Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

Similar documents
To ensure proper installation, digital pictures with contact information to before startup.

AUTO-EC-3-E-PLC Electric Filter Backwash Controller Operation & Maintenance Manual

Tekleen LPF USERS AUTOMATIC FILTERS, INC. MANUAL

Tekleen ABW USERS AUTOMATIC FILTERS, INC. MANUAL

To ensure proper installation, digital pictures with contact information to before startup.

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

Check List for Optimal Filter Performance

ALEX-TRONIX SMART CLOCK TM. BATTERY POWERED TEMPERATURE BUDGETING CONTROLLER MANUAL Patent Pending A DIVISION OF GNA INDUSTRIES, INC.

90 SERIES SELF CLEANING WATER FILTER OPERATION & MAINTENANCE MANUAL

Updated: October 2012

R & D SPECIALTIES ROTROL I USER'S MANUAL

TotalPac 3 Firecyle III Wet pipe Remote controlled system

Arch HTH Water Chemicals Commercial Equipment Trouble Shooting Guide

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

INSTRUCTION MANUAL INSTALLATION, OPERATION, AND MAINTENANCE ACTUATOR MANIFOLD

NECO Pumping Systems

COMPRESSED AIR LOADER MODEL: AL-1

Power Distribution System User s Manual. Model: PDS-100

REVISION HISTORY REVISION HISTORY

CAPACITOR ACTUATED PORTABLE STARTER CAPS USER GUIDE. INST048 Doc 3.01

TALCO FIRE SYSTEMS. LSF Start-Up Instructions. 1) IMPORTANT: Inspect the unit for damage. Report any damage to the freight carrier immediately.

Aqua-Clear Fiberglass Sand Filters

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

INSTALLATION/OPERATING INSTRUCTIONS TSC

ValveMate 7000 Controller Operating Manual

GENSET CONTROL MODULE A121A / A241A

Installation, Operation & Maintenance Manual Control Panels for Automatic Self-Cleaning Strainers Model 596 and Model 2596

Wiring Installation Instructions for : Pressure. Wiring Installation Instructions for : Temperature. 2 1/16 Spek Pro Professional Racing Gauge

1200+ WITH LVD (LOW VOLTAGE DISCONNECT) USER GUIDE

INSTRUCTION MANUAL. A battery protector for vehicles with equipment that Is operated with the engine not running. MODEL# INPUT: 12 Volts D.C.

Internal MAP Water/Methanol Injection Controller ,

HT Dielectric Withstand Tester Volts AC Output 25mA Leakage Option

Operator's Manual. Models (¾") (1") (1½ ) (2 ) (3") (4") (6") (8")

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

ARKAL SCREEN LINE H - SERIES Hydraulically Operated Self-Cleaning Screen Filter SERVICE & MAINTENANCE MANUAL

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

Two Channel Remote Shutdown Device

Pressure Makeup Jockey Pump Controller

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

GCU-10. Automatic Engine Control Unit Operators Manual

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

ITS-50R TRANSFER SWITCH OWNER S MANUAL

GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

ODY-19-1 AIR PRESSURE GAUGE

CHIP. Reverse Osmosis System Controller Documentation

Service Manual for Battery Control Center

1200+ WITH LVD (LOW VOLTAGE DISCONNECT) V1.00 OWNERS MANUAL

INDUSTRIAL CHARGER AUTOMATIC BATTERY CHARGER SERIES 150 KUSSMAUL ELECTRONICS CO., INC. MODEL # XX YEAR WARRANTY INSTRUCTION MANUAL

3143 Production Drive Fairfeild, Ohio Model HA-45. Installation and Service Manual

Cascade Master Series

Value Super Filter Max Installation Manual

ODY-05-2 VOLTMETER FOR REMOTE MONITORING

Linear Actuator Swing Gate Operator Installation Manual Model # LA405-24

FILTRON 1-10 (DC/AC) BERMAD Irrigation

BMF TROUBLESHOOTING GUIDE

1200+ WITH TIMER V1.00 OWNERS MANUAL

RK Standby Battery Operator s Manual

CRD610 Automatic Fitting Inserter

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

LX-80 COMMERCIAL POOL & SPA CONTROL INSTALLATION INSTRUCTIONS

This document describes:

CRD600 Automatic Fitting Inserter

TRAILER AUXILIARY POWER SYSTEM (TAPS) INSTALLATION GUIDE V1.10

Grundfos Variable Speed GRUNDFOS INSTRUCTIONS. Installation and Operation

Operators Manual ECO-AIR-IVS Internal Valve Actuation System

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

Airpax Dimensions, Inc.

Application Engineering

Redundant Control System

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

Series. idrive 300. Installation and User s Guide INTELLIGENT ENVIRONMENTAL CONTROL. March 2014 v1.1 Edition Copyright 2014 Corporation

OVERLOAD PROTECTION. All electrical circuits must have some means of protecting against overload.

CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER"

Gate & Door Controller with LCD and Intelligent Technology

HYDROTEK INTERNATIONAL, INC Forsyth Commerce Rd., Ste. 124, Orlando, FL Phone (800) / Fax (866)

DIFFERENTIAL THERMOSTAT

UniTorq UTQ Quarter-Turn Actuator Installation and Operation Manual

PowerVac. Service and Parts Manual P3 P5 P7. Single Vac Units. Twin Vac Units P6 P10 P14 FOR USE BY MIDMARK TRAINED TECHNICIANS ONLY.

Loctite Spray Valve Controller Part Number EQUIPMENT Operation Manual

MODEL 422 Submersible Pump Controller

ECONOMISER SERIES E2T USER MANUAL

INSTALLATION AND SERVICE MANUAL FOR TURBO-CARB HIGH CAPACITY CARBONATOR

Operations Manual. Zero Speed Switch Sensor Model ZS09P

DART Charger Product Description, Information and Specification

POWERLINE 2000 Energy Management System TM

SPIN KLIN GALAXY. Service & Maintenance Manual

Cat/DCG-6D1I/07-08/03/Ver 1 Page 2/10

Advantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.

HT Dielectric Withstand Tester Volts AC Output Volts DC Output COMPLIANCE WESTUSA. Instruction Manual

Superior Water And Air

FAN-STOP INSTRUCTION MANUAL

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

A/C PRESSURE MONITOR INSTALLATION INSTRUCTIONS SYSTEM OPERATION GREEN INDICATOR LIGHT

RK Standby Battery Operator s Manual

Instruction Manual MINI IRRIGATION CONTROLLER.

CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER"

TotalPac 3 Deluge, Electric release Remote controlled system

APOLLO Gate Operators, Inc.

INSTALLATION/OPERATING INSTRUCTIONS MCP

INSTRUCTION MANUAL MODEL # YEAR WARRANTY KUSSMAUL ELECTRONICS CO., INC.

Transcription:

AUTOMATIC FILTERS, INC. 67 S. LA CIENEGA BLVD. LOS ANGELES, CA 90034 30 839 88 800 336 94 FAX 30 839 6878 www.tekleen.com info@tekleen.com Tekleen GB6 & GB7 USERS MANUAL

GB6 & GB7 USERS MANUAL AUTOMATIC FILTERS, INC. Tekleen 67 S. LA CIENEGA BLVD. LOS ANGELES, CA 90034 30 839 88 800 336 94 FAX 30 839 6878 www.tekleen.com info@tekleen.com

Table of Contents SECTION I INTRODUCTION SECTION II INSTALLATION SECTION III SOLENOID SECTION IV FRONT PANEL CONTROLS & SETTINGS 4. Periodic Flush 4. Flush Time 4.3 Dwell Time 4.4 Power On/Off Switch 3 4.5 LCD Screen 3 4.6 Manual Start Button 3 4.7 Counter Reset Button 3 4.8 Alarm Reset 3 SECTION V BEHIND-THE-PANEL CONTROLS 5. AC/DC Voltage Switch 3 5. Circuit Board Fuse 4 SECTION VI TERMINAL STRIP CONNECTIONS 6. Transformer RWR 4 6. Solenoid C 4 6.3 Solenoid C 4 6.4 Master Valve CM 4 6.5 Alarm Output CA 5 6.6 PD Gauge PD 5 SECTION VII GENERAL NOTES 7. st Filter Actuation 5 7. Cautions 5 7.3 Common Sense 6 ILLUSTRATIONS 4 VAC or VDC 3-Way Solenoid Flushing Valve Connection 7 Controller Assembly 8 GB6 Battery Controller 9 Dual Chamber Valve: ABWxxP with GB6 0 Single Chamber Valve: MTF or Bell with GB6 SECTION VIII STARTING THE FILTER UP SECTION IX LIMITED WARRANTY & LIABILITY AGREEMENT 3

SECTION I INTRODUCTION features state of the art electronic backwash controllers in the GB series. GB6 and GB7 controllers are complete with a solenoid, a differential pressure sensor, a backwash counter, and an emergency alarm output. GB6 controllers backwash a single filter, while GB7 controllers control up to two filters simultaneously. The filters can be cleaned in 3 different modes: D/P, timer, and manual. They are available in 5/30 volts or are battery operated, 9V/V. The solenoid needs to be energized to open the flushing valve. SECTION II INSTALLATION The controllers come factory-prepared and are ready to use. The only steps necessary for installation are:. Mounting the controller. Connecting the tubings and wires of the PD gauge 3. Connecting the power supply (AC models) 4. Connecting the tubing and wires of the solenoid Mount the electric controller on a convenient wall or panel as close as possible to the filter to minimize the length of the pressure tubing. The controller can also be mounted directly on the filter itself with brackets. The pressure differential (PD) gauge/switch is to be installed on the bottom of the controller housing. The /8 tubing from the high pressure connection (red) on the center of the PD gauge goes to the high pressure side of the filter or manifold (inlet). The low pressure connection (blue) of the PD goes to the low pressure side of the filter or manifold (outlet). If desired, the gauge may be removed from the housing and mounted at a suitable location on the filter. For 0/30 Volt AC models, connect 0 VAC or 30 VAC, depending on the primary voltage in your area, to the transformer terminals. The 4 VAC leads are to be connected to the terminal strip.

SECTION III SOLENOID The GB6 and GB7 controllers come with a standard 4 volt AC 3-way solenoid, a VDC 3-way solenoid, or a 9V 3-way latching solenoid. The solenoid may use filter inlet water or instrument air (80 PSI) to open the flushing valve. The vent line should be drained. Install the solenoid not more than 3 ft. (m) away from the flushing valve. SECTION IV FRONT PANEL CONTROLS & SETTINGS 4. Periodic Flush A periodic flush will occur at the elapsed time set on the PERIODIC switch -- provided a normal PD flush or manual flush has not occurred during that time cycle. The PD periodic switch resets after each backwash. For example, if the switch is set for one hour and a PD flush occurs at 49 minutes, the periodic flush will not start a cycle minutes later. It will reset for hour later. Settings range from OFF to 4 hours. 4. Flush Time The amount of time that the filter backwashes should be set in a range of to 5 seconds. 4.3 Dwell Time The GB6 controller can control filter, while the GB7 models can control up to filters. The controller flushes each filter in sequence, starting with filter #. The dwell switch sets the time between successive filter flushes. It allows the st filter s rinse valves to close completely before the nd filter starts to flush, and so on. If only one filter is being controlled, this switch is not used. Factory setting is 0 seconds.

4.4 Power On/Off Switch The power on/off switch controls power to the controller and to all filter solenoids, alarms, and the master valve solenoid. Make sure that this switch is in the OFF position when the system is not in use or work is being performed on the electrical system. 4.5 LCD Screen The LCD screen displays the backwash counter. Also, when the output fuse has blown, the display indicated FUSE, and the PD and DWELL lights will flash alternately until the fuse is replaced. 4.6 Manual Start Button The manual start button activates back flushing of filter(s). 4.7 Counter Reset Button The counter reset button resets the back flush counter. 4.8 Alarm Reset An alarm output is activated whenever the controller initiates three or more consecutive backwashes by pressure differential signal in less than minutes. This alarm has both a visible light and an electrical output capable of activating a relay which can, in turn, operate a lamp or a bell. The alarm is resettable with the push button on the panel. SECTION V BEHIND-THE-PANEL CONTROLS 5. AC/DC Voltage Switch The AC/DC voltage switch is a large black toggle-type switch located near the bottom center on the backside of the control panel. It controls the voltage available to operate either 4 VAC or VDC solenoids. OUTSIDE is for the 4 VAC setting -- INSIDE is for VDC The factory preset is 4 VAC for 0/30 volts. 3

5. Circuit Board Fuse The fuse for the electronics is located between the front panel and circuit board. To replace, remove the front panel and replace with a amp, 5 X 0 mm fuse. DO NOT replace with higher amp fuse. SECTION VI TERMINAL STRIP CONNECTIONS 6. Transformer RWR These transformers are three terminals which connect to the power supply from the transformer -- two red leads and one white lead. The white lead should be connected in the middle terminal. This will be pre-installed by the manufacturer. R + R = 4VAC R + W = VAC R + W = VAC 6. Solenoid C These terminals control the solenoid valve. C stands for common, and indicates the solenoid #. This will be installed by the customer. Polarity is not important. 6.3 Solenoid C These are the terminals for solenoid #. 6.4 Master Valve CM The master valve output is marked with an M on the terminal block. This output is ON at the start of each backwash cycle and goes OFF when the controller returns to IDLE. The master valve output is only used when the filter system requires the optional pressure sustaining valve at the down stream of the filter. The filter needs to maintain inlet pressure greater than 35 PSI (.5 BAR) during rinsing. 4

6.5 Alarm Output CA These are terminals for the alarm output. The GB6/7 are available in two pre-set logic versions. The first does not disable the operation of the filter. This type is supplied. The second version does disable the operation of the filter by cutting out power to the solenoid. Reactivation of the controller is by alarm reset. 6.6 PD Gauge PD These are terminals for the PD gauge. Polarity is not important. They are installed by either the manufacturer or by the customer. Please make sure to install the DP gauge upside down. This will eliminate any future shorts if the high or low pressure tubing leaks. You may cover the contact points with silicone or any water sealant to prevent shorting. SECTION VII GENERAL NOTES 7. st Filter Actuation A built-in time delay of 30 seconds before the st filter starts to flush is activated as soon as a signal to flush (from the PD gauge) enters the computer. The purpose of this delay is to eliminate any water pressure spikes or false pressure surges from actuating a rinse. 7. Cautions. DO NOT exceed output ratings of controller (.5 amps).. Make sure output voltage switch is correctly set for 4 VAC or VDC solenoids. 3. When coming in with VDC, only use the first two terminals on the terminal block. The third terminal is not used for DC input. Also, the output switch (the toggle switch at the backside of the board) needs to be in the DC position. 4. DO NOT connect 30 VAC to a 5 VAC transformer. 5

7.3 Common Sense. You may install the controller far away from the filter. Providing that the solenoid and the DP switch are at the filter.. Any time the flush valve fails to open or close, please check for plugged dirty solenoid or dirty tubing. 3. A surge protector is needed to protect the controller from voltage spikes. Will result in burnt PC. If absent, surge protection can be purchased at any electrical supplies store. 4. It is always advisable to check and clean the minifilter which supplies water to the piston. 6

4 VAC OR VDC 3-WAY SOLENOID FLUSHING VALVE CONNECTION SINGLE CHAMBER VALVES SOLENOID To GB Controller VENT SOLENOID SUPPLY 3 To GB Controller PLASTIC VALVE VENT SUPPLY 3 FLUSH VALVE (90 deg. Globe Type) SOLENOID VENT 3 SUPPLY To GB Controller FLUSH VALVE (90 deg. Globe Type) DUAL CHAMBER VALVES To GB Controller SUPPLY SOLENOID SUPPLY SOLENOID To GB Controller VENT 3 VENT 3 FLUSH VALVE FLUSH VALVE 7

CONTROLLER ASSEMBLY PD DWELL ALARM OFF ON POWER MANUAL START/ ADVANCE COUNTER RESET ALARM RESET BACKWASH COUNTER TEKLEEN 67 S. La Cienega Blvd. Los Angeles, CA 90034 (30) 839-88 P OFF E 4 / 4 R 6 / I O D 8 I 6 C (Hour) 4 3 F L U S H (Sec) D W E L L (Sec) 30 5 0 90 75 60 0 4 6 8 8 0 6 4 5 0 50 5 40 30 0 + - R W R C M A PD Power Supply AC 0V/0V 50/60 HZ V DC 3 Way Solenoid Valve PSI Differential Pressure Gauge* * To prevent shorting, we recommend installing the D/P upside down. 8

GB6 BATTERY CONTROLLER PERIODIC FLUSH FLUSH TIME DWELL TIME D/P SWITCH POWER OFF ON DC PD S S LATCHING SOLENOID VALVE P C V P = Vent V = Water Supply C = To Valve (Red wire to +) (Black wire to -) 9

SOLENOID VALVE 3 VENT DOUB L E C HA MB E R V A L V E INLET BY-PASS VALVE HIGH PRESSURE (RED FITTING) LOW PRESSURE (BLUE FITTING) D/P SWITCH 0 6 5 8 8 75 60 50 OFF /4 P E R I O D I C F L U S H D W E L L GB6 ELECTRIC CONTROLLER PD DWELL ALARM (Hour) MANUAL START/ ADVANCE COUNTER RESET BACKWASH COUNTER ALARM RESET (Sec) POWER 90 TEKLEEN OFF ON (Sec) R W R C M A PD Power Supply AC 0V/0V (ASCO) OUTLET 4 6 30 40 6 4 4 0 30 3 4 0 / 6 0 5 8 5 0 FLUSH VALVE WATER SUPPLY 0

SINGLE CHAMBER VALVE HIGH PRESSURE (CENTER FITTING) LOW PRESSURE (SIDE FITTING) D/P SWITCH GB6 ELECTRIC CONTROLLER PD DWELL ALARM MANUAL START/ ADVANCE COUNTER RESET ALARM RESET BACKWASH COUNTER POWER OFF ON TEKLEEN R W R C M A P D H Power Supply AC 0V/0V L OUTLET SOLENOID VALVE (ASCO) FLUSH VALVE 3 VENT WATER SUPPLY H MTF OR BELL FILTER INLET

SECTION VIII STARTING THE FILTER UP If possible, please send us a few digital pictures of the filter and controller before the start-up. These photos will help prevent many unforeseen problems in the start-up. Please address pictures to info@tekleen.com. Isolate the filter. Shut the inlet and outlet valves. Turn the power on, push manual start, and listen for the clicking-buzzing solenoid. Open the inlet and keep the outlet closed. The bypass should be left open. Check for leaks, trigger manual start and see that the flushing valve opens and closes after the flushing timed out. Make sure that the inlet pressure is greater than 35 PSI (.5 bars) during rinsing. Open the filter outlet and close the bypass. Trigger another manual start and see that the inlet pressure is greater than 35 PSI during the rinsing of the filter. Congratulations, you have successfully started a Tekleen filter.

SECTION IX LIMITED WARRANTY & LIABILITY AGREEMENT Upon purchase of this controller equipment, the user agrees to the following terms, conditions, and limitations of warranty and liability coverage: (AFI) warrants its filter controllers to be free from original defects for one year from the date of original sale. The manufacturer will replace, free of charge, any part found defective under normal use and service within the guarantee period, provided the product is installed, used, and maintained in accordance with good engineering practice and all applicable instructions or limitations issued by AFI. Components supplied as replacement parts are warranted for 90 days from the date of shipment. The manufacturer assumes no liability for incidental or consequential damage sustained in the adoption or use of our engineering data, service, or products. Liability is limited to the repair or replacement of the products. No agent or representative of AFI has the authority to waive or add to this agreement. Altered products or use of products in a manner not intended shall void this warranty. All product claims under this warranty must be sent along with the defective product, freight prepaid, to AFI a the address listed below: AUTOMATIC FILTERS, INC. 67 South La Cienega Boulevard Los Angeles, CA 90034 Phone: (30) 839-88 Fax: (30) 839-6878 info@tekleen.com www.tekleen.com 3