40A DC US Module Jameco SKU Number: 2103273 DR-US40 SECIFICATION MODEL DC INUT / DC BUS BATTERY INUT / OUTUT FUNCTION ENVIRONMENT SAFETY & EMC OTHERS NOTE DC VOLTAGE (Typ.) RATED CURRENT VOLTAGE RANGE (Typ.) CURRENT RANGE CHARGE CURRENT (Typ.) EXTERNAL BATTERY (Typ.) EMS IMMUNITY MTBF DIMENSION ACKING DR-US40 RELAY CONTACT RATING (max.) 30VDC, 1A DC BUS BATTERY FAIL BATTERY DISCHARGE WORKING TEM. WORKING HUMIDITY STORAGE TEM., HUMIDITY VIBRATION WITHSTAND VOLTAGE 24 ~ 29V 40A 21 ~ 29V 0 ~ 40A 2A 4 / 7 / 12AH / 24V Relay contact : Short when DC voltage between 21~29V( 3%), relay contacts LED(Green) : DC BUS : light ; DC BUS fail : dark Relay contact : Short when battery failure is observed through the battery test function, relay contacts Note.2 LED(Red) : Battery over-discharge warning or battery broken : light ; Battery : dark Relay contact : Short when battery in discharge condition, relay contacts LED(Yellow) : Battery discharging : light ; Battery is not discharging or discharging current<2.0a : dark -20 ~ 70 20 ~ 90% RH -20 ~ 85, 10 ~ 95% RH Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y, Z axes ; Mounting : Compliance to IEC600068-2-6 Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC ISOLATION RESISTANCE Terminal-Chassis :>100M Ohms/500VDC 25 70%RH EMI CONDUCTION & RADIATION Compliance to EN55022 (CISR22) Class B Compliance to EN61000-4-2,3,4,5,6,8, ENV50204, heavy industry level, criteria A 161.9Khrs min. MIL-HDBK-217F (25 ) 55.5*125.2*100mm (W*H*D) 0.55Kg; 20pcs/12Kg/1.29CUFT File Name:DR-US40-SEC 2007-09-19
40A DC US Module Jameco SKU Number: 2103273 DR-US40 Mechanical Specification Case No.923D Unit:mm 100 125.2 1 2 TB1 3 4 LED TB2 1 2 3 4 5 6 55.5 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 35 Terminal in No. Assignment (TB1) in No. Assignment 1 BATTERY INUT 2 BATTERY INUT - 3 DC INUT - 4 DC INUT Terminal in No. Assignment (TB2) in No. Assignment 1 BAT DISC 1 BAT DISC 2 2 3 4 5 6 BAT FAIL 1 BAT FAIL 2 DC 1 DC 2 Block Diagram Derating Curve LOAD OWER SULY INUT CHARGE CIRCUIT LIMIT DETECTION CIRCUIT 25Ax2 BAT. TEST 24V BATTERY LOAD (%) 100 80 60 40 20 DC BAT FAIL BAT DISCHARGE -20 0 10 20 30 45 50 60 70 (VERTICAL) AMBIENT TEMERATURE ( ) File Name:DR-US40-SEC 2007-09-19
40A DC US Module Jameco SKU Number: 2103273 DR-US40 Suggested Application 1.Back up connection for AC interruption DR-US40 24V SU Battery BAT DC - - 24V/40A max. Load - - - 2.Combine redundancy module (DR-RDN20) to back up AC interruption or failure of SU DR-US40 DR-RDN20 24V Battery SU Load BAT DC - - - - - - - - File Name:DR-US40-SEC 2007-09-19
40Amp US DR-US40 MODEL:DR-US40 DC INUT / DC BUS NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 DC VOLTAGE RANGE (TY) 24V~29V I/: TESTING O/:FULL LOAD 23.68V~29.16 V 2 RATED CURRENT 40A I/: 24 VDC O/:FULL LOAD BATTERY INUT / OUTUT NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 VOLTAGE RANGE (TY) 21VDC~29VDC I/: TESTING O/: BATTERY 20.76V~29V 2 CURRENT RANGE 0~40A I/: 23V O/: BATTERY 3 CHARGE CURRENT (TY) 2A I/: 24.5VDC O/:BATTERY 2.1A 4 EXTERNAL BATTERY (TY) 4 / 7 / 12AH /24V I/: 24VDC O/:BATTERY FUNCTION TEST NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 RELAY CONTACT RATING 30VDC / 1A (MAX) I/: 30VDC O/:1A 2 DC BUS Relay contact : short when DC voltage I/: TESTING Between 21~29V ( 3%), O/:FULL LOAD relay contacts ; Green LED on front panel LED (Green) : DC BUS : light : DC BUS fail : dark 3 BATTERY FAIL Relay contact : short when battery failure Is observed through the battery test Function, relay contacts ; Red LED on front panel LED(Green): DC BUS : light : DC BUS fail : dark I/: TESTING O/:FULL LOAD 4 BATTERY DISCHARGE Relay contact : short when battery in discharge condition relay contacts ; Yellow LED on front panel LED(Green) : DC BUS : light : DC BUS fail : dark I/: TESTING O/:FULL LOAD Model: DR-US40 Test Report 1 / 3
40Amp US DR-US40 ENVIRONMENT TEST NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 TEMERATURE RISE TEST MODEL:DR-US40 1. ROOM AMBIENT BURN-IN:1HRS I/: 24VDC O/: FULL LOAD Ta= 32.7 2. HIGH AMBIENT BURN-IN:1HRS I/: 24VVDC O/: FULL LOAD Ta= 69.8 NO osition /N ROOM AMBIENT Ta= 32.7 HIGH AMBIENT Ta= 69.8 1 D16 MBR1545CT 15A/45V 37.9 73.4 2 RG1 7812 1A/12V 41.9 76.8 3 D9 YG802C04 10A/40V 36.7 72.6 4 RY5 VK31H42 24V/40A 36.4 72.4 5 RY4 VK31H42 24V/40A 52.9 86.6 6 D17 SB540 5A/40V 45.8 79.7 7 Q6 IRFZ44V 55A/60V 36.2 71.8 8 Q8 IRFZ44V 55A/60V 37.0 73.0 9 RY1 OUAZ-SS-1246 1A/24V 44.8 79.0 10 RY2 OUAZ-SS-1246 1A/24V 43.4 77.7 11 RY3 OUAZ-SS-1246 1A/24V 38.8 73.7 12 C3 2.2U/50V 105 KY 42.4 77.1 13 C1 220U/35V 105 KY 41.6 76.4 14 U1 LM358 44.6 79.9 2 LOW TEMERATURE TURN ON TEST TURN ON AFTER 2 HOUR I/: 24VDC O/: 100 % LOAD Ta= -20 TEST: 3 HIGH HUMIDITY HIGH TEMERATURE HIGH VOLTAGE TURN ON TEST AFTER 12 HOURS IN CHAMBER ON CONTROL 70 NO DAMAGE 4 VIBRATION TEST 1 Carton & 1 Set (1) Waveform: Sine Wave (2) Frequency:10~500Hz (3) Sweep Time:10min/sweep cycle (4) Acceleration:2G (5) Test Time:1 hour in each axis (X.Y.Z) (6) I/: 24VDC O/:FULL LOAD Ta= 70 HUMIDITY= 95 %R.H TEST: TEST: SAFETY TEST NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 WITHSTAND VOLTAGE Terminal-chassis: 0.5 KVAC/min Terminal-chassis: 0.6 KVAC/min Terminal-chassis: 0.06 ma Relay contacts-terminal:0.5 KVAC/min Relay contacts-terminal:0.6 KVAC/min Relay contacts-terminal: 0.06 ma NO DAMAGE 2 ISOLATION RESISTANCE Terminal-chassis : 500VDC>100MΩ Terminal-chassis : 500 VDC Terminal-chassis 16 GΩ NO DAMAGE Model: DR-US40 Test Report 2 / 3
40Amp US DR-US40 E.M.C TEST NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 CONDUCTION EN55022 CLASS B 2 RADIATION EN55022 CLASS B I/: 24VDC O/:FULL/50% LOAD I/: 24VDC O/:FULL/50% LOAD ASS Test by certified Lab ASS Test by certified Lab 3 E.S.D EN61000-4-2 INDUSTRY AIR:8KV / Contact:4KV I/: 24VDC O/:FULL/50% LOAD CRITERIA A 4 E.F.T EN61000-4-4 INDUSTRY V / V-: 0.5KV I/: 24VDC O/:FULL/50% LOAD CRITERIA A 5 SURGE IEC61000-4-5 INDUSTRY V / V- :0.5KV V,V- / E : 0.5KV I/: 24VDC O/:FULL/50% LOAD CRITERIA A 6 Test by certified Lab & Test Report repare M.T.B.F & LIFE CYCLE CALCULATION NO TEST ITEM SECICATION TEST CONDITION RESULT VERDICT 1 CAACITOR LIFE CYCLE SUOSE C1 IS THE MOST CRITICAL COMONENT I/: 24VDC O/:FULL LOAD Ta= 25 LIFE TIME= 966988 HRS I/: 24VDC O/:FULL LOAD Ta= 70 LIFE TIME= 50120 HRS 2 MTBF MIL-HDBK-217F NOTICES2 ARTS COUNT TOTAL FAILURE RATE: 161.9KHRS DATE SAMLE TEST RESULT TESTER AROVAL 2007/1/16 RD SAMLE ASS VINCENT TSENG MAX LIN 2007/3/10 2007/5/9 2007/8/31 RODUCT SAMLE W0702A10 RODUCT SAMLE W0704C05 RODUCT SAMLE W0708D06 ASS VINCENT TSENG MAX LIN ASS VINCENT TSENG MAX LIN ASS VINCENT TSENG MAX LIN 2003/12/12 A50-F023 Model: DR-US40 Test Report 3 / 3