Impact of Photovoltaic Power Plant on the Transient Stability Compared With Synchronous Generator.

Similar documents
Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

Grid Stability Analysis for High Penetration Solar Photovoltaics

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

ELG4125 Themes of Course Projects

New York Science Journal 2017;10(3)

Analysis of Grid Connected Solar Farm in ETAP Software

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

DISTRIBUTED GENERATION FROM SMALL HYDRO PLANTS. A CASE STUDY OF THE IMPACTS ON THE POWER DISTRIBUTION NETWORK.

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

Voltage Control Strategies for Distributed Generation

Impact of Distributed Generation on Reliability of Distribution System

Investigation of Transient Recovery Voltage Across a Circuit Breaker with Presence of Braking Resistor

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

Cabo Verde s new Renewable-Energy-Friendly Grid Code

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Modelling and Simulation of DFIG with Fault Rid Through Protection

Reactive power support of smart distribution grids using optimal management of charging parking of PHEV

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

Critical Clearing Time and Voltage Stability of DG Integration in Lebanon: A Simulation Using MATLAB/SIMULINK

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Aggregation of plug-in electric vehicles in electric power systems for primary frequency control

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Using Active Customer Participation in Managing Distribution Systems

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Renewable Grid Integration Research in the U.S.

Power Conditioning of Microgrids and Co-Generation Systems

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

Testing Renewable Power Plants on High-Voltage-Ride-Through Capability

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

HOMER OPTIMIZATION BASED SOLAR WIND HYBRID SYSTEM 1 Supriya A. Barge, 2 Prof. D.B. Pawar,

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

Distributed Energy Resources

Computer Aided Transient Stability Analysis

Performance Analysis of Transient Stability on a Power System Network

Wind Farm Evaluation and Control

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

Solar Development in New Jersey, and PV Impacts on the Distribution System Carnegie Mellon Conference on the Electricity Industry - March 9, 2011

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

Available online at ScienceDirect. Procedia Engineering 170 (2017 )

Workshop on Grid Integration of Variable Renewable Energy: Part 1

OPTIMUM ALLOCATION OF DISTRIBUTED GENERATION BY LOAD FLOW ANALYSIS METHOD: A CASE STUDY

Project introduction

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

Fault Rid Through Protection of DFIG Based Wind Generation System

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

PV Grid Integration Research in the U.S.

A.Arun 1, M.Porkodi 2 1 PG student, 2 Associate Professor. Department of Electrical Engineering, Sona College of Technology, Salem, India

Black Start capability in the Wind Turbine Market

Assessing Feeder Hosting Capacity for Distributed Generation Integration

Behaviour of battery energy storage system with PV

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

Case No. 5 Sequential Motor Dynamic Acceleration Simulation ETAP TS V&V Case Number TCS-TS-181

Impacts of distributed photovoltaic generation on Jenin distribution network: voltage level, power losses, power factor and power quality

Intelligent Control Algorithm for Distributed Battery Energy Storage Systems

Power Management with Solar PV in Grid-connected and Stand-alone Modes

BIDIRECTIONAL DC-DC CONVERTER FOR INTEGRATION OF BATTERY ENERGY STORAGE SYSTEM WITH DC GRID

Statcom Operation for Wind Power Generator with Improved Transient Stability

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

COMPARISON OF DIFFERENT SOFTWARE PACKAGES IN POWER FLOW AND SHORT-CIRCUIT SIMULATION STUDIES. A Project

Combined Inertia and De-loading Frequency Response Control by Variable Speed Wind Turbines

IJREE - International Journal of Research in Electrical Engineering ISSN:

Influence of Distributed Generations and Renewable Energy Resources Power Plant on Power System Transient Stability

POWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS

GTG MW GTG MW STG 2 36 MW CB11 CB9 GEN TRAFO-4. GEN TRAFO-5 50 MVA 11/34.5 kv %Z. GEN TRAFO-2 50 MVA 11/34.5 kv 15.

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

Presentation to the PJM NEMSTF Interconnection Issues. Interconnecting Solar Projects on the PSE&G Distribution System

Modeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation. X. XU, M. BISHOP, D. OIKARINEN S&C Electric Company USA

Reactive Power Sharing Droop Control Strategy for DG Units in an Islanded Microgrid

Design of Active and Reactive Power Control of Grid Tied Photovoltaics

Energy Security Electrical Islanding Approach and Assessment Tools. Dr. Bill Kramer Senior Research Engineer Distributed Energy Systems Integration

Small Scale-Wind Power Dispatchable Energy Source Modeling

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Power System Analysis for a Utility with Localized Wind Generation: Southern Negros Oriental Case

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Cost Benefit Analysis of Faster Transmission System Protection Systems

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Design Modeling and Simulation of Supervisor Control for Hybrid Power System

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Smart Power Management System for Leisure-ship

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

Optimal Placement of Distributed Generation for Voltage Stability Improvement and Loss Reduction in Distribution Network

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

PES Cook Islands KEMA Grid Study Final Report

Control Application of PV Solar Farm as PV- STATCOM for Reactive Power Compensation during Day and Night in a Transmission Network

Hybrid Energy Powered Water Pumping System

Improved PV Module Performance Under Partial Shading Conditions

Design of Three Input Buck-Boost DC-DC Converter with Constant input voltage and Variable duty ratio using MATLAB/Simulink

Control Strategies for Supply Reliability of Microgrid

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

Transcription:

Impact of Photovoltaic Power Plant on the Transient Stability Compared With Synchronous Generator BARJANEH, A. 1 *, HEDAYATFAR, B. 2 KHAKSAR, M. 3 1 Electronic Engineering Department, Islamic Azad University, Saveh Branch, Saveh, Iran 2 Electronic Engineering Department, Islamic Azad University, Saveh Branch, Saveh, Iran 3 Electronic Engineering Department, Islamic Azad University, Saveh Branch, Saveh, Iran Amir.Barjaneh@Gmail.com Abstract: In the recent years the power system is changing and distributed generation (DG) units are used in power systems at the distribution level regularly. The power demand is increasing and it can be fulfilled by use of renewable energy sources like solar energy. This paper discusses the using of Photovoltaic power plant as a DG in distrusted network and its effect on transient stability. In order to scrutinizing the effect of PV system as a DG in redial distribution system, 3 IEEE standard test systems are simulated with Dig SILENT software. In all 3 networks a short circuit fault is taken and the effect of that is analyzed in 2 modes; first with synchronous generators (SG) and second with Photovoltaic (PV) power plant and the results are compared. Comparing the results shows that in all 3 networks PV power plant work could save the stability in active power and voltage without using any extra devices. [BARJANEH, A., HEDAYATFAR, B. KHAKSAR, M.. Impact Of Photovoltaic Power Plant On The Transient Stability Compared With Synchronous Generator. LIFE SCI J 2013;10(8S): 294-298] (ISSN:1097-8135). Http://www.Lifesciencesite.Com. 46 Keywords: : Activ Power; Distributed Generation; Photovoltaic; Transient Stability 1. Introduction The traditional way in electric power generation is centralized power plants and a broad distribution network. However, the power system is changing and distributed generation (DG) units are used in power systems at the distribution level. DG has different types depending on the type of energy sources, such as renewable and nonrenewable energy sources. In recent years, it can be witnessed a rapid development of renewable energy, e.g. wind power, photovoltaic (PV), etc. throughout the world. The main motivations behind this fastgrowing development are the rising environmental concerns, i.e. greenhouse gas emission, and carbon footprint reduction, and the increase in the fuel cost used for the electricity production.[1]. Accelerated tendency to industrialization and raised interest in environmental issues recently led us to explore the use of renewable sources such as solar energy. Photovoltaic (PV) power plants are increased as a renewable source due to its advantages. Compared to other electricity generating technologies, however, PVs are still more expensive; improvements in technology will hopefully bring this cost [2]. In a traditional power system, synchronous generators (SG) have the most important task in the secure operation and the stability of power system. During a disturbance, the speed governor and AVR/exciter regulate the frequency (active power) and terminal voltage (reactive power) of the SG respectively back to steady state operating point. The stability of the SG and the power network is therefore maintained. However the controllability of the SG controllers is restricted by the operating limits of the SG [3]. Several high level studies analyzed the impacts of DG on the power system design and operation [4], [5]. However, only recently also transient phenomena are being studied in detail [6], [7]. One interesting phenomena is transient stability. In [8] impact of fixed and variable speed wind generators on the transient stability of a power system network are studied. In This paper investigates transient stability of a power system, in which the SGs are replaced by PV power plant with the same generation capacity. In both cases, with SG and PV, speed governor and AVR/exciter regulate the frequency (active power) and terminal voltage are not used and being stable or not is just based on characteristics of the power plant. 3 IEEE standard test system with 12 bus, 33 bus and 69 bus are used in this study. Networks are simulated by DIgSILENT Ver. 14. This paper is organized as follow. Section II describes the simulated test systems and the amount of DG in each network. Section III presents the results of taking a short circuit fault in each test system in modes; with SG and PV power plant. Output Active power and voltage of DG are shown before fault, during the fault and after clearing the fault. The conclusion of the paper is presented in section IV. 294

I. Simulated test systems The test systems and characteristics of synchronous generator and PV would be different in each case and are depend on the network. PV just products active power but synchronous generator power factor is 0.8. A. 12 Bus Radial Test System This system is introduced in [9]. In this network power plant could generate 235.6 kw and is located in bus number 9. The conditions are same for synchronous generator and PV power plant. B. 33 Bus Radial Test System The network is introduced in [10]. In this case the best place for installing the DG is bus number 6 with an amount of 2400 kw.[10] C. 69 Bus Radial Test System In 69 bus radial distributed system the active generated power via Dg is 1883.8 kw. The DG is located in bus number 61. All characteristics of this network are introduced in [11]. Figure 2. Active power stability in 12 bus Active power and voltage are not stable in this case. In next step, synchronous generator would be replacing with PV power plant. The fault conditions are the same as pervious. The effect of fault on power plant is like Fig below. II. Simulated results A. 12 Bus Radial Test System Network is simulated in DIgSILENT software. The short circuit fault is started 0.5 sec after starting the simulation and it is occurs on line number 7. It would be finished after 0.3 sec. At first synchronous generator is used as a DG source. The effect of fault on active power and Figure 3. Voltage stability in 12 bus Figure 1. Voltage stability in 12 bus Figure 4. Active power stability in 12 bus As shown in above Fig. power and voltage are stable when PV is used as a DG source. B. 33 Bus Radial Test System 295

The short circuit fault place is on line number 3. Fault is started 0.5 sec after starting the simulation and it would be finished after 0.4 sec. Firstly, DG is a synchronous generator that is located on bus number 6. The effect of fault on active power and Figure 8. Active power stability in 12 bus Figure 5. Voltage stability in 12 bus In this case, both voltage and active power are stable because of using PV as a DG power source. C. 69 Bus Radial Test System Like others, this network is simulated in DIgSILENT software too. The short circuit fault is started 0.5 sec after starting the simulation and it is occurs on line number 59. It would be finished after 0.4 sec. In first mode, synchronous generator is used as a DG source. The effect of fault on active power and Figure 6. Active power stability in 12 bus Like pervious network, in this network power and voltage are not stable after fault. Pictures below show the results for the same network but with PV power plant instead of synchronous generator. Figure 9. Voltage stability in 12 bus Figure 7. Voltage stability in 12 bus 296

Figure 10. Active power stability in 12 bus The diagrams show that in 69 bus radial test system, after a longer period of time, the system could be stable as it was before. In second mode, PV generator is used as a DG source. The effect of fault on active power and Figure 11. Voltage stability in 12 bus system with PV Figure 12. Active power stability in 12 bus Like two pervious test system, in 69 bus radial distribution system, the network with PV get stable in a short time after clearing the fault. III. CONCLUSION Transient stability in 3 IEEE standard test system is compared between to case in each network. In first case DG is a SG and in second case DG is PV power plant. Fault conditions are same in both cases. According to results that are shown in pictures 1 to 12, in the case that PV is used as a DG, active power and voltage have same condition before and after fault. It means power and voltage are stable in this case and PV leads to a stable condition. On the other hand, in case that SG is used as a DG, in the same condition with PV case, active power and voltage are not stable after accruing the short circuit fault. In one word, using PV cause transient stability in distributions network because unlike the SG it does not have moving parts. REFERENCES 1. N.Hoang Viet, "Impact of fault ride-through characteristics of high-penetration photovoltaic generation on transient stability", Power System Technology (POWERCON), 2010 International Conference on, Conference Publications, Publication Year: 2010, Page(s): 1-7 2. Durgadevi, A.; Arulselvi, S.; Natarajan, S.P.,"Photovoltaic Modeling and Its Characteristics ",Emerging Trends in Electrical and Computer Technology (ICETECT), 2011 International Conference on, Publication Year: 2011, Page(s): 469-475 3. P. Kundur, Power System Stability and Control, McGraw-Hill, New York, 1994. 4. M. O'Malley, C. Nabe, J. Bömer, and D. Broad, The irish "all island grid study" - methodological approach and outcomes, in 2009 Powe Systems Conference and Exposition, March 15-18, 2009, Seattle, Washington, USA. Ecofys Germany GmbH, 2009. 5. Project Steering Group, Planning of the grid integration of wind energy in germany onshore and offshore up to the year 2020 (dena grid study), Deutsche Energie- Agentur GmbH, Tech. Rep., February 2005. 6. H. Lemmens and W. Winter, European wind integration study (EWIS). EWISinterim report, European Transmission System Operators, Tech. Rep., 2008. 7. H. Holttinen, P. Meibom, A. Orths, F. van Hulle, B. Lange, A. Tiedemann, M. O Malley, J. Pierik, B. Ummels, J. O. Tande, A. Estanqueiro, M. Matos, E. Gomez, L. Söder, G. Strbac, A. Shakoor, J. C. Smith, M. Milligan, and E. Ela, Task 25 - design and operation of power systems with large amounts of wind power. final report, phase one 2006-08 (draft), 2009, Implementing Agreement for Co-operation in the Research, Development, and Deployment of Wind Energy Systems 297

8. Folly, K.A.; Sheetekela, S., "Impact of fixed and variable speed wind generators on the transient stability of a power system network", Power Systems Conference and Exposition, 2009. PSCE '09. IEEE/PES, Publication Year: 2009, Page(s): 1-7 9. H. Hou, L. Lin, T. Wu, and Y. Miao," Comparison of Transient Stability between Wind Farm Based on DFIG and Traditional Power Plant in an Actual Grid", Power and Energy Engineering Conference (APPEEC), Asia-Pacific,. 2010, Pages: 1-4. 10. Abu-Mouti, F.S. and El-Hawary, M.E.," A Priority-Ordered Constrained Search Technique For Optimal Distributed Generation Allocation In Radial Distribution Feeder Systems". Electrical and Computer Engineering (CCECE), 23rd Canadian Conference on,, 2010. Pages: 1-7 11. Mistry, K., " GSA based optimal capacity and location determination of distributed generation in radial distribution system for loss minimization". Environment and Electrical Engineering (EEEIC), 2012 11th International Conference, 18-25 May 2012, Pages: 513-518. 4/2/2013 298