SICOP. Bimetal Overload Relays Type 3UA5/6 & 3UC5/6. Introduction. Application

Similar documents
Bimetal Overload Relays 3UA and 3UC

Contactor Relays 3TH30

Ph.no / Kanchan Eneterprises. id- DOL Starter Type 3TW42 00 (open execution)

Miniature Circuit Breaker

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.

Controls. THERMAL OVERLOAD RELAYS RW..D (up to 40A)

Meta Solution. Contactors and Overload relays

SIRIUS 3RU2 Thermal Overload Relays

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400

About us. Switchgear Factory, Mumbai

Meta Solution. Contactors and Overload relays

3VU13, 3VU16 Circuit-Breakers

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

MINIATURE CIRCUIT BREAKER

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

KD LV Motor Protection Relay

Motor Protection Circuit Breakers 3VU13 and 3VU16

AF40... AF96 3-pole contactors Technical data

All round protection guaranteed

LR9 F OVERLOAD RELAYS

K50H004UP cam changeover switch - 4-pole A - screw mounting

Industrial Contactors CTX 3 3P 185A - 800A

Protection Equipment. Overload Relays. Reference Manual 04/2011. Industrial Controls. Answers for industry.

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29

THERMAL OVERLOAD RELAYS

Overload Relays. SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A for standard applications. 5/78 Siemens IC Overview

Manual Motor Starters. Meta-MEC

General technical data. Ambient conditions

27Overload Relays. Overview Combinations of overload relays and contactors SIRIUS 3R. Thermally delayed overload relays CLASS 10

Thermal overload relay TF65 and TF96

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

Manual Motor Starters

SENTRON Switching and Protection Devices Switch Disconnectors

CA Z-EN Overload relays, CT-operated overload relays

K30H001YP cam star-delta switch - 3-pole A - screw mounting

FMotor Circuit Controllers

LV Switchgear Maximum Retail Price w.e.f 15 th December, Answers for industry.

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products

Thermal Overload Relays

Contactors and Overload Relays

CI-TI Contactors and motor starters Types CI 61 - CI 98

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

Technical Information

K63F003UP cam changeover switch - 3-pole A - screw mounting

K50F003UP cam changeover switch - 3-pole A - screw mounting

AF / AF30Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

Protection components

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

AF / AF16Z pole Contactors AC / DC Operated - with Screw Terminals

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

(Miniature Circuit Breaker)

Electronic Circuit Breaker ESS20-0..

General technical data: CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S0 SCREW TERMINAL. product brand name

Short form catalogue. Motor protection & control

General technical data: CONTACTOR, AC-3, 4KW/400V, 2NO+2NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL REMOVABLE AUX. SWITCH. product brand name

Industrial Protection Products Edition

Modular contactors and relays

Thermal overload relays Type TA Class 10

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

Ktec Contactors and thermal overloads

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Selection Guide Motor Control Device Solutions

Contactor Types CI 61-98

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

Power distribution. RiLine fuse elements. NH fuse-switch disconnectors, size 000. For mounting plate assembly

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

General technical data: CONTACTOR, AC-3, 5.5KW/400V, 1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S00 SCREW TERMINAL. product brand name

DPX moulded case circuit breakers

01 Spectra Plus - Introduction

AF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals

CI-TI Contactors and Motor Starters Type CI 6-50

RESIDUAL CURRENT CIRCUIT BREAKER

Modular contactor for installation into distribution boards

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Motor Protection Circuit Breaker

S840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en

Mini contactors B6, BC6 with 3 pole


C -5 to +55 (0.8 to 1.1Uc) Permissible o

Combined instrument transformers

Essential equipment for all your requirements

Moulded Case Circuit Breakers

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B

Series KTU7 UL489 Molded Case Circuit Breakers

Thermal overload relay TF140DU and TF140DU-V1000

3 - Protection components Motor circuit-breakers

General technical data: CONTACTOR, AC-3, 18.5KW/400V, 1NO+1NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL. product brand name

Installation instructions for ATS panel Ref:ATS --/2 M2GC705 Issue

AE 9... AE 40 Contactors NE... Contactor Relays

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors

LA Motor Protection. A South African Company to be Proud of

Transcription:

s SICOP Bimetal Overload Relays Type 3UA5/6 & 3UC5/6 Introduction The bimetal overload relays type 3UA5/6 & 3UC5/6 relays are indigenously manufactured and bring to the users a whole range of benefits, which are a direct result of extensive R & D efforts in design, materials and manufacturing technology. They also incorporate additional features/benefits as a result of feedback from the users of our 3UA19 relays. Application 3UA5 and 3UA5 are triple pole adjustable bimetal overload relays with built in single phasing protection. In conjunction with contactors and other motor control equipment, they provide accurate and reliable protection to motors against overload and single phasing as per 'Class 10A', in conformance to IEC 947-1-4 and IS 13947-4-1. They also offer protection against unbalanced voltages. reliable protection to motors, with an acceleration time upto 30 sec. and starting current upto 6 times the rated current, against overload and single phasing as per 'Class 30', in conformance to IEC 947-4-1 and IS 13947-4-1. The 3UC5/6 relays comprise of 3 saturable current transformers, a resistance unit and a special bimetal relay connected to the secondary winding of the C.T. It is a composite unit with bimetal relay mounted on the C.T.s. For mounting the C.T. and relay separately, please enquire. The saturable current transformers linearly transform the current upto approx. twice the set current, but above this value the transformer core gets saturated and the secondary current is proportionately less. Thus, these relays permit heavy starting conditions of motors and offer dependable protection against overload. 3UC5 and 3UC6 are triple pole adjustable, saturable C.T. operated bimetal overload relays (with built in single phasing protection feature). They are ideal for heavy starting applications, when heavy masses are to be put in motion with the resultant long starting period. In conjunction with contactors and other motor control equipment, they provide accurate

Description Salient Features Built-in single phasing protection Besides 3 phase overload protection, the relays offer a builtin single phasing protection using differential slider principle. Temperature Compensation The relays are temperature compensated between service temperatures of -25 C to +55 C. Overlapping Setting Ranges For proper selection of overload relays to match the current drawn by the motors, a number of overlapping ranges are incorporated. decide the insertion depth of the connective wire. As the wire cannot now protrude into the relay housing, it does not hamper the movement of the auxiliary contacts. Further, since the insertion depth is predetermined, insulation of the cable can be cut accordingly and the possibility of insulation getting inadvertently caught under the terminal, is avoided, Screw-driver guides reduce wiring time as they allow the use of power screw-drivers. Auxiliary Contacts Potential free 1NO + 1NC contact arrangement is provided as a standard feature. The 1NO contact above can be used for various applications such as annunciation. International Terminal Markings The terminal markings on the relay conform to international standards. The clear markings for power and auxiliary terminals in accordance with IS/IEC are incorporated to facilitate easy wiring and to minimise wiring errors (Fig. 1). Short-circuit Protection The relays protect themselves against overload upto 10 times the maximum setting. Beyond this, i.e. in the short circuit zone, the relays must be protected by a short circuit protection device (HRC fuses as per the details given in the selection table.) Other features and benefits SIGUT termination The relays have the Siemens patented SIGUT termination technique. It is acknowledged worldwide to be "user friendly". The SIGUT feature increases safety and reduces wiring time. It includes the following: Shrouded auxiliary terminals increases safety as they protect against accidental contact with live parts. Ready to wire terminals and captive screws reduce wiring time. The screws being captive, do not fall out. Hence, the relays are delivered with untightened terminals, i.e. in ready-to-wire condition. This eliminates the operation of untightening terminals before wiring. Funnel shaped cable entrances reduce wiring time by facilitating quick location of the connecting wire. 'Cable-End-Stops' reduce wiring and testing time as they Fig. 1 Terminal markings & Internal connection diagrams Mounting Relays type 3UA50, 52, 55, 58 & 5830 are suitable for mounting on SICOP power contactors (Fig. 2). However, a simple accessory is available for converting contactor mounting relay to individual mounting, (Fig. 3) suitable for screw type mounting & DIN RAIL (35 mm) mounting. Relays type 3UA68 & 3UC5/6 are suitable for screw type mounting and also for DIN RAIL (75 mm) mounting. Fig. 3 Mounting Adaptor Fig. 2 Contactor mounting 2

Controls Current setting (P1) A recessed dial is provides for easy setting of the relay from the front. Since the dial is recessed, there is no possibility of accidental change in current setting. Changeover from manual reset to automatic reset (P2) The relays are supplied in manual reset execution. They can be easily converted from manual reset mode to automatic reset mode from the front just by turning the blue knob. As a standard practice, trip free feature is incorporated in the Reset push button. Test Button (P3) The trip circuit can be manually checked by this Red button. Accessories Adaptor: To convert contactor mounting relay to individual mounting, (Fig. 3) suitable for screw type mounting & DIN RAIL (35 mm) mounting. * Protective cover: To avoid tampering of the setting, auto Trip indicator (P4) A separate mechanical Green Trip Indicator is provided in the front cover of the relay to indicate the tripped state of the 'manual reset' relay. P1 Fig. 4 Controls manual mode or test button. (Fig. 5) * Reset cord: To reset the relay in switchboard with door closed. (length: 400/600 mm) (Fig. 6) * Reset slider with funnel: P3 P2 P4 Identification tag (P5) Blank identification tag is incorporated on every bimetal relay to enable the user to designate it suitably. P1 - Recessed Dial P2 - Manual/Auto Reset (Trip-free) P3 - Test Button P4 - Trip Indicator (HR Mode only) P5 - Identification tag Instead of reset cord for resetting the relay in switchboard with door closed. (Fig. 7) Connection links: For connection of individual mounted relays to contactor. (Fig. 8) Fig. 5 Protective cover Fig. 7 Reset Slider + Funnel 400mm-3UXI 015 600mm-3UXI 016 Fig. 6 Reset Cord with Holder Fig. 8 Connecting link for 3UA62 30 & 3UC66 30 * Only one of the three can be used at a time. 3

Technical Data Type 3UA50 3UA52 3UA55 3UA58 Trip class 10A Phase failure protection Changeover to auto-reset at site RESET button (trip-free) Blue Ambient temperature compensation Trip indicator Green TEST button Red Terminal for contactor coil X Permissible service temperature 25 C to +55 C Mounting Contactor/ Contactor/ Contactor/ Contactor/ 3TB40/41 3TF42/43 3TF44/45 3TF46 to 49 Main Circuit Rated current (Max) A 14.5 25 45 80 Rated insulation voltage Ui V 690 690 690 1000 (Pollution degree 3) Rated impulse withstand Uimp kv 6 6 6 8 Heating Direct Direct Direct Direct Conductor cross-section Solid or stranded sqmm 2.5 to 6 2.5 to 6 1.5 to 25 2.5 to 35 Finely stranded with end sleeve sqmm 1.5 to 4 1.5 to 4 1 to 16 1.5 to 25 Multi-conductors with cable lugs sqmm Flats sqmm Terminal screw M4 M4 M5 M5 Power loss per pole (max) Minimum setting W(VA) 0.9 0.9 1.2 2.6 Maximum setting W(VA) 2.25 2.25 3 4 Auxiliary Circuit (application for all types) Auxiliary contacts 1NO + 1NC (Potential free) Rated thermal current Ith A 6 Short circuit protection (max) A 6 (HRC Fuse type 3NA1) Switching capacity AC15 V 24 60 125 230 415 500 A 2 1.5 1.25 1.15 1 1 DC13 V 24 60 110 220 A 1 0.4 0.22 0.1 Conductor cross-section Solid or stranded sqmm 2 x (1 to 2.5) Finely started with end sleeve sqmm 2 x (0.75 to 1.5) Terminal screw M3.5 * For relay above 180 A 4

3UA5830 3UA6230 3UA6830 3UC5030 3UC5830 3UC6230 3UC6630 10A 30 X X X X X X X Contactor/ Individual Individual Individual Individual Individual Individual 3TF50 120 400 630 12.5 63 160 400 1000 1000 1000 1000 1000 1000 1000 8 8 8 8 8 8 8 Direct Indirect Indirect Indirect Indirect Indirect Indirect 35 to 70 50 to 120/ 2 x 240 1 to 4 240* 1 to 2.5 35 120 240 50 to 120/ 2 x 240 240* 1 x 20 x 3/ 2 x 30 x 5 1 x 15 x 3 1 x 20 x 5 2 x 30 x 5 2 x 3- x 5* M8 M10 M10 M4 M6 M8 M10 2.8 5 6(9) 2.5 2.5 3.5 5.5 4 7 15(22) 6.5 6.5 9 14 Fig. 9 3UC66 Fig. 10 Birelay with adaptor for individual mounting 5

Selection Table Setting range Type reference Backup Mounting HRC fuse 3NA1 (A) A (max) Normal Motor Starting time 3UA50 0.1-0.16 3UA50 00-0A 2 0.16-0.25 3UA50 00-0C 2 0.25-0.4 3UA50 00-0E 2 0.4-0.63 3UA50 00-0G 2 0.63-1 3UA50 00-0J 2 0.6-1.25 3UA50 00-0K 4 1-1.60 3UA50 00-1A 6 With 1.25-2 3UA50 00-1B 6 Contactor 1.6-2.5 3UA50 00-1C 6 3TB40/41 2-3.2 3UA50 00-1D 10 2.5-4 3UA50 00-1E 10 3.2-5 3UA50 00-1F 16 4-6.3 3UA50 00-1G 16 5-8 3UA50 00-1H 20 6.3-10 3UA50 00-1J 25 8-12.5 3UA50 00-1K 25 10-14.5 3UA50 00-2S 25 3UA52 1-1.6 3UA52 00-1A 6 1.25-2 3UA52 00-1B 6 1.6-2.5 3UA52 00-1C 6 2-3.2 3UA52 00-1D 10 2.5-4 3UA52 00-1E 10 3.2-5 3UA52 00-1F 16 With 4-6.3 3UA52 00-1K 16 Contactor 5-8 3UA52 00-1H 20 3TF42/43 6.3-10 3UA52 00-1J 25 8-12.5 3UA52 00-1K 25 10-16 3UA52 00-2A 32 12.5-20 3UA52 00-2B 50 16-25 3UA52 002C 50 3UA55 10-16 3UA55 00-2A 32 12.5-20 3UA55 00-2B 50 16-25 3UA55 00-2C 50 With 20-32 3UA55 00-2D 80 Contactor 25-36 3UA55 00-2Q 80 32-40 3UA55 00-2R 80 36-45 3UA55 00-8M 80 3UA58 16-25 3UA58 00-2CZ1 50 20-32 3UA58 00-2DZ1 63 25-40 3UA58 00-2EZ1 80 With 32-50 3UA58 00-2FZ1 100 Contactor 40-57 3UA58 00-2TZ1 100 3TF46-Z/ 50-63 3UA58 00-2PZ1 125 3TF47-Z 57-70 3UA58 00-2VZ1 125 3TF48 63-80 3UA58 00-2UZ1 160 3TF49 70-95 3UA58 00-8YZ1 160 16-25 3UA58 00-2CZ2 50 20-32 3UA58 00-2DZ2 63 25-40 3UA58 00-2EZ2 80 With 32-50 3UA58 00-2FZ2 100 Contactor 40-57 3UA58 00-2TZ2 100 3TF47 7 50-63 3UA58 00-2PZ2 125 57-70 3UA58 00-2VZ2 125 63-80 3UA58 00-2UZ2 160 3UA58 30 70-95 3UA58 30-5B 160 With 85-105 3UA58 30-5C 160 Contactor 95-120 3UA58 30-5D 200 3TF50 Setting range Type reference Backup Mounting HRC fuse 3NA1 (A) A (max) 3UA62 30 85-135 3UA62 30-5A 224 115-180 3UA62 30-5B 250 160-250 3UA62 30-5C 400 Individual 200-320 3UA62 30-5D 400 250-400 3UA62 30-5E 500 3UA68 30 320-500 3UA68 30-3F 500 Individual 400-630 3UA68 30-3G 630 Long Motor Starting time (Heavy duty) 3UC50 30 2.5-4 3UC50 30-1E 16 4-6.3 3UC50 30-1G 25 Individual 6.3-10 3UC50 30-1J 25 8-12.5 3UC50 30-1K 32 3UC58 30 10-16 3UC58 30-2A 32 16-25 3UC58 30-2C 63 Individual 25-40 3UC58 30-2E 100 40-63 3UC58 30-2G 125 3UC62 30 63-100 3UC62 30-2J 250 Individual 100-160 3UC62 30-3A 315 3UC66 30 125-200 3UC66 30-3B 500 160-250 3UC66 30-3C 630 Individual 200-320 3UC66 30-3D 630 250-400 3UC66 30-3E 630 Accessories Description Type reference Relay type Reset Plunger 3UX1 011 Funnel 3UX1 013 3UA50/3UA6230 Reset cord with 3UX1 015 3UC50/58/62/66 Holder (400mm) Reset cord with 3UX1 016 Holder (600mm) 3UA50/3UA6230/ Protection Cover 3UX1 111 3UA6830/52/55 3UC50/58/62/66 Protection Cover 3UX1 110 3UA58/3UA5830 Adaptor to 3UX1 418 3UA50 convert to 3UX1 420 3UA52 individual 3UX1 425 3UA55 mounting 3UX1 421 3UA58 3UX1 421-0XA 3UA5830 3UX 1206 3UC58 with 3TF48/49 3UX 1221 0YA 3UC62 with 3TF48/49 3UA62 or 3UC62 or Connecting 3UX 1221 0YA 3UC66 with Strips 3TF50/51/52 3UX 1211 3UA62 or 3UC66 with 3TF53/54/55/56 3UX 1211 3UA68 with 3TF56 3UX 1218 3UA68 with 3TF57/68 3UA5800-2 or to 3UX58 11 3UA5800-2 Z2 to 3UA5800-2 Z1 Set of terminals 3UA5800-2 Z1 or convert relay 3UX58 12 3UA5800-2 Z2 to type 3UA5800-2 3UA5800-2 or 3UX58 13 3UA5800-2 Z1 to 3UA5800-3 Z2 6

Characteristic Curves The characteristics given are mainly intended the inverse time current characteristics of the same, the tripping times shown are for relay starting from the cold state. At operating temperatures (heated at rated current) these are reduced to about 25% of the value obtained from these characteristics curves. The above curves are the general characteristics curves; for individual characteristics curves of each rating, please contact our nearest sales office. 7

Dimensions (mm) 3UA50 with individual Mounting Adapter Type 3UX1 418 ** Dimension for the square OFF-button (stroke 3mm) Dimension for the round RESET-button (stroke 2.5mm) less 2.5mm 1) For 35mm standard (DIN) mounting rail 3UA50 mounted on 3TB40/41 Auxiliary Contact a b c d 1NO or 1NC 125 85 108 55 1NO + 1NC or 130 100 100 60 2NO + 2NC 2) Minimum clearance from earthed element 10mm 8

Dimensions (mm) 3AU52/55 with individual mounting ** Dimension For square OFF button (Stroke 3mm) For Round RESET button (Stroke 2.5mm) less 2.5 mm 1) Suitable for DIN RAIL 35mm as per DIN EN 50022 Type Dim a b 3UA52 + 3UX1420 M4 14.3 3UA55 + 3UX1425 M5 18.2 3UA52 mounted on 3TF 42/43 * Minimum clearance from the earthed components. ** Dimension For square OFF button (Stroke 3mm) For Round RESET button (Stroke 2.5mm) less 2.5mm 9

Dimensions (mm) 3UA55 mounted on 3TF 44/45 * Minimum clearance from the earthed components. ** Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke 2.5mm) less 2.5mm *** Width for the 3TF4411 and 3TF4511 contactors 1) Suitable for DIN RAIL 35mm as per DIN 50022 3UA58 with individual mounting adaptor type 3UX1 421 Dimensions (mm) 3UA5800 mounted on 3TF46/47 3UA5800_.. Z1 mounted on 3TF48/49 * Minimum clearance from the earthed components. ** Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke 2.5mm) less 2.5mm 1) Suitable for DIN RAIL 35mm as per DIN 50022 * Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke = 2.5mm) less 2.5mm 1) Minimum clearance from insulated components : 3mm Minimum clearance from earthed components: 10mm 3UA58+ a1 a2 a3 b1 b2 b3 c1 d1 d2 d3 e1 e2 f1 f2 f3 g φg1 φg2 3TF46/47 90 113 70 117 175 100 123 8 25 25 94 34 80 63 122 28 4.8 6.1 3TF48/49 100 123 80 133 194 110 140 10.5 25 26.5 116 31.5 89 71 132 39 5.5 6.1 10

Dimensions (mm) 3UA5800_.. Z2 mounted on 3TF47 7 * Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke = 2.5mm) less 2.5mm 1) Minimum clearance from insulated components : 3mm Minimum clearance from earthed components: 10mm 3UA5830 with individual mounting adaptor type 3UX1 421 - OXA 3UA5830 mounting on 3TF50 * Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke 2.5mm) less 2.5mm 1) Suitable for DIN RAIL 35mm as per DIN 50022 * Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke 2.5mm) less 2.5mm 1) Minimum clearance from insulated components : 3mm Minimum clearance from earthed components: 10mm 11

Dimensions (mm) 3UA6230 CT Operated Birelay ** Dimension For square OFF button (Stroke 3mm) For round RESET button (Stroke 2.5mm) less 2.5mm Range A 85-135A 20 115-180A 160-250A 200-320A 25 250-400A 3UA68 CT Operated Birelay ** Dimension For TEST button (Stroke 3mm) For Round RESET button (Stroke 2.5mm) less 2.5mm 2) Suitable for DIN RAIL 75mm as per DIN EN 50023 12

Dimensions (mm) 3UC50 CT Operated Birelay ** Dimension For Square OFF button (Stroke 3mm) For Round RESET button (Stroke 2.5mm) less 2.5mm 2) Suitable for DIN RAIL 75mm as per DIN EN 50023 3UC5830/3UC6230/3UC6630 CT Operated Birelay Relay Type A B C D E F 3UC58 30 46 135 69 6.6 150 15x3 3UC62 30 46 140 69 9 160 20x3 3UC66 30-3B (200A) 50 146 69 9 160 20x3 3UC66 30-3C/3D-3E(400A) 50 146 70 11 171 25x4 ** Dimension For TEST button (Stroke 3mm) For Round RESET button (Stroke 2.5mm) less 2.5mm 2) Suitable for DIN RAIL 75mm as per DIN EN 50023 13

Switchgear Division Control Systems & Products P.B. No. 85 Thane Belapur Road Thane 400 601 Tel : (022) 7692381-4 Fax : (022) 7694626 Siemens Ltd. SGR-01-102-023 This replaces SGR-01-102-016 Product upgradation is a continous process. Hence, data in this booklet is subject to change without prior notice. For the latest information, please get in touch with our Sales Offices. 019905 UNIFORM