The X, Y, and Z of Circuit Breaker Control

Similar documents
Circuit breaker interlocking and operation requirements SIEMENS

BREAKER FAILURE PROTECTION

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Beware of Ghost Voltage

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

COLDWATER LAKE FACILITIES DUPLEX PUMP STATION

Flotection: Building Main Shutoff System

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Close-Open (Short-Circuit) Time Results Interpretation

Horizontal Circuit Switchers

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Horizontal Circuit Switchers

J1 Plug Pin Identification

J1 Plug Pin Identification

Tattletale Annunciators and Magnetic Switches

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

Trip Circuit and Trip coil supervision Relay

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.

Transformer Protection

J1 Plug Pin Identification

SECTION MOTOR CONTROL

Foreword



Application Note. Common Bussing AC Drives. For 650 and 690+ series drives APP-AC-03

Motor Protection Fundamentals. Motor Protection - Agenda

Why is the Breaker Tripping?

Type SOQ Negative Sequence Time Overcurrent Relay

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Dual Power. Protection. Protection

Phone: Fax: Web: -

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

5 Series - Mechanical Latch 2PDT - 4PST, 30 Amps

Pump Installation and Service Manual HRS Hydromatic Retractable System

Vacuum Circuit Breaker Type VAD-3

Grounding Of Standby & Emergency Power Systems

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Electric Motor Controls BOMA Pre-Quiz

Chapter Assessment Use with Chapter 22.

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

Transmission ITP. Monitoring of BES Equipment. PJM State & Member Training Dept. PJM /10/2018

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Exercise 4-1. Friction Brakes EXERCISE OBJECTIVE DISCUSSION. Understand the construction and operation of friction brakes.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

MOTOR TERMINAL CONNECTIONS

Reversing Hand Throttle and Horn Relay Board RBT / HRB

Quick Start Guide TS 910 & TS 920

Source-Side Fuse/Load-Side Recloser Coordination

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

1.0 Features and Description

BILL OF MATERIAL 2 C EA SP CURRENT TRANSDUCER BI-DIRECTIONAL, MV INPUT, MA OUTPUT, 125VDC POWER SUPPLY SMC

(Example) In case of DC24 to 48V, it is operating time for DC24V.

CHAPTER 4 PROTECTION REQUIREMENTS

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

Pretest Module 29 High Voltage Unit 1

SPC-PANEL Simplex, Single Phase Pump Control Panel

Service and Parts Manual. NO LONGER IN PRODUCTION Some service parts may not be available for this product. Otolaryngology Chair.

OpenEVSE. Testing Basic and Advanced

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Extracting Valuable Information from HV Circuit Breaker Testing. Charles Sweetser - OMICRON MIPSYCON 2014

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

GET GROUNDED. Renewable Energy System Grounding Basics

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

1-3 MANUAL STARTERS EXERCISE OBJECTIVE. Examine and describe the operation of manual motor starters. DISCUSSION

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

Optimizing Emergency Power Systems for Health Care Applications

TMC 91H is now TMC 60 C Series

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

Quick Start Guide TS 910

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

SUBSTATION EQUIPMENT - Page 1 of 8

Application Engineering

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

Components for EEx e Panels

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Linear Actuator Swing Gate Operator Installation Manual Model # LA405-24

LEVEL 1/2 CAMBRIDGE NATIONAL AWARD/CERTIFICATE IN PRINCIPLES IN ENGINEERING AND ENGINEERING BUSINESS. Candidate Surname

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

Installation Sheet January, 2016 Supersedes February, 2013

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

Designed for ease of integration with automation systems

P144F REQUESTED INFORMATION P144F EGR COOLER BYPASS STATUS LINE CIRCUIT HIGH RAM Pickup 6.7L Eng /12/2014 Printer Friendly View

SECTION MOTOR CONTROLLERS

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY


IAE-101: Electrical Fundamentals for Non-Electrical Personnel

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014

Transcription:

The X, Y, and Z of Circuit Breaker Control BRENT L. CARPER, P.E. Principal Engineer Presented at the 35th Annual Hands-On Relay School March 12-16, 2018

Agenda Importance of Breaker Control The IEEE C37.11 Standard Breaker control circuit 12 step program for breaker closing Trip coil monitoring Seal-in Anti-pump Demonstrations

The importance of breaker control Mechanical forces Acceleration-Travel-Deceleration Very fast from one closed to open, or open to closed (e.g. 3 cycles = 0.050 seconds) Electrical forces Magnetic forces from fault currents (e.g. 40,000 Amps)

The importance of breaker control

The importance of breaker control

The importance of breaker control

The importance of breaker control

The importance of breaker control

IEEE C37.11

IEEE C37.11 IEEE Standard Requirements for Electrical Control for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Contains 5 Sections 1. Overview 2. References 3. Functional Requirements 4. Devices and Auxiliaries 5. Wiring Requirements

IEEE C37.11 Section 5: Wiring Requirements

C37.11 Part 5: Wiring Requirements

Section 5: Wiring Requirements

Section 5: Wiring Requirements

Section 5: Wiring Requirements

Section 5: Wiring Requirements

Circuit Breaker Controls

The 12 Step Program for Successful Breaker Closing

1. Normal state Breaker is open Mechanism is not charged Control power is not applied

2. Apply Closing Power Motor (88) runs to charge mechanism

3. Mechanism charged All 63 contacts change state Motor stops running

4. Apply Control Power Breaker is still open Green light is on

5. Close Command Energizes 52X relay

6. 52X Relay Operates All 52X contacts change state Energizes 52CC breaker closing coil 52CC releases energy to close the breaker

7. Breaker Closing Breaker begins to close All 52b contacts open

8. Breaker Closed All 52a contacts close Energizes 52Y relay Red light is on (trip coil monitoring)

Sidebar: Trip Coil Monitoring Q: Why does this circuit not trip the breaker? It is a complete circuit. A: Circuit is a voltage divider (two impedances in series), and the Red Light is a much larger impedance than the Trip Coil. Example: 48 Vdc control circuit Red Lamp = 1200 ohms; Trip Coil = 3 ohms Voltage across the Red Light = 48 x 1200 / (1200+3) = 47.88 V Voltage across the Trip Coil = 48 x 3 / (1200+3) = 0.12 V Power absorbed by the Red Light = 47.88 2 / 1200 = 1.9 Watts Power absorbed by the Trip Coil = 0.12 2 / 3 = 0.005 Watts Current in the circuit = 48 / (1200+3) = 0.040 A Current through the trip coil during a trip = 48 / 3 = 16 A

Sidebar: Trip Coil and 52a Contact Q: Why does the trip coil always have a 52a contact in series with it? A: 3 Reasons: 1. Block energizing the coil when the breaker is already open. 2. Trip coil passes a lot of current (e.g. 16 Amps in the previous example; often more). 52a is a heavy-duty contact that is rated to interrupt that current so that the tripping devices (relays) do not have to. 3. Trip coil is not rated for continuous current. It needs to be de-energized as soon as possible after it has done its job to trip the breaker. Q: Why use a coil that isn t rated for continuous use? A: Speed. And... Because we are intentionally over-dutying the trip coil, trip coil monitoring is critically important.

9. 52Y Relay Operates All 52Y contacts change state 52X relay drops out

10. 52X Relay Resets All 52X contacts change state back to normal 52CC drops out

11. Close Command is Released 52Y relay drops out

12. 52Y Relay Resets All 52Y contacts change state back to normal Closing cycle complete

Breaker Tripping

Breaker Trip

Breaker Trip Trip command

Breaker Trip Trip command Energizes 52TC breaker trip coil Breaker begins to open

Breaker Trip Trip command Energizes 52TC breaker trip coil Breaker begins to open 52a contacts open

Breaker Trip Trip command Energizes 52TC breaker trip coil Breaker begins to open 52a contacts open Breaker fully open 52b contacts close

Breaker Trip Trip command Energizes 52TC breaker trip coil Breaker begins to open 52a contacts open Breaker fully open 52b contacts close Trip command is released

IEEE C37.11 Section 3: Functional Requirements

C37.11 Part 3: Functional Requirements 3a) Seal-in for close 3b) Anti-pump 3c) Reset after an incomplete close 3d) No close operation if already closed 3e) Block close for low stored energy 3f) Low gas block trip and close 3g) Low gas alarm 3h) Block close if tripped free 3i) Pressure nuisance alarms 3j) Pole disagreement tripping

IEEE C37.11 Section 3e

3e) Block close for low stored energy Breaker is open

3e) Block close for low stored energy Breaker is open Low stored energy 63 contact in the close control circuit accomplishes the 3e) requirements

IEEE C37.11 Section 3d

3d) No close if already closed Breaker is closed 52b contact in the close control circuit accomplishes the 3d) requirements Just like the 52a prevents reenergizing the trip coil if the breaker is already open Demonstration

IEEE C37.11 Section 3a

3a) Seal-in for close Breaker is open Step 5. 52X relay is energized Step 6. 52X relay operates What happens if the close command drops out before the breaker completes its close cycle? Doesn t matter. 52X is sealed-in. Demonstration

IEEE C37.11 Section 3c

3c) Reset after an incomplete close 52X seal-in lasts forever Must fully reset if control power is cycled

3c) Reset after an incomplete close 52X seal-in lasts forever Must fully reset if control power is cycled 52X drops out and contacts return to normal

3c) Reset after an incomplete close 52X seal-in lasts forever Must fully reset if control power is cycled 52X drops out and contacts return to normal Restoring control power does not cause 52X to pick up and does not result in the breaker closing; all devices remain reset Demonstration

IEEE C37.11 Section 3b

3b) Anti-pumping Breaker is open Step 7. Closing coil operates

3b) Anti-pumping 52b contact opens Breaker closes 52a contact closes

3b) Anti-pumping 52b contact opens Breaker closes 52a contact closes 52Y relay energizes 52Y contacts change state

3b) Anti-pumping 52b contact opens Breaker closes 52a contact closes 52Y relay energizes 52Y contacts change state 52X relay drops out 52CC drops out But what if closing in to a fault?

3b) Anti-pumping Breaker closes... Into a fault!

3b) Anti-pumping Breaker closes... Into a fault! Same 52Y energize, 52X drop out, 52CC drop out

3b) Anti-pumping Breaker closes... Into a fault! Same 52Y energize, 52X drop out, 52CC drop out Relay trip to the breaker

3b) Anti-pumping Breaker closes... Into a fault! Same 52Y energize, 52X drop out, 52CC drop out Relay trip to the breaker Breaker opens Even though there is still a close command, the breaker will not close. Demonstration

3b) Anti-pumping

3b) Anti-pumping

Summary

Summary Breaker terminal block numbers Specified in IEEE C37.11 Can vary depending on type of breaker and AC/DC Trip Coil Monitoring (TCM) Required in the standard for most breaker types Good practice for other devices as well (86 lockout relays), especially when the coil is not rated for continuous duty IEEE C37.11 Primarily applies to circuit breaker manufacturers But... it is important for engineers and techs and wiremen to understand X/Y schemes Maintenance, testing, and troubleshooting operations

Summary X/Y Schemes Protect the breaker and are required by IEEE C37.11 Schematics can be confusing; work through one action/reaction one step at a time. If you can sequence an X/Y scheme, you can do any schematic! 52X relay provides Seal-In for closing Remember this if troubleshooting a stuck breaker Not all breaker types need a 52X relay 52Y relay provides Anti-Pump protection The breaker s 52Y relay can be fooled by chattering closing relays (25, 27/59, 79) or worn contacts on closing devices (relays, 01, SCADA)

BRENT L. CARPER, P.E. Principal Engineer brent.carper@3ac-eng.com office: 509-339-7626 cell: 509-339-3848 3AC-Eng.com