VGD20... VGD40... Double Gas Valves. Siemens Building Technologies Landis & Staefa Division

Similar documents
Gas Pressure Governors

VKF41...C. Butterfly Valves. Building Technologies Division Industry Sector

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

VLF45... Hot Air Valves. Building Technologies Division

Proportional controlling element

SKPx5... Actuators for Gas Valves. Building Technologies HVAC Products SKP15... SKP25... / SKL25 SKP55... SKP75...

Actuators for Air and Gas Dampers

Actuators for air dampers and control valves of oil burners

Actuators for air dampers and control valves of oil burners

Actuators for Air and Gas Dampers

For air dampers and control valves of oil or gas burners

VGD Series VGDxx.xxxU Gas Valves for use with SKPxx.xxxU electro hydraulic actuators

Actuators for air dampers and control valves of oil burners

Series 42 Self-operated Regulators. Type RS Check Valve (backflow protection)

SQN9... Damper Actuators. Building Technologies HVAC Products. SQN9..., front (covers removed) SQN9..., rear (covers fitted)

ASZ... Potentiometers. Building Technologies Division. ASZxx.3x

Actuators for air and gas dampers

For air / gas dampers and control valves of oil or gas burners

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

Electronic Ignition Module

MBC-300-SE MBC-700-SE MBC-1200-SE MBC-300-N MBC-700-N

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07

Safety. Operating instructions Solenoid valve VGP DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 10.

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01 MB-D(LE) 053 B01

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) 403 B01

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

Actuators for Air and Gas Dampers

Electronic Ignition Equipment

Mounting and Operating Instructions EB 5863 EN. Electric Control Valves. Pneumatic Control Valve

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function Integrated bypass valve MB-ZRD(LE) B07

SERIES 2000 GAS SAFETY SHUT OFF VALVE

Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black Tekn gas Black

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

2-port ball valves with flanged connection, PN25

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function Integrated bypass valve MB-D(LE) B07

Two-port seat valves with male thread, PN16

HS10S-FA. Water station. Product specification sheet

HS10S-FA. Water station. Product specification sheet

Butterfly valves PN6, PN10, PN16

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function MB-ZRD(LE) B01

Modulating Control Valve PN 16 with Magnetic Actuator

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

Electro- Hydraulic Actuator Gas Valves GH-5000

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

Old documentation - Only for your information! Product is not available any more!

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Butterfly valves, PN6, PN10, PN16

2-Port Seat Valves with Flange, PN 25

Modulating control valve PN16

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Combi valves PN 16 with flanged connections

Connection Accessories for small Burner Controls

2-Port and 3-Port Zone Valves PN 16

Gas and air filter. GF/1: Rp 1/2 - Rp 2 GF/3: DN 40 GF/4: DN 50 - DN 100 GF: DN DN 200

Actuators. Building Technologies Division

Self-operated Pressure Regulators Type Universal Excess Pressure Valve

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Air damper actuators

Electromotoric Actuators

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

Differential Pressure Switch QBM81-

Heating Cost Allocation Valve with local acquisition of the flow temperature

FRM. Medium Pressure Regulator. Medium pressure regulator Type FRM

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

3 Edition Product brochure GB AGA

Differential Pressure Switch QBM81-

Double solenoid valve Rp 3/8 - Rp 2 nominal diameters DMV-D/11 DMV-DLE/11

VPI45..Q with pressure test points. Combi valves, PN 25

3-port seat valves PN16 with flanged connection

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 057 D01

FRM. Medium Pressure Regulator. Medium pressure regulator Type FRM

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION

SKP Series SKP15 U.. Gas Valve Actuator with Safety Shutoff Function

Modulating control valve PN16 with magnetic actuator

ANSI version. The valve closes when the differential pressure rises

Type 2511/12. Type Type 2030 Cable plug. ASI cable plug. Dosing control. General technical data Orifice Type 6518

3-port seat valves PN16 with flanged connection

B21 Series BASOTROL Gas Valve

Flow controller (PN 25) AVQ - return and flow mounting

2-port seat valves PN16 with flanged connection

Cooling water Chilled water Low temperature hot water C Water with anti-freeze (max. 50%vol.)

Cable Temperature QAP... Sensor. Use

822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE

TECHNICAL MANUAL MT029

SQL35.00 SQL85.00 SQK angle of rotation

Valve Series V2001 Three-way Valve Type 3323

Modulating control valves with magnetic actuators, PN 16

Actuators for small valves

Modulating control valve PN16 with magnetic actuator

3-port seat valves PN10 with flanged connection

Solenoid Valves Type 3963

Gas pressure regulator R 100 / R 100U / R 100UD

3-Port Seat Valves with Flange, PN 6

Transcription:

7 631 ISO 9001 VGD40... Double Gas Valves VGD40... Double gas valves for use on gas trains, consisting of 2 safety shut-off valves of class A. Suited for use with gases of gas families I...III. The double gas valve is to be combined with 2 actuators of the SKP line (e.g. to provide the functions of 2 safety shut-off valves in series, complete with gas pressure governor). The / VGD40... and this Data Sheet are intended for use by OEMs which integrate the double gas valves in their products. Use The double gas valves are used primarily on gas trains for burners. In combination with appropriate SKP actuators, the valve also serves as a: - shut-off valve (in connection with SKP10...) - control valve with shut-off function (in connection with SKP20..., SKP27..., SKP50... or SKP70...). For description and function of the SKP... actuators, refer to the relevant Data Sheets: SKP10... / SKP20... Data Sheet 7641 SKP11... Data Sheet 7639 SKP27... Data Sheet 7644 SKP50... Data Sheet 7648 SKP70... Data Sheet 7651 22.02.2001 Landis & Staefa Division

Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! It is not permitted to open, interfere with or modify the double gas valve VGD40... Fall or shock can adversely affect the safety functions. Such valves may not be put into operation, even if they do not exhibit any damage. Mounting notes The relevant national safety regulations must be complied with The double gas valve can be mounted either vertically or horizontally (spring housing either horizontally or pointing downward) The direction of gas flow must be in accordance with the arrow on the valve body When used in combination with the SKP20..., SKP27..., SKP50... or SKP70... actuator, the minimum gas pressure switch must always be mounted upstream of the double gas valve! VGD40... The electrohydraulic SKP10... actuator, which is used for shut-off functions, must always be mounted on the inlet side while the actuators with integrated governor (SKP20..., SKP27..., SKP50... or SKP70...) must always be mounted on the outlet side of the valve (with a contoured disk) To mount the double gas valve, 2 flanges type AGA41... / AGA51... are required To prevent cuttings from getting inside the valve, first mount the flanges to the piping and then clean the associated parts Ensure that the O-rings are fitted between the flanges and the valve body Ensure that the gaskets are fitted between the flanges Check to ensure the bolts on the flanges are properly tightened Check to ensure the connections with all components are tight Installation notes Installation work must be carried out by qualified staff. Commissioning notes Commissioning work must be carried out by qualified staff. Disposal The unit contains hydraulic oil, it is not allowed throwing into household garbage. Pay attention to the local and actualize law. 2/10

Mechanical design The double gas valves are of the normally closed type and have 2 disks, one non-contoured disk on the inlet side and one contoured disk on the outlet side. The stems are guided on both sides of the disks, thus ensuring precise alignment and tight shut-off. The closing force of the return spring is supported by the prevailing gas pressure (class A to EN 161). A removable strainer on the inlet side protects the valve and downstream controls against dirt. Valve body and connecting flanges are made of die-cast aluminium, the seals of nitril rubber, and the stems of stainless steel. The double gas valves feature a pilot gas connection Rp¾" (refer to «Type summary» and «Dimensions»). Gas valve, flanges and actuators are supplied as separate items. No special tools are required for assembly. Connecting flanges AGA41 / AGA51 for The connecting flanges are provided with a test point. They are internally threaded and supplied as separate items, together with the necessary accessories, such as bolts, nuts, seals, etc. The overall flange dimensions and bore-holes are identical so that all types of flanges can be fitted to the valve body, irrespective of their nominal size. This means that a 1½" flange can be fitted to a 2" VGD... valve, and vice versa. Each double gas valve requires 2 connecting flanges, which are to be ordered as separate items. Sectional view of V1 V2 Connecting flange Profiled valve disk 7631z03e/0101 Application example with SKP10... and SKP70... (mounted on «V2») 3/10 Landis & Staefa Division 22.02.2001

VGD40... The VGD40... double gas valves are double seat disk valves of the normally closed type. The stems are guided on both sides. The patented double seats are closed by 2 springs. The spring of each stem exerts a pressure on the disk so that there is a defined closing force acting on each disk. The surface area proportions of the 2 valve disks per stem are such that the closing force increases as the inlet pressure increases (class A valve to EN 161). A removable strainer on the inlet side protects the valve and downstream controls against dirt. The double gas valves DN65 150 correspond to the standard valve sizes of single valves (conforming to EN 558). Sectional view of VGD40... V1 V2 7631z02/1100 The VGD40... are supplied with a pilot gas flange having a ¾ connection for the pilot gas line and a ¼ connection for an impulse line. This impulse line connection between the 2 valves and another impulse line connection on the outlet flange can be connected directly to the SKP20 constant pressure governor fitted to «V1» or «V2». A universal mounting plate facilitates attachment of a number of commercially available pressure switches or valves proving devices. Both the pilot gas flange and the universal mounting plate are exchangeable and can be fitted on either side of the valve. Application example VGD40.080 with SKP10... and SKP20... (mounted on «V2»). 4/10

Type summary Double gas valves Flanges Service replacement sets (for only) DN Flow rate at p = 10 mbar m³ / h air¹) Type reference 1 ½ 85 VGD20.403 2 100 VGD20.503 40 85 VGD40.040 50 100 VGD40.050 65 160 VGD40.065 80 250 VGD40.080 100 400 VGD40.100 125 580 (630 ²)) VGD40.125 150 700 (800 ²)) VGD40.150 ¹) Flow rate to EN 161 2) Flow rate with future SKP...line (available from 2002) For use with with test point Rp ¼ (to be ordered as separate items) Type DN 1 ) For double gas valve AGA41 1 ½ VGD20.403 AGA51 2 VGD20.503 1 ) Internally threaded to ISO R 7/1 Consisting of: Stems, disks, strainer and screws, washers and seals: For double gas valve Part number VGD20.40... 4 679 1550 0 VGD20.50... 4 679 1550 0 Ordering only When ordering, please give type references of double gas valve and flanges. Example: Double gas valve 2 with 2 connecting flanges 1 VGD20.503 2 AGA51 The SKP... actuators are to be ordered as separate items. VGD40... only When ordering, please give type reference of double gas valve. Example: Double gas valve DN80 1 VGD40.080 The 2 lateral mounting plates for the pilot gas connection and a universal adapter plate are included and ready fitted. The SKP... actuators are to be ordered as separate items. 5/10

Technical data General data Class A (EN 161) Group 2 (EN 161) Types of gases gas families I, II, III (to G260 of DVGW) air Built-in strainer, mesh size 0.9 mm Flow rates refer to «Flow chart» Perm. medium temperature -15...+60 C Mounting spring housing horizontal or vertical, pointing downward Flanges VGD40... to ISO 7005; PN16 Materials - - VGD40... Net weight - VGD... - AGA41 - AGA51 die-cast aluminium sand-cast aluminium refer to the table below approx. 266 g approx. 264 g Max. permissible operating pressure: Double gas Static pressure / mbar valve (with double gas valves closed) Dynamic / mbar Weight (approx.) Volume between V1 / V2 (dm³) VGD20.403 600 3.2 kg 0.75 VGD20.503 600 3.15 kg 0.8 VGD40.040 1000 7 kg 0.8 VGD40.050 1000 7,2 kg 0.8 VGD40.065 1200 700 8.4 kg 1.3 VGD40.080 700 9.6 kg 1.53 VGD40.100 700 12.9 kg 3 VGD40.125 700 18.2 kg 5.175 VGD40.150 700 24.1 kg 8.7 Environmental conditions Transport IEC 721-3-2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range -15...+60 C Humidity < 95 % r.h. Operation IEC 721-3-3 Climatic conditions class 3K5 Mechanical conditions class 3M2 Temperature range -15...+60 C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! 6/10

Function / VGD40... Simplified sizing example VGD... with SKP70... Prerequisites Gas outlet of burner toward combustion chamber Simplified example Combustion chamber = 0 mbar pressure constant Required control ratio RV = 4:1 Gas inlet pressure 20 mbar 1. Nominal load Burner pressure at nominal load 16 mbar Volumetric flow at nominal load 200 m³ / h natural gas, corresponding to 156 m³ / h air - pvgd40.080 at nominal load 20-16 = 4 mbar Point «PA» in the chart Point «PA» placed on the characteristic line or on the right side of the characteristic line. 2. Low-flame PG min = PG max 16 mbar = = 1mbar 2 RV 16 3 VGas max 200 m / h 3 VG min = = = 50 m corresponding to RV 4 3 h = 39 m / h air Point «PB» in the chart - Selected valve size: VGD40.080 Point «PB» placed on the characteristic line or on the left side of the characteristic line. Conversion of air volume to a corresponding gas volume (natural gas) Basis for scale Abscissa Medium volumetric flow QG in m³ / h Density ratio dv to air 1 Natural gas 0.61 1.28 2 Propane 1.562 0.8 3 Town gas 0.46 1.47 4 Air 1 1 Conversion factor 1 f = dv Conversion to air (m³ / h) from other types of gases: QG QL = f QL = air volume in m³ / h that produces the same pressure drop as «QG». 7/10

Sizing flow chart for VGD... 3 m /h VGD40.150* VGD40.125* VGD40.150 VGD40.125 VGD40.100 VGD40.080 VGD40.065 VGD40.050 / VGD20.503 VGD40.040 / VGD20.403 VDG40.150 PA x VGD40.125 VGD40.100 VGD40.080 VGD40.065 VGD40.050 / VGD20.503 VGD40.040 / VGD20.403 PB x Minimum flow Maximum flow (valve fully open) Points "PA / PB", refer to chapter Function "Simplified sizing example" PA / PB = Operating points 8/10

Combinations of VGD40... and actuator (here with SKP10... and SKP20...) PM 100 2 92,5 57 7631m07e/0201 Pi 310 30 Valve proving device "A" and pressure switch (Pi) Valve proving device "A" and pressure switch (Pi) 107 61 Valve proving device "A" 2 pressure switches (PM, Pi) Valve proving device "A" 210,2 453 Ancillary units Legend Pi Inlet pressure upstream of valve 1 PM Intermediate chamber pressure upstream of valve 2 9/10

Dimensions SKP... C SKP... 19 50 63,5 63,5 50 19 B Rp1/4" G3/4" B Rp1/4" AGA41 or AGA51 19,5 103 30 AGA41 or AGA51 DN SW80 61 A 265 10 11/2": 22,5 2": 27,5 7631m05e/0101 F G 3/4" Rp 1/4 Rp 1/4 D B M E I VGD40... P G A K L C Pressure switch plate Pressure switch plate Rp 1/8 Q Pm 22 J 58 Pm 22 2 16 Pilot gas connection 11 5 17 7 Pi 2 Pm Rp 1/8 Pi 7631m02e/0101 Dimensions Type reference DN A B C D E F G I J K L M P Q VGD40.040 40 240 195 168 115 58 88 110 77 79 20 50 2 19 70 VGD40.050 50 240 202 174 115 58 88 125 77 79 20 50 2 19 70 VGD40.065 65 290 215 194 118 60 102 145 87 90 30 60 4 19 81 VGD40.080 80 310 236 204 132 54 107 160 90 92 30 60 2 19 88 VGD40.100 100 350 259 227 145 43 131 180 105 108 41 71 13 19 99 VGD40.125 125 400 305 255 175 31 150 210 119 122 41 71 25 19 113 VGD40.150 150 480 335 293 188 20 168 240 140 143 39 69 36 23 134 36 54 10/10 2001 Siemens Landis & Staefa Produktion GmbH Landis & Staefa Division Subject to alteration 22.02.2001