Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Similar documents
Selective Coordination

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

A. Submit manufacturer's literature and technical data before starting work.

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

SECTION MOTOR CONTROL

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Enhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

B CW POWER RELAY

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

MAGNETIC MOTOR STARTERS

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Electromagnetic Industries LLP

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

SECTION PANELBOARDS

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

AP/UP, AP/MIL Series Magnetic Circuit Protectors

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

COM Overcurrent Relay

GE 8000-Line Motor Control Centers Mains, Feeders, Incoming Lines C-1

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

AIR COOLED RECTIFIER SPECIFICATION S-50-A

SECTION MOTOR CONTROLLERS

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Phenix Technologies Inc. 75 Speicher Drive Accident, Maryland 21520

1492-CB 1492-GH 1492-GS

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

GP/GPA GROUND FAULT PROTECTION

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

KD LV Motor Protection Relay

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

PD-Series Ground Fault Circuit Protection

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

Horizontal Circuit Switchers

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

www. ElectricalPartManuals. com Instructions for Ground Fault Protection Systems INTRODUCTION SENSOR Fig. 1 Cu"ent Monitor

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

P. Sub 4 184A404. Sub 3 876A220

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

Bulletin 1489 Circuit Breakers. Selection Guide

Type IMC Indoor current transformer

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

Bussmann series Quik-Spec Power Module Switch elevator disconnect

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

MODEL 422 Submersible Pump Controller

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

SURE TRIP RETRO KITS

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

Motor Protection. Presented By. Scott Peele PE

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

3.2. Current Limiting Fuses. Contents

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Contacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact.

209 Series. Magnetic Circuit Protectors

INSTRUCTION MANUAL MODEL CB-7120A CIRCUIT BREAKER

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

High Frequency SineWave Guardian TM

Functions provided by measuring relays in railway equipment

Horizontal Circuit Switchers

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

TO COME. CEP7 Solid-State Overload Relay for Motor Control Centers and Enclosed Control

Transcription:

Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC Relay Monitor Components Contents Application Data.................................................. 2-4 Suggested Specifications.......................................... 5-6 Characteristic Tripping Curve......................................... 7 Dimensions........................................................ 8

Ground-Censor Ground-Fault Protection System Type GC Bulletin No. 0931DB0101 Data Bulletin July 2001 APPLICATION DATA Description Application Ratings Operation 09313064 SOURCE Main Bonding Jumper Grounding Electrode Neutral Assembly Equipment Ground Connection A B C N G Equipment Grounding Conductor Equipment type ground-fault protection system. Consists of ground-fault relay, ground-fault sensor, and a nameplate for monitor-test system. The Ground-censor Type GC equipment ground-fault protection system is for use on grounded alternating current systems rated up to 600 volts ac, 60 hertz (cycle) to provide protection in accordance with National Electrical Code Paragraphs 110-10 and 230-95. The GC-100 Ground-fault Relay is rated 600 volts ac, 60 hertz. Suitable for use on equipment connected to a source having 200,000 RMS amperes or less available ground-fault current. The GC-100 relay requires a 120 volt ac source; power of 3 watts typical in standby and 12 watts typical during trip. Each GC-100 relay can drive up to eight additional GC-100 relays for the purpose of zone selective interlocking (ZSI). The components are UL listed in File E-48368 as Ground-fault Sensing and Relaying Equipment. Under normal load conditions, the vector summation of all phase and neutral (if used) currents approaches zero. However, under ground-fault conditions, these currents do not add to zero. A sensor (differential current transformer) around the phase and neutral conductors detects the current imbalance when a ground fault occurs. The output of the sensor is proportional to the magnitude of the ground-fault current. This output is fed to a ground-fault relay. When the ground-fault current exceeds a pre-selected level, the relay will activate the circuit interrupting device. Figure 1: Operation Ground-fault Relay 09313065 The GC-100 relay continuously monitors the output of the sensor and initiates the opening of the circuit. The ground-fault current pick-up is field adjustable from 100 to 1,200 amperes. The restrained time delay is field adjustable for 0.1, 0.2, 0.3, or 0.5 seconds. Two or more relays may be zone selective interlocked to provide instantaneous operation (0.03 seconds) in each zone and system coordination. Figure 2: GC 100Relay Sensor 09313066 The sensor consists of a laminated iron core with two main windings on opposite sides. The windings are connected in parallel so that the effects of local saturation of the iron core are minimized and greater reliability is gained due to the redundancy of the windings. Should one winding be opened or shorted, the other would continue to operate satisfactorily (but with less accuracy or sensitivity). The iron core is bolted at the corners and a leg may be removed to facilitate installation of the sensor around the conductors in existing equipment. A special test winding is super-imposed on one of the main windings and when energized, induces a current in the main winding, simulating a ground-fault condition. Figure 3: GT Sensor 2

Bulletin No. 0931DB0101 July 2001 Ground-Censor Ground-Fault Protection System Type GC Data Bulletin Monitor-test System 09313067 A red light indicates tripping due to a ground-fault condition. A nameplate with instructions for test with or without trip is provided with each GC-100 relay. For test with or without trip (per nameplate provided), the following components are required: One green illuminated push button with contact block. One red illuminated push button with contact block. One miniature or general purpose relay with socket. Figure 4: Monitor Components For test with trip only (no nameplate provided), the following components are required: Non-illuminated push button with contact block. Red illuminated push button with contact block. Electrical Conditions Circuit Interrupting Device 09313068 All components have screw terminal connections. Wires from sensor to relay should not be longer than 25 feet and no smaller than No. 14 AWG. Wires from the test-monitor components should not be longer than 50 feet and no smaller than No. 18 AWG. Interconnecting wires between relays should be in accordance with the following: 1 150 feet one way #16 AWG 151 250 feet one way #14 AWG 251 400 feet one way #12 AWG 401 650 feet one way #10 AWG 651 1000 feet one way #8 AWG Any circuit interrupting device suitably rated for the duty, and incorporating a 120 volt ac shunt trip or electric tripping mechanism with less than 50 amperes inrush and less than 10 amperes continuous current requirements. Figure 5: Molded Case Circuit Breaker 09313072 Figure 6: Bolted Pressure Switch 3

Ground-Censor Ground-Fault Protection System Type GC Bulletin No. 0931DB0101 Data Bulletin July 2001 System Coordination Refer to Figure 7 for a typical coordination arrangement. Relay No. 3 will restrain in a timedelay mode Relay No. 2 which in turn restrains Relay No. 1; Relay No. 2 restrains Relay No. 1. For example, with a ground-fault of 1500 amperes at Location No. 3, Relay No. 3 will initiate a signal in 0.03 seconds to the Branch Device to open the circuit. At time of the fault, Relay No. 3 also sends a restraining signal to Relay No. 2 which in turn sends a restraining signal to Relay No. 1 causing these two relays to start timing duration of the fault. Relay No. 2 will initiate a signal to Feeder Device only if Branch Device fails to open circuit 0.2 seconds after ground-fault occured. Relay No. 1 will initiate a signal to Main Device only if Branch Device and Feeder Device fail to open circuit 0.5 seconds after ground-fault occurred. If a 1500 ampere ground-fault occurs at Location No. 2, Relay No. 2 will initiate a signal in 0.03 seconds to Feeder Device to open circuit. At time of the fault, Relay No. 2 also sends a restraining signal to Relay No. 1. Relay No. 1 will initiate a signal to Main Device only if Feeder Device fails to open circuit 0.5 seconds after ground fault occurred. If a 1500 ampere ground fault occurs at Location No. 1, Relay No. 1 will initiate signal in 0.03 seconds to Main Device to open circuit. This type system coordination allows the circuit interrupting device nearest the ground-fault to receive an operation signal instantaneously (0.03 seconds) and provide time delay in only the back-up devices. Clearing time of circuit interrupting device must also be considered in complete system coordination. MAIN DEVICE FEEDER DEVICE Line Sensor X Sensor X Shunt Trip Relay Reset Fault LOCATION No. 1 Shunt Trip Relay Reset Fault LOCATION No. 2 11 12 13 14 15 16 17 18 19 11 12 13 14 15 16 17 18 19 120 Vac Source GC 100 RELAY No. 1 120 Vac Source GC 100 RELAY No. 2 120 Vac Source Typical Setting: Trip Setting 1200 Amp Time Delay 0.5 Seconds Typical Setting: Trip Setting 700 Amp Time Delay 0.2 Seconds BRANCH DEVICE Shunt Trip Relay Reset 11 12 13 Sensor 14 15 16 GC 100 RELAY No. 3 Typical Setting: Trip Setting 100 Amp 17 18 19 X Fault LOCATION No. 3 NOTE: For clarity, not, all power supply and test circuit connections are shown. Figure 7: System Coordination 4

Bulletin No. 0931DB0101 July 2001 Ground-Censor Ground-Fault Protection System Type GC Data Bulletin SUGGESTED SPECIFICATIONS General Current Sensor Ground-fault Relay Circuit Breaker A ground-fault protection system shall be included when indicated in switchboard schedule and where otherwise indicated on the plans. It shall consist of a current sensor enclosing all phase (and neutral, if present) conductors of the circuit to be monitored, appropriate relaying equipment to provide the desired ground-fault current sensitivity and time-current response characteristics, and (an appropriately sized molded case circuit breaker) (an appropriately sized fusible bolted pressure contact switch) (an appropriately sized low-voltage power breaker) equipped to function in conjunction with the other elements of the ground-fault protection system. Installation of equipment shall in all respects be in accordance to manufacturer s recommendations. A sensitive current sensor shall be provided to sufficient size to encircle phase conductors and, where used, neutral conductor of circuit to be monitored. Current sensor output shall be coordinated with required input to the relay. A test winding shall be included to simulate flow of ground-fault current through current sensor in order to test operation of the ground-fault protection system including pick-up, relay and circuit protective device operation. The frame of the current sensor shall be so constructed that one leg can be opened to allow removal or installation around cable or bus without disturbing the cable or requiring drop-links on the bus. The relay shall be solid state construction for maximum reliability and shall provide zone-selective interlocking for instantaneous (0.03 seconds) operation in each zone. The relay shall require only 120 volt power to operate associated molded case circuit breaker, fusible bolted pressure contact switch or low-voltage power breaker. Adjustable pickup current sensitivity for ground-fault currents from 100 amperes to 1,200 amperes shall be provided. A calibrated dial shall be provided for setting the current pickup point in the field. Settings for individual relays shall be (as shown on the plans) ( amperes). The restrained time delay provided by the relay zone selective interlock circuitry shall be nominally (0.1, 0.2, 0.3 or 0.5 seconds) for main, (0.1, 0.2, 0.3 or 0.5 seconds) for feeder, (0.1, 0.2, 0.3, or 0.5 seconds) for branch, and shall be field adjustable. A self-contained test circuit utilizing the test coil provided in the current sensor shall be incorporated for testing with and without tripping of the circuit interrupting device. A self-contained test circuit utilizing the test coil provided in the current sensor shall be incorporated for testing with tripping and the circuit interrupting device. A molded case circuit breaker rated at amperes and having an interrupting rating of amperes RMS symmetrical at volts shall be provided to open the circuit. It shall incorporate thermal and magnetic elements for conventional overload and fault current protection as well as a ground-fault trip mechanism activated by the ground-fault relay causing it to open the circuit in the event of ground-fault conditions sufficient to operate ground protection system. 5

Ground-Censor Ground-Fault Protection System Type GC Bulletin No. 0931DB0101 Data Bulletin July 2001 Fusible Bolted Pressure Contact Switch (Alternate) Low Voltage Power Breaker (Alternate) A fusible bolted pressure contact switch rated at amperes, volts, and equipped with fuses shall be provided to open the circuit for normal switching, overload, short circuit, or ground-fault current sufficient to operate the relay. It shall include ground-fault trip mechanism activated by the ground-fault relay which, operating in conjunction with an interposing relay and auxiliary power source, will release a storedenergy device to open the switch. The ground-fault trip mechanism must be capable of operating satisfactorily at 55% of rated voltage to provide satisfactory operation under the reduced voltage that might accompany a ground-fault condition. The switch interrupting rating shall be coordinated with the time delay of the relay to insure that the switch is capable of interrupting any current it may be required to open. A low voltage power breaker rated at amperes, volts shall be provided to open the circuit for normal switching, overload, short circuit, or ground-fault current sufficient to operate the relay. This power breaker shall include ground-fault trip mechanism activated by the ground-fault relay which, operating in conjunction with an interposing relay and auxiliary power source, will release a stored-energy device to open the breaker. The shunt trip release must be capable of operating satisfactorily at 55% of normal operating voltage to provide satisfactory operation under the reduced voltage that might accompany a ground-fault condition. 6

Bulletin No. 0931DB0101 July 2001 Ground-Censor Ground-Fault Protection System Type GC Data Bulletin CHARACTERISTIC TRIPPING CURVE 09313070 Figure 8: Characteristic Tripping Curve 7

Ground-Censor Ground-Fault Protection System Type GC Bulletin No. 0931DB0101 Data Bulletin July 2001 DIMENSIONS 09313071 1.31 [33] 7.34 [186] 9.60 [244] 9.00 [229] 7.75 [197] 5.13 [130] 1.19 [96] Dia. 2.94 [75] 3.76 [96] 0.82 [21] 2.50 [64] 1.25 [32] 5.60 [145] 5.50 [140] 4.50 [114] Cat. No. A B C D E F G GT 912 12.12 [308] 13.00 [330] 13.00 [330] 14.60 [371] 16.05 [408] 5.00 [127] 8.00 [203] GT 918 GT 930 12.12 [308] 12.12 [308] 13.00 [330] 13.00 [330] 19.00 [483] 31.00 [787] 20.60 [523] 32.60 [828] 22.05 [560] 34.05 [865] 5.00 [127] 5.00 [127] 14.00 [356] 26.00 [660] G C D GT 1218 15.12 [384] 16.00 [406] 19.00 [483] 20.60 [523] 22.05 [560] 8.00 [203] 14.00 [356] E GT 1224 15.12 [384] 16.00 [406] 25.00 [635] 26.60 [676] 28.05 [712] 8.00 [203] 20.00 [508] GT 1230 15.12 [384] 16.00 [406] 31.00 [787] 32.60 [828] 34.05 [865] 8.00 [203] 26.00 [660] GT 1530 18.12 [460] 19.00 [483] 31.00 [787] 32.60 [828] 34.05 [865] 11.00 [279] 26.00 [660] F Square D Company PO Box 3069 3700 Sixth St SW Cedar Rapids IA 52406-3069 USA 1-888-SquareD (1-888-778-2733) www.squared.com A B Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. Bulletin No. 0931DB0101 July 2001 Replaces 931 dated 04/82. 0.44 [11] 0.82 [21] 3.00 [76] 0.53 [13] 0.78 [20] in. Dimensions: [mm] 8