VFT Response to a Breaker Trip and Runback Event

Similar documents
Variable frequency transformer for asynchronous power transfer

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant

GE Energy. Variable Frequency Transformers Grid Inter-tie

Electric Power Research Institute, USA 2 ABB, USA

2015 Grid of the Future Symposium

Deploying Power Flow Control to Improve the Flexibility of Utilities Subject to Rate Freezes and Other Regulatory Restrictions

Hurricane Sandy. Preparations, Response & Recovery. Wes Yeomans Vice President Operations Management Committee Meeting November 2, 2012

Synchronous Condenser Conversions at FirstEnergy Eastlake Plant. C.R. SLATTERY FirstEnergy Corporation. J.M. FOGARTY General Electric Company USA

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

Modeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation. X. XU, M. BISHOP, D. OIKARINEN S&C Electric Company USA

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Novel Use of Existing Data for Smart Grid Preliminary Analysis and for Asset Optimization

IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008

SEL Microgrid Lessons Learned

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Margarett Jolly DG Manager, Consolidated Edison Company of New York, Inc

MINIMUM OIL BURN/AUTOMATIC FUEL SWAPPING CAPABILITY

MMP Investigation of Arthur Kill 2 and 3

EXCEPTIONS TO NYSRC RELIABILITY RULES

Power Conditioning of Microgrids and Co-Generation Systems

IEEE SESSION COMPUTER AIDED SMART POWER GRID

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

INTERCONNECTED POWER SYSTEMS POWER GRIDS. Chapter 8

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Initial Field Trials of Distributed Series Reactors and Implications for Future Applications

Essential Reliability Services Engineering the Changing Grid

Workshop on Grid Integration of Variable Renewable Energy: Part 1

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

ASSESSING BEHAVOIR OF THE OUTER CROWBAR PROTECTION WITH THE DFIG DURING GRID FAULT

Implementation of software application for lightning strikes locating within analysis of power transmission network elements fault emergence

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

Climate change drivers for a single and smart EU grid

Renewable and Distributed Energy Resource Technologies

Electrical Theory. Generator Theory. PJM State & Member Training Dept. PJM /22/2018

PSNH INTERCONNECTION REQUEST

Computer Aided Transient Stability Analysis

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Guidelines for connection of generators:

ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT

34 th Hands-On Relay School

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

GENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview

Power Systems Fundamentals

EXCEPTIONS TO RELIABILITY RULES REVISION 4 MAY 8, 2015

Synthetic Inertia from Wind Turbine Generation

Possibilities of Distributed Generation Simulations Using by MATLAB

2013 Grid of the Future Symposium. Modeling, Simulation, and Applications of Distributed Battery Energy Storage Systems in Power Systems

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

G. K. VENAYAGAMOORTHY

Reliable Integration of Inverter-Based DER

New Method for Improving On-Line Loading Rates on Mechanical Governors By Gerald G. Runyan

ANN Peak Load Shaver.

ABB POWER SYSTEMS CONSULTING

3.0 Radial Distribution Systems

NYISO Market Initiatives

Electrical Machines II. Week 5-6: Induction Motor Construction, theory of operation, rotating magnetic field and equivalent circuit

Prepared. FUNCTION 3 Start up 3 Continuous operation 3 Shut down 3 Stand still 3

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Pumped Storage Power Plants Solution

Hybrid DC-DC-AC Main Drive for ILVA, Taranto Finishing Mill

Development of Electrical Power System Simulator.

Georgia Transmission Corporation Georgia Systems Operations Corporation

Small Electrical Systems (Microgrids)

Connecting to the Grid

Energy Storage for the Grid

STABILITY ANALYSIS OF VARIABLE FREQUENCY TRANSFORMER PARK USING ADVANCED CONTROLLING SCHEME S.VIJAY

Basics of Paralleling

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

AGN Unbalanced Loads

Power Purchase and Grid Connection Procedures

APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION

100 MW Wind Generation Project

Appendix G Examples and Recommended Methods

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

Simulation and Visualization of Power Grid Operations with High Renewable Penetration

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

Lesson 16: Asynchronous Generators/Induction Generators

DG SYNCHRONIZING &AMF PANEL

Protection with distributed generation, experience with the Mont-Soleil wind farm project

Benefits of HVDC and FACTS Devices Applied in Power Systems

AC MOTOR TYPES. DESCRIBE how torque is produced in a single-phase AC motor. EXPLAIN why an AC synchronous motor does not have starting torque.

Ancillary Services & Essential Reliability Services

New Jersey State Report

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

2016 Load & Capacity Data Report

World s Largest Air-cooled Turbogenerator in operation

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Synchronous Generators I. Spring 2013

Transcription:

21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium VFT Response to a Breaker Trip and Runback Event P.E. MARKEN GE Digital Energy Indiana, USA M. KURZIUS Linden VFT LLC New Jersey, USA SUMMARY An inadvertent circuit breaker trip caused Linden Cogen s supply of power to New York City to go from 530MW to 0. The three Linden VFT s were on line at the time but were not sending power into New York City before the event. While the generator runback system tripped all the steam turbines and all but one of the gas turbines, the VFT s stayed on line and prevented Linden Cogen from being islanded. The remaining gas turbine was producing 90MW of power, of which, 7MW was needed for house load. The VFT s moved the remaining 83 MW into the PJM grid in New Jersey. This was not an operator action but the function of the VFT governor controls. The response of the VFT s was stable and helpful and resulted in simpler and faster restoration. This paper describes the event in detail with a focus on the VFT response. KEYWORDS VFT, Reverse Power, Runback. paul.marken@ieee.org.

INTRODUCTION Linden Cogen supplies electrical power to New York City and steam to the Bayway refinery. Although it sits in Linden, NJ, the five gas turbines and three steam turbines supply electricity into the city through an underground 345kV cable under the Arthur Kills waterway. The generators are connected to a 345kV ring bus with the underground cable to New York City at one end of the ring bus. In 2009 three Variable Frequency Transformers (VFT s) were added to the other end of the ring bus. The VFT s connect the PJM grid to Linden Cogen, which is part of NYISO s system. VFT s are rated a nominal 100MW each. At Linden there are three units in parallel. Figure 1 shows a simplified one line diagram of the arrangement.[1] At the bottom of the figure are circuit breakers 52-3 and 52-4. These are the circuit breakers involved in this particular event. Normally, all circuit breakers are closed. In this case, circuit breaker 52-3 was open for maintenance, when 52-4 inadvertently opened, isolating Linden Cogen from the NYISO grid. FROM PJM VFT1 VFT2 VFT3 GT400 GT500 GT300 ST300 Breaker 52-3 GT100 ST100 GT200 ST200 Breaker 52-4 TO NYISO Figure 1 One-line diagram of ring bus at Linden Cogen and Linden VFT. This paper examines the details surrounding this event and in particular the response of the Linden VFT. The VFT response was logical and helpful and resulted in faster restoration to normal conditions. 2

VFT TECHNOLOGY The VFT can be considered a one to one transformer where the phase angle of one threephase winding can be varied with respect to the other three-phase winding. It s function can be compared to a continuously variable phase angle regulator. The control system varies the angle to cause power to flow per operator dispatch. Equation 1 below shows the relationship between the phase angle and the flow of power in an AC system, V is the system voltage, X is the impedance between the points involved and δ and σ are the phase angles at the two points. In this case the two points are each side of the VFT. It is clear that by controlling the phase angle across the VFT, full control of power flow can be achieved. V P = X 2 sin ( δ σ ) (1) From a physical standpoint, a VFT is not unlike a wound rotor induction motor with fully rated slip rings, called a collector. A torque motor controls the angle between the two windings and thereby controls the power flow. Figure 2 depicts the physical arrangement of a single machine. [2] Collector Torque Motor Main Windings Figure 2 Arrangement of a VFT. 3

EVENT DESCRIPTION At 11:55 on February 8, 2011, circuit breaker 52-4 (refer to Figure 1) inadvertently opened while circuit breaker 52-3 was already opened for maintenance. This isolated Linden Cogen from Con-Ed. At the time, Linden Cogen s net output to Con-Ed was 530MW. When circuit breaker 52-4 opened, the connected load dropped from 530 MW to 0 MW. The runback system initiated a trip on all running machines except GT-300, as it was programmed to do. GT-300 stayed on line generating 90 MW. There was a total house load of 7 MW connected, leaving an additional 83 MW. In any AC power system, the amount of power produced, at any moment in time, must match exactly the amount of power consumed. If more power is produced than is consumed, the frequency will increase. If less power is produced than is needed, frequency will decrease. The VFT controls take this into account and include a governor function. The additional 83MW being produced by Linden Cogen resulted in a frequency increase. When the VFT controls observed a frequency error the controls overrode the power order. The VFT began exporting the 83MW of excess power into the PJM grid and stayed connected to Linden Cogen. In this particular case, the governor function did not operate but instead it was the speed regulator of the rotor controls. Because both sides of the VFT are connected to the same Eastern US grid, the same frequency should always be observed on both sides. Normally the rotors of the Linden VFTs do not turn and only move upon changes in power order. In this case the faster speed regulator sensed the event before the actual governor function, and provided essentially the same response of changing the power order. Plant restoration immediately began with the start-up on steam turbines 100 and 200. Gas turbine 400 was started and synchronized at 12:50. A back-up air compressor and diesel generator were placed in service. At 13:05, Linden Cogen was informed by NYISO through ConEd not to exceed 100 MW into the PJM Grid. At 13:15, Linden Cogen was informed Goethals breaker 6 and 8 were closed, however Linden Cogen was unable to synchronize while connected to VFT. All running generators were removed from the grid with the exception of GT-400. Gas turbine 400 output was reduced to house load and VFT was isolated from Linden Cogen. At 13:55, 345 kv breaker 52-4 was closed and Linden Cogen proceeded to restore load to scheduled dispatch requirements. By 13:56 Linden Cogen resumed normal operation. 4

SUMMARY The controls of the VFTs displayed a response that was helpful overall. It is generally accepted that Linden Cogen was able to restore the situation to normal in a timelier manner because of the response of the VFTs. Instead of simply following the given power order, in this case 0MW, the controls sensed an extreme condition and did what they were able to, to alleviate the condition. The transmission grid has become far more complex and complicated than ever before. Transmission devices must focus not only on their own functions and purposes but can also be programmed to provide support during extreme grid events. In this case the VFT controls sensed an abnormal condition at Linden Cogen and acted without waiting for operator input. A similar event is documented in [3]. These experiences verify that the VFT continues to be a helpful technology for the transmission grid in North America. BIBLIOGRAPHY [1] E. R. Pratico, C. Wegner, P. E. Marken and J. J. Marczewski, First Multi-Channel VFT Application The Linden Project, presented at IEEE PES Transmission and Distribution Conference and Exposition, New Orleans, LA, April 2010. [2] P. Marken, J. Marczewski, R. D Aquila, P. Hassink, J. Roedel, R. Bodo, VFT A Smart Transmission Technology That Is Compatible With the Existing and Future Grid, presented at IEEE PES Power Systems Conference and Exposition, Seattle, WA, March 2009. [3] D. Nadeau, A 100-MW Variable Frequency Transformer (VFT) on the Hydro-Québec TransÉnergie Network The Behavior during Disturbance, presented at the IEEE PES General Meeting, Tampa, FL, June 2007. 5