ROTARY PRESSURE INDEPENDENT CONTROL VALVE TECHNICAL MANUAL

Similar documents
Terminator PICV. Technical Manual

Direct/Factory Mounting Valve Set

Pressure Independent Control Valve

VE-S_15-32 Pressure Independent Balancing & Control Valves

Technote. Frese OPTIMA Compact DN10-DN50 - pressure independent balancing & control valve. Application. Features. Benefits.

PCS. HVAC Products. Technical submission. Type of Product

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits.

Pressure Independent Control Valve

Pre-Fabricated Flushing Bypass Assembly for Plant Applications Hero Plant DN15-150

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Plant Applications Hero Plant DN15-150

VP1000. Pressure Independent Control Valve. Product Bulletin

Pressure Independent Control Valve

Balancing Valves. Venturi Commissioning Valve (FODRV) & (DRV) Cu x Cu Compression DN10-DN50. BOSS TM 901SC Venturi DRV DN

Ballorex Venturi 3.1 Introduction

2-port and 3-port ball valves PN 40

Pressure Independent Control Valve. Technical manual

Technote. Frese ALPHA HCR Dynamic Balancing Valve. Application. Features. Benefits. Design. Installation. Operation.

FCU 6-PORT PICV VALVE SET MODULE BROCHURE

VZ*19* VZ219E, VZ319E, VZ419E VZ219C, VZ319C, VZ419C

FlowCon Energy FIT System

Balancing Basics. Mike Weisman, ASHRAE Treasurer. ASHRAE Golf Outing: May 18 th, 2018! HEATHERWOODE

Fig.306F (DN50-150) Pressure Independent Control Valve (PICV)

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

Flow Data for NIBCO Circuit Balancing Valves 1/2 to 2 (Figure Number 1710)

Figure 1710 Flow Data

P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends

Automatic balancing valves ASV-PV DN (3rd gen.)

Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings

Combined automatic balancing valve AB-PM valve DN 10-32, PN 16

Modulating control valve PN16 with magnetic actuator

VG6000 Series Forged Brass Valves

Modulating control valve PN16 with magnetic actuator

2-port ball valves with flanged connection, PN25

VPI45.. VPI45..Q. Combi valves, PN 25. Building Technologies. VPI45..Q with pressure test points ACVATIX

HERZ-Connect 4 / Compact Connect 4 & Commissioning Centres

CIMBERIO VALVES. SAV Systems. Product Brochure.

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

3-port seat valves, external thread, PN16

FO-BV Series. Fixed-orifice balancing and control valves. Technical Data Sheet. WattsIndustries.com

TRF.. series spring return rotary actuators for CCV

Ballorex Vario. Description. Versions. Benefits. Applications. Balancing

Pressure independent balancing and control valve AB-QM DN

CBV Series. Circuit Balancing Valves

The Siemens 599 Series Ball Valve Portfolio simplifies installations and maximizes control usa.siemens.com/hvac

2-port seat valves PN16 with flanged connection

TA-6-way valve. Standard control valves 6-way valve for change-over systems

TA-6-way valve. NPT threads. Standard control valves 6-way valve for change-over systems

Connection and regulation kit for HVAC terminal units

CONTENTS. Double Flow Measurement Device 1. Fixed Orifice Double Regulating Valve 3. Variable Orifice Double Regulating Valve 7

BALANCING VALVES FOR BUILDING

R2F Compact Commissioning & 4 Port Control Valve Fan Coil Unit Valve Set Module

Pressure independent balancing and control valve AB-QM DN

ATi Max Series. Pressure Independent Control Valves 2 Way 2-1/2-6

TA-Mini-Fast-Fit. Prefab units Fabricated solutions for small terminal units

Spring Achieve System Balance Without All The Spin. PICCV. Complete Details Inside!

DESCRIPTION 9.4 G 3/4"M

Characterized Control Valves Actuators. Technical Databook Ver. 2

ChangeOver6 and NovoCon ChangeOver6 - Motorized 6-port Ball Valves

VE-x Plug & Seat Valve Assemblies

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

Product Table of overview contents and table of contents. Table of contents

VPI45..Q with pressure test points. Combi valves, PN 25

Description. Ballorex Venturi. Versions. Benefits. Robinets manuels Balancing

Globe Valves. Technical Databook Version 1.2. Belimo Asia Pacific

Innovation + Quality. Valves, controls + systems Balancing and Control Valves

TECHNICAL SPECIFICATIONS 63/2E DN15 Kvmax /4"E. ( 3 4"x18) 3/4"E

Combi valves, PN 25. for rooms, zones, ventilation and air-conditioning systems

CHBE320 LECTURE III ACTUATOR AND CONTROL VALVE SELECTION. Professor Dae Ryook Yang

20 to 150 mm 2-Way Automatic Flow Balancing Control Ball Valves

VPP46.. Combi valves, PN 25 VPP46..Q VPI46.. VPI46..Q ACVATIX. for rooms, zones, ventilation and air-conditioning systems

Combi valves PN 16 with flanged connections

AUTOMATIC CONTROL VALVES. TIS asia

Pressure independent balancing and control valve

3-port seat valves PN16 with flanged connection

Differential pressure controller with flow limitation and with integrated control valve (PN 16) AHPBM-F flow mounting, fixed setting

2-position electric actuators with Ball valves VBZ ½...11/4

Pressure Independent Control Valve Applications for Building Automation, Temperature Controls, and HVAC Two-Way Chilled Water Hot Water

HVAC Products PCS. Pettinaroli Commissioning Solutions

Pre-assembled distribution manifolds for radiant panel systems

Modulating control valve PN16

3-Port Seat Valves with Male Thread, PN 16

Automizer Combination Control Valves

3-port seat valves PN16 with flanged connection

2-Port and 3-Port Zone Valves, PN 16 / 20

VG9000 Flanged Valves

VPA Series and VAP Actuator

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

VPI45..Q with pressure test points. Combi valves, PN 25

485 - NC NO/DA DN

Written By : Simon Teo B. ENG (HONS)

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

V5000. Globe Valves Series for Terminal Units. Product Bulletin

HVAC Products PCS. Pettinaroli Commissioning Solutions

3-Port Seat Valves with Male Thread, PN 16

About Us Our Mission Table of Contents 04 Automatic Flow Limiting Valves 06 Manual Balance Valves 08 2-Way & 3-Way Actuated Ball Valves

36486_HVAC-Catalog_r1.pdf 1 1/12/17 11:57 AM HVAC CATALOG

2-port seat valves PN25 with flanged connection

Control of cutting-oil emulsion for industrial grinding machines. Applications for CHW and LPHW systems, see data sheet CA1N4454E.

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

Transcription:

ROTARY PRESSURE INDEPENDENT CONTROL VALVE TECHNICAL MANUAL

Introduction The EVOPICV-R Rotary Pressure Independent Control Valve EVOPICV-R is a combined constant flow limiter and rotary characterised control valve, giving full authority equal percentage temperature control valve. Application Examples The EVOPICV-R is suitable for use in variable and constant temperature systems and may be used as constant flow limiter in constant volume systems (without an actuator head) or as a true PICV in variable volume systems. Typical applications of the EVOPICV-R include Fan coils Chilled Beams Heater Batteries Small Air Handling units Heat Recovery Units Over-door Heaters Features and Benefits Features A wide range of actuators suitable for many applications High precision equal percentage ball gives maximum flow control under all conditions The EVOPICV-R shuts off fully leak tight due to the ball valve element Benefits Reduces capital outlay by eliminating the need for separate terminal balancing valves, temperature control valves, branch and mains balancing valves, and system differential pressure control valves. The valve has been designed to be easily close coupled to the terminal unit, even on 40mm centres Selection is simple as no authority calculations are needed. Late design changes and changes of use are more easily accommodated. Reduces circuit interactivity. Commissioning is simplified as no costly proportional balance is required. Controllability is improved due to the equal percentage characteristic. User comfort maximised by ensuring every temperature control valve has full authority. Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 2

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk Valve Specifications Sectional View - DN15/DN20 15 Very Low Low High Part Number PE81VL.04 PE81L.04 PE81H.04 Nominal [l/s] 0.090 0.175 0.250 Max Flow l/h] 324 (396) 630 (770) 900 (1100) Nominal Min Flow [l/s] 0.010 0.019 0.028 [l/h] 36 70 100 Accuracy [0.2-4 Bar] ±10% ±10% ±10% Accuracy includes linearity and hysteresis. Start Up ΔP [kpa] 20 20 20 Max Working ΔP [kpa] 400 400 400 Working Pressure PN 25 25 25 Min Temp [ C] -10-10 -10 Max Temp [ C] 120 120 120 Connections Rp ["] 1/2 1/2 1/2 Connections are parallel BSP to BS-EN10226-1.

Material Specification 7 8 1 2 3 4 5 6 1 Body Forging DZR Brass CW602N 2 Cartridge Body Brass CW614N 3 Cartridge Seat Brass CW614N 4 Cartridge Spring Stainless Steel AISI 302 5 Diaphragm EPDM 6 Ball Brass CW617N 7 Stem Brass CW614N 8 Stem O-Rings Viton Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 4

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk Dimensions No Actuator Dimension A B C D DN15 60 20 142 166 BEKR24 Actuator Dimension A B C D DN15 95 20 142 166 BELR24A Actuator Dimension A B C D DN15 146 20 142 166

Valve Operation The EVOPICV-R pressure independent control valve consists of two main functional groups: 1. Differential pressure regulator 2. Characterised Ball valve for flow regulation and temperature control Pressure Regulator P2 Flow & Temperature Control P1 P3 B A 1. Differential Pressure Regulator The differential pressure regulator is the heart of the pressure independent control valve, by keeping a constant differential pressure across the valve seats constant flow and full authority temperature control can be achieved. Incoming pressure P1 is transmitted to the top face of the diaphragm, outgoing pressure P3 is transmitted to the underside of this same diaphragm. A constant effective differential pressure is maintained between P2 and P3. As P1 increases relative to P3 it acts on the diaphragm closing the shutter (A) against a seat (B) thereby lowering the effective differential pressure. As P1 decreases relative to P3 the diaphragm acts to open the shutter (A) from the seat (B) thus increasing the effective differential pressure. The diaphragm acts against a spring in order to balance the pressure control and stop the diaphragm oscillating. Functional Schematic Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 6

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 2. Flow Rate Limitation and Temperature Control The temperature control element of the valve consists of an oblique pattern globe valve the differential pressure (P2-P3) across which is held constant by the differential pressure regulator. The authority (n) of a valve can be calculated from the pressure drops across that valve compared with the local system. In this case written as n P a P a P b In the case of a Pressure Independent Control Valve the system P b is close to 0 meaning that the authority is very close to 1. Flow rate limitation and modulating flow control are both achieved using a single characterised port in the ball element of the valve. As the differential pressure across this characterised port is held constant by the pressure regulator flow rate is now only a function of the cross sectional area of this port. As the ball closes against the Teflon seat a portion of the port is occluded, the characterised port has been designed such that the rate of change of area as the ball closes produces an equal percentage characteristic. Maximum flow rate limitation is achieved by limiting the position to which the ball may open. This can be achieved in two ways, firstly by means of a mechanical adaptor or more commonly by limiting the maximum opening position of the attached actuator. Modulating flow rate control is achieved by positioning the ball between the fully closed position and the point at which the design flow rate is achieved, in other the words the point at which the maximum opening position of the actuator is reached. Drawing showing how characterised ball is occluded by Teflon seat

Flow Control Figure A. Figure A. describes the general flow performance of the valve as the differential pressure changes. It can be seen that before the start-up pressure is achieved the flow rate increases almost as a fixed orifice valve. Once the start-up pressure has been achieved the valve controls the flow within a proportional band around the set point range. Values stated for the start-up pressure are calculated with the valve in the fully open position as the lowest differential pressure at which the valve will give a constant flow (±10% of nominal). It can be observed that as the valve is regulated to lower flow rates that the start-up pressure decreases. It can also be seen that once the working differential pressure range has been exceeded that the flow rate begins to rise out of the tolerance bands, however this happens at a much lower rate than a fixed orifice valve would exhibit. It should be noted that for a particular pressure a range of flows (within ± 10% of the nominal) can be produced depending on if the pressure is rising or falling. This hysteresis effect is typical of all dynamic balancing valves due to the internal tolerances of the pressure regulator. When designing the pipe system the start-up pressure should be used as the nominal resistance of the valve for pump sizing purposes. The proportional band of the valve accounts for both linearity and hysteresis effects. When deciding on tolerances for witnessing the proportional band (± 10%) of the valve should be taken in to account, we would suggest a tolerance of 0%, +20% is used. Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 8

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk PE81VL.04 - Flow Performance PE81L.04 - Flow Performance PE81H.04 - Flow Performance

Flow Rate [Kv/Kvmax] Flow Rate [Kv/Kvmax] Flow Rate [Kv/Kvmax] Power Output Temperature Control The valve characteristic is a measure of the rate at which the valve controls flow in relation to its opening position, authority is a measure of how well a valve performs in relation to its characteristic curve when in use. Exact curve depends on ΔT Flow Rate [Kv/Kv max ] Figure A. Coil Power Output Power output through a coil is related to water flow rate but it can be seen from figure A. that this relation ship is not linear. Figure A. shows that as flow increases the power output tends towards some maximum value. It can also be seen that power output increases rapidly from 0-50% of water flow and thereafter the rate of increase of power output decreases. The steepness of this curve is typically dependant on the temperature difference induced in the heating or cooling media (ΔT). Valve Characterisation Curves Stroke [H/H max ] Figure B. ON/OFF, Quick Acting Curve Stroke [H/H max ] Figure C. Linear Curve Stroke [H/H max ] Figure D. Equal Percentage Curve Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 10

Power Output Power Output Power Output Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk Figure B. describes an ON/OFF or quick acting valve characteristic, it can be seen that flow rate increases rapidly until 30% of the valve stroke and then slowly thereafter. Figure C. describes a Linear valve characteristic, flow rate increases in direct linear proportion to the valve stroke. Figure D. describes an Equal Percentage (modified logarithmic) valve characteristic. It can be seen that flow rate increases slowly until the valve stroke is approximately 70% and thereafter flow rate increases rapidly. It is generally desirable that the power output of a coil is linear in relation to the valve stoke as this results in the most easily controllable situation. System Response Curves Stroke [H/H max ] Stroke [H/H max ] Stroke [H/H max ] Figure E. (Fig A. + Fig B.) Figure F. (Fig A. + Fig C.) Figure G. (Fig A. + Fig D.) Figure E. describes the system response (power output of a coil vs. valve stroke) when a quick acting or ON/OFF valve is used. It can be observed that the power output rises to over 95% before the valve is more than 20% open. Figure F. describes the system response when a linear valve is used, it can be seen that power output rises quickly for the first 50% of valve stroke and thereafter the rate of change decreases. It can also be seen that 95% of the power output is achieved with a valve stroke of approximately 80%. Figure G. describes the system response when an equal percentage valve is used, it can be observed that power output increases linearly with increasing valve stroke. From the above graphs it can be seen that the equal percentage characteristic gives the most desirable system response. It should be noted that in any practical system the valve characteristic and coil characteristics may not be 100% matched but an equal percentage characteristic valve will always give a more linear response than any other profile. The characteristic curves of the EVOPICV-R valves are shown overleaf.

Characterisation of the regulating ball. The diagram below shows the free area of passage at various opening positions, it can be seen that as the ball opens up to 50% open only a very small area of passage is presented. As the ball opens to 75% a much greater area of passage is formed until at 100% open the full area of passage is presented. This rate of change of area of passage is the factor which governs the valve characteristic. The characterised slot is laser cut directly into the ball, this allows the characterisation profile to be very precise and repeatable. 0% Open 25% Open 75% Open 100% Open Open % Open 81VL 81L 81H 0% 0 0.0000 0.0000 0.0000 10% 9 0.0000 0.0000 0.0000 20% 18 0.0013 0.0000 0.0000 30% 27 0.0013 0.0108 0.0157 40% 36 0.002 0.021 0.030 50% 45 0.006 0.027 0.039 60% 54 0.013 0.042 0.061 70% 63 0.021 0.057 0.083 80% 72 0.034 0.095 0.137 90% 81 0.055 0.156 0.226 100% 90 0.100 0.194 0.281 Flow Rate at Each Position Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 12

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk PE81VL.04 - Characteristic Curves 100.00% 80.00% [%] Kv/KvMax 60.00% 40.00% 20.00% 0.00% 0% 20% 40% 60% 80% 100% [%] H/H Max PE81L.04 - Characteristic Curves 100.00% 80.00% [%] Kv/KvMax 60.00% 40.00% 20.00% 0.00% 0% 20% 40% 60% 80% 100% PE81H.04 Characteristic Curves 100.00% [%] H/H Max [%] Kv/KvMax 80.00% 60.00% 40.00% 20.00% 0.00% 0% 20% 40% 60% 80% 100% [%] H/H Max

Actuators The EVOPICV-R has been designed with an ISO standard mounting arrangement that can accommodate actuators with both ISO4 and ISO5 mounting pads. This means that almost any type of rotary valve actuator may be used with the valve so long as the minimum torque requirements are met. A wide range of actuators are available from Marflow for the EVOPICV-R valves, split into three functional types. 3 Point floating (Raise/Lower, Drive Open/Drive Close Actuators) 0-10v Proportional Actuators Programmable Multifunction Actuators BELR24A-MF Factory Setting Range Control Type 0-10v 0.2-30v Characteristic Linear 3 Point Operating Voltage [V] AC/DC 24v ±20% Open/Close Operating Power [W] 2 Quiesent Power [W] 1.2 Wiring [VA] 3.5 Actuating Torque [Nm] 5 Angle Of Rotation [ ] 90 Feedback [V] 2-10v 0.5-10v Run Time [s] 90 35-150 Operating Temperature [ C] -30-50 Fluid Temperature [ C] 5-80 Max Relative Humidity [%] 95 IP Rating 54 Cable Type 4 x 0.75 mm² Cable Length [mm] 1000 Housing Colour Orange Dimensions H/W/L [mm] 84/71/182 Input Resistance [kω] 100 Common Black 1 Live Red 2 Control White 3 Feedback Orange 5 Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 14

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk BEKR24 Control Type 3 Point Characteristic Linear Operating Voltage [V] AC/DC 24v ±20% Operating Power [W] 1 Quiesent Power [W] 0.2 Wiring [VA] 2 Actuating Torque [Nm] 5 Angle Of Rotation [ ] 90 Run Time [s] 90 Operating Temperature [ C] 0-50 Fluid Temperature [ C] 5-110 Max Relative Humidity [%] 95 IP Rating 54 Cable Type 3 x 0.75 mm² Cable Length [mm] 1000 Housing Colour Orange Dimensions H/W/L [mm] 84/71/160 Common Black 1 Close Red 2 Open White 3 BEKR24 Control Type 3 Point Characteristic Linear Operating Voltage [V] AC/DC 24v ±20% Operating Power [W] 0.5 Quiesent Power [W] 0.2 Wiring [VA] 1 Actuating Torque [Nm] 2 Angle Of Rotation [ ] 90 Run Time [s] 75 Operating Temperature [ C] -30-50 Fluid Temperature [ C] 5-80 Max Relative Humidity [%] 95 IP Rating 54 Cable Type 3 x 0.75 mm² Cable Length [mm] 1000 Housing Colour Orange Dimensions H/W/L [mm] 34/56/164 Common Black 1 Close Red 2 Open White 3

Wiring diagram, 3-Point actuators. Wiring diagram, 0-10v actuator. Setting Maximum Flow Rate To set the selected flow, follow these steps: Maximum flow rate limitation to a particular design flow rate can be achieved in practice by the following methods Mechanical setting device and manual flow measurement A mechanical device (TBR) may be fitted to the valve in order to limit the maximum opening position of the valve. A flow measurement device should also be installed. The valve should be opened manually until the deign flow rate is measured on the flow measurement device, once this is achieved then the manual regulating device can be locked in position. Manually limiting the drive time or scaling the control voltage in each BMS controller (not recommended). Using the control curves for each valve the drive time (or control voltage) for a particular flow rate can be calculated. This drive time or control voltage can then be programmed into each building management system controller. e.g. A valve is selected and the design flow rate required equates to an open position of 60 degrees (90 degrees being fully open). The actuator selected has a drive time of 90 second (or 1 second per degree) it can be calculated that the drive time required to achieve design flow is 60 seconds. This is the drive time that should be programmed into the BMS controller. Using a programmable actuator The programmable actuator internally scales its drive time to provide a particular design flow rate. The actuator can be delivered pre-programmed but is also settable on site using the programming tool. In order to program the actuator the opening percentage for a particular valve should be calculated, the example below shows the procedure for this calculation. Once the opening position has been determined the programming tool can be used program this into the actuator. Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 16

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk If desired the programming tool can also be used in concert with a flow measurement device. Whist reading from the flow measuring device the programming tool can be used to drive the valve to any position form 0 100%, when the desired flow reading is achieved the programming tool can be used to set this opening percentage in the actuator. It should be noted that the setting scale on the programming device is a linear percentage (i.e. 0-100% 0% = 0 50 = 45 100% = 90 ) however because the the valve characteristic follows a square function the percentage setting must be calculated from the square root of the ratio of design flow over maximum valve flow. For Example; A design flow rate of 0.05 l/s is required and a PEB81VL.04 (Maximum Nominal Flow 0.1 l/s) has been selected, the percentage setting is calculated as follows. Using a remote commissioning capable BMS control strategy By using a remote commissioning capable BMS controller the design flow rate can be directly programmed into the BMS controller. For more information on remote commissioning and controlling the valve in this way please see our dedicated remote commissioning documentation.

Flushing and Media Quality It is expected that the system to which the EVOPICV-R is fitted be pre cleaned and flushed in accordance to the standards and principles detailed in the BSRIA guide Pre commission cleaning of pipework systems (BG29/2011) and the water quality maintained to standards as detailed in BSRIA guide Water treatment for building service systems. Please ensure the compatibility of any cleaning agents and water treatments with the materials listed at the front of this datasheet. It should be noted that because the pressure independent valve will limit flow to a pre-set value regardless of the differential pressure, the valve should not be forward flushed when mounted in the flow connection. It is recommended that if the terminal units need to be flushed that the system is flushed to drain whilst bypassing the EVOPICV-R. On systems where the water quality is not known or is known to be poor it is recommend that a strainer is fitted to protect the EVOPICV-R. Verification In order to verify that a particular valve is within its working range the differential pressure can be measured across the installed pressure test points, if this pressure is between the upper and lower differential pressure limits (20kPa and 400kPa) the valve is within it operational range. Note: flow rate cannot be measured across the EVOPICV-R using the incorporated test points as due to the internal function of the valve the KV is not fixed. If flow measurement is required a separate orifice plate or venturi should be installed downstream. Before onsite verification commences it should be ensured that; The circulation pump has been correctly sized. The circulation pumps are operating in constant pressure or proportional pressure mode. The system has been flushed and treated. The system is free of air. Any local strainers are clean and have remained clean for at least 24hrs of pump operation. All actuators are driven fully open. CIBSE Commissioning Code W (2010) covers the verification of PICVs in section W7.7.3 Summated flow measurement at the branch and sub mains. Since each of the EVOPICV-R valves give a constant flow the expected flow at the branch or sub mains measuring station will be the sum of all the expected flows down stream of that measuring station. If the measured flow is within ±10% of the expected flow then it can be said that all the PICV valves are functioning correctly. Further problem solving can be carried out if necessary by means of either direct flow measurement at the terminal units or by the Marflow Single Station Balancing method. Direct flow measurement at the terminal units. The flow rate can be verified by direct flow measurement at each terminal unit if it is thought necessary however it would be more usual to measure the flow rate at 10% of the terminal units and only investigate further if discrepancies are found. Optimisation When the verification stage is complete the system can be optimised for energy usage by reducing the pump speed. In order to do this the index loop must be identified, this will be the Pressure independent valve that has the lowest differential pressure across it. When the index loop has been identified the pump speed may be lowered until the pressure drop across the index PICV is equal to or just above 1.5 times the start-up pressure for that valve. This will ensure excess energy is not used in circulating water around the system. Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk 18

Call us on +44 (0)845 564 1555 or visit www.marflowhydronics.co.uk Reference Terminal Unit Schematics PICV Constant Flow Regulator Flow Mounted, Variable Volume System with local flow measurement Filterball Isolating Strainer Flow Measurement Valve Return Mounted, Variable Volume System Isolation Valve Coil/Heat Emitter 3 Port Control Valve Return Mounted, Constant Volume System

Marflow Hydronics Limited Britannia House Austin Way Hamstead Industrial Estate Birmingham, England B42 1DU XLIT-EVOPICVR-04/12 Tel - 0121 358 1555 Fax - 0121 358 1444 www.marflowhydronics.co.uk Errors and Omissions Excepted, Marflow reserve the right to change specification at any time