QUICK FLOW CDT1 Series Digital Flowmeter for Air Conditioning Application OUTLINE CDT1 is a new series of flowmeter which combines a multidigital indicator with a pitot tube. CDT1 detects the differential pressure exerted by flow velocity in the pitot tube inserted in the pipe and outputs flow rate with digital indication. Applicable sizes range from 2mm to 4mm dia. The principal applications are for hot and cooling water lines for air conditioning in apartment and office buildings and other facilities. FEATURES Easy installation Installation simply by making a 5mm dia. hole and welding 2mm (/4") socket at measuring point of existing pipes. This is most convenient for renewal use when additional flow sensor is required on the line. Low pressure drop Wide measuring range Measuring range selectable depending on application Applicable for both horizontal and vertical pipes. Various indicator functions selectable from the following: Battery type, Current Output type (2wire 4 to 2mA), Alarm Output type, and LonWorks type Indicator parts are interchangeable. Easy to see because of large LCD display Compact size and lightweight Quick delivery STANDARD SPECIFICATION Measuring Fluid : Water, Cold water, Hot water Max. Pressure : 2MPa Max. Allowable Differential Pressure : 2kPa (Bias pressure) Temperature and Relative Humidity Fluid temperature : 1 to 7 o C Ambient Temp. : 1 to o C < 85%RH Storage Temp. : 2 to 6 o C < 85%RH (Without icing, without condensation) Process pipe size : 2mm(/4") to 4mm(18") Adaptation pipe : Carbon steel pipe for piping (JIS G 452) [1MPa class] Carbon steel pipe for pressure piping (JIS G 454 Sch4) [2MPa class] Note : If pipe other than above is required, special calibration may be necessary. Consult factory for details. Accuracy : 5% F.S. [std.] Accuracy is guaranteed for fluid temperature range 7 to 6 o C Measuring range : Flow rate from 1 to 1% of full scale Protection class : IP65 (JIS C 92) (Except for the air introduction port at the bottom of housing.) Mass : Approx. 2kg Indicator type function (All types with indicator) Type Battery type Current output type Alarm output type LonWorks Type Function Battery drive, Indication only 42mA DC (2wire) 2 points 42mA DC Applicable to LON communication network Indication function Flow rate indication 1/2 digits LCD (Height 18mm) : to 1999 (FFF appears in case of out of range) 11 segment bar graph Totalizer indication 71/2 digits LCD (Height 5mm): to 19999999 Indication interval : 1s (Sampling.5 sec) Filter :,2,4,8,16,2s (Moving average) LCD back light : Continue 1s after operation (Except current output type) Material of Pitot tube parts : Refer to [OUTLINE DIMENSION] and [MATERIAL] Material of wetted parts of indicator Diaphragm : 16L SS Body : 16SS : Fluorine rubber (JIS Class4D) Drain hole sealing : Alumina ceramics Material of indicator body: Aluminium alloy Painting : Melamine resin painting (Indicator housing) Painting color Front : Wine red (Munsell 1RP/8) Rear : Light gray (Munsell N7.5) Process connection : R/4" (M) Installation posture : Front vertical installation TGF9762E May. 2K
CDT1 QUICK FLOW for Air Conditioning Application Digital Flowmeter Standard full scale range [SGP,STPG(4~4mm)pipe] Process pipe size Full scale range [L/min] Inside dia. (mm) mm inch Code 5 1 2 1MPa 2MPa 2 /4 7 1 (26) Refer to 25 1 7 1 1 (4) following 2 11/4 12 16 2 (4) table 4 11/2 1 2 41.6 41.2 2 2 4 52.9 52.7 65 21/2 4 7 67.9 65.9 8 7 1 8.7 78.1 1 4 9 1 18 15. 12. 125 5 1 2 28 1.8 126.6 1 6 2 4 155.2 151. 2 8 7 24.7 199.9 2 1 7 1 254.2 248.8 12 8 1 16 4.7 297.9 14 1 1 2 9.8.4 4 16 1 18 2 9.6 81. 4 18 16 2 441.4 428.6 Standard full scale range [2MPa version = 2~2mm] Process pipe size Full scale range [L/min] Inside dia. mm inch Code 1 2 (mm) 2 /4 7 1 21.4 25 1 7 1 1 27.2 2 11/4 12 16 2 5.5 Standard full scale range [PVC lined pipe] Process pipe size Full scale range [L/min] Inside dia. mm inch Code (mm) 5 1 2 2 11/4 75 1 1 29.5 4 11/2 1 1 2 4.7 2 17 2 46.2 65 21/2 4 6 59.7 8 4 6 9 7.9 1 4 8 1 16 95.2 125 5 12 18 2 119.7 1 6 17 2 142 Note 1) The inside diameter of pipe size 2 to 2mm in 1MPa is based on threeway socket (JIS B 21). (It is possible to attach threeway socket as option.) 2) The inside diameter of pipe size 2 to 2mm in 2MPa is based on threeway socket (Sch.4). (Supplied by customer.) ) 4mm or more, the inside diameter of in 1MPa specification is based on Carbon steel tube for ordinary piping SGP (JIS G452), and the inside diameter of in 2MPa specification is based on Carbon steel pipes for pressure piping STPG (JIS G 454 Sch4). 4) Scale range of PVC lining is based on the inside diameter of the upper table. In the case of inside diameter other than the upper table, special calibration is required. Consult after checking L and D size of the figure in page 6. 2) Current output type Power supply :24V DC 1% Output :42mA DC (2wire) Max. load :6Ω Output accuracy :.5% F.S. at 2 o C Response :Less than 2 s (At filter setting ) ) Alarm output type Power Supply :24V DC 1% Power Consumption :Less than 25mA Alarm Output :Open Collector x 2 (Independent) Load :Less than V DC / 8mA Response :Less than 2 s (At Filter setting ) Alarm setting :Selectable (high / Low), Reset Span: Adjustable / Min. 1digit Output : 42mA DC Max. load :6Ω Output Accuracy :.5%F.S.at 2 o C 4) LonWorks type Applicable to Lon communication network. Communication with network devices by FTT1A Transceiver. Power Supply :24V AC 1% /, 6Hz Power Consumption :Less than 8mA Transmission LON Value :Flowrate and differential pressure (Convert the Indication value to LON value) Response :Less than 2 s (At Filter setting ) The communication of each device is in accordance with definite procedure related to its LON value. FTT1A can be connected by free topology and multi drop connection. Refer to [Function Profile] for detailed information Cable entry Type Cable entry L Cable entry R Battery type Current output type Alarm output type LonWorks type Acceptable cable outside diameter 8mm OPTION (Factory set) Totalizing indication Selection of totalizer function OPTION (Others) Refer to L CODE CODE : /TLZ : Yes : No Specification and function of each type 1) Battery type Battery Battery life :Alkali battery (LR6) x 2 pcs. :Approx. 2 years at 2 o C Auto power off mode selectable Low Battery monitor as standard 2 TOKYO KEISO CO., LTD. TGF9762E
l CDT1 QUICK FLOW for Air Conditioning Digital Flowmeter WIRING DIAGRAM [Current output type] [Alarm output type] Alarm output (1)/(2) : Open collector Load: Less than V DC/8mA (each) [LonWorks Type] 42mA DC24V Receiver ANA OUT DC24V Alarm output (1) Alarm output (2) 42mA Receiver Black Red White blue ~ AC24V NETB NETA Host device MATERIAL and OUTLINE DIMENSION CDT12 9 (.5) (184) (84) (1) l 1 2 4 5 6 72 1 ADJ. Ao f f O U T 1 O U T 2 LRZ.kPa UNI T m / h cm / h o C (95) 16 1.5 (9) (9) R/4 (Refer to approval drawing for the dimension I.) (21) Drain hole Cable entry L 21 CDT14 9 24 Cable entry R 5 (91.5) (84) 1 (14) Socket (CFSW) 9 /4 4.5 [OPTION] 8 SGP threeway socket (JIS B 21/CFTW) Rc/4 A A 1 O U T 1 O U T 2 UNI T m / h Air vent screw B 2d cm / h Aof f LRZ.kPa o C 72 Dimension of threeway socket Size d A B 2mm Rc/4 25mm Rc1 5 6 2mm Rc11/4 6 41 (199) 2 No. Part Description Material (41) (47) (127) (66.5) 4 Indicator body Aluminum alloy Isolation valve SCS 14 Valve Shaft SUS 16 NBR 5 Vent valve SUS 16 Cap nut SCS1 R/4 6 Fittings BC6 Pitot tube SUS 16 Socket SS 4*1 8 Threeway socket FCMB*1,2 *1 It is possible to attach standard material for socket (SS4 or FCMB) if requested, but material besides these materials shall be provided by customer when needed. *1,2 For the 2 MPa rating, the parts made of proper material such as S25C be selected and provided by customers considering pipe sch4. TGF9762E TOKYO KEISO CO., LTD.
1 o 1 1 o C cm/h o CDT1 QUICK FLOW for Air Conditioning Application Digital Flowmeter CONSTURUCTION CDT12 Vent valve (4pcs) Equalizing pressure valve with (P4) Bolt, Washer M5 x 2(4pcs) (S4) Vent plug (4pcs) (P8) (P8) Cap nut (S1.5) Pitot tube SCS14 Isolation valve Socket Fittings Screwing Welding Blind plug Piping Indicator Aoff LRZ kpa UNIT m/h cm/h Hexagon socket head cap screws M4 x 14(4pcs) C CDT14 Hexagon socket head cap screws M4 x 14(4pcs) Indicator Aoff LRZ kpa UNIT m/h cm/h [Option] Protection cover (For indicator protection) CODE : /HGC CAUTIONS ON INSTALLATION Avoid direct rays and equip with a protection cover or install in the place which a direct rainstorm does not splash. (If protection cover is used, it may be difficult to read the display.) Protection cover Equalizing pressure valve with (P4) (S4) Isolation valve Screwing Fittings Socket Blind plug Vent valve (2pcs) Vent plug (2pcs) Bolt, Washer M5 x 2(4pcs) (P8) (P8) Pitot tube (S1.5) Cap nut Welding Aoff UNIT m/h C Piping 4 TOKYO KEISO CO., LTD. TGF9762E
CDT1 QUICK FLOW for Air Conditioning Digital Flowmeter L CODE CDT1 L A / Description Installation 2 Horizontal type type 4 Perpendicular type 1 1MPa class Pressure rating 2 2MPa class 2 2mm 25 25mm 2 2mm 4 4mm mm 65 65mm 8 8mm 1 1mm Main pipe size 125 125mm 1 1mm 2 2mm 2 2mm mm mm 4 4mm 4 4mm 5 1 Full scale range Flow rate range 2 4 Battery type 5 Current output type 6 Alarm output type Indicator type 9 LonWorks type Application L For liquid Version A Version code /TLZ Totalization indicator With protection cover /HGC at display part Option* Threeway socket for /CFT piping (CFTW) /CFS Welding sockt (CFSW) /PL PVC lined pipe specification Blank Not provided Additional function /Z Provided Note Standard type Vertical type Carbon steel pipe for piping (JIS G 452) Carbon steel pipe for pressure piping (JIS G 454 Sch4) Nominal diameter for installation pipe Select for the code of Standard full scale range Battery drive 42mA DC (2wire) 2 points 42mA DC LonWorks available Attachment is possible in case of the quality of the material FCMB and 1MPa specification Available only for SS4 Inform us L and D dimension of figure in page 6. Not necessary if abovementioned code is available. Consult about the details of the pipe material or Pitottube length. *Note) Insert / between each code when the plural codes are selected. Code example 1: [In case optional code is not selected] Horizontal installation, Connection size mm, 1MPa class, Full scale flow rate code[1], Battery drive type Model code: CDT12114LA Code example 2: [In case all of the possible optional codes are selected] Vertical installation, Connection size 1mm, 1MPa class, Full scale flow rate code[5], Current output type, Totalization indicator, indication, With protection cover at display part, With welding socket Model code: CDT141155LA/TLZ/HGC/CFS Code example : [In case piping type specification] Horizontal installation, Connection size 8mm, Pipe material SUS4TPD, 1MPa class, Full scale flow rate code[2], Current output type, Totalization indicator, With welding socket Model code: CDT121825LA/TLZ/CFS/Z When the piping type is specified as seen in the above Code example, it will be additional function. Moreover, in case socket and threeway socket are prepared by customer, Pitot tube length may be changed by installation dimension. This will be an additional function. Accordingly the last letter of model code will be /Z in case of such special specification as not mentioned in the above mode code. TGF9762E TOKYO KEISO CO., LTD. 5
CDT1 QUICK FLOW for Air Conditioning Application Digtal Flowmeter INSTALLATION 1) Keep the upstream and downstream straight runs as required. 2) To install the flowmeters, Drill a hole of 5mm diameter into the pipe having more than or equal to 4mm diameter. Use the threeway socket for the pipe having less than or equal to 2 mm diameter. ) Select and drill the hole at right place so that the final fixed posture of indicator should be horizontal. 4) Weld the socket to the drilled hole. The centerline of the socket must be in line with the one of the pipe. 5) Screw the CDT1 into the welded socket to complete the installation. SUGGESTIONS The model CDT 12(4) 1 flowmeter is calibrated based on the inside diameter of JIS G452 SGP. For the model CDT 12(4) 2, calibrated JIS G454 Sch.4. Consult TOKYO KEISO if pipes are different from above. Specific calibration is required. Straight length for upstream and downstream is required for accurate measurement as shown in the following table, Size Upstream Downstream 2mm 1D 5D 4mm 5D D Note) D : Inside diameter of main pipe. Piping CDT12 CDT14 Threeway socket (2 to 2mm) Threeway socket Rc/4 Rc/4 Threeway socket Run the fluid fully in the pipe. Otherwise it could not be measured. Vent the air before measurement. See CDT1 Instruction Manual for further details. LINING AND OTHER PIPING In case of PVC lining piping, prepare bushing (25mm x 2mm) for the main pipe in more than 2mm and for branch tube in 25mm. Available for other piping. Inform of the types of piping and dimension of L and D of the following figure. Refer to the table for full scale flow rate. Straight piping ( 4mm) /4 /4 9 ØD 2mm L Bushing (R1 x Rc/4) ØD L Rc/4 Ø5 Ø5 Lining piping (PVC) Other piping 9 ORDERING INFORMATION Indicator 1. Model code 2. Quantity * Specification is subject to change without notice. Head Office : Shiba Toho Building, 1 7 24 Shibakoen, Minatoku, Tokyo 15 8558 Tel : 81 41 1625 (KEY) ; Fax : 81 4 4922 email : overseas.sales@tokyokeiso.co.jp ; URL : http://www.tokyokeiso.co.jp 6 TGF9762E