VFC. Operating manual TROX air terminal units Type VFC volume flow controllers. General information 2. VFC series volume flow controllers

Similar documents
CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

Control units. Simple. Precise. Efficient. Control units LVC, TZ-/TA-Silenzio and VFL

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

Operating and Installation Manual Shut-off damper Type AK-Ex with control components T0* and P50

CAV controllers Type RN

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

Volume Flow Limiters Type VFL

Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

Type TVR FOR THE MOST DIVERSE APPLICATIONS REGARDING STANDARD VOLUME FLOW RATE RANGES

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

VAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1

VAV terminal units VARYCONTROL. Installation and commissioning manual. GB/en. LVC TVR TVJ TVT TZ-/TA-Silenzio TVZ TVA TVM TVRK TVLK

VAV terminal units. Type TVA. For extract air systems with demanding acoustic requi rements K

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

Parts and characteristics

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

Type RN FOR THE PRECISE CONTROL OF CONSTANT VOLUME FLOW RATES. Homepage > Products > Control units > Constant volume flow control CONSTANTFLOW

Type RN FOR THE PRECISE CONTROL OF CONSTANT VOLUME FLOW RATES. Homepage > Products > Control units > Constant volume flow control CONSTANTFLOW

Air terminal devices

5/9.2/EN/6. Volume Flow Limiter. Type VFL for insertion into air ducting. The art of handling air

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Ceiling swirl diffusers

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES

Type TVZ. VAV terminal units for the supply air control in buildings with variable air volume systems and demanding acoustic requirements

Shut-off dampers. Type AKK. For contaminated air PD AKK 1

Type AKK FOR CONTAMINATED AIR. Homepage > Products > Airflow Control - VAV and CAV > Shut-off and restriction > Shut-Off Devices > Type AKK

CONSTANTFLOW Volume Flow Controllers

RN-S: 80, 100, 125 RN: 80, 100, 125, 160, 200, 250, 315, 400 RN-FL: 100, 125, 160, 200, 250, 315, 400

Type AK FOR LOW-LEAKAGE SHUT-OFF. Homepage > Products > Control units > Shut-off and restriction > Shut-Off Devices > Type AK

Technical documentation

Type TVA FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS

Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES

Heat exchanger. Type WL. For the reheating of airflows in circular ducting PD WL 1. 03/2017 DE/en

Operating instructions ErgoPack 600 E

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

Minimum 18 in-lb Torque

User Manual Rittal PMC UPS 6kVA

Mechanical mixing box MBM

S10010 / S SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS 10/20 Nm (88/177 lb-in) FOR MODULATING AND FLOATING CONTROL SPECIFICATIONS GENERAL

BA 46 BA 46-ASME BA 47 BA 47-ASME BAE BAE ASME BAE BAE ASME

ALWAYS follow all Webasto installation and repair instructions and observe all warning instructions.

Type TVA FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Fan - Powered Terminal Unit Series Flow

7 Services Control and monitoring

Electrical data Nominal voltage AC 24 V Nominal voltage frequency

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU

Homepage > Products > Control units > VARYCONTROL > VAV TERMINAL UNITS > Type TVR. Type TVR

VAV TERMINAL BOXES TYPE: BA BT

Operating instructions Rotary actuators M135 M140 M150 M180. June 2012 / / EN

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

Fire damper. Type FKA-3.8. GB/en. Installation and operating manual. according to Declaration of Performance. DoP / FKA-3.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

S1024-2POS / S POS S2024-2POS / S POS

AXIAL FANS Axis / Tubo OPERATION MANUAL

Power consuption Motor (Motion) Power consuption Standby (end position) 0(2)...10 VDC / Ri > 50 kω 0(4)...20 ma / Rext.= 500 Ω

Ceiling swirl diffusers with perforated face plate

STR Circular VAV Terminal Units

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

ceiling swirl diffuser DQJ

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

Duct Nozzle Diffuser. L e

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Halton Rex 600 RE6 - Adaptable active chilled beam

Operating instructions Accu Jet

GL1200T Cut & Seal. (GL1200 Seal only)

Ceiling Swirl Diffuser DQJ

Globe Valves. Technical Databook Version 1.2. Belimo Asia Pacific

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

MANIFOLDS & WATER TEMPERATURE CONTROL

Features: Concealed installation. Compact design. Available in electric, LPHW or ambient.

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

Multileaf damper with actuator

Electromotoric actuators

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

INSTRUCTION MANUAL Oil level with pointer indicator

VORTICENT C E RANGE Centrifugal fans

RVP-R VAV REGULATORS. Intended use: VAV regulators are used for automatic airflow regulation in the ventilation and air conditioning systems.

kvs theor.: Theoretical kvs value for pressure drop calculation Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency


LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

ROM Series. Keeping the World Flowing. Installation Manual. Valve Actuators

Condensate Drain Valve AK 45. Original Installation Instructions English

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

Model 20 DPS.2005 Doc: J2-20DPS2005/01 Nov 2006

PNEUMATIC PUMP Series

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

230V DIESEL FUEL TRANSFER PUMP MODEL NO: DFT230

Ceiling swirl diffusers with perforated face plate

ATP-2040 Electric Damper Actuator/Transmitter

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

MS Application. Features. Proportional Valve Actuator General Instructions

Transcription:

Type volume flow controllers series volume flow controllers General information Correct use Safety notes Area of application Operating modes Product description Installation Commissioning and wiring 5 Constant volume flow rate operation 5 Variable volume flow rate operation, actuator with potentiometers 6 min - max switching wiring 7 Variable volume flow rate wiring 7 min - max switching operation, actuator with mechanical stops 8 min - max switching wiring 9 min - max switching setting 10 Retrofitting an actuator 11 Variable volume flow rate expansion set 11 min - max switching expansion set 1 Code 1) Function 1) Actuators for CAV controllers according to order code series volume flow controllers Actuator TROX part no. untill /018 from 5/018 Expansion set Code TROX part no. - Constant volume flow rate - - - - E01 V, min - max switching, potentiometer M66EP6 A000000858 E01 NR-VAV-E01 E0 0 VAC, min- max switching, potentiometer M66EP8 A000000859 E0 NR-VAV-E0 E0 V AC/DC, variable volume flow, potentiometer, control signal 0 to 10 V DC M66EP7 A000000860 E0 NR-VAV-E0 M01 V, min - max switching, mechanical stops M66EP M66EP M01 NR-VAV-M01 M0 0 VAC, min - max switching, mechanical stops M66EP5 M66EP M0 NR-VAV-M0 Subject to change All rights reserved TROX GmbH (10/018) Publication no. M//EN/ 1

Type volume flow controllers General information Correct use The volume flow controllers are suitable for use in ventilation and air conditioning systems. Particular conditions can restrict the functioning capacity and must be taken into account during the design stage: Use of series volume flow controller in aircraft is not permitted. In systems with aggressive air, only air terminal units made of plastic should be used, subject to extensive tests for suitability. Galvanised sheet steel units must not be installed in contaminated environments (e.g. acetic acid). The controller and actuator do not contain any parts that can be exchanged or repaired by the user. The actuator contains electronic components therefore must be separated from domestic waste. When disposed of, local up to date regulations must be complied with. The mechanical components of series volume flow controllers are maintenance-free. Sticky constituents of the air, in particular in association with fluff, can lead to impairment or failure of the regulation function. Safety notes Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. Area of application TROX series volume flow controllers are mechanical system-powered controllers for controlling the airflow in constant and variable air volume systems. variants of the volume flow controllers are available: Constant volume flow rate min - max switching Actuator with potentiometers (type E01, E0) Actuator with mechanical stops (type M01, M0) Variable volume flow rate, Actuator with potentiometers (type E0) The set flow rate must always be set by the customer on site. The setting is made without adjustment devices. Each volume flow controller has a sticker with a characteristic for determining the volume flow rate. One or two settings are read off and transferred to the rotary knob or actuator (potentiometer or mechanical stops). Operating modes Constant volume flow rate The volume flow controller keeps the set flow rate constant independently of the duct pressure. Variable volume flow rate The volume flow controller keeps a variable set flow rate constant independently of the duct pressure. For this purpose, the volume flow controller receives a control variable from a room temperature controller or air quality controller, a set point adjuster or a DDC outstation. The control variable is a 0 to 10 V DC voltage signal. min - max switching The volume flow controller works with two setpoint values that are switched over using switches or relays provided by the customer. Safety transformers must be used. Installation should only be carried out by specialists. The normal rules of site working, in particular the health and safety regulations must be complied with. For installation, wiring, and commissioning observe the recognised technical regulations, especially safety and accident prevention regulations. Due to the danger of injury on edges and burrs, transport and installation may only be performed while wearing gloves. Install the units proficiently with suspension points and secure with locknuts. Only load the suspension points with the units' own weight. Adjacent components and connecting ducts must be supported separately. Only use units with ATEX approval for rooms containing a potentially explosive atmosphere.

Type volume flow controllers Product description Constant volume flow rate For constant air flow rate Volume flow rate is set on site using the rotary knob Factory setting 5 1 Variable volume flow rate, actuator with potentiometers 1 E01... E0 min - max switching, actuator with mechanical stops 5 Actuator E01, E0, E0 For variable airflow rate or min - max switching Volume flow rate is set on potentiometers Shut-off down to leakage airflow is possible (setting 0) Height of the actuator 85 mm Factory settings: min = max = 8 Actuator M01, M0 For min - max switching Volume flow rate is set using mechanical stops Shut-off down to leakage airflow is possible (setting 0) Flat design, height of the actuator 5 mm 1 M01... M0 1 Adjustment scale 5 Volume flow rate characteristic Rotary knob Actuator, volume flow rate is set on potentiometers Actuator, volume flow rate is set with mechanical stops For technical and acoustic data on series volume flow controllers, refer to the control units catalogue.

Type volume flow controllers Installation Installation behind a bend min. 1 D Combination with volume flow rate measuring unit VMR Installation in a branch 1.5 D Manifold Connection with ducting D Installation location and type of connection Select the installation location so the scale and characteristic of the controller remain accessible. With reference to the characteristic, set the pointer to the required volume flow rate. Horizontal or vertical controller installation. Note the airflow direction according to the arrow on the characteristic. Note for installation in front of and behind elbows, flaps or other obstacles with aerodynamic and acoustic effects. Horizontal or vertical installation; in combination with volume flow rate measuring unit (VMR), arrange the sensor tubes at 5 offset from the controller axis. Installation behind a bend: Maintain a curvature radius of at least 1D unless there is an additional straight inflow length. Direct connection to a main duct/manifold: Maintain at least 1.5 D straight inflow length Shorter inflow lengths result in tighter tolerances. Direct connection to a main duct is permitted without perforated sheet metal in extract air operation. Free intake not permitted, inflow length 1.5 D required. Inflow nozzles are recommended in order to reduce the pressure losses. Connection with ducting The connection diameters are appropriate for tubes according to EN 1506 or EN 1180. No drilling work is allowed to be performed on the controller! Before connecting the controllers, check the ducting for contamination. Use standard TROX lip seals for connecting to the ducting. Suspension Connection elements, e.g. tube clamp with rubber seal

Type volume flow controllers Commissioning and wiring Constant volume flow rate operation Setting the set flow rate Each carries a characteristic to determine the setting values on site (see example, nominal size 160). min settings below results in an unregulated airflow dependent on the duct pressure that is not less than min-unit. Characteristic for determining the volume flow rate 10 160 l/s 18 0 60 80 100 10 10 160 180 185 m³/h 65 100 150 00 50 00 50 00 50 500 550 600 650 666 cfm 9 8 7 6 5 8 50 100 150 00 50 00 50 9 Constant volume flow control, volume flow rate setting with rotary knob Rotary knob Set the set flow rate as follows: Determine the setting value for the set flow rate from the characteristic or the table below. Unscrew the locking screw. Move the pointer of the rotary knob to the setting value. Tighten the locking screw. Locking screw Volume flow rate setting values l/s m /h Value to be set Value to be set Nominal size 5 6 7 8 9 10 5 6 7 8 9 10 80 6 7 10 1 19 5 0 6 5 9 68 91 119 150 100 6 10 15 0 0 50 65 6 5 79 108 1 180 15 11 15 0 60 78 100 0 5 79 108 160 15 80 60 160 18 1 5 60 8 110 16 18 65 110 16 16 00 96 55 660 00 5 0 60 85 10 155 05 50 90 1 16 06 558 78 900 50 7 6 100 15 18 0 10 70 1 0 60 86 660 86 1116 1 5

Type volume flow controllers Actuator E01... E0 Variable volume flow rate operation, actuator with potentiometers Indicator light max potentiometer Service button min potentiometer Characteristic for determining the volume flow rate 10 9 8 7 6 5 160 l/s 18 0 60 80 100 10 10 160 180 185 m³/h 65 100 150 00 50 00 50 00 50 500 550 600 650 666 Setting the set flow rate Each carries a characteristic to determine the setting values on site (see example, nominal size 160). min values below results in an unregulated airflow dependent on the duct pressure that is not less than min-unit. Set the set flow rate as follows: Determine the setting value for the set flow rate from the characteristic or the table on page 5. Set the values on the min - and max potentiometers. Factory setting: min = max = 8 Shut-off down to leakage airflow is possible, value to be set 0 Functional test A functional test can be performed very easily using the service button and the indicator light. Press service button for at least 1 second Actuator turns toward min Actuator turns toward max Actuator returns to control mode Indicator light provides functional information Permanently on : Position set Flashing once a second : Actuator operating Flashing twice a second : Actuator is jammed and stationary Off : No supply voltage cfm 8 50 100 150 00 50 00 50 9 Characteristics of the control signal Value to be set Value to be set 10 8 max 6 min 0 0 5 V 10 VDC Control signal w Characteristic of the actual value signal 10 6 0 0 6 V Output signal U 10 VDC E0 E0 Actuator E0 The relationships between the setting value and output signal U, or control signal w, are shown in the two characteristics on the left. The output signal does not correspond to the currently measured volume flow rate, but reflects the setpoint value. Example: Factory set values: min = min = 8 Required value: 6 --> Required control signal: 5 V Available output signal: 6 V corresponding to set value 6 6

min - max switching wiring 1-wire control min / max V / 0 VAC ~ - + N L~ S1 1 -wire control min / max E01, E0 Operating manual Type volume flow controllers Actuator E01... E0 Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. Actuator E01, E0 Electrical connection data: E01: V AC ±0% 50/60 Hz; VA V DC ±0%,5 W E0: 0 V AC 50/60 Hz VA Switches provided by the customer (volt-free contacts) can be used for making the switching procedures shown below: 1-wire control (illustration above) Switch S1 open : min Switch S1 closed : max V / 0 VAC ~ - + N L ~ S 0 -wire control (-point) (illustration in middle) Switch S at 0: Drive stopped Switch S at : min Switch S at : max 1 E01, E0 Variable volume flow rate wiring Continuous control input signal V Room temperature controller y - + ~ ~ 1 Actual value output (value to be set) E0 Actuator E0 Electrical connection data: Supply: V AC ±0% 50/60 Hz VA V DC ±0%,5 W Control signal: 0-10 V DC Ra > 100 kohm Actual value output: 0-10 V DC Room temperature control A dedicated room temperature controller or a DDC outstation with 0-10 V DC output is connected with at least wires (terminals 1 and ) as shown in the circuit diagram. If the controllers are on the same supply voltage ( V) make sure that terminal 1 of the is identical to the ground of the control signal. Note: Override control max with V DC at terminal. 7

Type volume flow controllers Actuator M01... M0 min - max switching operation, actuator with mechanical stops Setting the set flow rate Each carries a characteristic to determine the setting values on site (see example, nominal size 160). min settings below results in an unregulated airflow dependent on the duct pressure that is not less than min-unit. Characteristic for determining the volume flow rate 10 9 8 160 7 6 5 l/s 18 0 60 80 100 10 10 160 180 185 Set the set flow rate as follows: Determine the setting value for the set flow rate from the characteristic or the table on page 5. Activate gearbox disengagement with magnet. The magnet is integrated in the removable position indicator Make the corresponding settings on the mechanical stops. Deactivate gearbox disengagement again and reconnect the position indicator, see also page 10. m³/h 65 100 150 00 50 00 50 00 50 500 550 600 650 666 cfm 8 50 100 150 00 50 00 50 9 Variable volume flow control, min and max setting with mechanical stops Magnetic gearbox disengagement U.. Mechanical stop for min Position indicator with magnet Mechanical stop for max 8

Type volume flow controllers Actuator M01... M0 min - max switching wiring 1-wire control min / max V / 0 VAC ~ - + N L~ S1 1 M01, M0 Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. Only skilled qualified electricians are allowed to work on the electrical system. Switch off the power supply before working on any electrical equipment. Electrical connection data: M01: V AC ±0% 50/60 Hz 1 VA V DC ±0% 0,5 W M0: 0 V AC 50/60 Hz VA Switches provided by the customer (volt-free contacts) can be used for making the switching procedures shown below: 1-wire control (illustration above) Switch S1 open : max Switch S1 closed : min -wire control (-point) min / max V / 0 VAC ~ - + N L ~ S 0 -wire control (-point) (illustration in middle) Switch S at 0: Drive stopped Switch S at : max Switch S at : min 1 M01, M0 9

Type volume flow controllers Actuator M01... M0 min - max switching setting 1 Magnet magnetic gear release Setting the mechanical stops Remove the position indicator, there is a magnet on the reverse Place the magnet on the point indicated with magnetic gear release. The gearbox is now disengaged and the actuator can be moved. U.. Remove the mechanical limiters Set min or max on the rotary knob; reattach the mechanical limiters in the corresponding positions. Remove the position indicator with magnet and put back on the axial holder. 10

Type volume flow controllers Actuator E01... E0 Retrofitting an actuator Variable volume flow rate expansion set Subsequent installation of actuators The version with a rotary knob can be subsequently equipped with an actuator. For this purpose, it is first necessary to remove the locking screw and move the rotary knob to position 5. The actuator is simply pushed on, and it engages in the mounting bracket. Order code for expansion sets, see page 1 Mounting bracket Rotary knob Actuator Mounting the actuator Fixing screw Perform the following steps to mount the actuator: Unscrew the locking screw and remove it Move the rotary knob to setting 5 Push on the actuator until the fixing lugs engage See page 6 for setting the set flow rates Setting 5 11

Type volume flow controllers Actuator M01... M0 min - max switching expansion set Rotary knob, standard construction Mounting bracket Actuator Subsequent installation of actuators The version with a rotary knob can be subsequently equipped with an actuator. For this purpose, it is first necessary to remove the locking screw and move the rotary knob to position 5. Order code for expansion sets, see page 1 Coupling Anti-twist facility Mounting the actuator Locking screw Rotary knob 1 Perform the following steps to mount the actuator: Unscrew the locking screw and remove it Move the rotary knob to position 5 Engage the coupling Coupling Engage the anti-twist facility on the mounting bracket Attach the actuator, it engages in the anti-twist facility See page 10 for setting the set flow rates 1