T-6-way valve NPT threads Standard control valves 6-way valve for change-over systems
IMI T / Control valves / T-6-way valve NPT threads T-6-way valve NPT threads The 6-way valve solution enables various control set-ups for heating and cooling in sequence on one terminal unit. Provides automatically adopted settings of max. flows for heating and cooling modes together with T-Modulator and T-Slider 160 Plus or T-Slider 160 KNX R24. Key features > > Easy commissioning and balancing Provides automatically adopted settings of max. flows for heating and cooling mode together with T-Modulator and T-Slider 160 Plus or T-Slider 160 KNX R24. > > Precise flow control Provides uniquely shaped EQM characteristic for best modulating control together with T-Modulator. > > Easy troubleshooting Provides flow and differential pressure measuring for system diagnostics and pump optimization together with T-Modulator. > > Compact installation Saves space by using one terminal unit for heating and cooling. Technical description Valve pplication: Heating and cooling systems. (Change-over system) Functions: Control Dimensions: DN 15-20 Pressure class: PN 16 Max. differential pressure (ΔpV): 200 kpa Temperature: Max. working temperature: 120 C Min. working temperature: -10 C Media: Water or neutral fluids, water-glycol mixtures (0-57%). Leakage rate: Level (EN 12266-1/12 - P12) Characteristics: Linear, best suited for on/off control. Material: ody: Standard version: rass CW617N CuZn40Pb2 DZR version: rass CW602N CuZn36Pb2s alls: rass CW614N CuZn39Pb3 Stems: rass CW614N CuZn39Pb3 Seats: PTFE O-rings: EPDM (Perox) Surface treatment: Standard version: Chrome plated body, stems and balls. DZR version: Chrome plated stems and balls (body yellow). Marking: IMI T, PN, DN. Connection: Male thread according to ISO 228. Connections (accessories) with female and male thread NPT according to NSI/ SME 1.20.1-2013, or for soldering according to SME/NSI 16.18. Female threads according to NSI/SME 1.20.1-2013. Connection to actuator: F03 and F04 according to EN ISO 5211. ngle of rotation: 90 ctuators: T-M106, T-MC106Y 2
Technical description ctuator Functions: Proportional control 3-point control Manual override Supply voltage: T-M106/24: 24 VC +6% -10% T-M106/230: 230 VC +6% -10% T-MC106Y: 24 VC ±10% Frequency: 50/60 Hz ±5%. Power consumption: T-M106: 3.5 V T-M106Y: 3.0 V Input signal: T-M106: 3-point T-MC106Y: 0(2)-10 VDC, R i 77 kω. (0-10, 10-0, 2-10, 10-2) Output signal: T-MC106Y: 0-10 VDC (0-10, 10-0), max. 8 m, min. 1.2 kω. ctuating time: T-M106: 130 s (at 50 Hz/90 ) T-MC106Y: 150/80 s (at 50 Hz/90 ) djusting torque: 8 Nm Temperature: Medium temperature: max. 80 C Operating environment: 0 C - +50 C Ingress protection: IP43 Protection class: EN 60730 24 VC: III 230 VC: II End position switch-off: Fixed at 90 Cable: 1,5 m, three wire (0,5 mm 2 ) with wire end ferrule Colour: Orange RL 2011, grey RL 7043. Marking: Label: IMI T, CE, product name and technical specification. Connection to valve: F04 according to EN ISO 5211. ngle of rotation: 90 pplication examples Control via the actuator T-Slider 160 Plus or T-Slider 160 KNX R24 and the pressure independent control valve T-Modulator (See connection diagrams T-Slider 160 Plus + T-M106 and T-Slider 160 KNX R24 + T-M106) Control via the actuator T-MC106Y and the T-6-way valve (See connection diagram T-MC106Y) T-Modulator + T-Slider 160 Plus T-Modulator + T-Slider 160 Plus T-COMPCT-P T-COMPCT-P T-COMPCT-P T-COMPCT-P q 0(2) 10 U [VDC] q 0 (2) 3.3 (4.7) 6.7 (7.3) 10 U [VDC] - Valve characteristic best suited for on/off-control. - Pressure independent flow settings for heating and cooling mode with the valve T-COMPCT-P. Control via the actuator T-MC106Y and the T-6-way valve (See connection diagram T-MC106Y) - EQM valve characteristic for best modulating control. - High valve authority thanks to pressure independent control valve. - utomatically adopted flow settings for heating and cooling mode. - The 6-way valve for change-over between heating and cooling. STD STD STD STD - Valve characteristic best suited for on/off-control. - Flow balancing of heating and cooling mode with the valve STD. Note: Differential pressure control with STP/STD is recommended in branches for pressure independent modules. 3
IMI T / Control valves / T-6-way valve NPT threads Installation Flow distribution Kv/Kvs [%] 100 0 0 10 32 45 50 58 80 90 *) Pressurisation NOTE! When designing the pressurisation system: please consider that change-over systems have hydraulic interaction between the cooling and the heating system via the terminals, which cause a fluid mass transfer from the cooling to the heating system. For further information please contact IMI Hydronic Engineering. Example valve + bracket See ccessories 45 *) Pressure balance function: Pressure connection between port 1 and 2, at 32 to 50, for proper pressurisation of the terminal at zero flow. NOTE! ny control valve should be connected to port 3. M4x4 / M8x1 1 2 5 4 3 6 T-M106/T-MC106Y IP43 IP43 IP43 Connection diagram T-M106 3-point T-MC106Y Proportional (0(2)-10 VDC) 24 VC 0 VC 0-10 VDC 0(2)-10 VDC 24/230 VC * 0 VC *) Depending on T-M106 version. 4
T-Slider 160 Plus + T-M106 (See pplication example 1) Modulating control q Dual range modulating control q 0(2) 10 U [VDC] 0 (2) 3.3 (4.7) 6.7 (7.3) 10 U [VDC] T-Slider 160 Plus T-M106 T-Slider 160 Plus T-M106 M M L24 M Y v X v COM NC NO L24 M Y v X v COM NC NO rown White Green Grey Yellow rown lack Grey rown White Green Grey Yellow rown lack Grey COM NC NO L24 M Connec on box COM NC NO L24 M Connec on box * 24 VC 0 VC 0(2)..10 VDC 0(2)..10 VDC 24 VC 0 VC 2-4.7/7.3-10 VDC ** 0(2)..10 VDC *) inary input for toggling between heating and cooling mode. **) Dual range signal 0-3.3/6.7-10 VDC or 2-4.7/7.3-10 VDC. T-Slider 160 KNX R24 + T-M106 (See pplication example 1) Control by KNX bus T-Slider 160 KNX R24 M - + M COM NC NO lack Red Yellow White Dk Green Violet Orange COM NC NO L24 M T-M106 Terminal L24 M Y V X V COM NC NO Description Power supply 24 VC Neutral for power supply 24 VC and signals Input signal for proportional control 0(2)-10 VDC, 47 kω Output signal 0(2)-10 VDC, max. 8 m or min. load resistance 1.25 kω Connection for potential free contact (e.g. open window detection), max. 100 Ω, max. 10 m cable or shielded Common relay contact, max. 250 VC, max. 5 @ 250 VC on resistive load, max. 5 @ 30 VDC on resistive load Normally closed contact for relay Normally open contact for relay - + KNX us 24 VC/VDC 0 VC/VDC * *) inary input can be used to toggle between heating and cooling mode as an alternative to toggling by KNX bus. 5
IMI T / Control valves / T-6-way valve NPT threads Diagram Δp [kpa] 100 90 80 70 Kvs 1.25 Kvs 2.8 Kvs 4 60 50 40 30 20 10 9 8 7 6 5 4 3 2 1 100 200 300 500 1000 2000 3000 5000 q [l/h] Kvs = Kv of both ball valves fully open ( and side equal) 6
rticles Male threads Thread according to ISO 228. Separate connections with NPT threads see Connections. Standard version (chrome plated) DN D L1 L2 H H1 H2 h W Kvs Kg EN rticle No 15 G3/4 42 34 117 29 50 9,4 35 1,25 1,0 8016603306090 322203-13000 DZR version (yellow) DN D L1 L2 H H1 H2 h W Kvs Kg EN rticle No 15 G3/4 42 34 117 29 50 9,4 35 1,25 1,0 8016603308186 322031-30402 15* G3/4 47 39 141 37 60 9,4 41 2,80 1,9 8016603309466 322031-30500 Female threads Threads according to NSI/SME 1.20.1-2013. DZR version (yellow) DN D L1 L2 H H1 H2 h W Kvs Kg EN rticle No 20 3/4 NPT 47,5 48 141 37 60 9,4 40 4,00 2,0 8016603312992 322031-30505 Valve and actuator to be ordered and delivered separately. *) ody marked with DN 20 (connections DN 15). T-M106/T-MC106Y actuators Supply voltage Input signal Kg EN rticle No T-M106 24 VC 3-point 0,5 5902276884016 322204-29000 T-M106 230 VC 3-point 0,5 5902276884023 322204-29001 T-MC106Y 24 VC 0(2)-10 VDC 0,5 5902276884030 322204-29002 7
IMI T / Control valves / T-6-way valve NPT threads Connections D D1 With female thread NPT Threads according to NSI/SME 1.20.1-1983. Swivelling nut L Valve DN D D1 L* EN rticle No 15 G3/4 1/2 NPT 25 7318794017900 52 163-215 D D1 With male thread NPT Threads according to NSI/SME 1.20.1-1983. Swivelling nut L Valve DN D D1 L* EN rticle No 15 G3/4 1/2 NPT 29 4024052928415 2400-02.350 D Ø Soldering connection ccording to SME/NSI 16.18 Swivelling nut L Valve DN D Pipe Ø [in] ~ [mm] L* EN rticle No 15 G3/4 0.629 16.0 16 7318794022904 52 009-715 *) Fitting length (from the gasket surface to the end of the connection). Other type of connections (ISO), see international version of T-COMPCT-P. ccessories H W racket For easier mounting on walls or ceilings. 2 pcs of M4 screws for fixing the valve to the bracket are included in the package. L H W EN rticle No 80 100 80 8016603308032 322031-30000 L The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.imi-hydronic.com. T-6-way valve NPT threads ed.4 07.2018