Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Similar documents
Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION

K-Limiter high ampere Companion II fuse

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

3.2. Current Limiting Fuses. Contents

Application of Primary Fuses

Disconnect & ByPass Switches

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

THE CURVE FOR DOUBLE PROTECTION TRANSFORMER & SYSTEM PROTECTION WITH CHANCE SLOFAST FUSE LINKS

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

X-Limiter full-range current-limiting fuse

FUSE LINKS. Catalog 10B October Phone: Web: hubbellpowersystems.com October 2015.

NX indoor current-limiting fuses

Figure 1. HX cutout fuseholders.

Figure 1. Two and Three-phase MagneX.

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

Figure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION

TEMPERATURE RISE TESTS

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Product Selection Guide

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

GENERAL. CONSTRUCTION External

34-SDMS-02 SPECIFICATIONS FOR

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

ECET Distribution System Protection. Overcurrent Protection

Figure 1. HX cutout fuseholders. Positive Interruption

Fuse Link Designation

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.

Technical Specification for Pole Mounted Capacitor Rack

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

Recommended Procedures

CMU medium voltage power fuses

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

EE 741 Over-voltage and Overcurrent. Spring 2014

MAGNETIC MOTOR STARTERS

Source-Side Fuse/Load-Side Recloser Coordination

Electric vehicle auxiliary fuses 500 Vdc, A

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

Boric Acid Fuse Links

A 1.2 kv class externally removable secondary bushing

600 A 15 and 25 kv class Cleer grounding elbow

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Equipment Protection. Transformers 600V or Less

FUSE TECHNOLOGY Ambient temperature

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

Medium Voltage Metal-Enclosed Switches

Equipment Protection. Transformers 600V or Less

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

A. Submit manufacturer's literature and technical data before starting work.

UL248 North American Low Voltage Fuses

Edison modular fuse, vault application products

Electronic Resettable Sectionalizer

INSTALLATION PRODUCTION TESTS

Selection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage

Each of these factors, as they apply to the selection of Types CLE and CLS current limiting fuses, is briefly outlined on the following pages.

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Section 1 Introduction to the Presentation

FUSES. Safety through quality

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

600 A 15 kv class T-OP II deadbreak connector

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Power Fuses. > Power Fuses > BPA & HPA kv AMPs

Tolerance-Based Time-Current Coordination

ELF -LR current-limiting fuse

Selection Guide Motor Control Device Solutions

Direct-connected capacitor fuse

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014

Section Contents. Page. Introduction... 72

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SPECIFICATION BULLETIN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

ATX DPD Series Distribution Panelboards Flameproof

SECTION PANELBOARDS

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

University of Houston Master Construction Specifications Insert Project Name

Fuseology. High Speed Fuses

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

Power systems Protection course

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

Transcription:

Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment. When properly coordinated with other overcurrent protective devices, sectionalizing to isolate faulted feeder branches or equipment can be accomplished. Edison Links are manufactured in a variety of styles, link speeds, and voltage ratings to ensure effective system coordination and overcurrent protection. They are available in nonremovable buttonhead, and open-link styles. All Cooper Power Systems expulsion fuse link designs were tested in accordance with ANSI standard C37.41, Section 12, and IEC Standard 282-2-1970, Section 15.8. Data from these tests have been utilized to plot the time-current characteristics for each fuse rating. Publication of minimum melting and total clearing TCCs certifies compliance with testing fuse links in accordance with these standards. EDISON LINK FUSES Edison Links are manufactured in removable and nonremovable buttonhead designs for use in open or enclosed distribution cutouts. Standard links are usable where the system voltage is 27 kv or less. For higher voltages, Edison Links are available for systems up to 38 kv. In addition, Cooper Power Systems provides open-link (STF) designs for use in open-link style distribution cutouts. A wide variety of open-links are available for system voltage at 15 kv or less. Edison Links are available for the higher system voltages through 18 kv. Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs System Fuse Ampere Rating Type Rating 27 kv Distribution K (tin) 1-200 (Open-type cutout) K (silver) 6-100 T 1-200 S 3-200 H 1-8 N 5-200 D 1-20 C 100* 38 kv Distribution EK 6-100 (Open-type cutout) ET 6-100 EH 1-5 15 kv Distribution K 6-50 (Open-link cutout) T 6-50 H 1-8 D 1-20 *140 and 200 coordinating links. PRODUCTION QUALITY ASSURANCE To assure Edison Link reliability, all incoming material must pass rigid material specifications. Each completed Edison Link must pass a 15 lb. pull strength test (ANSI Std requires 10 lb.) and simultaneously pass a resistance check for element verification and quality of current interchanges. June 2000 Supersedes 8/94 Printed in U.S.A. 1

Edison Links EDISON LINK SELECTION Coordination of a power system requires selective operation of the fuse with other protective equipment such as reclosers, sectionalizers, power circuit breakers, and other fuses. All electrical equipment, such as transformers, switches, conductors, and those mentioned above can withstand various levels of current for different intervals of time. This ability is usually shown as a time-current characteristic and, generally, the device will permit high current for a short period of time and low current for longer periods of time without thermal or mechanical damage. Proper coordination and protection can only be accomplished when the system designer has a variety of fuses with a wide range of timecurrent characteristics at his disposal. The speed ratio (Table 2) of a fuse link design (for fuse links 100 A and below) can be determined by calculating the ratio between the current that melts the fuse in 0.1 second to the current that melts the fuse in 300 seconds. For fuse links rated greater than 100 A, the ratio is calculated between melting currents at 0.1 second and 600 seconds. Refer to Figure 2 for a comparison of minimum melt curves for Types K, T, N and S Fuse Links. CURRENT CAPACITY When properly applied, Edison Links can be operated continuously at their current rating. Certain links can be operated at levels higher than rating (see Table 3) without damaging the fusible element. Care must be exercised to assure that the maximum current the Edison Link carries does not exceed the continuous current rating of the cutout. It may be possible for the cutout to carry higher continuous current levels than its rating. In these cases, the cutout manufacturer should be consulted. Additional continuous current-carrying capacity is particularly useful in applications where coordination requires greater load-carrying ability for specific time periods. Edison Links melting characteristics curves are determined without preload and at an ambient operating temperature of 20 to 30 C, as specified in ANSI C37.41 and IEC 232-2. Both preload and ambient operating temperatures can affect the melting characteristics of a fuse link. TABLE 2 Speed Ratios* Edison Link Description Average Speed Ratio Distribution Systems through 27 kv Type K Fast 6 through 8.1 (meets ANSI standards for a fast fuse) Type N Fast 6 through 11 (universal fuse link similar to Type K link) Type T Slow 10 through 13.1 (meets ANSI standards for a slow fuse) Type H Very Slow 6 through 18 (high-surge withstand characteristics) Type D Very Slow 7 through 46 (high-surge withstand characteristics) Type S Very Slow 15 through 20 (high-surge withstand characteristics) Type C Slow 18 through 26 (time-current characteristics similar to 140 and 200 A Type T links in high-current range) *Figure 3 compares the speed ratios of McGraw-Edison Type K, Type N, Type T, and Type S Edison links. Distribution Systems through 38 kv TIME (sec) Type EK Fast 6 through 8.1 Type ET Slow 10 through 13.1 Type EH Very Slow 13 through 22 (high-surge fuse link) 500 100 50 10 5 1 0.5 0.2 0.1 0.05 0.01 0.5 1 5 10 20 40 60 80 100 200 500 1000 2000 3000 10000 Figure 2. Speed ratio comparisons, typical minimum melt curves types K, T, N and S fuse links. 25N 25K CURRENT (amps) 25S 25T While many applications can overlook these factors as negligible, they should be considered when the preload on the fuse link is at a high percentage level and/or when the fuse link may be exposed to a high ambient operating temperature. Cooper Power Systems application engineers are available to assist in the proper application of Edison Links for these operating conditions. TABLE 3 Continuous Current Ratings Edison Link Allowable Continuous Type Current (% of rating) K-tin 150 K-silver 100 N 100 H 100 D 100 T 150 S 150* C 100 EK 150 ET 150 EH 100 *Except 125, 150, and 200 A 100% 2

K-SEC 100 EDISON LINK FUSE DESIGNS Type K Links Tin Type K links are available in ratings from 1-200 A in the buttonhead design and from 6-50 A in the openlink design. The standard Type K link is constructed with a tin fuse element. Type K Links Silver Type K links with a silver fuse element are also available as an option. They are manufactured in removable and nonremovable buttonhead designs with ratings from 6-100 A. Type T Links Type T links are available in ratings from 1-200 A in the buttonhead design and from 6-50 A in the openlink design. The standard Type T link is constructed with a tin fuse element. Type T links exhibit the same overload characteristics as similarly rated Type K links at the 300-or 600-second points. The time-current characteristics differ below these points. Hence, the T link is slower at the high-current end than the same size K link. Type H (High Surge) Links Type H links are manufactured in ratings of 1, 2, 3, 5 and 8 A. Type H high-surge links are designed principally for primary fusing of small distribution transformers. These fuse links are designed specifically to provide the overload protection normally associated with fuse links of 1, 2, 3, 5, and 8 A, yet avoid unnecessary operation during short-time transient current surges such as those resulting from motor starting, lightning, or other causes. The Type H links are constructed of multiple elements of specially selected alloys. In addition, open link designs are available for use in open link distribution cutouts. Type D Links Type D links are multiple-element links of specially designed alloys, and are available in ratings of 1 through 20 A. The D link is similar in design to the H high-surge link except it is slower at the high-current end. The superior surge withstand makes the probability of lightning damage very small, making the D link ideal for protection of small-to medium kva distribution transformers. The link can be mounted in series and on the source side of the arrester, freeing the arrester for mounting directly on the transformer. Type N Fuse Links Type N links are manufactured in ratings of 5-200 A. Type N links conform to applicable ANSI standards for mechanical interchangeability. They exhibit speed ratios approximately the same as the Type K link. The Type N link features a tin fuse element. Type S Links Type S links are manufactured in ratings of 3-200 A with removable buttonheads. These links exhibit very slow time-current characteristics, making them ideal for protecting equipment from faults and overloads requiring a slow-speed, high-surge application. Type S links coordinate particularly well with reclosers. Type C Coordinating Links Type C links are available in removable buttonhead design rated 100 A and can be used in standard 100 A distribution cutouts. They exhibit time-current characteristics in the high-current range similar to 140 A and 200 A Type T links. Time-current characteristics in the low-current range are similar to 100 A Type T fuse links. Type C links are used in coordination schemes where the high-current, short-duration characteristics of 140 A and 200 A links are desired, but where the load current does not exceed 100 A. Types EH, EK, and ET Links These Edison Links are designed for use on 38 kv distribution systems. Types EH, EK, and ET Edison Links are manufactured in a nonremovable buttonhead design with ratings from 1-5 A EH, 3-100 A EK and 6-100 A ET. These links exhibit the same time-current characteristics as similarly rated Types H, K, and T Edison Links. ADDITIONAL OPTIONS Edison Links are also available with a number of options including those listed below. Contact your Cooper Power Systems representative for information on availability and pricing. Ferrule Adapter Converts removable buttonhead links into a double-leader link for use in older-style, double-vented cutouts with clamping-type leader connections at both the upper and the lower fuse leader connection. Wedge Adapter Provides positive leader termination in distribution fuse cutouts designed with a wedge-type fuse leader connection. Leader Options 26-and 30-in. fuse link lengths and larger-diameter flexible leaders are available. Packaging Buttonhead type Edison Links rated 27 kv, 1-100 A are packaged in individual bags. All other Edison Links are available with individual bag packaging only. Five individual boxed fuses fit in one larger box, which is of a compact size for ease of storage and handling. There are perforations on the sides of each individual box, which allows the line person to easily break the box and remove the Edison Link. To order Edison Links packaged in boxes rather than bags, a B suffix is added to the catalog number. 3

Edison Links CONSTRUCTION FEATURES Single Element CAPTIVE WASHER Washer is held in place and will not fall off fuse link. Washer can still be removed if needed. FUSE ELEMENT Engineered for accurate fusing using a single tin element for cooler operation. AUXILIARY TUBE Provides gases for low-current interruption. BUTTONHEAD STRAIN WIRE Provides exceptional tension relief in excess of standards. FERRULE Copper construction for better soldering, conductivity, and strength LEADER Stranded for strength and flexibility Figure 3. Typical Types K, T, N, and H (8 A) link construction. Dual Element BUTTONHEAD FUSE ELEMENT Provides accurate fusing characteristics for overloads and fault protection, with high-surge withstand capability. LEADER Stranded for strenght and flexibility. CAPTIVE WASHER Washer is held in place and will not fall off fuse link. Washer can still be removed if needed. AUXILIARY TUBE Provides gases for low-current interruption. SPRING (Only used on H-Links through 5 A and S Links through 25 A.) Assists in leader ejection to provide consistent time-current characteristics. Figure 4. Typical Type D, S, and H (1 A through 5 A) link construction. 4

K-SEC 100 8 3 / 8 " 1 7 / 8 " 1" DIA. 1" ID Figure 5. Dimensions of open-link Edison Link. 1 / 2 " DIA. 19 / 64 " WASHER 1 THROUGH 50 A 23" MIN. 13 / 32 " 65 THROUGH 100 A 23" MIN. 21 / 32 " 1" DIA. 140 THROUGH 200 A 23" MIN. Figure 6. Dimensions of typical Types D, H, K, T, N Edison Links (removable buttonhead shown; nonremovable buttonhead dimensions are similar). 140 A and 200 A Type C fuse links (Table 7) are the same size as the 65 through 100 A fuse links. 5

Edison Links 1 / 2 " DIA. 19 / 64" 1 1 / 8 " WASHER 23" 1 / 2 " DIA. 3 THROUGH 25 A 19 / 64" WASHER 23" 30 THROUGH 50 A 13 / 32" DIA. 1" DIA. 23" 65 THROUGH 100 A 21 / 32 " DIA. 23" 125 THROUGH 200 A Figure 7. Dimensions of typical Types S Edison Links (nonremovable buttonhead). 9 1 /2" 3 / 4 " 7 / 16 " 13 / 32 " 30" MIN. *8 1 / 2" for EK and ET 65 through 100 A. Figure 8. Dimensions for nonremovable buttonhead links for 38 kv distribution systems. 6

K-SEC 100 ORDERING AND DIMENSIONAL INFORMATION To build a catalog number, add the Edison Link ampere rating required to the catalog number listed in Tables 4 through 7. For example: the catalog number for a 25 A Type K open-link Edison Link used with a 7.8 kv-rated fuse cutout is FL4K25. (Refer to Table 6.) TABLE 4 Removable and Buttonhead Edison Links for Distribution Systems Rated through 27 kv (23" Length) Edison Link Rating Type (A) Buttonhead Catalog Number H-tin 1,2,3,5,8 Removable FL3H_ (high surge) FL11H_ FL24H_* D-tin 1,1.5,2,3,4,5,7,10,15,20 FL1D_ (high surge) Removable FL3D_ K-tin 1 through 200 Removable FL3K_ (fast) FL11K_ FL24K_* FL25K_** Removable FL26K_** Removable FL27K_* K-silver 6 through 100 Removable FL6K_ (fast) FL12K_ N-tin 5 through 200 Removable FL3N_ (fast) 5 through 200 FL11N_ T-tin 1 through 200 Removable FL3T_ (slow) FL11T_ FL24T_* FL25T_** Removable FL26T_** Removable FL27T_* S-copper 3 through 200 Removable FL2S_ (very slow) * Length of link is 2. **Fuse link has heavy-duty leader. TABLE 5 Removable Buttonhead Edison Links for 38 kv Distribution Systems Edison Link Catalog Type Rating (A) Number EH-tin 1,2,3,5 FL8H_ (high surge) EK-tin 6 through 100** FL16K_ (fast) ET-tin 6 through 100** FL16T_ (slow) * Length of link is 2. **Fuse link has heavy-duty leader. TABLE 6 Open-Link Edison Links Edison Link Cutout Rating Catalog Type Rating (A) (kv) Number H (high surge) 1,2,3,5,8 7.8 through 15 FL4H_ D (high surge) 1,1.5,2,3,4,5,7,10,15,20 7.8 through 15 FL4D_ K (fast) 6 through 50 7.8 through 15 FL4K_ T (slow) 6 through 50 7.8 through 15 FL4T_ 7

Edison Links TABLE 7 Type C Universal Edison Links Link Rating Rating for Coordination Continuous Purposes Catalog (ampere) (ampere) Number 100 140 FL1C140 100 200 FL1C200 ADDITIONAL INFORMATION Cooper Power Systems has additional reference information available for Edison Link selection and coordination. See Tables 8 and 9. For copies of additional literature, contact your local Cooper Power Systems representative. TABLE 8 Edison Link TCC Curves R240-91-1 Type K Tin time-current characteristics curves R240-91-2 Type T Tin time-current characteristics curves R240-91-3 Type H High-surge time-current characteristics curves R240-91-4 Type K Silver time-current characteristics curves R240-91-5 Type EK Tin time-current characteristics curves R240-91-6 Type ET Tin time-current characteristics curves R240-91-7 Type EH High-surge time-current characteristics curves R240-91-8 Type C Tin time-current characteristics curves R240-91-9 Type N Tin time-current characteristics curves R240-91-15 Type S Time-current characteristics curves R240-91-16 Type D Time-current characteristics curves TABLE 9 Fuse Link Reference Information Reference No. Title 240-91 Index of TCC s TD-311 Comparison of Tin and Silver Fuse Links. CP7734 What the Rating System on Fuses Actually Means 90016 D-link Brochure 91027 Developing a Fusing Schedule (PD Update 12) 92024 D-Link, New Ratings and Surge Durability (PD Update) R240-30-2 Coordination Tables for T, H, N Fuse Links R240-30-3 Coordination of Fuse Links with Oil Circuit Reclosers R240-30-5 Fuse Links for Carrying Lightning Surges R240-30-6 Suggested D-link for Distribution Transformers R240-30-7 Coordination of D-link with K, T and S links 2000 Cooper Industries, Inc. Edison and NX are registered trademarks of Cooper Industries, Inc. Kearney is a trademark of Cooper Industries, Inc. P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com 8 Printed on Recycled Paper MI 6/00