters. Wide selection of flanges

INSTRUCTION MANUAL ACTUATOR CLASSE I TYPE MA, MB

Single foot switches PX and PA series

RVS-DX Digital Reduced Voltage Motor Starter

Explosion and flame-proof cast iron electric motors

EPS/ELA-Series User Manual EPS/ELA 250W

Electronic circuit breaker EBU10-T

Transcription:

General information Actuator controls AC 01.2 for controlling multi-turn actuators of the SA/SAR type range and part-turn actuators of the SQ/SQR.2 type range. Power supply Standard voltages AC: 3-phase AC ages/frequencies 230 380 380 400 400 415 440 4 480 0 1-phase AC ages/frequencies 110 120 110 120 240 240 Special voltages: age >0 V AC are only permissible with external control box. 3-phase AC ages/frequencies 1-phase AC ages/frequencies 240 525 575 575 0 6 690 208 Permissible variation of mains voltage: ±10 % Permissible variation of mains voltage: ±30 % (option) Permissible variation of mains frequency: ±5 % Special voltages DC: (on request) DC current ages 24 48 110 125 External supply of the electronics (option) Current consumption Overvoltage category Rated power Switchgear Permissible voltage deviation: (on request) 24 V DC +20 %/ 15 % Current consumption: Basic version approx. 2 ma, with options up to 0 ma External power supply must have reinforced insulation against mains voltage in accordance with IEC 61010-1 and may only be supplied by a circuit limited to 1 VA in accordance with IEC 61010-1. Current consumption of the actuator controls depending on mains voltage: For permissible variation of mains voltage of ±10 %: 100 to 120 V AC = max. 740 ma 208 to 240 V AC = max. 400 ma 380 to 0 V AC = max. 2 ma 515 to 690 V AC = max. 200 ma For permissible variation of mains voltage of ±30 %: 100 to 120 V AC = max. 1,200 ma 208 to 240 V AC = max. 7 ma 380 to 0 V AC = max. 400 ma 515 to 690 V AC = max. 400 ma Category III according to IEC 364-4-443 Actuator controls are designed for nominal motor power, refer to Electrical data pertaining to the actuator Reversing contactors (mechanically and electrically interlocked) for AUMA power classes A1/A2 Reversing contactors (mechanically and electrically interlocked) for AUMA power class A3 Thyristor unit for mains voltage up to 0 V AC (recommended for modulating actuators) for AUMA power classes B1, B2 and B3 The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high number of starts, we recommend the use of thyristor units. For the assignment of AUMA power classes, please refer to Electrical data on actuator Y004.678/003/en Issue 1.17 Page 1/5

Control inputs Control voltage/current consumption for control inputs Status signals (output signals) 6 digital inputs: OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, thereof OPEN, STOP, CLOSE with one common and EMERGENCY without common, respect minimum pulse duration for modulating actuators). Standard 24 V DC, current consumption: approx. 10 ma per input 48 V DC, current consumption: approx. 7 ma per input V DC, current consumption: approx. 9 ma per input 115 V DC, current consumption: approx. 15 ma per input 100 120 V AC, current consumption : approx. 15 ma per input All input signals must be supplied with the same potential. - 5 potential-free NO contacts with one common, max. 2 V AC, 1 A (resistive load) Default configuration: End position CLOSED, end position OPEN, selector switch REMOTE, torque fault CLOSE, torque fault OPEN - 1 potential-free change-over contact, max. 2 V AC, 5 A (resistive load) Default configuration: Collective fault signal (torque fault, phase failure, motor protection tripped) Analogue output signal for position feedback - Galvanically isolated position feedback 0/4 20 ma (load max. 0 Ω) age output Analogue output (option) Analogue input (option) - 5 change-over contacts with one common, max. 2 V AC, 1 A (resistive load), 1 potential-free change-over contact, max. 2 V AC, 5 A (resistive load) - 10 potential-free NO contacts, 5 with one common each, max. 2 V AC, 1 A (resistive load), 2 potential-free change-over contacts, max. 2 V AC, 5 A (resistive load) - 6 potential-free change-over contacts without one common, per contact max. 2 V AC, 5 A (resistive load) 10 programmable output contacts: - 10 potential-free change-over contacts without one common, per contact max. 2 V AC, 5 A (resistive load) - 4 mains failure proof potential-free NO contacts with one common, max. 2 V AC, 1 A (resistive load), 1 potential-free NO contact, max. 2 V AC, 1 A (resistive load), 1 potential-free change-over contact, max. 2 V AC, 5 A (resistive load) - 4 mains failure proof potential-free NO contacts, max. 2 V AC, 5 A (resistive load), 2 potential-free change-over contacts, max. 2 V AC, 5 A (resistive load), - 8 mains failure proof potential-free NO contacts, max. 2 V AC, 1 A (resistive load), 2 potential-free NO contacts, max. 2 V AC, 1 A (resistive load), 2 potential-free change-over contacts, max. 2 V AC, 5 A (resistive load) - 8 mains failure proof potential-free NO contacts, max. 2 V AC, 5 A (resistive load), 4 potential-free change-over contacts, max. 2 V AC, 5 A (resistive load), All output signals must be supplied with the same potential. Auxiliary voltage 24 V DC: max. 100 ma for supply of control inputs, galvanically isolated from internal voltage supply. Auxiliary voltage 115 V AC: max. 30 ma for supply of control inputs, galvanically isolated from internal voltage supply (Not possible in combination with PTC tripping device) 2 analogue outputs: With position transmitter option: Output of travel and torque as continuous values between 0/4 and 20 ma 2 analogue inputs: With positioner/process controller option: Input of actual position value/actual process value as continuous values between 0/4 and 20 ma Y004.678/003/en Issue 1.17 Page 2/5

Local controls Selector switch: LOCAL - OFF - REMOTE (lockable in all three positions) Push buttons OPEN, STOP, CLOSE, RESET - Local STOP The actuator can be stopped via push button STOP of local controls if the selector switch is in position REMOTE. (Not activated when leaving the factory.) 6 indication lights: - End position and running indication CLOSED (yellow), torque fault CLOSE (red), motor protection tripped (red), torque fault OPEN (red), end position and running indication OPEN (green), Bluetooth (blue) Graphic LC display: illuminated Special colours for the indication lights: - End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN (yellow), motor protection tripped (violet), end position OPEN (red) Bluetooth Communication interface Bluetooth class II chip, version 2.1: With a range up to 10 m in industrial environments, supports the SPP Bluetooth profile (Serial Port Profile). Required accessories: AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC) AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices) Application functions Safety functions Selectable type of seating, limit or torque seating for end position OPEN and end position CLOSED Torque by-pass: Adjustable duration (with adjustable peak torque during start-up time) Start and end of stepping mode as well as ON and OFF times can be set individually for directions OPEN and CLOSE, 1 to 1,800 seconds Any 8 intermediate positions: can be set between 0 and 100 %, reaction and signal behaviour programmable Running indication blinking: can be set Positioner - Position setpoint via analogue input 0/4 20 ma - Programmable behaviour on loss of signal - Automatic adaptation of dead band (adaptive behaviour selectable) - Split range operation - MODE input for selecting between OPEN-CLOSE and setpoint control PID process controller: with adaptive positioner, via 0/4 20 ma analogue inputs for process setpoint and actual process value Multiport valve: Up to 16 positions, signals (pulse or edge) Automatic deblocking: Up to 5 operation trials, travel time in opposite direction can be set Static and dynamic torque recording for both rotation directions with torque measurement flange as additional accessory EMERGENCY operation (programmable behaviour) - Digital input: Low active - Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN, run to intermediate position - Torque monitoring can be by-passed during EMERGENCY operation - Thermal protection can be by-passed during EMERGENCY operation (only in combination with thermoswitch within actuator, not with PTC thermistor). Enabling local controls via digital input Enable LOCAL. Thus, actuator operation can be enabled or disabled via push buttons on the local controls. Interlock for main/by-pass valve: Enabling the operation commands OPEN or CLOSE via two digital inputs EMERGENCY Stop push button (latching): interrupts electrical operation, irrespective of the selector switch positions. PVST (Partial Valve Stroke Test): programmable to check the function of both actuator and actuator controls: Direction, stroke, operation time, reversing time Y004.678/003/en Issue 1.17 Page 3/5

Monitoring functions Diagnostic functions Motor protection evaluation Electrical connection Threads for cable entries Wiring diagram (basic version) Valve overload protection: adjustable, results in switching off and generates fault signal Motor temperature monitoring (thermal monitoring): results in switching off and generates fault indication Monitoring the heater within actuator: generates warning signal Monitoring of permissible on-time and number of starts: adjustable, generates warning signal Operation time monitoring: adjustable, generates warning signal Phase failure monitoring: results in switching off and generates fault signal Automatic correction of rotation direction upon wrong phase sequence (3-ph AC current) Electronic device ID with order and product data Logging of operating data: A resettable counter and a lifetime counter each for: - Motor running time, number of starts, torque switch trippings in end position CLOSED, limit switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor protection trippings Time-stamped event report with history for setting, operation and faults Status signals according to NAMUR recommendation NE 107: "Failure", "Function check", "Out of specification", "Maintenance required" Torque characteristics (for version with MWG in actuator): - 3 torque characteristics (torque-travel characteristic) for opening and closing directions can be saved separately. - Torque characteristics stored can be shown on the display. Monitoring the motor temperature in combination with thermoswitches within actuator motor Thermal overload relay in controls combined with thermoswitches within actuator PTC tripping device in combination with PTC thermistors within actuator motor AUMA plug/socket connector with screw-type connection Gold-plated control plug (sockets and plugs) Metric threads Pg-threads, NPT-threads, G-threads TPCA-0A1-1C1-A000 TPA00R1AA-0A1-000 Further options for Non-intrusive version with MWG in the actuator Setting of limit and torque switching via local controls Torque feedback signal Galvanically isolated analogue output 0/4 20 ma (load max. 0 Ω). Wiring diagram (basic version) TPCA-0A1-1C1-A000 TPA00R100-0I1-000 Service conditions Use Mounting position Installation altitude Ambient temperature Humidity Enclosure protection according to EN 529 Indoor and outdoor use permissible Any position 2,000 m above sea level > 2,000 m above sea level, on request 30 C to +70 C C to + C, extreme low temperature version Low temperature versions incl. heating system for connection to external power supply 230 V AC or 115 V AC, or internal version 400 V AC. Up to 100 % relative humidity across the entire permissible temperature range IP68 Terminal compartment additionally sealed against interior of actuator controls (double sealed) According to AUMA definition, enclosure protection IP68 meets the following requirements: Depth of water: Maximum 8 m head of water Duration of continuous immersion in water: Maximum 96 hours Up to 10 operations during continuous immersion Modulating duty is not possible during continuous immersion. Pollution degree according to IEC 664-1 Pollution degree 4 (when closed), pollution degree 2 (internal) Y004.678/003/en Issue 1.17 Page 4/5

Service conditions Corrosion protection Coating Colour KS: Suitable for use in areas with high salinity, almost permanent condensation, and high pollution. KX: Suitable for use in areas with extremely high salinity, permanent condensation, and high pollution. Double layer powder coating Two-component iron-mica combination AUMA silver-grey (similar to RAL 7037) Available colours on request Accessories Wall bracket Programming software Torque measurement flange DMF For actuator controls mounted separately from the actuator, including plug/socket connector. Connecting cable on request. Recommended for high ambient temperatures, difficult access, or heavy vibration during service. Cable length between actuator and actuator controls is max. 100 m (Not suitable for version with potentiometer in the actuator). Instead of the potentiometer, the actuator has to be equipped with an electronic position transmitter. (MWG requires a separate data cable.) AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC) AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices) Accessory for torque measurement for SA/SAR 07.2 SA/SAR 16.2 Further information Weight EU Directives Reference documents Approx. 7 kg (with AUMA plug/socket connector) Electromagnetic Compatibility (EMC): (2014/30/EU) Low age Directive: (2014/35/EU) Machinery Directive: (2006/42/EC) Brochure Electric actuators for industrial valve automation Dimensions Multi-turn actuators with AUMATIC integral controls Dimensions Part-turn actuators with AUMATIC integral controls Y004.678/003/en Issue 1.17 Page 5/5