Samsung Modelling Guide for equest

Similar documents
VRF. Technical Data Book. Ceiling for America (R410A, 60Hz, HP) Model : AM***FNCDCH***

VRF. Technical Data Book. DVM IDU_Vertical AHU for NA (R410A, 60Hz, HP) Model : AM***JNZDCH/AA

VRF. Technical Data Book. DVM Indoor Unit PAC for Global (INV, R410A, HP) Model : AM140JNPDKH/TK (50/60Hz) AM280JNPDKH/TK (50Hz)

VRF. Technical Data Book. Duct S for Europe (R410, 50Hz)

ERV. Technical Data Book. ERV for Europe (NASA, 50Hz, 60Hz)

SINGLE. Technical Data Book. Big Duct for Europe (R410A, 50Hz, H/P) Model : AC180JNHPKH/EU AC180JXAPNH/EU AC200JNHPKH/EU AC200JXAPNH/EU

RAC. Technical Data Book. RAC for North America (Inv, R410A, 60Hz, HP)

SINGLE. Technical Data Book. Big Ceiling for Europe (R410A, 50Hz, H/P)

SINGLE. Technical Data Book. HSP Duct for America (R410A, 60Hz, H/P)

VHIA High-Static Ducted Indoor Units - 60HZ

12185 Presilla Road Camarillo, California phone: (805) fax: (805)

Engineering Data Book

Version Modification Date Remark

General Purpose Ignition System GS6. User Manual. Document No PS-0009

V33B High Efficiency 360 Cassette Indoor Models - 60HZ

Engineering Data Book

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

Engineering Data Book

FDCLP2 Constant Volume Series Flow, Low Profile

Fiorano ESB 2007 Oracle Enterprise Gateway Integration Guide

Signature: Date: April

Dynojet Research, Inc. All Rights Reserved. Optical RPM Sensor Installation Guide.

2017 Commercial & Industrial Program K-12 Schools Program Rebate Application

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Introduction. E-Trac Xchange is versatile and easy to use, so make the most of your E-Trac with this great new feature. Enjoy!

TECHNICAL GUIDE. Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES

STARDEX 0303, 0304, 0305, 0306, 0402, STARDEX Master Ultima. STARDEX Dimas. STARDEX Dimas Ultima

AASHTOWare Bridge Rating Vehicle Library Setup

TECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES

Q7RE Series Single Packaged Heat Pump, Single Phase

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ

DUCTED INDOOR UNIT ENGINEERING MANUAL

FULL DC INVERTER SYSTEMS INDIVIDUAL AND MODULAR CONSTRUCTION FLEXIBLE COMBINATIONS AIR CONDITIONING COMMERCIAL AIR CONDITIONERS SDV4 2014

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ

ZC706 MIG Design Creation November 2014

High Performance Axial Fans

A, B, C Permit Truck Classification Calculator

Midea VRFs/ Midea V5X. Timothy Huang Senior Engineer

200, 9200 & 9200-VIB SERIES

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

QUICK START GUIDE 199R10546

Rack Installation Guide (Steelhead Series 3000, 5000, and 6000, and Interceptor Systems)

13 SEER Light Commercial 3 Phase

ZC706 MIG Design Creation November 2015

Ceiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

RS-110 Rainfall Sensor Installation Guide

Predator Model Number Nomenclature

SEMIS ABB semiconductor simulation tool Web manual - two-level VSC

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

Air Conditioners. Technical Data UATYQ-CY1

ISO INTERNATIONAL STANDARD. Measurement of noise emitted by accelerating road vehicles Engineering method Part 2: L category

VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ

DVM. Technical Data Book

Performance Rating of Single Package Vertical Air-Conditioners And Heat Pumps

Q7RE Series Single Packaged Heat Pump, Single Phase

2600T Series Pressure Transmitters Custom Linearization Table with ABB Asset Vision Basic

TECHNICAL GUIDE GENERAL HIGH-EFFICIENCY WATER SOURCE HEAT PUMPS AND WATER COOLED AIR CONDITIONERS

Laboratory Exhaust Systems

COAXIAL SPEAKERS FI4-F3, FI5-F3, FI57-F3, FI6-F3, FI69-F3

Fan Powered Terminal Units FPV, FDV Series Variable Volume Parallel Flow

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

Product Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil

NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues. March 27, 2014

Aluminum Capacitors Standard C Snap-In

TORQUE CALIBRATION USING THE PROEDIT PROCEDURE WIZARD AND CALIBRATING USING PROCAL

All Worn Out! Measure the voltage of batteries as they discharge. Predict how different size batteries will behave when being discharged.

Product Information. Applications. Warranty. Lab Calibrated. Residential, Commercial, OEM. ABV Sizes Available Airflow Range THE USA PROUDLY MADE IN

Version Modification Date Remark

Q5RD Series Single Packaged Heat Pump, Single Phase

Motors and Variable Speed Drives for Pumps and Fans. Reid Hart, PE

S5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

GQ5RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase 13 SEER, R-410A, WARRANTY

Certified Energy Efficiency.

REVIT CONTENT GUIDE. Instance Properties. Manufacturer: File: Type Catalog: Rendering file: Schedule file:

Product Catalog. Variable Refrigerant Flow (VRF) VRF-PRC026A-EN. Mid-Static Concealed (Ducted) Indoor Units. November 2015

Latch Baseline Application Detail

Aluminum Capacitors Standard - 85 C Snap-In

PRPHP14 PRODUCT SPECIFICATIONS 14 SEER HEAT PUMP PACKAGED UNIT REFRIGERANT SYSTEM CABINET CONSTRUCTION BLOWER CONTROLS INSTALLATION ACCESSORIES

SEMIS Simulation Tool for 6 pulse Controlled Rectifier

PRAC14 PRODUCT SPECIFICATIONS

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

JUMO DSM software. PC software for management, configuration, and maintenance of digital sensors. Operating Manual T90Z001K000

NTC Thermistors, 2-Point Micro Chip Sensor Insulated Leads

TECHNICAL GUIDE FLEXIBLE LIGHT COMMERCIAL UNIT CHAMPION SERIES (WORLD 50 HZ) SINGLE PACKAGE COOLING UNITS D1EB036, 048 AND 060 3, 4 & 5 NOMINAL TONS

Smart-UPS RC External Battery Pack Tower/Rack-Mount 4U

Product Data. Features/Benefits. 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

Diagram Of Ac System Ford Ranger

REVIT CONTENT GUIDE. Instance Properties. Manufacturer: File: Type Catalog: Rendering file: Schedule file:

Solar-Powered Battery Bank

B6VMMX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler with TXV 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

GENERAL ELECTRIC CONCEALED CHILLED WATER FAN COIL UNITS

Model 8144NC Fresh Air Ventilator

Performance Data. Fan Performance Curves - FDCLP2 with ECM. Unit Size Unit Size FDCLP2 Fan Curves-1 v001

AMCA International s Opening Session

REVIT CONTENT GUIDE. Instance Properties. Manufacturer: File: Type Catalog: Rendering file: Schedule file:

VAV AIRFLOW CONTROL. Reliable Without Limitations? Ron Simens, Facility Dynamics Engineering. 21 st National Conference on Building Commissioning

Transcription:

Samsung Modelling Guide for equest

Disclaimer The information contained in this equest Modeling Guide and in the DVM S library file (the Information ) is for informational purposes only and should not be construed as engineering or other technical advice. Samsung is under no obligation to update or keep current the information or to correct any inaccuracies therein. Samsung and its affiliates, directors, employees and agents expressly disclaim any liability or responsibility for any loss or damage arising out of the content, accuracy or appropriateness of the Information or from the use of all or any part of the Information by any person. You should obtain your own professional advice and conduct your own independent evaluation with respect to the subject matter herein. Samsung is not responsible for, and does not make any assurances regarding, the function or suitability of equest Building Energy Analysis Software. 2

Contents 1. Introduction 2. Program Installation 3. Importing SAMSUNG DVM S Library File 4. System Modeling Air Cooled DVM S Appendix A Appendix B Outdoor Unit Specifications Indoor Unit Specifications 3

1. Introduction This document aims to provide guidance for building a simulation model when analyzing annual energy consumption and conservation standard for energy and environmental design at the design stage of a HVAC system. It guides through the process of 1) installation of the library file for Samsung DVM S units and 2) building a DVM S system on equest Version 3.65, which is a building energy analysis software. Please visit the equest website (http://doe2.com/ equest/index.html) for information about downloading a copy of equest (including instructions). The library file can be downloaded at https://www.dvmdownload.com/. The library file includes 33 models of air cooled heat pump/heat recovery outdoor units (North American models) and 80 models of the following indoor unit types: duct, AHU, 1way/4way cassette, wall mount, ceiling, and floor standing. Each model was built on the basis of the cooling and heating performance curves (capacity ratio modifier function of temperature, energy input ratio modifier function of temperature, part load ratio correction factors, and piping correction factors). The rated specifications of the outdoor and indoor units are shown in Appendix A and Appendix B, respectively. The results of any simulation are only a guideline and actual system performance will depend on conditions in addition to the relevant units rated specifications. In order to increase the accuracy of a simulation, it is critical to use measured data from an actual building and HVAC system. Even if the DVM S system modeling is carried out per these instructions, Samsung HVAC does not represent or warrant that system performance will match the simulation results. 4

2. Program Installation Connect the below address and download equest Version 3.65 S/W Access the site : http://doe2.com/equest/index.html 5

3. Importing SAMSUNG DVM S Library File 1) Have a new or current project file open, then select Tools View File Locations View equestdata Directory 2) From equest 3 65 Data folder, open DOE 2 folder. 3) Replace/overwrite the old BDLLIB.DAT with the new BDLLIB.DAT that was downloaded from Samsung HVAC Website. 4) Restart the equest software. 1) 6

3. Importing SAMSUNG DVM S Library File 5) From Mode tab check Detailed Data Edit 6) From the top navigation bar click Air Side HVAC 7) Component Tree Performance Curves folder lists the performance curves of all the systems registered in the software library. 8) Right click Performance Curves folder Create Curve Fit 5) 6) 8) 7

3. Importing SAMSUNG DVM S Library File 9) From Create Curve Fit window click Load Component From Library 10) From Curve Fit Library Selection window Category = DVM S & Entry = select a Performance Curves 11) Click Ok 9) 10) 11) 8

3. Importing SAMSUNG DVM S Library File 12) Review the details on Performance Curve Properties Window, then click Done 13) For all DVM S Performance Curves, repeat steps 10 ~ 12 14) Component Tree Performance Curves folder lists all added DVM S Performance Curves 12) 14) 9

4. System Modeling Air cooled outdoor units 1) From Mode tab check Wizard Data Edit 2) Click Actions tab on the bottom left select Building Creation Wizard 1) 2) 10

4. System Modeling Air cooled outdoor units 3) On the bottom left of the equest Schematic Design Wizard window, select 19 of 43 from the drop down box to go to pg. 19 4) Make proper selections Cooling Source = DX Coils Heating Source = DX Coils (Heat Pump) Heat Pump Src = Air System Type = Packaged Single Zone Heat Pump 5) Click Finish 4) 3) 5) 11

4. System Modeling Air cooled outdoor units 6) Select: Mode > Detailed Data Edit 7) On Navigation bar, select Air Side HVAC, then double click Heat Pump Cooling coil icon from the System diagram. 6) 7) 12

4. System Modeling Air cooled outdoor units 8) On Air Side HVAC System Parameters window, select Cooling > Unitary Power 9) Input the value in Cooling Power, Cooling Electric Input Ratio. (refer to Appendix A Outdoor Unit Specifications) 10) For Cooling Electric Input Ratio Curves, refer back to pg.3 and select Cool EIRfIWB&ODB Curve and Cool EIR fplr Curve 11) From Capacity Curves tab, select Cool Cap fiwb&odb Curve for Total Capacity. 9) 8) 10) 11) 13

4. System Modeling Air cooled outdoor units 12) Air Side HVAC System Parameters window, go to Heating > Unitary Power tab. 13) Under Heating Electric Power, input the value for Heating Electric Input Ratio (refer to Appendix A Outdoor Unit Specifications) 14) For Heating Electric Input Ratio Curves, refer back to pg.3 and select Heat EIRfIDB&OWB Curve and Heat EIR fplr Curve. 15) From Cap Curves/Waste Ht tab, select Total Capacity as f(temperature). 13) 12) 14) 15) 14

4. System Modeling Air cooled outdoor units 16) Air Side HVAC System Parameters window, go to Fan > Fan Power and Control tab. 17) Input the fan s Full Load Energy Rate and Static Pressure. (refer to Appendix B Indoor Unit Specifications) In equest, only one indoor unit can be modeled in one system. If the target system includes multiple indoor units, the average of full load energy rate is calculated. The calculation method is as follows. Target indoor units : AM007FNLDCH X 1ea, AM012FNLDCH X 2ea, AM024FNLDCH X 3ea Cooling Capacity : (7500 X 1) + (12000 X 2) + (24000 X 3) = 103500 [BTU/h] Average Full Load Energy : {(7500 X 1 X 0.0001664) + (12000 X 2 X 0.0002124) + (24000 X 3 X 0.0002488)} / (103500) = 0.000234 [kw/cfm] 18) Click Done 16) 17) 18) 15

Appendix A Outdoor Unit Specifications Heating Cooling Model Capacity Input EIR Capacity Input EIR [MBH] [kw] [ ] [MBH] [kw] [ ] AM216KXVGJH/AA 243 15.41 0.22 216 17.37 0.27 AM072FXVAFH2AA 81 4.80 0.20 72 4.34 0.21 AM096FXVAFH2AA 108 6.28 0.20 96 5.64 0.20 AM120FXVAFH2AA 135 8.92 0.23 120 8.10 0.23 AM144FXVAFH2AA 162 11.14 0.23 144 10.79 0.26 AM168HXVAFH2AA 189 13.64 0.25 168 13.86 0.28 AM192HXVAFH2AA 216 16.33 0.26 192 16.44 0.29 AM072FXVAJH2AA 81 4.80 0.20 72 4.34 0.21 AM096FXVAJH2AA 108 6.64 0.21 96 6.13 0.22 AM120FXVAJH2AA 135 8.92 0.23 120 8.59 0.24 AM144FXVAJH2AA 162 11.14 0.23 144 10.79 0.26 AM168HXVAJH2AA 189 13.64 0.25 168 13.86 0.28 AM192HXVAJH2AA 216 16.33 0.26 192 16.44 0.29 AM072KXVTFH/AA 81 5.01 0.21 72 4.45 0.21 AM096KXVTFH/AA 108 6.49 0.20 96 5.94 0.21 AM072KXVTJH/AA 81 5.01 0.21 72 4.45 0.21 AM096KXVTJH/AA 108 6.49 0.20 96 5.94 0.21 16

Appendix A Outdoor Unit Specifications Heating Cooling Model Capacity Input EIR Capacity Input EIR [MBH] [kw] [ ] [MBH] [kw] [ ] AM072FXVAFR2AA 81 4.80 0.20 72 4.34 0.21 AM096FXVAFR2AA 108 6.28 0.20 96 5.64 0.20 AM120FXVAFR2AA 135 8.92 0.23 120 8.10 0.23 AM144FXVAFR2AA 162 11.14 0.23 144 10.79 0.26 AM168HXVAFR2AA 189 13.64 0.25 168 13.86 0.28 AM192HXVAFR2AA 216 16.33 0.26 192 16.44 0.29 AM072FXVAJR2AA 81 4.80 0.20 72 4.34 0.21 AM096FXVAJR2AA 108 6.64 0.21 96 6.13 0.22 AM120FXVAJR2AA 135 8.92 0.23 120 8.59 0.24 AM144FXVAJR2AA 162 11.14 0.23 144 10.79 0.26 AM168HXVAJR2AA 189 13.64 0.25 168 13.86 0.28 AM192HXVAJR2AA 216 16.33 0.26 192 16.44 0.29 AM072KXVTFR/AA 81 4.63 0.19 72 4.08 0.19 AM096KXVTFR/AA 108 6.00 0.19 96 5.45 0.19 AM072KXVTJR/AA 81 4.63 0.19 72 4.08 0.19 AM096KXVTJR/AA 108 6.00 0.19 96 5.45 0.19 17

Appendix B Indoor Unit Specifications Model Cooling Capacity [Btu/h] Heating Capacity [Btu/h] Max Airflow [CFM] Fan Power [W] Energy Rate Units [kw / CFM] Static Pressure [in. wg] AM007MNMDCH 7500 8500 318.0 27 0.0000849 0.039 AM009MNMDCH 9500 10500 318.0 27 0.0000849 0.039 AM012MNMDCH 12000 13500 353.0 31 0.0000878 0.039 AM015MNMDCH 15000 17000 388.0 38 0.0000979 0.039 AM018MNMDCH 18000 20000 600.0 80 0.0001333 0.039 AM024MNHDCH 24000 27000 777.0 114 0.0001467 0.205 AM027MNHDCH 27000 30000 812.0 125 0.0001539 0.205 AM030MNHDCH 30000 34000 848.0 132 0.0001557 0.205 AM036MNHDCH 36000 40000 1024.0 165 0.0001611 0.205 AM048MNHDCH 48000 54000 1377.0 272 0.0001975 0.205 AM009FN4DCH 9000 10000 547.4 32 0.0000585 0 AM012FN4DCH 12000 13500 547.4 32 0.0000585 0 AM018FN4DCH 18000 20000 547.4 32 0.0000585 0 AM024FN4DCH 24000 27000 618.0 40 0.0000647 0 AM030FN4DCH 30000 34000 777.0 65 0.0000837 0 AM036FN4DCH 36000 40000 847.6 75 0.0000885 0 AM048FN4DCH 48000 54000 1024.2 95 0.0000928 0 18

Appendix B Indoor Unit Specifications Model Cooling Capacity [Btu/h] Heating Capacity [Btu/h] Max Airflow [CFM] Fan Power [W] Energy Rate Units [kw / CFM] Static Pressure [in. wg] AM007FNLDCH 7500 8500 282.5 47 0.0001664 0.04 AM009FNLDCH 9500 10500 317.8 60 0.0001888 0.04 AM012FNLDCH 12000 13500 353.2 75 0.0002124 0.04 AM018FNLDCH 18000 20000 547.4 140 0.0002558 0.04 AM024FNLDCH 24000 27000 582.7 145 0.0002488 0.04 AM030FNLDCH 30000 34000 1094.8 95 0.0000868 0.04 AM036FNLDCH 36000 40000 1200.7 120 0.0000999 0.12 AM048FNLDCH 48000 54000 1342.0 180 0.0001341 0.12 AM024JNHDCH 24000 27000 653.0 82 0.0001256 0.20 AM027JNHDCH 27000 30000 742 91 0.0001226 0.20 AM030JNHDCH 30000 34000 883.0 108 0.0001223 0.20 AM036JNHDCH 36000 40000 954.0 140 0.0001468 0.20 AM048JNHDCH 48000 54000 1236.0 200 0.0001618 0.20 AM054JNHDCH 54000 61400 1413.0 280 0.0001982 0.20 AM036FNHDCH 36000 40,000 988.9 210 0.0002124 0.39 AM048FNHDCH 48000 54,000 1377.3 330 0.0002396 0.39 AM076FNHDCH 76000 85200 2048.3 530 0.0002587 0.59 19

Appendix B Indoor Unit Specifications Model Cooling Capacity [Btu/h] Heating Capacity [Btu/h] Max Airflow [CFM] Fan Power [W] Energy Rate Units [kw / CFM] Static Pressure [in. wg] AM096FNHDCH 96000 108000 2542.8 790 0.0003107 0.59 AM012JNZDCH 12000 13500 373.0 64 0.0001716 0.40 AM018JNZDCH 18000 22000 531.0 94 0.0001770 0.40 AM024JNZDCH 24000 27000 706.0 144 0.0002040 0.40 AM030JNZDCH 30000 34000 1053.0 218 0.0002070 0.40 AM036JNZDCH 36000 40000 1053.0 218 0.0002070 0.40 AM048JNZDCH 48000 54000 1410.0 290 0.0002057 0.40 AM054JNZDCH 54000 60000 1603.0 341 0.0002127 0.40 AM060JNZDCH 60000 64000 1768.0 380 0.0002149 0.40 AM072JNZDCH 72000 80000 2110.0 620 0.0002938 0.40 AM007FN1DCH 7500 8500 247.2 40 0.0001618 0 AM009FN1DCH 9500 10500 247.2 45 0.0001820 0 AM012FN1DCH 12000 13500 282.5 50 0.0001770 0 AM005KNNDCH 5000 6000 300.0 18 0.0000600 0 AM007KNNDCH 7500 8700 300.0 18 0.0000600 0 AM009FNNDCH 9500 10500 353.0 24 0.0000680 0 AM012FNNDCH 12000 13500 371.0 28 0.0000755 0 20

Appendix B Indoor Unit Specifications Model Cooling Capacity [Btu/h] Heating Capacity [Btu/h] Max Airflow [CFM] Fan Power [W] Energy Rate Units [kw / CFM] Static Pressure [in. wg] AM018FNNDCH 18000 20000 459.0 36 0.0000784 0 AM020FNNDCH 20000 23000 477.0 38 0.0000797 0 AM009KN4DCH 9000 10000 565.1 26 0.0000460 0 AM012KN4DCH 12000 13500 565.1 26 0.0000460 0 AM018KN4DCH 18000 20000 565.1 26 0.0000460 0 AM024KN4DCH 24000 27000 671.0 38 0.0000566 0 AM030KN4DCH 30000 34000 900.6 54 0.0000600 0 AM036KN4DCH 36000 40000 988.9 71 0.0000718 0 AM048KN4DCH 48000 54000 1112.5 91 0.0000818 0 AM007HNQDCH 7500 8500 275.5 37 0.0001343 0 AM009HNQDCH 9500 10500 275.5 37 0.0001343 0 AM012HNQDCH 12000 13500 328.4 45 0.0001370 0 AM018HNQDCH 18000 20000 423.8 55 0.0001298 0 AM020HNQDCH 20000 23000 494.4 57 0.0001153 0 AM024HNQDCH 23200 23800 494.4 60 0.0001214 0 AM018FNCDCH 18000 20000 494.4 72 0.0001456 0 AM024FNCDCH 24000 27000 635.7 80 0.0001258 0 21

Appendix B Indoor Unit Specifications Model Cooling Capacity [Btu/h] Heating Capacity [Btu/h] Max Airflow [CFM] Fan Power [W] Energy Rate Units [kw / CFM] Static Pressure [in. wg] AM036JNCDCH 36000 40000 1035.0 92 0.0000889 0 AM048JNCDCH 48000 54000 1286.0 160 0.0001244 0 AM006JNFDCH 6000 6700 175.0 35 0.0002000 0 AM009JNFDCH 9500 10500 250.0 40 0.0001600 0 AM012JNFDCH 12000 13500 350 50 0.0001429 0 AM018JNFDCH 18000 20000 550 110 0.0002000 0 AM024JNFDCH 24000 27000 550.0 110 0.0002000 0 AM006JNGDCH 6000 6700 175.0 35 0.0002000 0 AM009JNGDCH 9500 10500 250.0 40 0.0001600 0 AM012JNGDCH 12000 13500 350 50 0.0001429 0 AM018JNGDCH 18000 20000 550.0 110 0.0002000 0 AM024JNGDCH 24000 27000 550.0 110 0.0002000 0 22

Samsung Electronics Co., LTD. R&D / SE Head Office (Suwon Korea) 129, Samsung Ro, Yeongtong Gu, Suwon City, Gyeonggi Do, Korea 443 742 Website : www.samsung.com/global/business/system air conditioner Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice. 2017.07 Ver.1.0