Replacement Parts List No. 700023300 Revision C 0/206 Daikin McQuay Air- Cooled Condenser ACH, ACX, ACL 04-225 Vintage A To find your Daikin Applied parts distributor, call -800-377-2787 or visit www.daikinapplied.com
Contents Parts List Revision History... 3 Nomenclature... 4 Unit Layout Diagrams... 5 Electrical Legend... 5 Unit Components... 6 Air- Cooled Condenser, ACH,ACX,ACL 04-225A Rev. C 0/6 RPL 7000233 / Page 2
Parts List Revision History Revision Date Description NEW 0/ New. A 08/4 Page 5: Added Speedtrol Control for R40. B 06/5 Cover: Updated to Daikin Legacy format. Page 4: Corrected S/N information & misc. coding. Page 5: Moved component table to new pg. 6. Added unit layout dwg. Page 6: (NEW): Added pg. for component table from pg. 5. Updated p/ns. Repaginated the form & updated the TOC. C 0/206 Page 6: Added Fan Motor Contactor 40A/5V. Daikin Applied, 3600 Industrial Park Blvd., P.O. Box 55, Minneapolis, MN 55440 (763) 553-5330 Air- Cooled Condenser, ACH,ACX,ACL 04-225A Rev. C 0/6 RPL 7000233 / Page 3
Nomenclature Unit Serial Number T 07 H 04596 Always T Serial Number Month of manufacture A= Jan B= Feb C= Mar D= Apr E= May F= Jun G= Jul H= Aug J= Sep K= Oct L= Nov M= Dec Year of manufacture 07= 2007 08= 2008 09= 2009, Etc. Model Number ACH 040A S N R4 4 N N N S N N N NNN 27 N N N Y MH CI NNNNNNDPNNNNNNNNNNNNS00 Code 0 02 03 04 05 06 07 08 09 0 2 3 4,5 6 7 8 9 20 2 22 23-32 Code 0= Unit Type ACH= Air-Cooled Condenser: 40 RPM,.5HP ACL= Air-Cooled Condenser: 830 RPM,.5HP ACX= Air-Cooled Condenser: 830 RPM,.0HP Code 02= Size (in tons) & Vintage ex. 040A= 40 Tons, A Vintage Code 03= Fan Rows/Circuits S= Single D= Dual Code 04= Always N Code 05= Refrigerant RS= R22 or R407c RA= R34a R4= R40A Code 06= Coil Density 4= 4 FPI 08= 8 FPI 0= 0 FPI 2= 2 FPI Code 07= Header Manifold S= With Manifold (dual circuit units only) Code 08= Perimeter Base Frame V= With Base Frame Code 09= Legs N= Fixed 20 Legs at Std. Locations E= Variable Extension Legs (30, 36 or 42 ) at Std. Locations P= Variable Extension 30, 36 or 42 At All Fan Cells Code 0= Cabinet Material S= Galvanized A= Aluminum P= Prepainted Galvanized Code = Access Door Y= With Door Code 2= Hinged Fan Deck Y= With Hinged Fan Deck Code 3= Coil Protection B= Blackfin C= Copper E= Electro-Fin Codes 4 & 5= Always NNN Code 6= Voltage 27= 460/60/3 42= 208/230/60/3 37= 575/60/3 Code 7= Electrical Box Size N= Standard Y= Oversized Codes 8= Disconnect Switch N= Non Fused D= Fused Code 9= Wiring N= Standard S= Sealtite Code 20= Control Circuit Transformer S= 20 VAC Code 2= Fan Cycle Control N MH= Mechanical Head VM= Variable Speed (Head Pressure 0F Min.) EH= Electric Temp. Control ST= Speedtrol Only (No Staging) Code 22= Power Connection NN= Standard CI= Contactors- Individual Motor BI= Circuit Breaker- Individual Motor Codes 23-25= Always NNNNNN Code 26= Warranty DPN= Domestic year, parts only CPN= Canadian year, parts only TPN= Export year, parts only Codes 27-32= Always NNNNNNNNNNNS00 Air- Cooled Condenser, ACH,ACX,ACL 04-225A Rev. C 0/6 RPL 7000233 / Page 4
Electrical Legend Schematic Sym. Description Location C- C4 Fan Contactor Electrical Box M- M4 Fan Motor Fan Deck FCP- FCP4 Fan Pressure Switch Electrical Box F- F4 Fuses Electrical Box Unit Layout Diagrams Air- Cooled Condenser, ACH,ACX,ACL 04-225A Rev. C 0/6 RPL 7000233 / Page 5
Unit Components Model Description Part Number Components for 208/230/460V units Code 6= 42, 27 4 Motor, Condenser Fan.5 HP 40 RPM, 208/230/460/3 253640.5 HP 830 RPM, 208/230/460/3 253660.5 HP 830 RPM, 208/230/460/3 253630.75 HP Variable Speed Mtr., 208/230/460/60/ Code 2= ST, VM 25370 Fan Blade, 40 RPM Motor 2290040 Fan Blade, 830 RPM Motor 2292950 Fan Blade, Variable Speed Motor 2292625 Fan Grille 230570 3 3 3 Rain Shield- Fan Motor 30004254 3 3 3 ACH ACL ACX Motor Rail 54 300040698 varies varies varies Motor Rail- Variable Speed Motor 54 400070 Motor Rail 55 300040699 varies varies varies Contactor- Fan Motor (C- C4) 25A/5V (std) 30004366 /fan /fan /fan Contactor- Fan Motor (C- C4) 25A/24V 2259996 /fan /fan /fan Contactor- Fan Motor (C- C4) 30A/24V 2254304 /fan /fan /fan Contactor- Fan Motor (C- C4) 30A/208-240V 2252330 /fan /fan /fan Contactor- Fan Motor (C- C4) 40A/5V 2254303 /fan /fan /fan Fuse- Fan Motor Contactor (F- F4) 5A/600V 046742222 2/fan 2/fan 2/fan Fuse- Control Transformer (C20= S) 30A/600V 046742225 3 3 3 Fan Cycling Pressure (FCP) Code 2= MH, VM 2894574 /fan /fan /fan Speedtrol Control, R22 Code 2= ST, VM 2894592 Speedtrol Control, R40 Code 2= ST, VM 2894590 Electric Temp Control Code 2= EH 2890640 Transformer- 24V (Speedtrol Control) Code 2= ST, VM 208/230V Units Code 6= 42 2254498 460V Units Code 6= 27 2254499 Transformer- 5V Control Circuit Code 20= S 03825399 Quantities: 020S,025S,030S= ; 040S,050S= 2; 055S,060S,040D,050D,060D= 3; 070S,080S= 4; 00S,080D,00D= 5; 0S= 6; 0D,30D= 7; 40D,60D= 9; 200D= ; 225D= 3. 2 Quantities: All single row units (ex. 04S)= ; All double row units (ex. 00D)= 2. 3 Quantities: 04S,06S= ; 020S,025S,030S= 2; 040S,050S= 3; 055S,060S,040D,050D,060D= 4; 070S,080S= 5; 00S,080D,00D= 6; 0S= 7; 0D,30D= 8; 40D,60D= 0; 200D= 3; 225D= 4. 4 For 575V units (Code 6= 37) Contact Daikin Applied with model and serial number information so that the correct part(s) can be identified. Air- Cooled Condenser, ACH,ACX,ACL 04-225A Rev. C 0/6 RPL 7000233 / Page 6