DW Series - Exhaust Only Wall Canopy

Similar documents
W-VI Series - Internal Make-up Air Wall Canopy

Model ND-2 Specification

HOOD ACCESSORIES HOOD ACCESSORIES HOOD ACCESSORIES

OPERATOR MANUAL IMPORTANT INFORMATION, KEEP FOR OPERATOR

Installation, Operation and Maintenance Manual

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets

RECEIVING AND INSPECTION EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE PRIOR TO INSTALLATION.

When Time Matters! listed Fire Damper

KVL-P with Plate Shelf

Installation, Operation and Maintenance Manual

RECEIVING AND INSPECTION

IAQ. Model AVC. SINGLE DUCT VAV Model AVC

Installation, Operation and Maintenance Manual

Filtered Kitchen Supply Packaged Ventilator

KVM KVM. Capture Jet Hybrid Backshelf Hood. Capture Jet TM Hybrid Backshelf Hood

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

Operators Manual. Manual provides Installation and Operating Instructions. Model MM1 Series Hood

Table of Contents WARRANTY...3 APPLICATION...4 MECHANICAL...5 Joint Sealant...5 Grease Duct Standard Connection...6 Collar and Adjustable Duct

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

Electrical Control Panel

Commercial Kitchen Hoods Installation, Operation, and Maintenance Manual

CANOPY HOOD ACCESSORIES

Commercial Kitchen Hoods Installation, Operation, and Maintenance Manual

Filter Hood Model CA-S

RECTANGULAR, 2-HOUR FIRE RATED, ZERO-CLEARANCE GREASE DUCT CO.

Operators Manual for JES-HD

Commercial Kitchen Hoods. Installation, Operation, and Maintenance Manual

A95-2V. 95% Gas Furnaces Two-Stage Variable Speed HEAT EXCHANGER DESIGN CONFIGURATIONS

Smith Memorial Stude t Union itchen Hood Replacement

2520- EC Motor Speed Controller

Inline Fans [ 14 ] * UL is optional and must be specified.

A Division of Nailor International Inc. ECONOMY AIR HANDLERS

95G2E PRODUCT SPECIFICATIONS 95% TWO-STAGE CONSTANT TORQUE GAS FURNACES CONTROLS VENTING CONFIGURATIONS HEAT EXCHANGER DESIGN INSTALLATION FEATURES

Model DW Series Positive Pressure Guidelines for Engine Exhaust Systems

KOMFORT ZONE KIT. For use with the Callway-50 #CLW-50 Direct Vent Gas Fireplace

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK

Tubular Centrifugal Fans

INSTRUCTIONS INSTALLATION OF NEMA-3R KIT FOR 43, 44 & 52 FRAME AF-6 DRIVES INTO WELDED ENCLOSURES

ICEMINI & Vertical MTI Units

Model DW Series Positive Pressure Guidelines for Engine Exhaust Systems

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

DF / DFB / DFC DOUBLE WIDTH DOUBLE INLET FORWARD CURVED FANS

forward curved inline duct blowers

CANOPY HOOD ACCESSORIES

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN

MODEL IFG INDIRECT FIRED MAKE-UP AIR HEATER

80% Gas Furnaces Single Stage - High Efficiency (Constant Torque) Motor

80% Gas Furnace. Single Stage - High Efficiency (Constant Torque) Motor. Features and Benefits 80G1-E CONFIGURATIONS HEAT EXCHANGER DESIGN BURNERS

Scope and Application of ASTM 1704, Standard Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems

PREFABRICATED ROOF CURBS

IAQ. ROUND DUCT RETROFIT Model ARR

General Purpose Walk-In Fume Hood

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

Bulletin BCF 103 DESIGN 10A BACKWARD INCLINED WHEELS

General. Technical Bulletin: ACCESSORY INFORMATION

LOW PRESSURE MIXED FLOW FANS

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

General Purpose Walk-In Fume Hood

RPGE13. Product Specifications. 13 SEER Gas / Electric Residential Packaged Unit. Refrigerant System. Heat Exchanger. Cabinet Construction.

Centrifugal Filtered Supply Roof Blowers

Installation Manual for Ecology

ExtractAire. Grease Filters for Commercial Kitchen Ventilation Hoods. Baffle. High Velocity Cartridge (HVC)

RDM. Laboratory Fume Hoods SEFA SCIENTIFIC EQUIPMENT & FURNITURE ASSOCIATION

SQBI BLOWERS BACKWARD INCLINED CLASS II CLASS IIP CLASS III. OEM and Industrial Air Handling Specialist

MODEL NBRTD BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

Charcoal Filter Installation NOTE: The charcoal filters are preinstalled if you purchased the range hood with re-circulating kit from us. 1. Remove st

XeteX, Inc. All Rights Reserved.

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

A962E PRODUCT SPECIFICATIONS TWO STAGE HIGH EFFICIENCY CONSTANT TORQUE GAS FURNACE CONTROLS VENTING CONFIGURATIONS HEAT EXCHANGER DESIGN

Centrifugal Plenum Fan

INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS. Twin City Fan MIXED FLOW FANS QSL QSLR QSLSH CATALOG 1060 MARCH 2017

Concentric Supply/Return Diffusers. Models CSR & CSR-P. Redefine your comfort zone.

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges

KWF Water Wash Canopy with Supply Air

FN Fan-Coil Units High-Performance, Horizontal

Upflow, Upflow / Horizontal, Counterflow / Horizontal

IAQ. Model AVW. SINGLE DUCT w/hot WATER HEAT Model AVW

Quiet-Duct Conic-Flow Silencers Section Specifications

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD

MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED ROOF SUPPLY FAN

CAR-MON ARTICULATED ARM ASSEMBLY INSTALLATION OPERATION MAINTENANCE

MOUNTING ARRANGEMENT OPTIONS OVERVIEW

13 SEER Light Commercial 3 Phase

STEEL LOUVERED DIFFUSERS [CFM Range is only a guide. See Manufacturer Catalog for complete data. All NC Levels in Acceptable Range<32.

GAS-FIRED CONDENSING MOBILE HOME FURNACE DOWN FLOW & DIRECT VENT (SEALED COMBUSTION) FURNACE SPECIFICATIONS

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

Tube Axial Inline Fans

SHELDONS ENGINEERING Inc. Sheldons Engineering Product Index

LABGARD FEATURES

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

INSULATED CANTED ROOF CURB NON-PROPELLER PRODUCTS

INSULATED CANTED ROOF CURB NON-PROPELLER PRODUCTS

GMH95/GCH9 PRODUCT SPECIFICATIONS 95%/93% AFUE HEAT REPLACEMENT MULTI-POSITION, TWO-STAGE (CONVERTIBLE), MULTI-SPEED GAS FURNACE

SD-1250 and SD-1600 Series Smoke Dampers

Centrifugal Ventilators Direct-Drive Upblast Centrifugal Roof & Wall Ventilators

NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG C-PREP

UTILITY BLOWERS. Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB. The Industrial Choice.

Transcription:

DW Exhaust Only Wall Canopy Model DW A single shell non-compensating exhaust only wall hung canopy constructed of stainless steel where visible and aluminized steel in concealed locations. All external seams shall be fluid welded, and internal seams shall be sealed with a high temp. silicone caulk. Canopy shall be Listed to meet NSF and UL 710 standards and constructed to meet NFPA-96. Grease trough to be easily removable and slope to removable grease cup. STANDARD FEATURES UL Listed Aluminum Grease Filters UL Listed Globe Lights 3" Rear Air Space Removable Grease Trough & Cup Hanging Brackets Exhaust Collar Installed OPTIONS All Stainless Steel Construction UL Listed Stainless Steel Grease Filters 14" Utility Cabinet for Fire Suppression System Electrical Control Panel Pre-Plumbed Fire Suppression Stainless Steel Top Enclosures Light Switch Fan Switch UL Listed Insulated Top, Back and/or Ends for Zero Clearance to Combustible (See reverse side for larger drawing) Note: Two exhaust ducts required after 12' long. DW Series - Exhaust Only Wall Canopy BUILT IN ACCORDANCE WITH NFPA 96 Revised July 2001 Duo-Aire

DW Series Specifications Project: ORDER ENTRY INFORMATION Item: A B Representative: Model: Length: Qty: Note: Two exhaust ducts required after 12' long. Width: Height: Exhaust CFM: Entered by: Date: Drawings Req d: Y N Section List Miscellaneous Options Separately EXHAUST RATE REQUIREMENTS ( Recommended Min. TEMPERATURE OF EQUIPMENT Exhaust Flow Rate) 400 600 700 CFM Exhaust / Ft. 200 300 350 Duo-Aire reserves the right to make changes in design and specifications without prior notice.

DW-AVC Exhaust Only Wall Canopy With Air Volume Controllers Model DW-AVC A single plenum non-compensating exhaust only wall hung canopy constructed of stainless steel where visible and aluminized steel in concealed locations. All external seams shall be fluid welded, and internal seams shall be sealed with a high temperature silicone caulk. Exhaust canopy to be equipped with adjustable Air Volume Controllers installed directly behind the filters. Air Volume Controllers are to be factory installed and adjusted for the cooking equipment specified. Canopy shall be listed to meet NSF and UL 710 standards and constructed to meet NFPA-96. Grease trough to be easily removable and slope to removable grease cup. STANDARD FEATURES UL Listed Aluminum Grease Filters UL Listed Globe Lights 3" Rear Air Space Removable Grease Trough & Cup Hanging Brackets Exhaust Collar Installed Adjustable Air Volume Controllers OPTIONS All Stainless Steel Construction UL Listed Stainless Steel Grease Filters 14" Utility Cabinet for Fire Suppression System Electrical Control Panel Pre-Plumbed Fire Suppression UL Listed Insulated Top, Back and/or Ends for Zero Clearance to Combustible Stainless Steel Top Enclosures Light Switch Fan Switch Rooftop Packages (See reverse side for larger drawing) DW-AVC Series - Exhaust Only Wall Canopy BUILT IN ACCORDANCE WITH NFPA 96 Revised July 2001 Duo-Aire

DW-AVC Series Specifications Project: ORDER ENTRY INFORMATION Item: A B Representative: Model: Length: Qty: Width: Height: Exhaust CFM: Entered by: Date: Section Drawings Req d: Y N List Miscellaneous Options Separately EXHAUST RATE REQUIREMENTS ( Recommended Min. TEMPERATURE OF EQUIPMENT Exhaust Flow Rate) 400 600 700 CFM Exhaust / Ft. 200 250 - Duo-Aire reserves the right to make changes in design and specifications without prior notice.

ENGINEERING WORKSHEET DW SERIES 400 F. EQUIPMENT 200/Ft. A X B FPM Sq. Ft. FPM 4 800 9 x 8 1600 4.2 191.75 5 1000 10 x 9 1600 5.3 189.75 6 1200 10 x 10 1728 6.3 191.75 7 1400 11 x 11 1666 7.4 190.75 8 1600 12 x 12 1600 8.4 191.75 9 1800 13 x 12 1662 9.5 190.75 10 2000 15 x 12 1600 10.5 191.75 11 2200 16 x 12 1650 11.6 190.75 12 2400 18 x 12 1600 12.6 191.75 13 2600 (2)11 x 10 1702 14.0 186.75 14 2800 (2)11 x 11 1666 15.0 187.75 15 3000 (2)12 x 11 1636 15.8 190.75 16 3200 (2)12 x 12 1600 16.8 191.75 DW SERIES 600 F. EQUIPMENT 300/Ft. A X B FPM Sq. Ft. FPM 4 1200 10 x 10 1728 4.2 286 1.0 5 1500 12 x 11 1636 5.3 283 1.0 6 1800 13 x 12 1662 6.3 286 1.0 7 2100 15 x 12 1680 7.4 284 1.0 8 2400 18 x 12 1600 8.4 286 1.0 9 2700 20 x 12 1620 9.5 284 1.0 10 3000 22 x 12 1636 10.5 286 1.0 11 3300 24 x 12 1650 11.6 284 1.0 12 3600 26 x 12 1662 12.6 286 1.0 13 3900 (2)14 x 12 1671 14.0 279 1.0 14 4200 (2)15 x 12 1680 15.0 280 1.0 15 4500 (2)16 x 12 1688 15.8 285 1.0 16 4800 (2)17 x 12 1694 16.8 286 1.0

ENGINEERING WORKSHEET DW-AVC SERIES 400 F. EQUIPMENT 200/Ft. A X B FPM Sq.Ft. FPM 4 800 9 x 8 1600 2.6 308 1.0 5 1000 10 x 9 1600 3.4 294 1.0 6 1200 10 x 10 1728 4.0 300 1.0 7 1400 11 x 11 1666 4.6 304 1.0 8 1600 12 x 12 1600 5.4 296 1.0 9 1800 13 x 12 1662 6.0 300 1.0 10 2000 15 x 12 1600 6.8 294 1.0 11 2200 16 x 12 1650 7.4 297 1.0 12 2400 18 x 12 1600 8.0 300 1.0 13 2600 19 x 12 1642 8.9 292 1.25 14 2800 20 x 12 1680 9.6 292 1.25 15 3000 22 x 12 1636 10.0 300 1.25 16 3200 23 x 12 1670 10.8 296 1.25 DW-AVC SERIES 600 F. EQUIPMENT 250Ft. A X B FPM Sq. Ft. FPM 4 1000 10 x 9 1600 2.6 385 1.25 5 1250 11 x 10 1636 3.4 368 1.25 6 1500 12 x 11 1636 4.0 375 1.25 7 1750 13 x 12 1615 4.6 380 1.25 8 2000 15 x 12 1600 5.4 370 1.25 9 2250 16 x 12 1688 6.0 375 1.25 10 2500 18 x 12 1667 6.8 368 1.25 11 2750 20 x 12 1650 7.4 372 1.25 12 3000 22 x 12 1636 8.0 375 1.25 13 3250 24 x 12 1625 8.9 365 1.50 14 3500 26 x 12 1615 9.6 365 1.50 15 3750 28 x 12 1607 10.0 375 1.50 16 4000 30 x 12 1600 10.8 370 1.50