DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

Similar documents
DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DW-03, -04 & BTG-D-0109

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE HEAT PUMP UNITS. BP 036 thru 072 HIGH EFFICIENCY YTG-D-0109

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DY 036, 048 & YTG-E-0109

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DH 036, 048 & YTG-C-0308

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D(CE, CG) 036, 048, 060 & YTG-A-0207

DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DL-15, -20 & BTG-F-1109

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DH 180, 210, 240 & YTG-F-1009

TECHNICAL GUIDE DESCRIPTION SERIES 20 SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS J15, 18, 20 & 25 DH JTG-A-1007

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DJ 180, 210, 240 & YTG-F-1009

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS WJ 180, 240 & YTG-C-0707

DESCRIPTION SINGLE PACKAGE HEAT PUMP UNITS BCB 036, 048 & BTG-A-0506

TECHNICAL GUIDE 50Hz DESCRIPTION SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS

TECHNICAL GUIDE. R-410A XP SERIES 15/20 TON 60 Hertz. Description. XP240 Shown YTG-B-1210

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D1HG/D1HE 180 & D-0602

D M S 760 C01 A A 1 1

R-410A ZS/ ZK / XA SERIES 3-6 TON 60 Hertz

TECHNICAL GUIDE (R-407C)

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS PRELIMINARY DATA

TECHNICAL GUIDE. R-410A ZF / ZR / XP SERIES 3-6 TON 60 Hertz. Description YTG-Q-0511

SUNLINE PLUS SINGLE PACKAGE GAS / ELECTRIC AIR CONDITIONERS DESCRIPTION. D1EG/D1EE 180 & and 20 NOMINAL TONS 9.5 EER

TECHNICAL GUIDE (R-407C)

TECHNICAL GUIDE 50 HZ

TECHNICAL GUIDE. SERIES 20 R-410A J**ZJ/ZR/ZF TON 60 Hertz. Description. J**ZJ/ZR/ZF Shown JTG-L-0612

TECHNICAL GUIDE R-410A ZJ/ZR/ZF SERIES TON 60 Hertz

DESCRIPTION SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DBUC/DBHB NOMINAL TONS 8.5 EER

SUNLINE 2000 SINGLE PACKAGE AIR - TO - AIR HEAT PUMPS DESCRIPTION. B1CH 180 & and 20 NOMINAL TONS ( EER)

FLEXIBLE EASY TO INSTALL SINGLE PACKAGE UNITS. TECHNICAL GUIDE SUNLINE PLUS AIR-COOLED AIR CONDITIONERS GENERAL FEATURING A-0204

SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DJ 180, 210, 240 & A-0502

SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS SUNLINE 2000 DESCRIPTION

SUNLINE PLUS SINGLE PACKAGE GAS / ELECTRIC AIR CONDITIONERS DESCRIPTION FEATURES

SUNLINE 2000 TM TECHNICAL GUIDE DESCRIPTION SINGLE PACKAGE AIR-TO-AIR HEAT PUMPS

TECHNICAL GUIDE. R-410A ZH/ZR/XP SERIES 6-1/2-12-1/2 TON 60 Hertz. Description YTG-E-0507 ASHRAE 90.1 COMPLIANT

SUNLINE 2000 SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DESCRIPTION FEATURES

TECHNICAL GUIDE R-410A ZH/ZJ SERIES /2 TON 60 Hertz

DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 2 THRU 5 NOMINAL TON FEATURING PTG-C-1108

TECHNICAL GUIDE R-410A ZF/ZR SERIES 6-1/2-12-1/2 TON 60 Hertz

SUNLINE 2000 (WORLD 50 HZ)

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

SUNLINE BP 180 SUNLINE MAGNUM - BP 240

DESCRIPTION TECHNICAL GUIDE AFFINITY SERIES SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 2 THRU 5 NOMINAL TON FEATURING YTG-B-0807

SINGLE PACKAGE HEAT PUMPS

FLEXIBLE LIGHT COMMERCIAL UNIT TECHNICAL GUIDE CHAMPION PLUS SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 1-1/2 THROUGH 5 NOMINAL TON

R6GP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Gas/Electric Units, with R-410A WARRANTY

DCG Series. Submittal Data Form. 7½ - 12½ Ton Packaged Gas/ Electric Up to 11.3 EER / 80% AFUE

TECHNICAL GUIDE FLEXIBLE LIGHT COMMERCIAL UNIT CHAMPION SERIES (WORLD 50 HZ) SINGLE PACKAGE COOLING UNITS D1EB036, 048 AND 060 3, 4 & 5 NOMINAL TONS

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS

R6GN Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Gas/Electric Units with R-410A WARRANTY

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

DESCRIPTION FEATURES

TECHNICAL GUIDE R-410A AFFINITY SERIES DNX, DNQ, DNZ MODELS 2-5 TON 60 Hertz

Q6SP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

FLEXIBLE LIGHT COMMERCIAL UNIT TECHNICAL GUIDE SUNLINE ULTRA SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS 4 AND 5 NOMINAL TON GENERAL FEATURING

DTC Series. Submittal Data Form 3- TO 5-TON SINGLE-PHASE PACKAGED AIR CONDITIONER

P6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6, 7½ and 10 Ton Packaged Electric Cooling Units EER Commercial System Units

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

TECHNICAL SPECIFICATIONS

GR4GN Series TECHNICAL SPECIFICATIONS. Single Packaged Gas/Electric Units. GR4GN 10.1 EER Commercial System 7½ and 10 Ton Units FEATURES AND BENEFITS

PGAA SERIES 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

S/T Ratio. Input BTU/h

14 SEER R -410A PACKAGE GAS / ELECTRIC UNIT 2 to 5 TON

K-SERIES COMMERCIAL PACKAGED ROOFTOP UNITS 2- TO 25-TON KG/KC/KH MODELS UP TO 16.5 SEER, 14.8 IEER AND 13.0 EER

FLEXIBLE LIGHT COMMERCIAL UNIT TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 1-1/2 THROUGH 5 NOMINAL TON GENERAL FEATURING

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units 11.0 EER

CPG Series. Submittal Data Form. 3- to 6-Ton Self-Contained. Packaged Gas/Electric. with R-410A

Q6SD Series 13 SEER, Three Phase, Packaged Heat Pump with R-410A 3-5 Ton Units

TECHNICAL GUIDE R-410A ACCLIMATE SERIES 2-5 TON 60 Hertz

AFGP12B. Features. Efficiency: 12 SEER 80% AFUE. Warranty: 10-year limited compressor 10-year limited heat exchanger 5-year limited components

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

Q6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

R6GI Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

R8HE Series Rev A. Single-Phase and Three-Phase TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

High Cap. (Btuh) HSPF COP

GP4SN Series TECHNICAL SPECIFICATIONS. Single Packaged Electric Cooling Units. P4SN 10.3 EER Commercial System 7½ and 10 Ton Units

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

Operating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16

GPG15 Series 80% AFUE. Single-Phase, Self-Contained. up to 15 SEER. Cooling Capacity: 23,200 56,500 BTU/h. Heating Capacity: 69, ,000 BTU/h

R-22, 13 SEER 60 Hertz

P6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

CPG COMMERCIAL 5-TON SELF-CONTAINED PACKAGED GAS/ELECTRIC UNIT

GQ6SD Series. Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY

Product Data. Features/Benefits 50JS SINGLE-PACKAGED HEAT PUMP 50 HZ UNITS 7 TO 18 KW (2 TO 5 NOMINAL TONS)

PHR5. Product Specifications

PGMD Series 10 SEER. International Comfort Products 651 Heil Quaker Avenue Lewisburg, Tn Part No

13 SEER Light Commercial 3 Phase

2SG13 60HZ P A C K A G E D G A S / E L E C T R I C

R6GF Series Rev B TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Gas/Electric Units Two-Stage Heat/Cool with Variable Speed Blower

ASHRAE 90.1 COMPLIANT PACKAGED ROOFTOP ELECTRIC COOLING UNITS, R 410A, TONS 3 Phase, 50 Hz. BUILT TO LAST, EASY TO INSTALL AND SERVICE

TECHNICAL GUIDE R-410A AFFINITY SERIES DEQ, DEX, DEY AND DEZ MODELS 2-5 TON 60 Hertz

TECHNICAL GUIDE. SERIES 20 R-410A J**ZJ/ZR/ZF TON 60 Hertz. Description. J**ZJ/ZR/ZF Shown JTG-H-0917

GPG COMMERCIAL PRODUCT SPECIFICATIONS 13 & 10 SEER 80% AFUE 3, 4, & 5 TON, 3-PHASE SELF-CONTAINED PACKAGED GAS/ELECTRIC

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS

TECHNICAL GUIDE R-410A AFFINITY SERIES DEZ MODELS 2-5 TON 60 Hertz

TECHNICAL GUIDE DESCRIPTION ACCLIMATE SERIES SINGLE PACKAGE COOLING UNITS DAPM024 THRU THRU 5 TON (13 SEER) STANDARD FEATURES / BENEFITS

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

2SA13 60HZ P A C K A G E D E L E C T R I C / E L E C T R I C

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

TECHNICAL GUIDE R-410A ZJ/ZR/ZF SERIES TON 60 Hertz

Transcription:

TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DK-03, -04, -05 and -A6 3, 4, 5 and 6 NOMINAL TONS 13.0 SEER 10.4 EER DESCRIPTION MagnaDRY units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. All units include: Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability (field convertible) Manufactured under the quality standards of ISO9001 Simplicity Control Board Copper tube/aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork lift slots on three sides Single point power connection Complete factory package - tested, charged and wired CSA agency listing on all units WARRANTY Factory Limited Parts Warranty One-year parts warranty A Five-year parts warranty on the compressor and electric heat elements. Ten-year parts warranty on the gas-fired heat exchangers. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TABLE OF CONTENTS DESCRIPTION............................. 1 TABLE OF CONTENTS....................... 2 PRODUCT NOMENCLATURE................. 4 FEATURES................................ 5 FACTORY-INSTALLED OPTIONS.............. 7 FIELD-INSTALLED ACCESSORIES............ 8 GUIDE SPECIFICATIONS................... 53 LIST OF FIGURES Fig. # Pg. # 1 UNIT CUTAWAY Gas/Electric................... 6 2 UNIT CUTAWAY Electric/Electric................ 7 3 DK-03 MOISTURE REMOVAL - REHEAT MODE... 25 4 DK-04 MOISTURE REMOVAL - REHEAT MODE... 25 5 DK-05 MOISTURE REMOVAL - REHEAT MODE... 26 6 DK-A6 MOISTURE REMOVAL - REHEAT MODE.. 26 7 Typical Power Wiring......................... 46 8 Typical Reheat Control Wiring.................. 46 9 UNIT DIMENSIONS (3-6 TON COOLING ONLY/ ELECTRIC HEAT) FRONT VIEW 47 10 UNIT DIMENSIONS (3-6 TON COOLING/GAS HEAT) FRONT VIEW......................... 47 11 UNIT WITH ECONOMIZER RAINHOOD.......... 48 12 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD........................ 48 13 UNIT DIMENSIONS (REAR VIEW).............. 49 14 DISCONNECT/BLOWER ACCESS LOCATION.... 49 15 TYPICAL APPLICATIONS..................... 50 16 FOUR AND SIX POINT LOADING.............. 51 17 ROOF CURB DIMENSIONS................... 52 LIST OF TABLES Tbl. # Pg. # 18 DK-03 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)................ 10 19 DK-03 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE).......... 10 20 DK-03 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)............................. 11 21 DK-03 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)....................... 11 Tbl. # Pg. # 22 DK-04 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)................ 12 23 DK-04 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE).......... 12 24 DK-04 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)............................ 13 25 DK-04 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)....................... 13 26 DK-05 & -A6 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)................ 14 27 DK-05 & -A6 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE).......... 14 28 DK-05 & -A6 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET).................. 15 29 DK-05 & -A6 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)............. 15 30 CAPACITY RATINGS........................ 16 31 GAS HEAT RATINGS........................ 16 32 2 STAGE GAS HEAT RATINGS................ 16 33 DK-03 COOLING CAPACITIES (3 TON) - NORMAL MODE..................................... 17 34 DK-03 COOLING CAPACITIES (3 TON) - REHEAT MODE..................................... 18 35 DK-04 COOLING CAPACITIES (4 TON) - NORMAL MODE..................................... 19 36 DK-04 COOLING CAPACITIES (4 TON) - REHEAT MODE..................................... 20 37 DK-05 COOLING CAPACITIES (5 TON) - NORMAL MODE..................................... 21 38 DK-05 COOLING CAPACITIES (5 TON) - REHEAT MODE..................................... 22 39 DK-A6 COOLING CAPACITIES (6 TON) - NORMAL MODE..................................... 23 40 DK-A6 COOLING CAPACITIES (6 TON) - REHEAT MODE..................................... 24 41 SUPPLY AIR BLOWER PERFORMANCE (DK-03 BELT DRIVE) - SIDE DUCT APPLICATION............ 27 42 SUPPLY AIR BLOWER PERFORMANCE (DK-03 BELT DRIVE) - BOTTOM DUCT APPLICATION......... 27 43 SUPPLY AIR BLOWER PERFORMANCE (DK-04 BELT DRIVE) - SIDE DUCT APPLICATION............ 27 44 SUPPLY AIR BLOWER PERFORMANCE (DK-04 BELT DRIVE) - BOTTOM DUCT APPLICATION......... 27 45 SUPPLY AIR BLOWER PERFORMANCE (DK-05 BELT DRIVE) - SIDE DUCT APPLICATION............ 28 2 Johnson Controls Unitary Products

LIST OF TABLES (Continued) Tbl. # Pg. # 46 SUPPLY AIR BLOWER PERFORMANCE (DK-05 BELT DRIVE) - BOTTOM DUCT APPLICATION......... 28 47 SUPPLY AIR BLOWER PERFORMANCE (DK-A6 BELT DRIVE) - SIDE DUCT APPLICATION............ 28 48 SUPPLY AIR BLOWER PERFORMANCE (DK-A6 BELT DRIVE) - BOTTOM DUCT APPLICATION......... 28 49 SUPPLY AIR BLOWER PERFORMANCE (DK-03, -04, -05 & -A6 DIRECT DRIVE) SIDE DUCT APPLICATION.............................. 29 50 SUPPLY AIR BLOWER PERFORMANCE (DK-03, -04, -05 & -A6 DIRECT DRIVE) BOTTOM DUCT APPLICATION.............................. 29 51 BELT DRIVE RPM SELECTION................ 30 52 BELT DRIVE BLOWER MOTOR AND DRIVE DATA..................................... 30 53 STATIC RESISTANCES...................... 30 54 ELECTRIC HEATER CFM LIMITATIONS......... 32 55 ELECTRICAL DATA - DK-03, -04, -05 & -A6 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET. 33 Tbl. # Pg. # 56 ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE W/O POWERED CONVENIENCE OUTLET. 35 57 ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE HIGH STATIC W/O POWERED CONVENIENCE OUTLET..................... 37 58 ELECTRICAL DATA - DK-03, -04, -05 & -A6 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET... 39 59 ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE W/POWERED CONVENIENCE OUTLET... 41 60 ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE HIGH STATIC W/POWERED CONVENIENCE OUTLET..................... 43 61 PHYSICAL DATA............................ 45 62 ELECTRIC HEAT CORRECTION FACTORS...... 45 63 VOLTAGE LIMITATIONS..................... 45 64 UTILITIES ENTRY........................... 49 65 MINIMUM CLEARANCES..................... 49 66 DK 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION............................. 51 67 CENTER OF GRAVITY....................... 51 68 OPERATING WEIGHTS (LBS.)................. 52 Johnson Controls Unitary Products 3

PRODUCT NOMENCLATURE 3-6 Ton MagnaDRY Model Number Nomenclature D K -04 N07 A T A AA 1 0 1 2 4 A Product Category D = A/C, Single Pkg., R-22 Product Style A = Style A -03 = 3.0 Ton -04 = 4.0 Ton -05 = 5.0 Ton -A6 = 6.0 Ton Heat Type and Nominal Heat Capacity C00 = Only. Suitable for Field Installed Electric Heat N05 = 50 MBH Input Aluminized Steel, 1 Stage (-03) N07 = 75 MBH Input Aluminized Steel, 1 Stage (-04) N11 = 100 MBH Input Aluminized Steel, 1 Stage (-03, -05, -A6) N13 = 125 MBH Input Aluminized Steel, 1 Stage ( -04, -05, -A6) D07 = 75 MBH Input Aluminized Steel, 2 Stage (-03, -04, -05, -A6) D13 = 125 MBH Input Aluminized Steel, 2 Stage (-03*, -04, -05, -A6) S05 = 50 MBH Input Stainless Steel, 1 Stage (-03) S07 = 75 MBH Input Stainless Steel, 1 Stage (-04) S11 = 100 MBH Input Stainless Steel, 1 Stage (-03, -05, -A6) S13 = 125 MBH Input Stainless Steel, 1 Stage (-04, -05, -A6) T07 = 75 MBH Input Stainless Steel, 2 Stage (-03, -04, -05, -A6) T13 = 125 MBH Input Stainless Steel, 2 Stage (-03*, -04, -05, -A6) E05 = 5 KW E07 = 7 KW E10 = 10 KW E15 = 15 KW E20 = 20 KW E30 = 30 KW Product Identifier K = 13.0 SEER Reheat Nominal Capacity Gas Heat Options Electric Heat Options * (D, T) 13 = 115 MBH Input on -03 Models Airflow A = Direct Drive B = Direct Drive/Economizer D = Direct Drive/Motorized Damper N = Belt Drive P = Belt Drive/Economizer R = Belt Drive/Motorized Damper T = Belt Drive High Static U = Belt Drive High Static/Economizer V = Belt Drive High Static/Motorized Damper Voltage F = 208/230-1-60 T = 208/230-3-60 W = 460-3-60 X = 575-3-60 Installation Options A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5 Configuration Options (not required for all units) These four digits will not be assigned until a quote is requested, or an order placed. SS Drain Pan CPC Controller, DFS, APS Johnson Controller, DFS, APS Honeywell Controller, DFS, APS Novar Controller, DFS, APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w/modlinc 2" Pleated filters BAS Ready Economizer (2-10 V. D. C. Actuator without a Controller) Any Combination of Additional Options that Don t Have an Option Code Pre-assigned Product Generation 1 = First Generation 2 = Second Generation Standard Cabinet AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch AS = Bottom Drain Connection RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator and Condenser Coil Additional Options Hinged Filter Door & Toolless Access Cabinet BA = Hinged Filter Door & Toolless Access Panels BB = Phase Monitor, Hinged Filter Door & Toolless Access Panels BC = Coil Guard, Hinged Filter Door & Toolless Access Panels BD = Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BE = Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels BF = Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BG = Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BH = Phase Monitor, Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be located in digits 15-18. Options 1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet 4 Johnson Controls Unitary Products

FEATURES All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit. All models are available with these factory mounted outdoor air damper options: Single enthalpy economizer Motorized outdoor air damper Supply air blowers are equipped with either direct drive or belt drive that can be adjusted to meet the exact requirements of the job. All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components. Simplicity Controls - Simplicity control boards have standardized a number of features previously available only as options or by utilizing additional controls. Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available. The Simplicity control board used in this product will effectively operate the cooling system down to 0 F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1-877- UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30 F. Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button. Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat. Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a three strikes, you re out philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor. On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power. Johnson Controls Unitary Products 5

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. All models are CSA listed. Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty. Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 80%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit. Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive temperature by thermal limit switches. The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit. BAS Controls - DK series units offer factory mounted BAS controls such as Simplicity INTELLI-Comfort, Novar, Honeywell, Johnson, and CPC. Economizer hood HACR breaker Belt drive or Direct drive blower 20 Gauge aluminized steel tubular heat exchanger Electric heat accessory location Power ventor motor with post purge cycle High efficiency compressor Copper tube/ aluminum fin condensing coil Knockout for side power entry Slide-in economizer Smoke detector 3/4" PVC female condensate drain Knockout for side gas supply entry Full perimeter baserails with forklift slots and lifting holes GFCI convenience outlet Simplicity Lite control board Knockout for side control entry FIGURE 1 - UNIT CUTAWAY GAS/ELECTRIC 6 Johnson Controls Unitary Products

Economizer hood Knockout for side power entry HACR breaker Belt drive or Direct drive blower High efficiency compressor Copper tube/ aluminum fin condensing coil Slide-in economizer Smoke detector Full perimeter baserails with forklift slots and lifting holes 3/4" PVC female condensate drain Electric Heat accessory location GFCI convenience outlet Simplicity Lite control board Knockout for side control entry FIGURE 2 - UNIT CUTAWAY ELECTRIC/ELECTRIC FACTORY-INSTALLED OPTIONS SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that utilizes Technicoat 10-1 TM processes. Coating is applied by total immersion of the complete coil for maximum protection. ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. FILTER OPTIONS - Standard units are shipped with 1 throw-away filters installed. 2 pleated filters are offered as a factory installed option. CONVENIENCE OUTLET - This 110 volt outlet can be powered by the unit with a stepdown transformer or the unit may be ordered with a non-powered convenience outlet that can be wired in the field. DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only. BAS - Building Automation System Controls Simplicity INTELLI-Comfort CONTROL - The Simplicity INTELLI-Comfort control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort using CO 2 sensors. It uses an inside CO 2 sensor to perform Demand Ventilation. It Johnson Controls Unitary Products 7

can also use an Outside CO 2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity INTELLI-Comfort balances space temperature, ventilation air temperature, CO 2 and humidity for ultimate comfort. Simplicity INTELLI-Comfort with MOD LINK CON- TROL - The York Simplicity INTELLI-Comfort with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort control with an additional control to translate communications from MOD- BUS to the BACnet MSTP protocol. Novar BAS CONTROL - The Novar building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch. JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch. CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch. HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch. SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. Factory installed Smoke Detectors in the return air, may be subjected to freezing temperatures during off times due to outside air infiltration. These smoke detectors have an operational limit of 32 F to 131 F. Smoke detectors installed in areas that could be outside those limitations will have to be moved to prevent having false alarms. STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly. STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments. BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connections for applications in cold environments to reduce freezing drain lines. PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition. DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory. HINGED FILTER DOOR/ TOOLLESS BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance. NOTE: Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation. HIGH STATIC DRIVE OPTION - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance. FIELD-INSTALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. 8 Johnson Controls Unitary Products

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports. HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane. HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit. LOW NOX KIT- Required to reduce the emission of nitrogen oxides below 40 nanograms per joule. POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. The power exhaust option can only be used on bottom duct configurations. BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy. BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work. FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. CO 2 SENSOR - Senses CO 2 levels and automatically overrides the economizer when levels rise above the present limits. COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. HAIL GUARD - Hail guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil. GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve. REHEAT MODE SEQUENCE OF OPERATION STANDARD A/C MODE: INPUT: Y1 ON, Y2 OFF, HUMIDISTAT OPEN - During normal cooling operation, a Y1 call from the thermostat will bring on the unit in the standard cooling mode. Since the humidistat is open, the liquid line solenoid (SLL) will be open and the hot gas solenoid (SHG) will be closed allowing the unit to operate in the standard cooling mode. REHEAT MODE: INPUT: Y1 ON, Y2 OFF, HUMIDISTAT CLOSED - During reheat mode, the Y1 signal will bring on the compressor and will send the 24V signal through the humidistat, through the normally closed contacts of the hot gas relay (RHG) and will energize both the liquid line and the hot gas solenoids which directs hot gas through part of the indoor coil and decreases the sensible capacity of the unit. STANDARD A/C MODE: INPUT: Y1 ON, Y2 ON, HUMIDISTAT OPEN OR CLOSED - If there is a call for Y1 and Y2, the unit will be in normal cooling mode regardless of the humidistat input. The Y2 signal will energize the hot gas relay (RHG) which will keep the liquid line solenoid (SLL) open and the hot gas solenoid (SHG) closed and the unit will operate in the normal cooling mode. NOTE: Y2 must be used or the function of the unit will be permanently in the Re-Heat mode and sensible cooling capacity will be affected. Johnson Controls Unitary Products 9

TABLE 1: DK-03 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-03 / 3 Ton / Belt Drive Horizontal Ducted Inlet 630 631 879 885 0.2 0.3 0.2 0.7 1116 928 1979 1020 0.41 0.37 0.76 0.53 Only Only 63 80 82 80 82 78 83 81 85 125 76 77 76 77 82 83 81 82 250 56 59 56 60 60 61 58 60 500 50 50 49 50 54 54 51 52 1000 40 43 39 42 49 50 44 45 2000 41 42 40 42 49 49 43 44 4000 41 41 41 41 49 49 41 41 8000 45 45 45 45 47 47 45 45 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. TABLE 2: DK-03 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only Only Only DK-03 / 3 Ton / Belt Drive Horizontal Ducted Discharge 630 631 879 885 0.2 0.3 0.2 0.7 1116 928 1979 1020 0.41 0.37 0.76 0.53 Only Only 63 80 84 80 83 85 87 84 87 125 74 77 74 76 80 82 80 83 250 58 61 58 61 68 68 63 65 500 48 51 47 50 58 58 53 54 1000 41 45 39 43 55 55 49 50 2000 39 41 37 39 53 53 46 47 4000 41 41 38 38 55 55 49 49 8000 45 45 44 44 52 53 47 47 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. 10 Johnson Controls Unitary Products

TABLE 3: DK-03 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-03 / 3 Ton / Belt Drive Vertical Ducted Inlet 632 632 881 883 0.2 0.3 0.2 0.7 1069 870 1903 917 0.36 0.33 0.71 0.49 Only Only 63 78 82 78 82 80 85 80 84 125 70 75 70 74 71 80 71 79 250 55 60 55 60 59 61 58 62 500 47 50 47 50 52 53 49 52 1000 40 43 39 43 50 51 45 46 2000 37 40 37 39 45 46 41 43 4000 36 37 36 37 45 46 40 40 8000 44 44 44 44 45 47 44 44 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. TABLE 4: DK-03 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only Only Only DK-03 / 3 Ton / Belt Drive Vertical Ducted Discharge 632 632 881 883 0.2 0.3 0.2 0.7 1069 870 1903 917 0.36 0.33 0.71 0.49 Only Only 63 80 83 80 83 83 86 82 85 125 78 79 77 78 80 83 79 82 250 55 60 54 59 63 63 58 62 500 48 51 46 50 58 59 52 53 1000 41 44 39 43 54 55 48 49 2000 37 40 35 38 50 50 42 44 4000 38 39 36 37 52 53 44 44 8000 44 45 44 44 49 50 45 45 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. Johnson Controls Unitary Products 11

TABLE 5: DK-04 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-04 / 4 Ton / Belt Drive Horizontal Ducted Inlet 766 769 1077 1087 0.2 0.5 0.4 1.0 1484 993 2270 1406 0.67 0.54 1.24 0.90 Only Only 63 74 97 74 95 77 90 77 90 125 70 86 69 86 73 78 72 77 250 53 58 52 57 60 61 58 61 500 49 55 47 54 54 56 51 53 1000 42 42 38 39 50 55 45 45 2000 40 44 38 43 48 51 45 46 4000 38 44 36 41 48 52 43 45 8000 42 43 42 44 45 48 44 45 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. TABLE 6: DK-04 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only Only DK-04 / 4 Ton / Belt Drive Horizontal Ducted Discharge 766 769 1077 1087 0.2 0.5 0.4 1.0 1484 993 2270 1406 0.67 0.54 1.24 0.90 Only Only Only 63 77 97 75 95 84 91 82 91 125 72 86 69 85 81 83 78 80 250 60 62 57 59 71 71 66 67 500 53 56 49 54 60 61 55 56 1000 47 47 42 43 58 59 52 52 2000 45 46 40 43 54 55 50 50 4000 46 47 40 42 57 58 52 52 8000 47 47 45 45 54 54 48 49 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. 12 Johnson Controls Unitary Products

TABLE 7: DK-04 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-04 / 4 Ton / Belt Drive Vertical Ducted Inlet 791 794 1084 1095 0.2 0.5 0.2 1.0 1408 1000 2336 1275 0.54 0.42 1.12 0.73 Only Only Only 63 76 95 77 93 80 91 79 91 125 68 84 67 82 76 84 73 80 250 54 57 52 56 63 61 57 59 500 48 53 46 53 54 57 50 53 1000 43 44 40 41 52 52 47 47 2000 40 43 38 42 49 51 44 46 4000 38 43 36 40 49 54 43 45 8000 43 43 43 43 45 47 44 44 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. TABLE 8: DK-04 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-04 / 4 Ton / Belt Drive Vertical Ducted Discharge 791 794 1084 1095 0.2 0.5 0.2 1.0 1408 1000 2336 1275 0.54 0.42 1.12 0.73 Only Only Only 63 78 95 77 93 85 92 82 91 125 73 84 72 82 84 87 78 82 250 56 58 53 56 68 68 60 61 500 51 54 48 53 61 62 54 55 1000 46 46 43 44 57 57 50 50 2000 42 44 38 42 53 54 46 48 4000 43 45 39 41 55 57 49 50 8000 44 44 43 43 52 52 46 47 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. Johnson Controls Unitary Products 13

TABLE 9: DK-05 & -A6 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-05 & -A6 / 5 & 6 Ton / Belt Drive Horizontal Ducted Inlet 840 845 1166 1188 0.2 0.6 0.3 1.3 1695 1100 2618 1323 0.67 0.50 1.51 0.80 Only Only 63 77 84 77 84 81 85 79 84 125 71 71 72 73 74 75 71 72 250 57 58 55 56 66 66 60 61 500 53 53 51 51 60 60 55 55 1000 50 50 45 46 60 60 53 53 2000 49 49 43 44 58 58 50 50 4000 49 49 42 43 59 59 47 47 8000 49 49 48 48 54 54 4 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. TABLE 10: DK-05 & -A6 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only Only Only DK-05 & -A6 / 5 & 6 Ton / Belt Drive Horizontal Ducted Discharge 840 845 1166 1188 0.2 1695 0.6 1100 0.3 2618 1.3 1323 0.67 0.50 1.51 0.80 Only (d Only 63 82 87 79 88 88 89 82 87 125 75 76 72 74 82 83 78 78 250 69 69 66 66 79 79 73 73 500 64 64 60 60 72 72 66 66 1000 59 60 55 56 68 68 61 61 2000 55 55 50 50 65 65 57 57 4000 58 58 52 52 68 68 60 60 8000 55 55 49 49 66 67 56 56 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. 14 Johnson Controls Unitary Products

TABLE 11: DK-05 & -A6 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-05 & -A6 / 5 & 6 Ton / Belt Drive Vertical Ducted Inlet 834 840 1171 1194 0.2 0.6 0.2 1.3 1525 1019 2624 1256 0.61 0.44 1.43 0.83 Only Only Only 63 77 86 79 88 81 86 83 87 125 69 70 70 72 71 73 72 72 250 56 63 56 58 64 72 63 69 500 50 52 48 49 57 59 53 56 1000 48 51 44 45 57 58 49 52 2000 43 47 39 41 54 57 47 50 4000 47 49 40 41 55 61 47 52 8000 46 47 44 45 51 57 47 4 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. TABLE 12: DK-05 & -A6 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP Octave Center Freq. Only DK-05 & -A6 / 5 & 6 Ton / Belt Drive Vertical Ducted Discharge 834 840 1171 1194 0.2 0.6 0.2 1.3 1525 1019 2624 1256 0.61 0.44 1.43 0.83 Only Only Only 63 83 88 82 88 91 91 85 88 125 78 78 75 76 85 85 79 79 250 66 67 62 62 77 78 70 72 500 59 60 54 54 70 70 61 61 1000 57 58 51 51 68 68 57 58 2000 51 52 45 45 62 63 52 53 4000 54 54 47 47 65 66 55 56 8000 52 52 46 47 65 66 52 5 1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. 2. Operation ID blower, compressor and outdoor fan operating. 3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m). 4. Test duct termination is flush with reverberation room wall. 5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) db at (63, 125, 250, 500, 1k, 4k, 8k) Hz. Johnson Controls Unitary Products 15

TABLE 13: CAPACITY RATINGS TABLE 14: GAS HEAT RATINGS 1 UNIT SIZE COOLING PERFORMANCE (MBH) DK-03 36.0 1 13.0 1 SOUND RATING 3 MBH SEER 4 EER 5 DECIBELS 11.5 84 DK-04 45.5 1 13.0 1 11.5 83 DK-05 56.5 1 13.0 1 11.5 81 DK-A6 70.0 2-10.4 2 84 1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240. 2. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360. 3. Rated in accordance with ARI Standard 270. 4. SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 5. EER = Energy Efficiency Ratio - the cooling capacity in BTU s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt). MODEL DK-03N05 DK-03N11 DK-04N07 DK-04N13 DK-05N11 DK-05N13 DK-A6N11 DK-A6N13 MBH INPUT 50 100 75 125 100 125 100 125 MBH OUTPUT 40 80 60 100 80 100 80 100 1. All units are single-stage heating. AFUE (%) 80.9 80.5 80.9 80.3 80.5 80.3 80.5 80.3 TEMP RISE ºF 15-45 45-75 25-70 45-75 25-55 35-75 25-55 30-75 TABLE 15: 2 STAGE GAS HEAT RATINGS MODEL 1, 2 MBH INPUT MBH OUTPUT STEADY STATE EFFICIENCY RISE MINIMUM HEATING 1 ST STAGE 2 ND STAGE 1 ST STAGE 2 ND STAGE 1 ST STAGE 2 ND STAGE MIN. MAX. AIRFLOW (CFM) DK-03D07 45 75 35.8 60.8 79.4 81.1 35 70 790 DK-03D13 69 115 55.2 92 80.0 80.2 55 90 950 DK-04D07 45 75 35.7 60.8 79.4 81.1 25 70 790 DK-04D13 75 125 60.4 100.6 80.5 80.5 45 75 1230 DK-05D07 45 75 35.8 60.8 79.4 81.1 20 55 1010 DK-05D13 75 125 60.4 100.6 80.5 80.5 35 75 1230 DK-A6D07 45 75 35.8 60.8 79.4 81.1 15 45 1230 DK-A6D13 75 125 60.4 100.6 80.5 80.5 30 75 1230 1. Models are 3Ø only. 2. All 2 Stage Gas Heat, 60% Capacity 1 ST Stage, 40% Capacity 2 ND Stage. 16 Johnson Controls Unitary Products

TABLE 16: DK-03 COOLING CAPACITIES (3 TON) - NORMAL MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 49.0 2.3 24.5 22.4 20.3 18.2 16.1 - - 44.6 2.6 22.7 20.6 18.6 16.5 14.4 - - 900 67 43.1 2.3 29.7 27.6 25.5 23.4 21.4 19.3 17.2 39.5 2.5 28.0 25.9 23.9 21.8 19.7 17.6 15.5 62 38.1 2.3 35.5 33.1 31.0 28.9 26.9 24.8 22.7 34.7 2.5 33.4 31.3 29.2 27.1 25.1 23.0 20.9 57 37.2 2.3 37.2 37.2 34.5 32.4 30.3 28.3 26.2 34.0 2.5 34.0 34.0 32.0 29.9 27.8 25.7 23.7 72 51.1 2.3 26.9 24.5 22.1 19.7 17.3 - - 46.3 2.6 24.9 22.6 20.2 17.8 15.4 - - 1050 67 44.9 2.3 32.6 30.2 27.8 25.5 23.1 20.7 18.3 41.0 2.6 30.7 28.3 25.9 23.6 21.2 18.8 16.4 62 39.7 2.3 38.4 36.9 33.9 31.5 29.1 26.7 24.3 36.0 2.5 35.4 34.2 31.8 29.4 27.0 24.6 22.3 57 38.7 2.3 38.7 38.7 37.6 35.3 32.9 30.5 28.1 35.3 2.5 35.3 35.3 34.8 32.4 30.0 27.6 25.3 72 53.2 2.3 29.4 26.7 24.0 21.3 18.6 - - 48.0 2.6 27.1 24.5 21.8 19.1 16.4 - - 1200 67 46.8 2.3 35.6 32.9 30.2 27.5 24.8 22.0 19.3 42.5 2.6 33.4 30.7 28.0 25.4 22.7 20.0 17.3 62 41.4 2.3 41.4 40.7 36.7 34.0 31.3 28.6 25.8 37.4 2.6 37.4 37.0 34.3 31.7 29.0 26.3 23.6 57 40.3 2.3 40.3 40.3 40.8 38.1 35.4 32.7 30.0 36.6 2.5 36.6 36.6 37.6 34.9 32.2 29.6 26.9 72 54.4 2.4 31.5 28.5 25.5 22.5 19.5 - - 48.8 2.6 29.1 26.2 23.2 20.3 17.3 - - 1350 67 47.8 2.4 38.1 35.1 32.1 29.1 26.1 23.1 20.2 43.2 2.6 35.7 32.8 29.8 26.9 24.0 21.0 18.1 62 42.3 2.3 42.3 41.9 39.9 37.0 34.0 31.0 28.0 38.0 2.6 38.0 37.8 36.5 33.5 30.6 27.6 24.7 57 41.2 2.3 41.2 41.2 41.5 38.5 35.5 32.5 29.5 37.2 2.5 37.2 37.2 37.7 34.7 31.8 28.8 25.9 72 55.6 2.4 33.6 30.3 27.0 23.8 20.5 - - 49.6 2.6 31.1 27.8 24.6 21.4 18.2 - - 1500 67 48.9 2.4 40.6 37.3 34.0 30.8 27.5 24.2 21.0 43.9 2.6 38.1 34.9 31.7 28.4 25.2 22.0 18.8 62 43.2 2.4 43.2 43.2 43.2 39.9 36.7 33.4 30.2 38.6 2.6 38.6 38.6 38.6 35.4 32.1 28.9 25.7 57 42.1 2.4 42.1 42.1 42.1 38.9 35.6 32.3 29.1 37.8 2.5 37.8 37.8 37.8 34.6 31.3 28.1 24.9 95 F 105 F 72 40.1 2.8 21.0 18.9 16.8 14.7 12.6 - - 36.5 3.0 18.9 16.8 14.8 12.8 10.8 - - 900 67 35.9 2.8 26.4 24.3 22.2 20.1 18.0 15.9 13.8 32.1 3.0 24.2 22.1 20.1 18.1 16.1 14.0 12.0 62 31.3 2.7 31.3 29.5 27.4 25.3 23.2 21.2 19.1 28.3 2.9 28.3 27.4 25.4 23.4 21.4 19.3 17.3 57 30.8 2.7 30.8 30.8 29.5 27.4 25.3 23.2 21.1 27.5 2.9 27.5 27.5 26.9 24.8 22.8 20.8 18.8 72 41.5 2.8 22.9 20.6 18.2 15.8 13.5 - - 37.4 3.0 20.7 18.4 16.1 13.8 11.5 - - 1050 67 37.1 2.8 28.8 26.4 24.0 21.7 19.3 16.9 14.6 32.9 3.0 26.4 24.1 21.8 19.5 17.2 14.9 12.6 62 32.3 2.7 32.3 31.4 29.7 27.3 25.0 22.6 20.2 29.0 2.9 29.0 28.5 27.6 25.3 22.9 20.6 18.3 57 31.8 2.7 31.8 31.8 31.9 29.6 27.2 24.8 22.5 28.2 2.9 28.2 28.2 29.5 26.5 24.9 22.6 20.3 72 42.8 2.8 24.9 22.3 19.6 17.0 14.3 - - 38.2 3.1 22.5 19.9 17.3 14.7 12.2 - - 1200 67 38.3 2.8 31.2 28.5 25.9 23.2 20.6 18.0 15.3 33.6 3.0 28.7 26.1 23.5 20.9 18.3 15.7 13.2 62 33.4 2.8 33.4 33.4 32.0 29.3 26.7 24.1 21.4 29.6 3.0 29.6 29.6 29.7 27.1 24.5 21.9 19.4 57 32.9 2.7 32.9 32.9 34.4 31.7 29.1 26.5 23.8 28.8 2.9 28.8 28.8 32.2 28.2 26.9 24.4 21.8 72 43.2 2.8 26.7 23.8 20.9 18.0 15.1 - - 38.4 3.1 24.1 21.3 18.5 15.7 12.8 - - 1350 67 38.6 2.8 33.4 30.5 27.6 24.7 21.8 18.9 16.0 33.8 3.0 30.5 27.9 25.1 22.3 19.4 16.6 13.8 62 33.7 2.8 33.7 33.7 33.0 30.1 27.1 24.2 21.3 29.8 3.0 29.8 29.8 29.8 27.0 24.1 21.3 18.5 57 33.2 2.7 33.2 33.2 33.9 31.0 28.1 25.2 22.3 28.9 2.9 28.9 28.9 30.6 27.1 24.9 22.1 19.3 72 43.6 2.8 28.6 25.4 22.2 19.0 15.9 - - 38.5 3.1 25.8 22.7 19.7 16.6 13.5 - - 1500 67 39.0 2.8 35.6 32.5 29.3 26.1 22.9 19.8 16.6 33.9 3.0 32.3 29.7 26.7 23.6 20.5 17.5 14.4 62 33.9 2.8 33.9 33.9 33.9 30.8 27.6 24.4 21.2 29.9 3.0 29.9 29.9 29.9 26.8 23.8 20.7 17.6 57 33.4 2.7 33.4 33.4 33.4 30.3 27.1 23.9 20.7 29.1 2.9 29.1 29.1 29.1 26.0 22.9 19.9 16.8 115 F 125 F 72 32.9 3.2 16.8 14.8 12.8 10.9 8.9 - - 29.3 3.5 14.7 12.8 10.9 9.0 7.1 - - 900 67 28.4 3.2 22.0 20.0 18.0 16.1 14.1 12.1 10.2 24.7 3.4 19.8 17.9 16.0 14.1 12.2 10.3 8.4 62 25.4 3.1 25.4 25.4 23.4 21.4 19.5 17.5 15.6 22.5 3.3 22.5 22.5 21.4 19.5 17.6 15.7 13.8 57 24.2 3.1 24.2 24.2 24.2 22.3 20.3 18.4 16.4 21.0 3.3 21.0 21.0 21.0 19.7 17.8 15.9 14.0 72 33.3 3.3 18.4 16.2 13.9 11.7 9.4 - - 29.2 3.5 16.2 14.0 11.8 9.6 7.4 - - 1050 67 28.7 3.2 24.1 21.8 19.6 17.3 15.1 12.8 10.6 24.5 3.4 21.7 19.5 17.3 15.2 13.0 10.8 8.6 62 25.7 3.1 25.7 25.6 25.4 23.2 20.9 18.7 16.4 22.3 3.3 22.3 22.3 22.3 21.1 18.9 16.7 14.5 57 24.5 3.1 24.5 24.5 27.1 23.5 22.5 20.4 18.1 20.8 3.3 20.8 20.8 20.8 20.5 20.2 18.1 16.0 72 33.6 3.3 20.1 17.6 15.0 12.5 10.0 - - 29.0 3.5 17.7 15.2 12.7 10.3 7.8 - - 1200 67 29.0 3.2 26.2 23.6 21.1 18.6 16.1 13.5 11.0 24.4 3.4 23.7 21.2 18.7 16.3 13.8 11.3 8.8 62 25.9 3.2 25.9 25.9 27.4 24.9 22.3 19.8 17.3 22.2 3.4 22.2 22.2 22.2 22.2 20.2 17.7 15.2 57 24.8 3.1 24.8 24.8 30.0 24.8 24.8 22.4 19.9 20.7 3.3 20.7 20.7 20.7 20.7 20.7 20.4 17.9 1350 1500 72 33.6 3.3 21.6 18.8 16.1 13.3 10.6 - - 28.8 3.5 19.0 16.3 13.7 11.0 8.3 - - 67 29.0 3.2 27.5 25.3 22.6 19.8 17.1 14.4 11.6 24.1 3.4 24.1 22.7 20.1 17.4 14.8 12.1 9.4 62 25.9 3.2 25.9 25.9 26.6 23.9 21.1 18.4 15.7 22.0 3.4 22.0 22.0 22.0 20.8 18.1 15.5 12.8 57 24.7 3.1 24.7 24.7 27.3 23.2 21.8 19.1 16.4 20.5 3.3 20.5 20.5 20.5 19.4 18.6 16.1 13.4 72 33.5 3.3 23.0 20.1 17.1 14.2 11.2 - - 28.5 3.6 20.3 17.4 14.6 11.7 8.9 - - 67 28.9 3.2 28.9 27.0 24.0 21.1 18.1 15.2 12.2 23.9 3.5 23.9 23.9 21.4 18.6 15.7 12.9 10.0 62 25.8 3.2 25.8 25.8 25.8 22.9 19.9 17.0 14.0 21.8 3.4 21.8 21.8 21.8 18.9 16.1 13.3 10.4 57 24.7 3.2 24.7 24.7 24.7 21.7 18.8 15.8 12.8 20.3 3.4 20.3 20.3 20.3 17.4 14.6 11.7 8.9 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products 17

TABLE 17: DK-03 COOLING CAPACITIES (3 TON) - REHEAT MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 36.2 2.2 15.4 14.6 13.7 12.8 12.0 - - 32.3 2.4 14.6 13.7 12.8 11.9 11.0 - - 900 67 29.7 2.3 17.1 16.2 15.3 14.5 13.6 12.8 11.9 27.3 2.4 16.9 16.0 15.1 14.2 13.3 12.4 11.5 62 28.8 2.1 20.4 19.5 18.7 17.8 17.0 16.1 15.3 25.4 2.3 20.0 19.1 18.2 17.3 16.4 15.6 14.7 57 26.9 2.2 26.9 26.9 26.0 25.1 24.3 23.4 22.6 23.5 2.3 23.5 23.5 23.0 22.1 21.2 20.3 19.4 72 37.0 2.3 16.8 15.9 14.9 13.9 12.9 - - 33.1 2.5 15.3 14.4 13.4 12.4 11.5 - - 1050 67 30.5 2.3 18.7 17.7 16.8 15.8 14.8 13.8 12.9 28.0 2.5 17.7 16.8 15.8 14.8 13.9 12.9 11.9 62 29.5 2.2 22.3 21.4 20.4 19.4 18.4 17.5 16.5 26.1 2.4 21.0 20.0 19.1 18.1 17.1 16.2 15.2 57 27.6 2.2 27.6 27.6 27.1 26.1 25.1 24.2 23.2 24.1 2.4 24.1 24.1 24.1 23.1 22.1 21.1 20.2 72 37.9 2.3 18.3 17.2 16.1 15.0 13.9 - - 33.9 2.5 16.1 15.0 14.0 12.9 11.9 - - 1200 67 31.2 2.4 20.4 19.3 18.2 17.1 16.0 14.9 13.8 28.7 2.5 18.6 17.5 16.5 15.5 14.4 13.4 12.3 62 30.2 2.3 24.3 23.2 22.1 21.0 19.9 18.8 17.7 26.7 2.4 22.0 21.0 19.9 18.9 17.8 16.8 15.7 57 28.2 2.3 28.2 28.2 28.2 27.1 26.0 24.9 23.8 24.6 2.4 24.6 24.6 25.1 24.1 23.0 22.0 20.9 72 40.1 2.3 19.6 18.4 17.2 16.0 14.8 - - 35.1 2.5 17.0 15.8 14.7 13.6 12.5 - - 1350 67 33.0 2.4 21.9 20.6 19.4 18.2 17.0 15.8 14.6 29.7 2.5 19.6 18.5 17.4 16.2 15.1 14.0 12.8 62 31.9 2.2 26.0 24.8 23.6 22.4 21.2 20.0 18.8 27.6 2.4 23.2 22.1 21.0 19.8 18.7 17.6 16.4 57 29.8 2.2 29.8 29.8 29.8 28.6 27.4 26.2 25.0 25.5 2.4 25.5 25.5 25.7 24.6 23.5 22.3 21.2 72 42.2 2.2 20.9 19.6 18.3 17.0 15.6 - - 36.3 2.5 17.9 16.7 15.4 14.2 13.0 - - 1500 67 34.8 2.3 23.3 22.0 20.7 19.4 18.0 16.7 15.4 30.7 2.5 20.7 19.4 18.2 17.0 15.8 14.6 13.4 62 33.6 2.2 27.8 26.5 25.2 23.8 22.5 21.2 19.9 28.6 2.4 24.4 23.2 22.0 20.8 19.6 18.4 17.1 57 31.4 2.2 31.4 31.4 31.4 30.0 28.7 27.4 26.1 26.4 2.4 26.4 26.4 26.4 25.1 23.9 22.7 21.5 95 F 105 F 72 28.4 2.6 13.7 12.8 11.9 11.0 10.0 - - 25.3 2.8 11.0 10.2 9.4 8.6 7.8 - - 900 67 25.0 2.6 16.7 15.8 14.9 13.9 13.0 12.1 11.1 22.0 2.8 13.7 12.9 12.1 11.3 10.5 9.7 8.9 62 22.0 2.5 19.6 18.7 17.8 16.9 15.9 15.0 14.1 19.1 2.7 16.5 15.7 14.9 14.1 13.3 12.5 11.7 57 20.0 2.5 20.0 20.0 20.0 19.1 18.1 17.2 16.3 17.4 2.7 17.4 17.4 17.4 16.6 15.8 15.0 14.2 72 29.2 2.7 13.8 12.8 11.9 10.9 10.0 - - 26.0 2.8 11.3 10.4 9.6 8.7 7.9 - - 1050 67 25.6 2.6 16.7 15.8 14.8 13.9 12.9 12.0 11.0 22.5 2.8 14.1 13.2 12.4 11.5 10.7 9.8 9.0 62 22.6 2.6 19.7 18.7 17.8 16.8 15.8 14.9 13.9 19.6 2.7 16.9 16.1 15.2 14.4 13.5 12.7 11.9 57 20.5 2.5 20.5 20.5 21.0 20.0 19.1 18.1 17.2 17.9 2.7 17.9 17.9 18.6 17.5 16.8 16.1 15.2 72 30.0 2.7 13.8 12.9 11.9 10.9 9.9 - - 26.7 2.9 11.5 10.7 9.8 8.9 8.0 - - 1200 67 26.3 2.6 16.8 15.8 14.8 13.8 12.8 11.8 10.9 23.1 2.8 14.4 13.5 12.6 11.7 10.8 9.9 9.0 62 23.2 2.6 19.7 18.7 17.7 16.7 15.8 14.8 13.8 20.1 2.8 17.3 16.5 15.6 14.7 13.8 12.9 12.0 57 21.1 2.6 21.1 21.1 22.0 21.0 20.0 19.0 18.1 18.3 2.7 18.3 18.3 19.8 18.3 17.8 17.1 16.2 72 30.1 2.7 14.3 13.3 12.2 11.2 10.1 - - 26.7 2.9 11.9 11.0 10.0 9.1 8.2 - - 1350 67 26.5 2.7 17.4 16.3 15.3 14.2 13.2 12.1 11.1 23.1 2.8 14.9 13.9 13.0 12.0 11.1 10.1 9.2 62 23.4 2.6 20.4 19.3 18.3 17.2 16.2 15.2 14.1 20.1 2.8 17.9 16.9 16.0 15.1 14.1 13.2 12.2 57 21.2 2.6 21.2 21.2 21.7 20.6 19.6 18.5 17.5 18.4 2.8 18.4 18.4 19.1 17.9 17.1 16.3 15.3 72 30.3 2.7 14.8 13.7 12.6 11.5 10.4 - - 26.7 2.9 12.3 11.3 10.3 9.3 8.3 - - 1500 67 26.7 2.7 18.0 16.9 15.8 14.6 13.5 12.4 11.3 23.2 2.9 15.3 14.3 13.3 12.3 11.3 10.4 9.4 62 23.5 2.6 21.1 20.0 18.9 17.8 16.6 15.5 14.4 20.2 2.8 18.4 17.4 16.4 15.4 14.5 13.5 12.5 57 21.3 2.6 21.3 21.3 21.3 20.2 19.1 18.0 16.9 18.4 2.8 18.4 18.4 18.4 17.4 16.4 15.4 14.4 115 F 125 F 72 22.2 3.0 8.3 7.6 6.9 6.2 5.6 - - 19.1 3.2 5.5 5.0 4.4 3.9 3.3 - - 900 67 19.0 2.9 10.8 10.1 9.4 8.7 8.0 7.4 6.7 16.0 3.1 7.8 7.2 6.7 6.1 5.6 5.0 4.5 62 16.2 2.9 13.4 12.8 12.1 11.4 10.7 10.0 9.4 13.2 3.0 10.3 9.8 9.2 8.7 8.1 7.6 7.0 57 14.9 2.8 14.9 14.9 14.9 14.2 13.5 12.8 12.2 12.3 3.0 12.3 12.3 12.3 11.7 11.2 10.6 10.1 72 22.8 3.0 8.8 8.0 7.3 6.5 5.8 - - 19.6 3.2 6.3 5.6 5.0 4.4 3.7 - - 1050 67 19.4 3.0 11.4 10.6 9.9 9.2 8.4 7.7 6.9 16.3 3.1 8.7 8.1 7.4 6.8 6.2 5.6 4.9 62 16.6 2.9 14.2 13.5 12.7 12.0 11.3 10.5 9.8 13.5 3.1 11.5 10.8 10.2 9.6 9.0 8.3 7.7 57 15.2 2.9 15.2 15.2 16.2 14.9 14.6 14.0 13.3 12.6 3.0 12.6 12.6 12.6 12.3 12.3 11.9 11.3 72 23.4 3.1 9.3 8.5 7.7 6.9 6.1 - - 20.1 3.3 7.0 6.3 5.6 4.9 4.2 - - 1200 67 19.9 3.0 12.0 11.2 10.4 9.6 8.8 8.0 7.2 16.7 3.2 9.6 8.9 8.2 7.5 6.8 6.1 5.4 62 17.0 2.9 15.0 14.2 13.4 12.6 11.8 11.0 10.2 13.9 3.1 12.6 11.9 11.2 10.5 9.8 9.1 8.4 57 15.6 2.9 15.6 15.6 17.6 15.6 15.6 15.2 14.4 12.9 3.1 12.9 12.9 12.9 12.9 12.9 12.9 12.5 1350 1500 72 23.2 3.1 9.5 8.7 7.8 7.0 6.2 - - 19.8 3.3 7.1 6.4 5.6 4.9 4.2 - - 67 19.8 3.0 12.3 11.5 10.7 9.8 9.0 8.1 7.3 16.5 3.2 9.8 9.1 8.3 7.6 6.9 6.1 5.4 62 16.9 2.9 15.4 14.5 13.7 12.9 12.0 11.2 10.3 13.7 3.1 12.9 12.1 11.4 10.7 9.9 9.2 8.5 57 15.5 2.9 15.5 15.5 16.5 15.1 14.7 14.0 13.2 12.7 3.1 12.7 12.7 12.7 12.3 12.2 11.7 11.0 72 23.1 3.1 9.8 8.9 8.0 7.1 6.3 - - 19.5 3.3 7.3 6.5 5.7 5.0 4.2 - - 67 19.7 3.0 12.7 11.8 10.9 10.0 9.2 8.3 7.4 16.3 3.2 10.0 9.2 8.5 7.7 7.0 6.2 5.4 62 16.8 3.0 15.8 14.9 14.0 13.1 12.3 11.4 10.5 13.5 3.1 13.1 12.4 11.6 10.8 10.1 9.3 8.6 57 15.5 2.9 15.5 15.5 15.5 14.6 13.7 12.8 12.0 12.5 3.1 12.5 12.5 12.5 11.8 11.0 10.2 9.5 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. 18 Johnson Controls Unitary Products

TABLE 18: DK-04 COOLING CAPACITIES (4 TON) - NORMAL MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 57.4 2.8 33.0 30.1 27.2 24.2 21.3 - - 53.3 3.1 31.7 28.9 26.0 23.1 20.3 - - 1200 67 53.2 2.8 39.3 36.3 33.4 30.5 27.6 24.6 21.7 49.2 3.1 37.5 34.6 31.8 28.9 26.0 23.2 20.3 62 48.8 2.8 48.1 43.9 41.0 38.1 35.1 32.2 29.3 45.2 3.0 44.9 42.0 39.2 36.3 33.4 30.6 27.7 57 48.4 2.8 48.4 45.5 42.6 39.6 36.7 33.8 30.8 44.8 3.0 44.8 42.6 39.8 36.9 34.0 31.2 28.3 72 58.5 2.8 36.3 33.0 29.6 26.3 22.9 - - 54.5 3.1 34.9 31.6 28.3 25.1 21.8 - - 1400 67 54.2 2.8 43.1 39.8 36.4 33.1 29.7 26.4 23.0 50.3 3.1 41.2 37.9 34.6 31.4 28.1 24.8 21.5 62 49.7 2.8 49.4 47.3 44.7 41.3 38.0 34.6 31.3 46.3 3.1 46.1 44.7 42.7 39.4 36.1 32.9 29.6 57 49.3 2.8 49.3 47.9 46.4 43.0 39.7 36.3 33.0 45.9 3.1 45.9 44.8 43.3 40.1 36.8 33.5 30.2 72 59.6 2.9 39.6 35.9 32.1 28.3 24.5 - - 55.8 3.1 38.1 34.4 30.7 27.0 23.3 - - 1600 67 55.2 2.9 47.0 43.2 39.5 35.7 31.9 28.1 24.3 51.5 3.1 44.9 41.2 37.5 33.8 30.1 26.4 22.7 62 50.7 2.8 50.7 50.7 48.4 44.6 40.8 37.0 33.2 47.4 3.1 47.4 47.4 46.2 42.5 38.8 35.2 31.5 57 50.2 2.8 50.2 50.2 50.2 46.5 42.7 38.9 35.1 46.9 3.1 46.9 46.9 46.9 43.2 39.5 35.9 32.2 72 61.7 2.8 42.3 38.2 34.1 30.0 25.9 - - 56.9 3.1 40.7 36.7 32.6 28.6 24.6 - - 1800 67 57.2 2.8 50.5 46.1 42.0 37.9 33.8 29.7 25.6 52.5 3.1 47.9 43.9 39.9 35.9 31.9 27.8 23.8 62 52.5 2.8 52.5 52.5 51.3 47.2 43.1 39.0 34.9 48.3 3.1 48.3 48.3 47.7 43.7 39.7 35.7 31.7 57 52.0 2.8 52.0 52.0 52.0 47.9 43.8 39.7 35.6 47.8 3.1 47.8 47.8 47.8 43.8 39.8 35.8 31.8 72 63.9 2.8 45.0 40.6 36.2 31.8 27.4 - - 58.0 3.1 43.3 38.9 34.6 30.3 25.9 - - 2000 67 59.1 2.8 54.0 48.9 44.5 40.1 35.7 31.3 26.9 53.5 3.1 51.0 46.6 42.3 37.9 33.6 29.3 24.9 62 54.3 2.8 54.3 54.3 54.3 49.8 45.4 41.0 36.6 49.2 3.1 49.2 49.2 49.2 44.9 40.5 36.2 31.8 57 53.8 2.8 53.8 53.8 53.8 49.4 45.0 40.6 36.2 48.8 3.1 48.8 48.8 48.8 44.4 40.1 35.7 31.4 95 F 105 F 72 49.1 3.4 30.5 27.7 24.8 22.0 19.2 - - 46.1 3.7 27.8 25.0 22.2 19.3 16.5 - - 1200 67 45.2 3.4 35.8 33.0 30.1 27.3 24.5 21.7 18.9 41.6 3.6 34.2 31.4 28.5 25.7 22.9 20.0 17.2 62 41.7 3.3 41.7 40.2 37.4 34.6 31.7 28.9 26.1 38.4 3.5 38.4 36.7 33.9 31.1 28.2 25.4 22.6 57 41.2 3.3 41.2 39.8 37.0 34.2 31.4 28.5 25.7 38.3 3.6 38.3 36.6 33.8 30.9 28.1 25.3 22.4 72 50.5 3.4 33.5 30.3 27.1 23.9 20.7 - - 47.2 3.7 30.6 27.4 24.2 20.9 17.7 - - 1400 67 46.5 3.4 39.2 36.0 32.8 29.6 26.4 23.2 20.0 42.5 3.6 37.5 34.4 31.1 27.9 24.7 21.4 18.2 62 42.9 3.3 42.9 42.1 40.7 37.5 34.3 31.1 27.9 39.3 3.6 39.3 38.4 37.0 33.8 30.6 27.3 24.1 57 42.4 3.3 42.4 41.7 40.3 37.1 33.9 30.7 27.5 39.1 3.6 39.1 38.3 36.9 33.6 30.4 27.2 23.9 72 51.9 3.4 36.5 32.9 29.3 25.7 22.1 - - 48.2 3.7 33.5 29.8 26.2 22.6 18.9 - - 1600 67 47.8 3.4 42.7 39.1 35.5 31.9 28.4 24.8 21.2 43.4 3.7 40.9 37.4 33.8 30.1 26.5 22.9 19.2 62 44.1 3.3 44.1 44.1 44.1 40.5 36.9 33.3 29.7 40.1 3.6 40.1 40.1 40.1 36.5 32.9 29.2 25.6 57 43.6 3.4 43.6 43.6 43.6 40.0 36.4 32.8 29.2 40.0 3.6 40.0 40.0 40.0 36.3 32.7 29.1 25.4 72 52.0 3.4 39.0 35.1 31.1 27.2 23.3 - - 48.1 3.8 35.8 31.9 27.9 23.9 19.9 - - 1800 67 47.8 3.4 45.3 41.7 37.8 33.9 29.9 26.0 22.0 43.4 3.7 42.1 39.5 35.9 31.9 28.0 24.0 20.0 62 44.1 3.4 44.1 44.1 44.1 40.2 36.3 32.3 28.4 40.1 3.6 40.1 40.1 40.1 36.1 32.1 28.2 24.2 57 43.7 3.4 43.7 43.7 43.7 39.7 35.8 31.9 27.9 39.9 3.7 39.9 39.9 39.9 35.9 32.0 28.0 24.0 72 52.1 3.5 41.6 37.3 33.0 28.7 24.5 - - 48.0 3.8 38.2 33.9 29.6 25.2 20.9 - - 2000 67 47.9 3.4 47.9 44.3 40.0 35.8 31.5 27.2 22.9 43.3 3.7 43.3 41.5 38.1 33.8 29.4 25.1 20.8 62 44.2 3.4 44.2 44.2 44.2 39.9 35.6 31.3 27.1 40.0 3.7 40.0 40.0 40.0 35.7 31.4 27.1 22.8 57 43.7 3.4 43.7 43.7 43.7 39.4 35.2 30.9 26.6 39.8 3.7 39.8 39.8 39.8 35.5 31.2 26.9 22.6 115 F 125 F 72 43.1 4.0 25.2 22.3 19.5 16.6 13.8 - - 40.2 4.2 22.5 19.6 16.8 13.9 11.0 - - 1200 67 38.0 3.9 32.6 29.8 26.9 24.1 21.2 18.4 15.5 34.3 4.1 31.0 28.2 25.3 22.4 19.6 16.7 13.8 62 35.2 3.8 35.2 33.3 30.5 27.6 24.8 21.9 19.1 31.9 4.0 31.9 29.9 27.0 24.1 21.3 18.4 15.5 57 35.3 3.8 35.3 33.4 30.6 27.7 24.9 22.0 19.2 32.3 4.1 32.3 30.2 27.4 24.5 21.6 18.8 15.9 72 43.8 4.0 27.8 24.6 21.3 18.0 14.8 - - 40.4 4.3 25.0 21.7 18.4 15.1 11.8 - - 1400 67 38.5 3.9 35.8 32.7 29.5 26.2 22.9 19.7 16.4 34.5 4.2 34.1 31.1 27.8 24.5 21.2 17.9 14.6 62 35.7 3.8 35.7 34.8 33.3 30.1 26.8 23.5 20.3 32.1 4.1 32.1 31.1 29.6 26.3 23.0 19.7 16.4 57 35.8 3.9 35.8 34.9 33.4 30.2 26.9 23.7 20.4 32.5 4.1 32.5 31.5 30.0 26.7 23.4 20.1 16.8 72 44.4 4.0 30.5 26.8 23.1 19.5 15.8 - - 40.6 4.3 27.5 23.8 20.1 16.3 12.6 - - 1600 67 39.1 3.9 39.1 35.7 32.0 28.3 24.6 20.9 17.3 34.7 4.2 34.7 34.0 30.2 26.5 22.8 19.0 15.3 62 36.2 3.9 36.2 36.2 36.2 32.5 28.8 25.2 21.5 32.3 4.1 32.3 32.3 32.3 28.5 24.8 21.1 17.4 57 36.3 3.9 36.3 36.3 36.3 32.6 29.0 25.3 21.6 32.7 4.2 32.7 32.7 32.7 29.0 25.2 21.5 17.8 1800 2000 72 44.2 4.1 32.6 28.6 24.6 20.6 16.6 - - 40.3 4.4 29.4 25.4 21.3 17.3 13.3 - - 67 38.9 4.0 38.9 37.2 34.0 30.0 26.0 22.0 18.0 34.4 4.3 34.4 34.4 32.2 28.1 24.1 20.0 16.0 62 36.0 3.9 36.0 36.0 36.0 32.0 28.0 24.0 20.0 32.0 4.2 32.0 32.0 32.0 27.9 23.9 19.8 15.8 57 36.2 3.9 36.2 36.2 36.2 32.1 28.1 24.1 20.1 32.4 4.2 32.4 32.4 32.4 28.4 24.3 20.3 16.2 72 44.0 4.1 34.8 30.4 26.1 21.8 17.4 - - 39.9 4.5 31.4 27.0 22.6 18.3 13.9 - - 67 38.7 4.0 38.7 38.7 36.1 31.7 27.4 23.1 18.7 34.1 4.3 34.1 34.1 34.1 29.7 25.4 21.0 16.6 62 35.8 4.0 35.8 35.8 35.8 31.5 27.2 22.8 18.5 31.7 4.2 31.7 31.7 31.7 27.3 22.9 18.6 14.2 57 36.0 4.0 36.0 36.0 36.0 31.6 27.3 23.0 18.6 32.1 4.3 32.1 32.1 32.1 27.7 23.4 19.0 14.6 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products 19

TABLE 19: DK-04 COOLING CAPACITIES (4 TON) - REHEAT MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 41.4 2.8 18.5 17.3 16.0 14.7 13.5 - - 39.0 3.0 17.8 16.6 15.4 14.1 12.9 - - 1200 67 37.6 2.7 24.2 22.9 21.7 20.4 19.1 17.9 16.6 35.1 2.9 22.7 21.5 20.3 19.0 17.8 16.6 15.4 62 33.8 2.7 26.7 25.5 24.2 22.9 21.7 20.4 19.1 31.8 2.9 25.9 24.7 23.4 22.2 21.0 19.8 18.5 57 30.4 2.6 30.4 29.3 28.0 26.8 25.5 24.3 23.0 28.9 2.8 28.9 28.3 27.1 25.8 24.6 23.4 22.2 72 43.7 2.8 20.4 19.0 17.6 16.2 14.8 - - 40.8 3.0 19.4 18.0 16.7 15.3 13.9 - - 1400 67 39.6 2.7 26.7 25.2 23.8 22.4 21.0 19.6 18.1 36.7 2.9 24.7 23.3 22.0 20.6 19.2 17.8 16.5 62 35.6 2.7 29.5 28.0 26.6 25.2 23.8 22.4 20.9 33.3 2.9 28.2 26.8 25.4 24.0 22.7 21.3 19.9 57 32.0 2.7 32.0 31.5 30.9 29.4 28.0 26.6 25.2 30.3 2.8 30.3 29.9 29.3 28.0 26.6 25.2 23.8 72 45.9 2.8 22.4 20.8 19.2 17.6 16.0 - - 42.6 3.1 21.0 19.5 17.9 16.4 14.9 - - 1600 67 41.7 2.7 29.1 27.6 26.0 24.4 22.8 21.2 19.6 38.4 3.0 26.7 25.2 23.7 22.1 20.6 19.1 17.5 62 37.4 2.7 32.2 30.6 29.1 27.5 25.9 24.3 22.7 34.8 2.9 30.5 28.9 27.4 25.9 24.3 22.8 21.3 57 33.7 2.7 33.7 33.7 33.7 32.1 30.5 28.9 27.4 31.6 2.9 31.6 31.6 31.6 30.1 28.5 27.0 25.5 72 47.4 2.8 23.1 21.4 19.7 18.0 16.3 - - 43.9 3.1 21.9 20.3 18.6 17.0 15.4 - - 1800 67 43.0 2.8 30.1 28.3 26.6 24.9 23.2 21.5 19.8 39.5 3.0 27.9 26.2 24.6 23.0 21.3 19.7 18.0 62 38.7 2.7 33.2 31.5 29.8 28.1 26.4 24.7 23.0 35.8 3.0 31.8 30.1 28.5 26.8 25.2 23.5 21.9 57 34.8 2.7 34.8 34.8 34.8 33.1 31.4 29.7 28.0 32.5 2.9 32.5 32.5 32.5 30.9 29.2 27.6 25.9 72 48.9 2.9 23.8 22.0 20.2 18.3 16.5 - - 45.1 3.1 22.9 21.1 19.3 17.6 15.8 - - 2000 67 44.4 2.8 31.0 29.1 27.3 25.5 23.6 21.8 20.0 40.6 3.0 29.0 27.3 25.5 23.8 22.0 20.2 18.5 62 39.9 2.8 34.1 32.3 30.5 28.7 26.8 25.0 23.2 36.8 3.0 33.0 31.3 29.5 27.8 26.0 24.3 22.5 57 35.9 2.7 35.9 35.9 35.9 34.1 32.3 30.4 28.6 33.4 2.9 33.4 33.4 33.4 31.7 29.9 28.2 26.4 95 F 105 F 72 36.6 3.2 17.1 15.9 14.7 13.5 12.3 - - 33.4 3.4 15.4 14.3 13.2 12.0 10.9 - - 1200 67 32.6 3.1 21.2 20.0 18.9 17.7 16.5 15.3 14.1 30.0 3.3 19.5 18.4 17.3 16.1 15.0 13.9 12.7 62 29.9 3.1 25.1 23.9 22.7 21.5 20.3 19.1 18.0 27.1 3.2 23.2 22.0 20.9 19.8 18.6 17.5 16.4 57 27.5 3.0 27.5 27.2 26.1 24.9 23.7 22.5 21.3 25.6 3.2 25.6 25.0 23.9 22.8 21.6 20.5 19.4 72 38.0 3.3 18.4 17.0 15.7 14.4 13.0 - - 34.7 3.5 16.7 15.4 14.1 12.9 11.6 - - 1400 67 33.8 3.2 22.8 21.4 20.1 18.8 17.4 16.1 14.8 31.2 3.4 21.1 19.8 18.6 17.3 16.0 14.7 13.5 62 31.1 3.1 26.9 25.5 24.2 22.9 21.5 20.2 18.9 28.2 3.3 25.1 23.8 22.5 21.2 19.9 18.7 17.4 57 28.5 3.0 28.5 28.4 27.8 26.5 25.1 23.8 22.5 26.6 3.2 26.6 26.3 25.7 24.4 23.2 21.9 20.6 72 39.3 3.3 19.6 18.2 16.7 15.2 13.7 - - 36.0 3.5 18.0 16.6 15.1 13.7 12.3 - - 1600 67 35.1 3.2 24.3 22.8 21.4 19.9 18.4 16.9 15.4 32.3 3.4 22.7 21.3 19.9 18.5 17.0 15.6 14.2 62 32.2 3.1 28.7 27.2 25.7 24.2 22.8 21.3 19.8 29.2 3.3 26.9 25.5 24.1 22.7 21.3 19.8 18.4 57 29.5 3.1 29.5 29.5 29.5 28.1 26.6 25.1 23.6 27.5 3.3 27.5 27.5 27.5 26.1 24.7 23.3 21.8 72 40.3 3.3 20.8 19.2 17.6 16.0 14.4 - - 36.7 3.6 19.1 17.6 16.0 14.5 13.0 - - 1800 67 35.9 3.2 25.7 24.1 22.6 21.0 19.4 17.8 16.2 33.0 3.4 24.1 22.6 21.1 19.5 18.0 16.5 14.9 62 33.0 3.2 30.3 28.7 27.1 25.6 24.0 22.4 20.8 29.8 3.4 28.2 27.0 25.5 24.0 22.5 20.9 19.4 57 30.2 3.1 30.2 30.2 30.2 28.7 27.1 25.5 23.9 28.1 3.3 28.1 28.1 28.1 26.5 25.0 23.5 21.9 72 41.2 3.4 21.9 20.2 18.5 16.8 15.2 - - 37.3 3.6 20.2 18.6 16.9 15.3 13.7 - - 2000 67 36.8 3.3 27.1 25.4 23.7 22.1 20.4 18.7 17.0 33.6 3.5 25.5 23.9 22.2 20.6 19.0 17.3 15.7 62 33.7 3.2 32.0 30.3 28.6 26.9 25.2 23.5 21.8 30.4 3.4 29.5 28.6 26.9 25.3 23.7 22.0 20.4 57 30.9 3.1 30.9 30.9 30.9 29.3 27.6 25.9 24.2 28.6 3.3 28.6 28.6 28.6 27.0 25.3 23.7 22.1 115 F 125 F 72 30.2 3.7 13.7 12.7 11.6 10.5 9.4 - - 27.0 3.9 12.1 11.0 10.0 9.0 8.0 - - 1200 67 27.4 3.5 17.8 16.7 15.7 14.6 13.5 12.4 11.4 24.8 3.7 16.1 15.1 14.1 13.0 12.0 11.0 10.0 62 24.3 3.4 21.3 20.2 19.1 18.0 17.0 15.9 14.8 21.5 3.6 19.4 18.4 17.3 16.3 15.3 14.3 13.2 57 23.7 3.4 23.7 22.8 21.7 20.6 19.6 18.5 17.4 21.8 3.6 21.8 20.6 19.6 18.5 17.5 16.5 15.5 72 31.4 3.7 15.0 13.8 12.6 11.4 10.2 - - 28.1 3.9 13.4 12.2 11.1 9.9 8.7 - - 1400 67 28.5 3.6 19.5 18.3 17.0 15.8 14.6 13.4 12.1 25.8 3.8 17.8 16.7 15.5 14.3 13.2 12.0 10.8 62 25.3 3.5 23.2 22.0 20.8 19.6 18.4 17.1 15.9 22.4 3.7 21.4 20.3 19.1 17.9 16.8 15.6 14.4 57 24.6 3.4 24.6 24.2 23.6 22.4 21.2 20.0 18.7 22.7 3.6 22.7 22.1 21.6 20.4 19.2 18.1 16.9 72 32.6 3.8 16.4 15.0 13.6 12.3 10.9 - - 29.2 4.0 14.7 13.4 12.1 10.8 9.5 - - 1600 67 29.6 3.6 21.1 19.8 18.4 17.0 15.7 14.3 12.9 26.9 3.9 19.5 18.2 16.9 15.6 14.3 13.0 11.7 62 26.3 3.5 25.2 23.8 22.5 21.1 19.8 18.4 17.0 23.3 3.7 23.3 22.2 20.9 19.6 18.3 16.9 15.6 57 25.5 3.5 25.5 25.5 25.5 24.2 22.8 21.4 20.1 23.5 3.7 23.5 23.5 23.5 22.2 20.9 19.6 18.3 1800 2000 72 33.0 3.8 17.4 15.9 14.5 13.0 11.5 - - 29.4 4.0 15.7 14.3 12.9 11.5 10.1 - - 67 30.0 3.7 22.5 21.0 19.6 18.1 16.6 15.1 13.7 27.0 3.9 20.9 19.5 18.1 16.6 15.2 13.8 12.4 62 26.6 3.5 26.1 25.4 23.9 22.4 20.9 19.5 18.0 23.5 3.7 23.5 23.5 22.3 20.8 19.4 18.0 16.6 57 25.9 3.5 25.9 25.9 25.9 24.4 22.9 21.5 20.0 23.7 3.7 23.7 23.7 23.7 22.3 20.9 19.5 18.1 72 33.5 3.8 18.5 16.9 15.3 13.7 12.2 - - 29.6 4.0 16.7 15.2 13.7 12.2 10.7 - - 67 30.4 3.7 23.9 22.3 20.7 19.1 17.5 16.0 14.4 27.2 3.9 22.2 20.7 19.2 17.7 16.1 14.6 13.1 62 27.0 3.6 27.0 26.9 25.3 23.7 22.1 20.5 19.0 23.6 3.7 23.6 23.6 23.6 22.1 20.6 19.1 17.5 57 26.2 3.5 26.2 26.2 26.2 24.7 23.1 21.5 19.9 23.9 3.7 23.9 23.9 23.9 22.4 20.8 19.3 17.8 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. 20 Johnson Controls Unitary Products

TABLE 20: DK-05 COOLING CAPACITIES (5 TON) - NORMAL MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 68.8 3.4 38.3 34.9 31.6 28.3 24.9 - - 65.9 3.8 36.7 33.4 30.0 26.7 23.3 - - 1500 67 63.4 3.4 47.2 43.9 40.6 37.2 33.9 30.6 27.2 60.3 3.8 45.8 42.4 39.1 35.8 32.4 29.1 25.7 62 57.5 3.3 57.0 52.9 49.6 46.3 42.9 39.6 36.3 54.9 3.8 54.7 51.3 48.0 44.6 41.3 37.9 34.6 57 56.0 3.3 56.0 56.0 54.4 51.1 47.7 44.4 41.0 53.7 3.7 53.7 53.7 51.8 48.4 45.1 41.7 38.4 72 70.4 3.4 40.8 36.9 33.0 29.2 25.3 - - 67.2 3.9 39.1 35.2 31.4 27.5 23.7 - - 1750 67 64.9 3.4 50.1 46.2 42.4 38.5 34.7 30.8 26.9 61.6 3.8 48.5 44.7 40.9 37.0 33.2 29.3 25.5 62 58.8 3.3 58.6 56.0 51.8 48.0 44.1 40.3 36.4 56.1 3.8 55.9 54.0 50.1 46.3 42.5 38.6 34.8 57 57.3 3.3 57.3 57.3 56.8 53.0 49.1 45.3 41.4 54.9 3.8 54.9 54.9 54.1 50.2 46.4 42.6 38.7 72 71.9 3.4 43.2 38.8 34.4 30.1 25.7 - - 68.6 3.9 41.4 37.1 32.7 28.4 24.1 - - 2000 67 66.3 3.4 53.0 48.6 44.2 39.8 35.4 31.1 26.7 62.9 3.8 51.3 47.0 42.6 38.3 33.9 29.6 25.3 62 60.2 3.3 60.2 59.0 54.1 49.7 45.3 40.9 36.5 57.2 3.8 57.2 56.6 52.3 48.0 43.6 39.3 34.9 57 58.6 3.3 58.6 58.6 59.3 54.9 50.5 46.1 41.7 56.0 3.8 56.0 56.0 56.4 52.1 47.7 43.4 39.1 72 73.5 3.4 47.2 42.5 37.9 33.2 28.6 - - 70.2 3.9 45.2 40.6 36.0 31.3 26.7 - - 2250 67 67.8 3.4 57.9 53.2 48.6 43.9 39.3 34.7 30.0 64.3 3.8 56.1 51.5 46.8 42.2 37.6 32.9 28.3 62 61.5 3.3 61.5 60.9 58.4 53.8 49.1 44.5 39.9 58.5 3.8 58.5 58.2 56.0 51.4 46.8 42.2 37.5 57 59.9 3.3 59.9 59.9 60.3 55.6 51.0 46.3 41.7 57.2 3.8 57.2 57.2 57.5 52.8 48.2 43.6 38.9 72 75.1 3.5 51.1 46.2 41.3 36.4 31.5 - - 71.7 3.9 49.0 44.1 39.2 34.3 29.4 - - 2500 67 69.3 3.4 62.8 57.9 53.0 48.1 43.1 38.2 33.3 65.7 3.8 60.9 55.9 51.0 46.1 41.2 36.3 31.4 62 62.8 3.3 62.8 62.8 62.8 57.9 53.0 48.1 43.2 59.8 3.8 59.8 59.8 59.8 54.9 49.9 45.0 40.1 57 61.2 3.3 61.2 61.2 61.2 56.3 51.4 46.5 41.6 58.5 3.8 58.5 58.5 58.5 53.6 48.6 43.7 38.8 95 F 105 F 72 63.0 4.3 35.1 31.8 28.4 25.1 21.7 - - 59.5 4.8 33.7 30.4 27.1 23.8 20.5 - - 1500 67 57.3 4.2 44.3 41.0 37.6 34.3 30.9 27.6 24.2 53.8 4.7 42.8 39.5 36.1 32.8 29.5 26.2 22.9 62 52.4 4.2 52.4 49.7 46.3 43.0 39.6 36.3 32.9 49.5 4.7 49.5 48.1 45.2 41.9 38.6 35.2 31.9 57 51.4 4.2 51.4 51.4 49.1 45.8 42.4 39.1 35.7 48.8 4.7 48.8 48.8 46.8 43.4 40.1 36.8 33.5 72 64.1 4.3 37.4 33.6 29.7 25.9 22.1 - - 60.4 4.8 35.8 32.0 28.2 24.4 20.7 - - 1750 67 58.3 4.2 47.0 43.2 39.3 35.5 31.7 27.8 24.0 54.7 4.8 45.2 41.4 37.6 33.9 30.1 26.3 22.5 62 53.3 4.2 53.3 52.0 48.4 44.6 40.8 37.0 33.1 50.3 4.7 50.3 49.6 47.1 43.3 39.5 35.8 32.0 57 52.4 4.2 52.4 52.4 51.4 47.5 43.7 39.9 36.0 49.6 4.7 49.6 49.6 48.7 44.9 41.2 37.4 33.6 72 65.3 4.3 39.6 35.3 31.0 26.7 22.4 - - 61.4 4.8 37.8 33.6 29.4 25.1 20.9 - - 2000 67 59.4 4.3 49.6 45.3 41.0 36.7 32.4 28.1 23.8 55.5 4.8 47.6 43.4 39.1 34.9 30.7 26.5 22.2 62 54.3 4.2 54.3 54.3 50.5 46.2 41.9 37.6 33.3 51.0 4.7 51.0 51.0 49.0 44.7 40.5 36.3 32.0 57 53.3 4.2 53.3 53.3 53.6 49.3 45.0 40.7 36.4 50.4 4.7 50.4 50.4 50.6 46.4 42.2 38.0 33.7 72 66.8 4.3 43.3 38.7 34.1 29.5 24.8 - - 62.7 4.8 41.4 36.9 32.3 27.8 23.3 - - 2250 67 60.7 4.3 54.3 49.7 45.1 40.4 35.8 31.2 26.6 56.7 4.8 52.0 47.7 43.1 38.6 34.0 29.5 25.0 62 55.5 4.2 55.5 55.5 53.6 49.0 44.4 39.8 35.2 52.1 4.7 52.1 52.1 51.1 46.5 42.0 37.5 32.9 57 54.5 4.2 54.5 54.5 54.6 50.0 45.4 40.8 36.2 51.5 4.7 51.5 51.5 51.6 47.1 42.5 38.0 33.4 72 68.3 4.3 47.0 42.0 37.1 32.2 27.3 - - 64.0 4.8 45.0 40.2 35.3 30.5 25.6 - - 2500 67 62.1 4.3 58.9 54.0 49.1 44.2 39.2 34.3 29.4 57.9 4.8 56.3 51.9 47.1 42.2 37.4 32.5 27.7 62 56.7 4.2 56.7 56.7 56.7 51.8 46.9 42.0 37.0 53.2 4.7 53.2 53.2 53.2 48.4 43.5 38.7 33.8 57 55.7 4.2 55.7 55.7 55.7 50.8 45.9 40.9 36.0 52.6 4.7 52.6 52.6 52.6 47.7 42.8 38.0 33.1 115 F 125 F 72 56.0 5.3 32.3 29.0 25.7 22.5 19.2 - - 52.5 5.9 30.9 27.6 24.4 21.1 17.9 - - 1500 67 50.4 5.3 41.2 37.9 34.6 31.4 28.1 24.8 21.5 46.9 5.8 39.7 36.4 33.2 29.9 26.6 23.4 20.1 62 46.6 5.2 46.6 46.6 44.0 40.8 37.5 34.2 30.9 43.7 5.7 43.7 43.7 42.9 39.6 36.4 33.1 29.9 57 46.3 5.2 46.3 46.3 44.4 41.1 37.8 34.5 31.2 43.7 5.7 43.7 43.7 42.0 38.7 35.5 32.2 29.0 72 56.7 5.3 34.2 30.4 26.7 23.0 19.3 - - 53.0 5.9 32.5 28.9 25.2 21.5 17.9 - - 1750 67 51.0 5.3 43.4 39.7 35.9 32.2 28.5 24.8 21.1 47.4 5.8 41.6 37.9 34.3 30.6 26.9 23.3 19.6 62 47.2 5.2 47.2 47.2 45.7 42.0 38.3 34.5 30.8 44.1 5.7 44.1 44.1 44.1 40.7 37.0 33.3 29.7 57 46.9 5.2 46.9 46.9 46.0 42.3 38.6 34.9 31.2 44.1 5.7 44.1 44.1 43.4 39.7 36.1 32.4 28.7 72 57.4 5.3 36.0 31.8 27.7 23.5 19.4 - - 53.5 5.9 34.2 30.1 26.0 21.9 17.9 - - 2000 67 51.7 5.3 45.6 41.4 37.3 33.1 28.9 24.8 20.6 47.8 5.8 43.5 39.4 35.4 31.3 27.2 23.1 19.0 62 47.8 5.2 47.8 47.8 47.4 43.2 39.1 34.9 30.7 44.5 5.7 44.5 44.5 44.5 41.7 37.6 33.5 29.5 57 47.5 5.2 47.5 47.5 47.7 43.6 39.4 35.3 31.1 44.6 5.8 44.6 44.6 44.6 40.7 36.6 32.6 28.5 2250 2500 72 58.6 5.4 39.5 35.1 30.6 26.1 21.7 - - 54.5 5.9 37.7 33.3 28.9 24.5 20.1 - - 67 52.7 5.3 49.7 45.6 41.2 36.7 32.2 27.8 23.3 48.7 5.8 47.3 43.6 39.2 34.8 30.4 26.0 21.7 62 48.8 5.2 48.8 48.8 48.5 44.1 39.6 35.1 30.7 45.4 5.8 45.4 45.4 45.4 41.6 37.2 32.8 28.4 57 48.4 5.2 48.4 48.4 48.6 44.1 39.6 35.2 30.7 45.4 5.8 45.4 45.4 45.4 41.1 36.7 32.3 27.9 72 59.7 5.4 43.1 38.3 33.5 28.7 23.9 - - 55.5 5.9 41.1 36.4 31.7 27.0 22.3 - - 67 53.7 5.3 53.7 49.9 45.1 40.3 35.5 30.8 26.0 49.6 5.8 49.6 47.8 43.1 38.4 33.7 29.0 24.3 62 49.7 5.3 49.7 49.7 49.7 44.9 40.2 35.4 30.6 46.2 5.8 46.2 46.2 46.2 41.5 36.8 32.1 27.4 57 49.4 5.3 49.4 49.4 49.4 44.6 39.8 35.1 30.3 46.2 5.8 46.2 46.2 46.2 41.5 36.8 32.1 27.4 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products 21

TABLE 21: DK-05 COOLING CAPACITIES (5 TON) - REHEAT MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 49.3 3.4 35.4 33.4 31.3 29.3 27.3 - - 46.1 3.7 27.8 26.2 24.6 23.0 21.3 - - 1500 67 45.3 3.3 42.0 40.0 38.0 35.9 33.9 31.9 29.9 42.2 3.7 33.2 31.6 30.0 28.4 26.7 25.1 23.5 62 40.9 3.3 47.9 46.4 44.3 42.3 40.3 38.3 36.2 38.3 3.7 38.3 36.9 35.3 33.6 32.0 30.4 28.8 57 36.1 3.2 36.1 36.7 38.0 35.9 33.9 31.9 29.9 34.6 3.6 34.6 34.6 34.6 33.0 31.4 29.8 28.1 72 49.9 3.3 30.4 28.5 26.7 24.9 23.1 - - 47.2 3.7 25.9 24.2 22.6 21.0 19.4 - - 1750 67 45.9 3.3 36.0 34.2 32.3 30.5 28.7 26.8 25.0 43.1 3.7 30.8 29.2 27.6 26.0 24.4 22.8 21.2 62 41.4 3.2 41.1 39.5 37.7 35.9 34.0 32.2 30.4 39.2 3.7 35.6 34.1 32.5 30.9 29.2 27.6 26.0 57 36.6 3.2 36.6 36.9 37.1 35.2 33.4 31.6 29.7 35.4 3.6 35.4 35.4 34.8 33.2 31.6 30.0 28.4 72 50.6 3.3 25.4 23.7 22.1 20.5 18.8 - - 48.2 3.7 23.9 22.3 20.7 19.1 17.5 - - 2000 67 46.5 3.2 30.0 28.3 26.7 25.0 23.4 21.8 20.1 44.1 3.7 28.4 26.8 25.2 23.6 22.0 20.4 18.8 62 41.9 3.2 34.3 32.7 31.0 29.4 27.8 26.1 24.5 40.0 3.7 32.9 31.3 29.7 28.1 26.5 24.9 23.3 57 37.0 3.1 37.0 37.1 36.2 34.5 32.9 31.3 29.6 36.2 3.6 36.2 36.2 35.0 33.4 31.8 30.2 28.6 72 52.3 3.3 26.9 25.2 23.5 21.8 20.1 - - 50.0 3.7 25.4 23.7 22.1 20.4 18.8 - - 2250 67 48.1 3.2 31.8 30.1 28.4 26.7 25.0 23.3 21.6 45.7 3.7 30.3 28.6 26.9 25.3 23.6 22.0 20.3 62 43.4 3.2 36.4 34.7 33.0 31.3 29.6 28.0 26.3 41.5 3.7 35.0 33.3 31.7 30.0 28.4 26.7 25.1 57 38.3 3.1 38.3 38.3 37.9 36.2 34.5 32.8 31.1 37.5 3.6 37.5 37.5 36.9 35.3 33.6 32.0 30.3 72 54.1 3.3 28.4 26.7 24.9 23.2 21.4 - - 51.7 3.7 26.9 25.2 23.5 21.8 20.1 - - 2500 67 49.7 3.2 33.6 31.8 30.1 28.3 26.6 24.9 23.1 47.3 3.7 32.1 30.4 28.7 26.9 25.2 23.5 21.8 62 44.9 3.2 38.5 36.7 35.0 33.3 31.5 29.8 28.0 42.9 3.7 37.1 35.4 33.7 32.0 30.3 28.6 26.9 57 39.5 3.1 39.5 39.5 39.5 37.8 36.1 34.3 32.6 38.9 3.6 38.9 38.9 38.9 37.1 35.4 33.7 32.0 95 F 105 F 72 42.9 4.1 20.3 19.1 17.8 16.6 15.4 - - 40.6 4.7 18.8 17.6 16.4 15.2 14.1 - - 1500 67 39.0 4.1 24.5 23.2 22.0 20.8 19.5 18.3 17.1 36.8 4.7 23.0 21.8 20.6 19.4 18.2 17.1 15.9 62 35.7 4.1 28.7 27.4 26.2 25.0 23.7 22.5 21.3 33.7 4.6 27.1 25.9 24.7 23.5 22.4 21.2 20.0 57 33.2 4.1 33.2 32.5 31.3 30.1 28.9 27.6 26.4 31.3 4.6 31.3 30.6 29.4 28.2 27.1 25.9 24.7 72 44.4 4.1 21.3 19.9 18.5 17.2 15.8 - - 41.9 4.7 19.7 18.4 17.1 15.7 14.4 - - 1750 67 40.4 4.1 25.7 24.3 22.9 21.5 20.1 18.7 17.3 37.9 4.7 24.1 22.7 21.4 20.1 18.7 17.4 16.1 62 36.9 4.1 30.0 28.6 27.2 25.9 24.5 23.1 21.7 34.7 4.6 28.4 27.0 25.7 24.4 23.0 21.7 20.3 57 34.3 4.1 34.3 34.0 32.6 31.2 29.8 28.4 27.0 32.2 4.6 32.2 31.9 30.6 29.3 27.9 26.6 25.2 72 45.9 4.1 22.4 20.8 19.3 17.7 16.2 - - 43.1 4.7 20.7 19.2 17.7 16.2 14.7 - - 2000 67 41.7 4.1 26.9 25.3 23.8 22.2 20.7 19.1 17.6 39.0 4.7 25.2 23.7 22.2 20.7 19.2 17.7 16.3 62 38.1 4.1 31.4 29.8 28.3 26.7 25.2 23.6 22.1 35.8 4.6 29.6 28.2 26.7 25.2 23.7 22.2 20.7 57 35.4 4.1 35.4 35.4 33.8 32.3 30.7 29.2 27.6 33.2 4.6 33.2 33.2 31.7 30.3 28.8 27.3 25.8 72 47.6 4.2 23.9 22.3 20.7 19.0 17.4 - - 44.7 4.7 22.1 20.6 19.0 17.5 15.9 - - 2250 67 43.3 4.1 28.7 27.1 25.5 23.9 22.3 20.6 19.0 40.4 4.7 27.0 25.4 23.9 22.3 20.8 19.2 17.7 62 39.6 4.1 33.6 32.0 30.4 28.7 27.1 25.5 23.9 37.1 4.6 31.8 30.2 28.7 27.1 25.5 24.0 22.4 57 36.8 4.1 36.8 36.8 36.0 34.4 32.7 31.1 29.5 34.4 4.6 34.4 34.4 33.7 32.1 30.6 29.0 27.4 72 49.4 4.2 25.5 23.8 22.1 20.4 18.7 - - 46.2 4.7 23.6 22.0 20.3 18.7 17.1 - - 2500 67 44.9 4.2 30.6 28.9 27.2 25.6 23.9 22.2 20.5 41.8 4.7 28.8 27.1 25.5 23.9 22.3 20.7 19.1 62 41.0 4.1 35.8 34.1 32.4 30.7 29.1 27.4 25.7 38.3 4.6 33.9 32.3 30.6 29.0 27.4 25.8 24.2 57 38.2 4.1 38.2 38.2 38.2 36.5 34.8 33.1 31.4 35.6 4.6 35.6 35.6 35.6 34.0 32.3 30.7 29.1 115 F 125 F 72 38.3 5.2 17.3 16.1 15.0 13.9 12.7 - - 36.0 5.8 15.7 14.7 13.6 12.5 11.4 - - 1500 67 34.5 5.2 21.4 20.3 19.2 18.1 16.9 15.8 14.7 32.3 5.7 19.9 18.9 17.8 16.7 15.6 14.5 13.4 62 31.7 5.1 25.5 24.4 23.2 22.1 21.0 19.8 18.7 29.7 5.6 23.9 22.8 21.7 20.7 19.6 18.5 17.4 57 29.3 5.2 29.3 28.7 27.5 26.4 25.3 24.2 23.0 27.4 5.7 27.4 26.7 25.7 24.6 23.5 22.4 21.3 72 39.3 5.2 18.1 16.9 15.6 14.3 13.0 - - 36.8 5.8 16.5 15.3 14.1 12.9 11.6 - - 1750 67 35.5 5.2 22.5 21.2 19.9 18.6 17.4 16.1 14.8 33.0 5.7 20.9 19.7 18.5 17.2 16.0 14.8 13.5 62 32.6 5.1 26.7 25.4 24.1 22.8 21.6 20.3 19.0 30.4 5.6 25.0 23.8 22.6 21.3 20.1 18.9 17.7 57 30.1 5.2 30.1 29.8 28.6 27.3 26.1 24.8 23.5 28.1 5.7 28.1 27.7 26.6 25.4 24.2 23.0 21.7 72 40.4 5.2 19.0 17.6 16.2 14.7 13.3 - - 37.6 5.8 17.3 16.0 14.6 13.2 11.9 - - 2000 67 36.4 5.2 23.5 22.1 20.7 19.2 17.8 16.4 14.9 33.7 5.7 21.9 20.5 19.1 17.8 16.4 15.0 13.6 62 33.4 5.1 27.9 26.5 25.0 23.6 22.2 20.7 19.3 31.1 5.6 26.1 24.8 23.4 22.0 20.7 19.3 17.9 57 31.0 5.2 31.0 31.0 29.7 28.3 26.8 25.4 24.0 28.7 5.7 28.7 28.7 27.6 26.2 24.9 23.5 22.1 2250 2500 72 41.7 5.2 20.4 18.9 17.4 15.9 14.4 - - 38.8 5.8 18.6 17.2 15.7 14.3 12.9 - - 67 37.6 5.2 25.2 23.7 22.2 20.8 19.3 17.8 16.3 34.7 5.7 23.5 22.0 20.6 19.2 17.8 16.3 14.9 62 34.5 5.1 29.9 28.4 26.9 25.4 24.0 22.5 21.0 32.0 5.6 28.1 26.6 25.2 23.8 22.4 21.0 19.5 57 32.0 5.2 32.0 32.0 31.3 29.8 28.4 26.9 25.4 29.6 5.7 29.6 29.6 29.0 27.6 26.2 24.7 23.3 72 43.0 5.2 21.7 20.2 18.6 17.1 15.5 - - 39.9 5.8 19.8 18.4 16.9 15.4 13.9 - - 67 38.8 5.2 26.9 25.4 23.8 22.3 20.7 19.2 17.6 35.8 5.7 25.1 23.6 22.1 20.6 19.2 17.7 16.2 62 35.6 5.1 31.9 30.4 28.8 27.3 25.7 24.2 22.7 32.9 5.6 30.0 28.5 27.0 25.6 24.1 22.6 21.1 57 33.0 5.2 33.0 33.0 33.0 31.4 29.9 28.4 26.8 30.4 5.7 30.4 30.4 30.4 28.9 27.5 26.0 24.5 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. 22 Johnson Controls Unitary Products

TABLE 22: DK-A6 COOLING CAPACITIES (6 TON) - NORMAL MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 84.4 4.8 45.5 41.9 38.3 34.6 31.0 - - 79.9 5.3 43.6 40.0 36.4 32.8 29.2 - - 1800 67 76.3 4.6 55.3 51.7 48.1 44.4 40.8 37.2 33.6 72.8 5.1 53.6 50.1 46.5 42.9 39.3 35.7 32.2 62 69.0 4.5 66.0 62.4 58.7 55.1 51.5 47.9 44.2 65.5 5.0 63.9 60.3 56.7 53.1 49.6 46.0 42.4 57 67.6 4.4 67.6 67.6 63.7 60.1 56.4 52.8 49.2 64.7 5.0 64.7 64.7 61.2 57.6 54.0 50.4 46.8 72 87.4 4.8 48.7 44.6 40.4 36.3 32.2 - - 82.5 5.3 46.6 42.5 38.4 34.3 30.2 - - 2100 67 79.0 4.6 59.0 54.9 50.8 46.6 42.5 38.4 34.3 75.2 5.1 57.2 53.1 49.1 45.0 40.9 36.8 32.7 62 71.4 4.5 69.9 66.2 62.0 57.9 53.8 49.7 45.5 67.7 5.0 66.9 63.9 59.9 55.8 51.7 47.6 43.5 57 70.0 4.5 70.0 70.0 67.3 63.1 59.0 54.9 50.7 66.8 5.0 66.8 66.8 64.6 60.5 56.4 52.3 48.2 72 90.3 4.8 51.8 47.2 42.6 37.9 33.3 - - 85.1 5.3 49.6 45.0 40.4 35.8 31.3 - - 2400 67 81.6 4.6 62.7 58.1 53.5 48.8 44.2 39.6 34.9 77.6 5.2 60.8 56.2 51.6 47.0 42.5 37.9 33.3 62 73.8 4.5 73.8 70.0 65.3 60.7 56.1 51.4 46.8 69.8 5.0 69.8 67.6 63.0 58.4 53.9 49.3 44.7 57 72.3 4.5 72.3 72.3 70.8 66.2 61.6 56.9 52.3 68.9 5.0 68.9 68.9 67.9 63.4 58.8 54.2 49.6 72 92.1 4.8 55.0 49.9 44.8 39.8 34.7 - - 86.5 5.3 52.5 47.5 42.5 37.4 32.4 - - 2700 67 83.3 4.7 66.5 61.4 56.3 51.3 46.2 41.1 36.1 78.9 5.2 64.3 59.2 54.2 49.2 44.2 39.2 34.1 62 75.2 4.5 75.2 73.3 68.8 63.8 58.7 53.6 48.6 71.0 5.1 71.0 69.9 66.2 61.2 56.1 51.1 46.1 57 73.8 4.5 73.8 73.8 73.0 68.0 62.9 57.8 52.7 70.1 5.0 70.1 70.1 69.6 64.6 59.6 54.5 49.5 72 93.9 4.8 58.1 52.6 47.1 41.6 36.1 - - 88.0 5.3 55.4 49.9 44.5 39.0 33.6 - - 3000 67 84.9 4.7 70.2 64.7 59.2 53.7 48.2 42.7 37.2 80.2 5.2 67.7 62.3 56.8 51.4 45.9 40.4 35.0 62 76.7 4.5 76.7 76.7 72.3 66.8 61.3 55.8 50.3 72.2 5.1 72.2 72.2 69.3 63.9 58.4 53.0 47.5 57 75.2 4.5 75.2 75.2 75.2 69.7 64.2 58.7 53.2 71.2 5.1 71.2 71.2 71.2 65.8 60.3 54.9 49.4 95 F 105 F 72 75.3 5.8 41.6 38.0 34.5 31.0 27.4 - - 70.4 6.5 39.9 36.3 32.8 29.2 25.7 - - 1800 67 69.4 5.6 52.0 48.4 44.9 41.3 37.8 34.3 30.7 64.8 6.3 50.2 46.7 43.1 39.6 36.0 32.5 28.9 62 62.1 5.5 61.8 58.2 54.7 51.2 47.6 44.1 40.6 57.9 6.2 57.7 55.9 52.7 49.1 45.6 42.0 38.5 57 61.7 5.5 61.7 61.7 58.7 55.1 51.6 48.0 44.5 57.8 6.2 57.8 57.8 55.9 52.4 48.8 45.3 41.7 72 77.6 5.8 44.4 40.4 36.4 32.4 28.3 - - 72.8 6.5 42.6 38.6 34.5 30.5 26.4 - - 2100 67 71.5 5.7 55.4 51.4 47.3 43.3 39.3 35.2 31.2 67.1 6.3 53.5 49.5 45.4 41.4 37.3 33.3 29.3 62 64.0 5.6 63.9 61.7 57.7 53.7 49.6 45.6 41.6 59.9 6.2 59.8 58.7 55.5 51.4 47.4 43.3 39.3 57 63.6 5.5 63.6 63.6 61.9 57.8 53.8 49.8 45.7 59.8 6.2 59.8 59.8 58.9 54.9 50.8 46.8 42.7 72 79.9 5.8 47.3 42.8 38.3 33.7 29.2 - - 75.3 6.5 45.4 40.8 36.3 31.7 27.2 - - 2400 67 73.6 5.7 58.8 54.3 49.8 45.3 40.7 36.2 31.7 69.4 6.3 56.8 52.3 47.7 43.2 38.7 34.1 29.6 62 65.9 5.6 65.9 65.2 60.7 56.1 51.6 47.1 42.6 61.9 6.2 61.9 61.5 58.3 53.7 49.2 44.7 40.1 57 65.5 5.6 65.5 65.5 65.0 60.5 56.0 51.5 47.0 61.9 6.2 61.9 61.9 61.9 57.3 52.8 48.2 43.7 72 81.0 5.8 50.0 45.0 40.1 35.1 30.1 - - 75.9 6.5 47.9 42.9 37.9 32.9 27.9 - - 2700 67 74.6 5.7 62.0 57.1 52.1 47.1 42.2 37.2 32.2 69.9 6.4 59.9 54.9 49.9 44.9 39.9 34.9 29.9 62 66.8 5.6 66.8 66.4 63.5 58.5 53.6 48.6 43.6 62.4 6.3 62.4 62.2 60.2 55.3 50.3 45.3 40.3 57 66.4 5.6 66.4 66.4 66.2 61.2 56.2 51.3 46.3 62.3 6.3 62.3 62.3 62.4 57.4 52.4 47.4 42.4 72 82.0 5.8 52.7 47.3 41.8 36.4 31.0 - - 76.5 6.6 50.4 45.0 39.5 34.1 28.7 - - 3000 67 75.6 5.7 65.3 59.8 54.4 49.0 43.6 38.2 32.8 70.5 6.4 62.9 57.5 52.0 46.6 41.2 35.7 30.3 62 67.7 5.6 67.7 67.7 66.3 60.9 55.5 50.1 44.7 62.9 6.3 62.9 62.9 62.2 56.8 51.3 45.9 40.5 57 67.3 5.6 67.3 67.3 67.3 61.8 56.4 51.0 45.6 62.8 6.3 62.8 62.8 62.8 57.4 52.0 46.5 41.1 115 F 125 F 72 65.4 7.2 38.2 34.6 31.1 27.5 23.9 - - 60.5 7.9 36.5 32.9 29.3 25.8 22.2 - - 1800 67 60.3 7.0 48.5 45.0 41.4 37.8 34.3 30.7 27.2 55.7 7.7 46.8 43.3 39.7 36.1 32.5 28.9 25.4 62 53.6 6.9 53.6 53.6 50.7 47.1 43.5 40.0 36.4 49.3 7.6 49.3 49.3 48.6 45.0 41.5 37.9 34.3 57 53.9 6.9 53.9 53.9 53.2 49.6 46.1 42.5 38.9 50.0 7.6 50.0 50.0 50.0 46.9 43.3 39.7 36.2 72 68.1 7.2 40.8 36.7 32.7 28.6 24.5 - - 63.3 7.9 39.0 34.9 30.8 26.7 22.6 - - 2100 67 62.7 7.0 51.7 47.6 43.6 39.5 35.4 31.4 27.3 58.3 7.7 49.9 45.8 41.7 37.6 33.5 29.4 25.3 62 55.7 6.9 55.7 55.7 53.3 49.2 45.1 41.1 37.0 51.6 7.6 51.6 51.6 51.1 47.0 42.9 38.8 34.7 57 56.0 6.9 56.0 56.0 56.0 51.9 47.8 43.8 39.7 52.3 7.6 52.3 52.3 52.3 48.9 44.8 40.7 36.7 72 70.7 7.2 43.4 38.9 34.3 29.7 25.1 - - 66.1 7.9 41.5 36.9 32.3 27.7 23.1 - - 2400 67 65.1 7.0 54.9 50.3 45.7 41.1 36.6 32.0 27.4 60.9 7.6 52.9 48.3 43.7 39.1 34.5 29.9 25.3 62 57.9 6.9 57.9 57.9 55.9 51.3 46.8 42.2 37.6 53.9 7.6 53.9 53.9 53.6 49.0 44.3 39.7 35.1 57 58.2 6.9 58.2 58.2 58.7 54.2 49.6 45.0 40.4 54.6 7.6 54.6 54.6 54.6 51.0 46.4 41.8 37.2 2700 3000 72 70.8 7.2 45.8 40.8 35.8 30.7 25.7 - - 65.7 7.9 43.7 38.7 33.6 28.6 23.5 - - 67 65.2 7.1 57.7 52.7 47.7 42.7 37.7 32.6 27.6 60.5 7.7 55.6 50.5 45.5 40.4 35.4 30.3 25.3 62 58.0 7.0 58.0 58.0 57.0 52.0 47.0 41.9 36.9 53.6 7.6 53.6 53.6 53.6 48.7 43.7 38.6 33.6 57 58.3 6.9 58.3 58.3 58.6 53.5 48.5 43.5 38.5 54.3 7.6 54.3 54.3 54.3 49.7 44.7 39.6 34.6 72 70.9 7.3 48.1 42.7 37.2 31.8 26.3 - - 65.4 8.0 45.9 40.4 34.9 29.5 24.0 - - 67 65.3 7.1 60.6 55.1 49.6 44.2 38.7 33.3 27.8 60.2 7.8 58.2 52.7 47.3 41.8 36.3 30.8 25.3 62 58.1 7.0 58.1 58.1 58.1 52.6 47.2 41.7 36.2 53.2 7.7 53.2 53.2 53.2 48.4 43.0 37.5 32.0 57 58.4 7.0 58.4 58.4 58.4 52.9 47.5 42.0 36.6 53.9 7.7 53.9 53.9 53.9 48.5 43.0 37.5 32.0 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. Johnson Controls Unitary Products 23

TABLE 23: DK-A6 COOLING CAPACITIES (6 TON) - REHEAT MODE Air on Evaporator Coil WB ( F) Total Cap. 1 (MBH) Total 2 Input (kw) Temperature of Air on Condenser Coil 75 F 85 F Sensible Capacity (MBH) * Return Dry Bulb ( F) Total Cap. * (MBH) Total Input (kw) Sensible Capacity (MBH) * Return Dry Bulb ( F) CFM 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 57.6 4.3 27.1 25.6 24.2 22.8 21.4 - - 55.3 4.9 25.7 24.2 22.8 21.4 20.0 - - 1800 67 53.4 4.2 33.2 31.8 30.3 28.9 27.5 26.1 24.6 51.1 4.8 31.8 30.3 28.9 27.5 26.1 24.7 23.2 62 47.4 4.2 37.8 36.4 34.9 33.5 32.1 30.7 29.2 45.9 4.7 36.4 35.0 33.5 32.1 30.7 29.3 27.9 57 44.6 4.1 41.0 39.6 38.2 36.8 35.3 33.9 32.5 39.4 4.6 36.8 35.4 34.0 32.6 31.1 29.7 28.3 72 61.1 4.3 29.0 27.4 25.9 24.3 22.7 - - 58.6 4.9 27.5 25.9 24.4 22.8 21.3 - - 2100 67 56.7 4.3 35.6 34.0 32.4 30.8 29.2 27.7 26.1 54.1 4.8 34.0 32.5 30.9 29.3 27.8 26.2 24.7 62 50.3 4.2 40.5 38.9 37.3 35.7 34.1 32.6 31.0 48.7 4.7 39.0 37.4 35.8 34.3 32.7 31.2 29.6 57 47.3 4.1 43.9 42.4 40.8 39.2 37.6 36.0 34.5 41.8 4.6 39.4 37.9 36.3 34.8 33.2 31.6 30.1 72 64.6 4.4 31.0 29.2 27.5 25.8 24.0 - - 61.9 4.9 29.4 27.7 25.9 24.2 22.5 - - 2400 67 60.0 4.3 37.9 36.2 34.5 32.7 31.0 29.3 27.5 57.2 4.9 36.3 34.6 32.9 31.2 29.5 27.8 26.1 62 53.2 4.2 43.2 41.4 39.7 37.9 36.2 34.5 32.7 51.4 4.8 41.6 39.9 38.2 36.4 34.7 33.0 31.3 57 50.0 4.1 46.9 45.1 43.4 41.6 39.9 38.2 36.4 44.1 4.7 42.1 40.4 38.7 37.0 35.2 33.5 31.8 72 65.5 4.4 31.6 29.7 27.8 25.9 24.0 - - 62.8 5.0 30.0 28.1 26.2 24.3 22.4 - - 2700 67 60.8 4.3 38.7 36.8 34.9 32.9 31.0 29.1 27.2 58.0 4.9 37.0 35.1 33.2 31.3 29.4 27.5 25.6 62 54.0 4.2 44.0 42.0 40.1 38.2 36.3 34.4 32.5 52.1 4.8 42.3 40.4 38.5 36.6 34.7 32.8 30.9 57 50.7 4.1 47.7 45.8 43.8 41.9 40.0 38.1 36.2 44.8 4.7 42.8 40.9 39.0 37.1 35.2 33.3 31.4 72 66.4 4.4 32.3 30.2 28.1 26.0 23.9 - - 63.7 5.0 30.6 28.5 26.4 24.3 22.2 - - 3000 67 61.6 4.3 39.4 37.3 35.2 33.1 31.0 29.0 26.9 58.8 4.9 37.6 35.5 33.5 31.4 29.3 27.2 25.2 62 54.7 4.3 44.7 42.7 40.6 38.5 36.4 34.3 32.2 52.9 4.8 43.0 40.9 38.8 36.7 34.7 32.6 30.5 57 51.4 4.2 48.5 46.4 44.3 42.2 40.1 38.0 35.9 45.4 4.7 43.5 41.4 39.3 37.3 35.2 33.1 31.0 95 F 105 F 72 53.0 5.4 24.3 22.8 21.4 20.0 18.6 - - 50.3 6.0 22.6 21.2 19.8 18.5 17.1 - - 1800 67 48.7 5.3 30.3 28.9 27.5 26.1 24.7 23.2 21.8 46.3 5.9 28.8 27.4 26.0 24.6 23.3 21.9 20.5 62 44.4 5.2 35.0 33.6 32.2 30.7 29.3 27.9 26.5 41.6 5.8 33.2 31.9 30.5 29.1 27.7 26.3 24.9 57 34.2 5.1 32.6 31.2 29.8 28.4 27.0 25.6 24.1 35.4 5.7 34.6 33.3 32.0 30.6 29.2 27.8 26.4 72 56.1 5.5 26.0 24.5 22.9 21.4 19.8 - - 53.2 6.1 24.3 22.8 21.2 19.7 18.2 - - 2100 67 51.6 5.4 32.5 30.9 29.4 27.9 26.3 24.8 23.2 49.0 6.0 30.9 29.4 27.9 26.3 24.8 23.3 21.8 62 47.0 5.2 37.5 35.9 34.4 32.8 31.3 29.8 28.2 43.9 5.9 35.6 34.1 32.6 31.1 29.6 28.1 26.6 57 36.2 5.1 35.0 33.4 31.9 30.3 28.8 27.2 25.7 37.4 5.7 36.8 35.7 34.2 32.7 31.2 29.7 28.2 72 59.2 5.5 27.7 26.1 24.4 22.7 21.1 - - 56.1 6.2 25.9 24.3 22.6 21.0 19.4 - - 2400 67 54.5 5.4 34.7 33.0 31.3 29.6 28.0 26.3 24.6 51.6 6.1 33.0 31.3 29.7 28.1 26.4 24.8 23.1 62 49.6 5.3 40.0 38.3 36.6 34.9 33.3 31.6 29.9 46.3 5.9 38.0 36.4 34.8 33.1 31.5 29.9 28.2 57 38.2 5.2 37.3 35.6 33.9 32.3 30.6 28.9 27.2 39.5 5.8 39.0 38.1 36.5 34.8 33.2 31.6 29.9 72 60.1 5.5 28.3 26.4 24.5 22.7 20.8 - - 56.8 6.2 26.4 24.5 22.7 20.9 19.0 - - 2700 67 55.2 5.4 35.2 33.4 31.5 29.6 27.8 25.9 24.0 52.2 6.1 33.4 31.6 29.8 27.9 26.1 24.3 22.4 62 50.3 5.3 40.6 38.7 36.8 35.0 33.1 31.2 29.4 46.9 5.9 38.5 36.7 34.8 33.0 31.2 29.3 27.5 57 38.8 5.2 37.9 36.0 34.1 32.3 30.4 28.6 26.7 39.9 5.8 39.5 38.4 36.5 34.7 32.9 31.0 29.2 72 60.9 5.6 28.8 26.8 24.7 22.6 20.6 - - 57.4 6.2 26.8 24.8 22.7 20.7 18.7 - - 3000 67 56.0 5.5 35.8 33.8 31.7 29.6 27.6 25.5 23.5 52.8 6.1 33.9 31.9 29.8 27.8 25.8 23.7 21.7 62 51.0 5.3 41.2 39.1 37.1 35.0 33.0 30.9 28.8 47.4 5.9 39.0 37.0 34.9 32.9 30.9 28.8 26.8 57 39.3 5.2 38.5 36.4 34.4 32.3 30.2 28.2 26.1 40.4 5.8 39.9 38.6 36.6 34.6 32.5 30.5 28.5 115 F 125 F 72 47.7 6.7 21.0 19.6 18.3 16.9 15.5 - - 45.0 7.3 19.3 18.0 16.7 15.4 14.0 - - 1800 67 43.8 6.6 27.3 25.9 24.6 23.2 21.8 20.5 19.1 41.4 7.3 25.7 24.4 23.1 21.8 20.4 19.1 17.8 62 38.7 6.4 31.5 30.1 28.8 27.4 26.1 24.7 23.4 35.9 7.0 29.8 28.4 27.1 25.8 24.5 23.1 21.8 57 36.6 6.2 36.6 35.5 34.1 32.8 31.4 30.0 28.7 37.8 6.8 37.8 37.6 36.3 34.9 33.6 32.3 31.0 72 50.3 6.7 22.5 21.1 19.6 18.1 16.6 - - 47.5 7.4 20.8 19.4 17.9 16.5 15.0 - - 2100 67 46.3 6.7 29.3 27.8 26.3 24.8 23.4 21.9 20.4 43.6 7.3 27.7 26.2 24.8 23.3 21.9 20.4 19.0 62 40.9 6.5 33.8 32.3 30.9 29.4 27.9 26.4 24.9 37.8 7.1 32.0 30.5 29.1 27.6 26.2 24.7 23.3 57 38.7 6.3 38.7 38.0 36.6 35.1 33.6 32.1 30.6 39.9 6.9 39.9 39.9 38.9 37.5 36.0 34.6 33.1 72 53.0 6.8 24.1 22.5 20.9 19.3 17.7 - - 49.9 7.5 22.3 20.7 19.1 17.6 16.0 - - 2400 67 48.7 6.8 31.3 29.7 28.1 26.5 24.9 23.3 21.7 45.9 7.4 29.6 28.0 26.5 24.9 23.3 21.8 20.2 62 43.0 6.6 36.1 34.5 32.9 31.3 29.7 28.1 26.5 39.7 7.2 34.2 32.6 31.1 29.5 27.9 26.4 24.8 57 40.7 6.4 40.7 40.6 39.0 37.4 35.8 34.2 32.6 42.0 7.0 42.0 42.0 41.6 40.0 38.4 36.8 35.3 2700 3000 72 53.4 6.8 24.4 22.6 20.8 19.0 17.2 - - 50.1 7.4 22.5 20.8 19.0 17.2 15.4 - - 67 49.2 6.7 31.6 29.8 28.0 26.2 24.4 22.6 20.8 46.1 7.4 29.8 28.0 26.3 24.5 22.7 21.0 19.2 62 43.4 6.6 36.5 34.7 32.9 31.0 29.2 27.4 25.6 39.9 7.2 34.4 32.6 30.9 29.1 27.3 25.5 23.8 57 41.1 6.4 41.1 40.7 38.9 37.1 35.3 33.5 31.7 42.2 7.0 42.2 42.2 41.3 39.6 37.8 36.0 34.2 72 53.9 6.8 24.8 22.8 20.8 18.8 16.8 - - 50.4 7.4 22.8 20.8 18.8 16.9 14.9 - - 67 49.6 6.7 32.0 30.0 28.0 26.0 24.0 22.0 20.0 46.3 7.4 30.0 28.0 26.1 24.1 22.1 20.2 18.2 62 43.8 6.5 36.8 34.8 32.8 30.8 28.8 26.8 24.8 40.1 7.1 34.6 32.6 30.6 28.7 26.7 24.7 22.8 57 41.4 6.4 41.4 40.8 38.8 36.8 34.8 32.8 30.8 42.5 6.9 42.5 42.5 41.1 39.1 37.1 35.2 33.2 1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors (total 1 kw) and the compressor motors but not the supply air blower motor. 24 Johnson Controls Unitary Products

25 DK-03 Moisture Removal @ 1200 cfm Reheat Mode @ Various Indoor (dry bulb / wet bulb) Conditions Moisture Removal Rate (lbs Water/Hour) 20 15 10 5 0 65 75 85 95 105 Outdoor Temperature (ºF) 75db/71wb 80db/71wb 75db/67wb 85db/71wb 80db/67wb 85db/67wb FIGURE 3 - DK-03 MOISTURE REMOVAL - REHEAT MODE 30 DK-04 Moisture Removal @ 1600 cfm Reheat Mode @ Various Indoor (dry bulb / wet bulb) Conditions Moisture Removal Rate (lbs Water/Hour) 25 20 15 10 5 0 65 75 85 95 105 Outdoor Temperature (ºF) 75db/71wb 80db/71wb 75db/67wb 85db/71wb 80db/67wb 85db/67wb FIGURE 4 - DK-04 MOISTURE REMOVAL - REHEAT MODE Johnson Controls Unitary Products 25

35 DK-05 Moisture Removal @ 2000 cfm Reheat Mode @ Various Indoor (dry bulb / wet bulb) Conditions 30 Moisture Removal Rate (lbs Water/Hour) 25 20 15 10 5 0 65 75 85 95 105 Outdoor Temperature (ºF) 75db/71wb 80db/71wb 75db/67wb 85db/71wb 80db/67wb 85db/67wb FIGURE 5 - DK-05 MOISTURE REMOVAL - REHEAT MODE 40 DK-A6 Moisture Removal @ 2400 cfm Reheat Mode @ Various Indoor (dry bulb / wet bulb) Conditions 35 Moisture Removal Rate (lbs Water/Hour) 30 25 20 15 10 5 0 65 75 85 95 105 Outdoor Temperature (ºF) 75db/71wb 80db/71wb 75db/67wb 85db/71wb 80db/67wb 85db/67wb FIGURE 6 - DK-A6 MOISTURE REMOVAL - REHEAT MODE 26 Johnson Controls Unitary Products

TABLE 24: SUPPLY AIR BLOWER PERFORMANCE (DK-03 BELT DRIVE) - SIDE DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 800 634 0.34 735 0.39 828 0.45 914 0.52 995 0.59 1070 0.67 1140 0.75 1207 0.83 1270 0.92 1332 1.00 1000 659 0.39 760 0.45 853 0.51 939 0.57 1019 0.65 1094 0.72 1165 0.80 1232 0.89 1295 0.97 1356 1.06 1200 685 0.47 786 0.52 879 0.58 965 0.65 1045 0.72 1120 0.80 1191 0.88 1258 0.96 1321 1.05 1382 1.13 1400 716 0.57 816 0.62 909 0.68 995 0.75 1076 0.82 1151 0.90 1221 0.98 1288 1.06 1352 1.15 1413 1.23 1600 752 0.69 852 0.75 945 0.81 1032 0.88 1112 0.95 1187 1.03 1258 1.11 1324 1.19 1388 1.27 1449 1.36 FS 4 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. 4. Field Supplied Drive. TABLE 25: SUPPLY AIR BLOWER PERFORMANCE (DK-03 BELT DRIVE) - BOTTOM DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 800 613 0.35 724 0.40 826 0.46 920 0.53 1007 0.60 1089 0.67 1165 0.75 1237 0.83 1306 0.91 1372 1.00 1000 640 0.40 751 0.46 853 0.52 947 0.58 1034 0.65 1116 0.73 1192 0.80 1264 0.89 1333 0.97 1399 1.05 1200 669 0.48 779 0.53 881 0.59 975 0.65 1063 0.73 1144 0.80 1220 0.88 1293 0.96 1361 1.04 1427 1.13 1400 702 0.57 812 0.63 914 0.69 1009 0.75 1096 0.82 1177 0.90 1254 0.98 1326 1.06 1394 1.14 1460 1.22 1600 741 0.70 852 0.75 954 0.81 1048 0.88 1135 0.95 1217 1.02 1293 1.10 1365 1.18 1434 1.26 1500 1.35 Field Supplied Drive 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. TABLE 26: SUPPLY AIR BLOWER PERFORMANCE (DK-04 BELT DRIVE) - SIDE DUCT APPLICATION Air Flow (CFM) Available External Static Pressure - IWG 1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 1000 703 0.39 786 0.47 866 0.54 942 0.62 1016 0.71 1087 0.79 1155 0.88 1221 0.98 1284 1.07 1345 1.17 1200 733 0.44 817 0.52 896 0.60 973 0.68 1047 0.76 1118 0.85 1186 0.94 1252 1.03 1315 1.12 1376 1.22 1400 770 0.52 853 0.60 933 0.67 1010 0.76 1083 0.84 1154 0.93 1222 1.02 1288 1.11 1352 1.20 1413 1.30 1600 811 0.64 895 0.71 974 0.79 1051 0.87 1125 0.96 1196 1.04 1264 1.13 1330 1.23 1393 1.32 1454 1.42 1800 857 0.80 940 0.87 1020 0.95 1097 1.03 1171 1.11 1242 1.20 1310 1.29 1375 1.38 1439 1.48 1500 1.58 2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.77 FS 4 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. 4. Field Supplied Drive. TABLE 27: SUPPLY AIR BLOWER PERFORMANCE (DK-04 BELT DRIVE) - BOTTOM DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 1000 688 0.40 779 0.47 866 0.55 949 0.63 1029 0.71 1107 0.80 1181 0.88 1253 0.97 1322 1.07 1388 1.16 1200 722 0.45 812 0.53 899 0.60 983 0.68 1063 0.76 1140 0.85 1215 0.93 1286 1.03 1355 1.12 1422 1.21 1400 761 0.53 852 0.60 939 0.68 1022 0.76 1103 0.84 1180 0.92 1254 1.01 1326 1.10 1395 1.20 1462 1.29 1600 807 0.65 897 0.72 984 0.79 1068 0.87 1148 0.95 1225 1.04 1300 1.13 1371 1.22 1440 1.31 1507 1.40 1800 856 0.80 947 0.87 1034 0.95 1118 1.02 1198 1.11 1275 1.19 1349 1.28 1421 1.37 1490 1.46 1557 1.56 2000 910 0.99 1001 1.06 1088 1.14 1172 1.22 1252 1.30 1329 1.39 1403 1.47 1475 1.56 1544 1.66 1611 1.75 Field Supplied Drive 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. Johnson Controls Unitary Products 27

TABLE 28: SUPPLY AIR BLOWER PERFORMANCE (DK-05 BELT DRIVE) - SIDE DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 1200 733 0.44 817 0.52 896 0.60 973 0.68 1047 0.76 1118 0.85 1186 0.94 1252 1.03 1315 1.12 1376 1.22 1400 770 0.52 853 0.60 933 0.67 1010 0.76 1083 0.84 1154 0.93 1222 1.02 1288 1.11 1352 1.20 1413 1.30 1600 811 0.64 895 0.71 974 0.79 1051 0.87 1125 0.96 1196 1.04 1264 1.13 1330 1.23 1393 1.32 1454 1.42 1800 857 0.80 940 0.87 1020 0.95 1097 1.03 1171 1.11 1242 1.20 1310 1.29 1375 1.38 1439 1.48 1500 1.58 2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.77 2200 960 1.24 1043 1.31 1123 1.39 1199 1.47 1273 1.55 1344 1.64 1412 1.73 1478 1.82 1541 1.92 1602 2.01 2400 1015 1.51 1099 1.59 1178 1.66 1255 1.74 1329 1.83 1400 1.92 1468 2.01 1534 2.10 1597 2.19 1658 2.29 2600 1074 1.83 1157 1.90 1237 1.98 1314 2.06 1387 2.14 1458 2.23 - - - - - - - - 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. TABLE 29: SUPPLY AIR BLOWER PERFORMANCE (DK-05 BELT DRIVE) - BOTTOM DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 1200 722 0.45 812 0.53 899 0.60 983 0.68 1063 0.76 1140 0.85 1215 0.93 1286 1.03 1355 1.12 1422 1.21 1400 761 0.53 852 0.60 939 0.68 1022 0.76 1103 0.84 1180 0.92 1254 1.01 1326 1.10 1395 1.20 1462 1.29 1600 807 0.65 897 0.72 984 0.79 1068 0.87 1148 0.95 1225 1.04 1300 1.13 1371 1.22 1440 1.31 1507 1.40 1800 856 0.80 947 0.87 1034 0.95 1118 1.02 1198 1.11 1275 1.19 1349 1.28 1421 1.37 1490 1.46 1557 1.56 2000 910 0.99 1001 1.06 1088 1.14 1172 1.22 1252 1.30 1329 1.39 1403 1.47 1475 1.56 1544 1.66 1611 1.75 2200 968 1.23 1059 1.30 1146 1.37 1229 1.45 1309 1.53 1387 1.62 1461 1.71 1533 1.80 1602 1.89 1668 1.99 2400 1029 1.50 1119 1.57 1206 1.65 1290 1.72 1370 1.81 1448 1.89 1522 1.98 1593 2.07 1663 2.16 1729 2.26 2600 1093 1.81 1183 1.88 1270 1.95 1354 2.03 1434 2.11 1511 2.20 1586 2.29 - - - - - - Field Supplied Drive 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. TABLE 30: SUPPLY AIR BLOWER PERFORMANCE (DK-A6 BELT DRIVE) - SIDE DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 1600 811 0.64 895 0.71 974 0.79 1051 0.87 1125 0.96 1196 1.04 1264 1.13 1330 1.23 1393 1.32 1454 1.42 1800 857 0.80 940 0.87 1020 0.95 1097 1.03 1171 1.11 1242 1.20 1310 1.29 1375 1.38 1439 1.48 1500 1.58 2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.77 2200 960 1.24 1043 1.31 1123 1.39 1199 1.47 1273 1.55 1344 1.64 1412 1.73 1478 1.82 1541 1.92 1602 2.01 2400 1015 1.51 1099 1.59 1178 1.66 1255 1.74 1329 1.83 1400 1.92 1468 2.01 1534 2.10 1597 2.19 1658 2.29 2600 1074 1.83 1157 1.90 1237 1.98 1314 2.06 1387 2.14 1458 2.23 1526 2.32 1592 2.41 1656 2.51 1717 2.61 2800 1135 2.18 1218 2.25 1298 2.33 1375 2.41 1448 2.49 1519 2.58 1587 2.67 1653 2.76 1717 2.86 1778 2.96 3000 1198 2.56 1281 2.64 1361 2.71 1438 2.79 1511 2.88 1582 2.96 1651 3.05 1716 3.15 1780 3.24 - - Field Supplied Drive 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. TABLE 31: SUPPLY AIR BLOWER PERFORMANCE (DK-A6 BELT DRIVE) - BOTTOM DUCT APPLICATION Air Available External Static Pressure - IWG 1 Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Drive Option HIgh Static Drive Option 1600 807 0.65 897 0.72 984 0.79 1068 0.87 1148 0.95 1225 1.04 1300 1.13 1371 1.22 1440 1.31 1507 1.40 1800 856 0.80 947 0.87 1034 0.95 1118 1.02 1198 1.11 1275 1.19 1349 1.28 1421 1.37 1490 1.46 1557 1.56 2000 910 0.99 1001 1.06 1088 1.14 1172 1.22 1252 1.30 1329 1.39 1403 1.47 1475 1.56 1544 1.66 1611 1.75 2200 968 1.23 1059 1.30 1146 1.37 1229 1.45 1309 1.53 1387 1.62 1461 1.71 1533 1.80 1602 1.89 1668 1.99 2400 1029 1.50 1119 1.57 1206 1.65 1290 1.72 1370 1.81 1448 1.89 1522 1.98 1593 2.07 1663 2.16 1729 2.26 2600 1093 1.81 1183 1.88 1270 1.95 1354 2.03 1434 2.11 1511 2.20 1586 2.29 1657 2.38 1726 2.47 1793 2.57 2800 1159 2.15 1250 2.22 1337 2.29 1420 2.37 1500 2.46 1578 2.54 1652 2.63 1724 2.72 1793 2.81 - - 3000 1228 2.52 1318 2.59 1405 2.67 1489 2.75 1569 2.83 1646 2.91 1721 3.00 1792 3.09 - - - - Field Supplied Drive 1. Blower performance includes gas heat exchangers and 1 filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kw = BHP x 0.932. 28 Johnson Controls Unitary Products

TABLE 32: SUPPLY AIR BLOWER PERFORMANCE (DK-03, -04, -05 & -A6 DIRECT DRIVE) SIDE DUCT APPLICATION UNIT TONNAGE MOTOR 1 SPEED CFM AVAILABLE EXTERNAL STATIC PRESSURE - IWG 2 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS 3 3 4 3 5 3 6 3 HI 1582 320 1538 335 1496 349 1458 363 1418 376 1381 390 1338 403 1298 417 1255 430 MED/HI 1488 263 1440 276 1396 290 1354 303 1309 316 1263 329 1214 343 1158 358 1085 374 MED 1339 208 1292 221 1247 234 1201 246 1152 258 1102 272 1036 288 967 303 924 313 MED/LOW 1233 171 1184 183 1135 195 1082 207 1026 220 957 235 895 248 - - - - LOW 1081 130 997 134 935 145 863 158 - - - - - - - - - - HI 2056 636 2017 696 1978 714 1942 734 1906 749 1864 764 1815 769 1728 743 1582 685 MED/HI 1866 539 1832 557 1795 571 1754 585 1722 602 1679 619 1636 638 1582 653 1508 639 MED 1680 408 1641 426 1594 438 1558 455 1517 472 1469 490 1415 505 1370 521 1337 536 MED/LOW 1582 362 1541 380 1495 391 1465 406 1426 423 1377 440 1326 455 1292 469 1247 485 LOW 1300 223 1258 237 1202 247 - - - - - - - - - - - - HI 2256 883 2258 931 2247 950 2223 964 2182 979 2125 971 2044 940 1958 898 1864 854 MED/HI 2145 771 2127 784 2119 808 2089 826 2051 844 2014 859 1965 861 1896 843 1801 806 MED 2020 637 1999 656 1985 675 1947 696 1910 715 1876 730 1832 740 1793 756 1725 748 MED/LOW 1757 413 1713 432 1677 451 1639 468 1597 479 1559 497 1521 513 1472 523 - - LOW 1570 327 1536 339 1499 356 - - - - - - - - - - - - HI 2256 883 2258 931 2247 950 2223 964 2182 979 2125 971 2044 940 1958 898 1864 854 MED/HI 2145 771 2127 784 2119 808 2089 826 2051 844 2014 859 1965 861 1896 843 1801 806 MED 2020 637 1999 656 1985 675 1947 696 1910 715 1876 730 1832 740 1793 756 - - MED/LOW - - - - - - - - - - - - - - - - - - LOW - - - - - - - - - - - - - - - - - - 1. Factory set on medium speed tap. 2. Includes allowances for a wet evaporator coil, 1 filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values. 3. Side Duct application (230 Volts) TABLE 33: SUPPLY AIR BLOWER PERFORMANCE (DK-03, -04, -05 & -A6 DIRECT DRIVE) BOTTOM DUCT APPLICATION UNIT TONNAGE MOTOR 1 SPEED CFM AVAILABLE EXTERNAL STATIC PRESSURE - IWG 2 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS 3 3 4 3 5 3 6 3 HI 1527 320 1485 335 1445 349 1408 363 1370 376 1334 390 1292 403 1254 417 1213 430 MED/HI 1437 263 1391 276 1349 290 1308 303 1265 316 1221 329 1174 343 1120 358 1049 374 MED 1293 208 1248 221 1205 234 1161 246 1114 258 1065 272 1002 288 935 303 894 313 MED/LOW 1191 171 1144 183 1097 195 1046 207 992 220 926 235 866 248 - - - - LOW 1045 130 964 134 904 145 - - - - - - - - - - - - HI 1985 636 1947 696 1909 714 1875 734 1840 749 1800 764 1752 769 1668 743 1528 685 MED/HI 1802 539 1768 557 1733 571 1694 585 1662 602 1621 619 1580 638 1528 653 1456 639 MED 1622 408 1585 426 1539 438 1505 455 1465 472 1419 490 1367 505 1324 521 1291 536 MED/LOW 1528 362 1489 380 1444 391 1415 406 1377 423 1330 440 1281 455 1248 469 1205 485 LOW 1256 223 1216 237 1161 247 - - - - - - - - - - - - HI 2177 883 2179 931 2169 950 2145 964 2106 979 2051 971 1973 940 1890 898 1800 854 MED/HI 2071 771 2053 784 2045 808 2016 826 1980 844 1944 859 1897 861 1830 843 1739 806 MED 1950 637 1929 656 1916 675 1880 696 1844 715 1811 730 1768 740 1731 756 1665 748 MED/LOW 1697 413 1654 432 1619 451 1583 468 1542 479 1506 497 1469 513 - - - - LOW 1516 327 1484 339 1448 356 - - - - - - - - - - - - HI 2177 883 2179 931 2169 950 2145 964 2106 979 2051 971 1973 940 1890 898 1800 854 MED/HI 2071 771 2053 784 2045 808 2016 826 1980 844 1944 859 1897 861 1830 843 - - MED 1950 637 1929 656 1916 675 1880 696 1844 715 1811 730 1768 740 - - - - MED/LOW - - - - - - - - - - - - - - - - - - LOW - - - - - - - - - - - - - - - - - - 1. Factory set on medium speed tap. 2. Includes allowances for a wet evaporator coil, 1 filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values. 3. Bottom Duct application (230 Volts) Johnson Controls Unitary Products 29

TABLE 34: BELT DRIVE RPM SELECTION Size (Tons) -03 (3) -04 (4) -05 (5) -A6 (6) HP Max BHP Motor Sheave Blower Sheave 5 Turns Open 4 Turns Open 3 Turns Open 2 Turns Open 1 Turn Open Fully Closed 1.5 1.73 1VL44 AK64 805 865 920 980 1035 1095 1.5 1.73 1VP56 AK66 1115 1170 1225 1280 1335 1390 1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 1260 1.5 1.73 1VP56 AK61 1210 1270 1330 1390 1455 1515 1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 1260 2 2.3 1VP56 AK56 1325 1395 1460 1525 1590 1660 1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 1260 3 3.45 1VP56 AK56 1325 1395 1460 1525 1590 1660 TABLE 35: BELT DRIVE BLOWER MOTOR AND DRIVE DATA MODEL SIZE 3 TON 4 TON 5 TON 6 TON MOTOR 1 Motor Sheave Blower Sheave HP RPM Eff. SF Frame Datum Dia. (in.) Bore (in.) 1-1/2 1725 0.8 1.15 56 2.8-3.8 7/8 1VL44 6.0 1 AK64 A37 1-1/2 1725 0.8 1.15 56 4.0-5.0 7/8 1VP56 6.2 1 AK66 A39 1-1/2 1725 0.8 1.15 56 2.8-3.8 7/8 1VL44 5.2 1 AK56 A36 1-1/2 1725 0.8 1.15 56 4.0-5.0 7/8 1VP56 5.7 1 AK61 A38 1-1/2 1725 0.8 1.15 56 2.8-3.8 7/8 1VL44 5.2 1 AK56 A36 2 1725 0.8 1.15 56 4.0-5.0 7/8 1VP56 5.2 1 AK56 A38 1-1/2 1725 0.8 1.15 56 2.8-3.8 7/8 1VL44 5.2 1 AK56 A36 3 1725 0.8 1.15 56 4.0-5.0 7/8 1VP56 5.2 1 AK56 A38 Model Datum Dia. (in.) Bore (in.) Model Belt 1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device. TABLE 36: STATIC RESISTANCES RESISTANCE, IWG DESCRIPTION CFM 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 ECONOMIZER 1,3 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30 ELECTRIC 7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22 HEATERS 1 20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 COOLING ONLY 2 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32 1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables. 2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables. 3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. 30 Johnson Controls Unitary Products

Drive Selection 1. Determine side or bottom supply air duct application. 2. Determine desired airflow. 3. Calculate or measure the amount of external static pressure. 4. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.) 5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table. 6. Review the BHP compared to the motor options available. Select the appropriate motor and/or drive. 7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor. 8. Determine turns open to obtain the desired operation point. Example 1. 2200 CFM 2. 1.6 iwg 3. Using the supply air blower performance table below, the following data point was located: 1478 RPM & 1.82 BHP. 4. Using the RPM selection table below, Size X and Model Y is found. 5. 1.82 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required. 6. 1478 RPM is within the range of the 2 HP drive. 7. Using the 2 HP motor and drive, 2.5 turns open will achieve 1478 RPM. Example Supply Air Blower Performance Air Flow (CFM) Available External Static Pressure - IWG 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Standard Drive Option HIgh Static Drive Option Drive 2000 907 1.00 990 1.07 1070 1.15 1146 1.23 1220 1.31 1291 1.40 1359 1.49 1425 1.58 1488 1.68 1550 1.77 2200 960 1.24 1043 1.31 1123 1.39 1199 1.47 1273 1.55 1344 1.64 1412 1.73 1478 1.82 1541 1.92 1602 2.01 2400 1015 1.51 1099 1.59 1178 1.66 1255 1.74 1329 1.83 1400 1.92 1468 2.01 1534 2.10 1597 2.19 1658 2.29 2600 1074 1.83 1157 1.90 1237 1.98 1314 2.06 1387 2.14 1458 2.23 - - - - - - - - Table X: RPM Selection Size (Tons) X Model Y HP Max Motor Blower 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully BHP Sheave Sheave Open Open Open Open Open Closed 1.5 1.73 1VL44 AK56 930 995 1060 1130 1195 1260 2 2.3 1VP56 AK56 1325 1395 1460 1525 1590 1660 Johnson Controls Unitary Products 31

Altitude/Temperature Correction Factors Air Altitude (Ft.) Temp. 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663 100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651 1.100 1.050 1.000 Correction Factor 0.950 0.900 0.850 0.800 0.750 0.700 0.650 0.600 40 50 60 70 80 90 100 Air Temperature (ºF) Sea Level 1000 ft 2000 ft 3000 ft 4000 ft 5000 ft 6000 ft 7000 ft 8000 ft 9000 ft 10000 ft TABLE 37: ELECTRIC HEATER CFM LIMITATIONS UNIT MODEL NOMINAL TONS -03 (3) -04 (4) -05 (5) -A6 (6) MINIMUM SUPPLY AIR CFM VOLTAGE HEATER SIZE NOMINAL KW 5 7 10 15 20 30 208/230-1-60 900 900 900 900 900-208/230-3-60 900 900 900 900 900-460-3-60 - 900 900 900 900-600-3-60 - - 900 900 900-208/230-1-60 1200 1200 1200 1200 1200-208/230-3-60 1200 1200 1200 1200 1200-460-3-60 - 1200 1200 1200 1200-600-3-60 - - 1200 1200 1200-208/230-1-60 1500 1500 1500 1500 1500 1500 208/230-3-60 1500 1500 1500 1500 1500 1500 460-3-60-1500 1500 1500 1500 1500 600-3-60 - - 1500 1500 1500 1500 208/230-1-60 1500 1500 1500 1500 1500 1500 208/230-3-60 1500 1500 1500 1500 1500 1500 460-3-60-1500 1500 1500 1500 1500 600-3-60 - - 1500 1500 1500 1500 32 Johnson Controls Unitary Products

TABLE 38: ELECTRICAL DATA - DK-03, -04, -05 & -A6 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET Size (Tons) -03 (3.0) -04 (4.0) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps 208-1-60 11.8 68.0 17.5 2.3 6.0 0.0 230-1-60 11.8 68.0 17.5 2.3 6.0 0.0 208-3-60 8.3 68.0 13.0 2.3 6.0 0.0 230-3-60 8.3 68.0 13.0 2.3 6.0 0.0 208-1-60 15.4 86.0 24.0 2.3 7.6 0.0 230-1-60 15.4 86.0 24.0 2.3 7.6 0.0 208-3-60 11.5 84.0 18.0 2.3 7.6 0.0 230-3-60 11.5 84.0 18.0 2.3 7.6 0.0 MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 23.0 30 E05 4.0 1 19.2 31.5 35 E07 5.6 1 26.9 41.2 45 E10 8.0 1 38.5 55.6 60 E15 11.9 2 57.2 79.0 80 E20 15.9 2 76.4 103.1 110 None - - - 23.0 30 E05 5.3 1 23.0 35.1 40 E07 7.5 1 32.6 46.6 50 E10 10.6 1 46.1 62.7 70 E15 15.9 2 69.1 90.3 100 E20 21.2 2 92.2 117.9 125 None - - - 18.7 25 E05 4.0 1 11.1 21.4 25 E07 5.6 1 15.5 26.9 30 E10 8.0 1 22.2 35.3 40 E15 11.9 2 33.0 48.8 50 E20 15.9 2 44.1 62.7 70 None - - - 18.7 25 E05 5.3 1 13.3 23.4 25 E07 7.5 1 18.8 30.1 35 E10 10.6 1 26.6 39.4 40 E15 15.9 2 39.9 55.3 60 E20 21.2 2 53.2 71.2 80 None - - - 29.1 35 E05 4.0 1 19.2 33.5 40 E07 5.6 1 26.9 43.2 45 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 None - - - 29.1 35 E05 5.3 1 23.0 37.1 40 E07 7.5 1 32.6 48.6 50 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 None - - - 24.3 30 E05 4.0 1 11.1 24.3 30 E07 5.6 1 15.5 28.9 35 E10 8.0 1 22.2 37.3 40 E15 11.9 2 33.0 50.8 60 E20 15.9 2 44.1 64.7 70 None - - - 24.3 30 E05 5.3 1 13.3 25.4 35 E07 7.5 1 18.8 32.1 35 E10 10.6 1 26.6 41.4 45 E15 15.9 2 39.9 57.3 60 E20 21.2 2 53.2 73.2 80 Johnson Controls Unitary Products 33

TABLE 38: ELECTRICAL DATA - DK-03, -04, -05 & -A6 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT) Size (Tons) -05 (5.0) -A6 (6.0) Volt Compressors (each) 208-1-60 25.0 150.0 39.0 2.3 7.6 0.0 230-1-60 25.0 150.0 39.0 2.3 7.6 0.0 208-3-60 17.3 123.0 27.0 2.3 7.6 0.0 230-3-60 17.3 123.0 27.0 2.3 7.6 0.0 208-3-60 18.6 156.0 29.0 2.3 7.6 0.0 230-3-60 18.6 156.0 29.0 2.3 7.6 0.0 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 41.2 50 E05 4.0 1 19.2 41.2 50 E07 5.6 1 26.9 43.2 60 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 E30 22.2 2 106.7 142.9 150 None - - - 41.2 50 E05 5.3 1 23.0 41.2 50 E07 7.5 1 32.6 48.6 60 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 E30 29.6 2 128.7 163.7 175 None - - - 31.5 40 E05 4.0 1 11.1 31.5 40 E07 5.6 1 15.5 31.5 40 E10 8.0 1 22.2 37.3 45 E15 11.9 2 33.0 50.8 60 E20 15.9 2 44.1 64.7 70 E30 22.2 2 61.6 86.5 90 None - - - 31.5 40 E05 5.3 1 13.3 31.5 40 E07 7.5 1 18.8 32.1 40 E10 10.6 1 26.6 41.4 45 E15 15.9 2 39.9 57.3 60 E20 21.2 2 53.2 73.2 80 E30 29.6 2 74.3 98.5 100 None - - - 33.2 40 E05 4.0 1 11.1 33.2 40 E07 5.6 1 15.5 33.2 40 E10 8.0 1 22.2 37.3 45 E15 11.9 2 33.0 50.8 60 E20 15.9 2 44.1 64.7 70 E30 22.2 2 61.6 86.5 90 None - - - 33.2 40 E05 5.3 1 13.3 33.2 40 E07 7.5 1 18.8 33.2 40 E10 10.6 1 26.6 41.4 50 E15 15.9 2 39.9 57.3 60 E20 21.2 2 53.2 73.2 80 E30 29.6 2 74.3 98.5 100 34 Johnson Controls Unitary Products

TABLE 39: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE W/O POWERED CONVENIENCE OUTLET Size (Tons) -03 (3.0) -04 (4.0) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps 208-1-60 11.8 68.0 17.5 2.3 7.6 0.0 230-1-60 11.8 68.0 17.5 2.3 7.6 0.0 208-3-60 8.3 68.0 13.0 2.3 5.2 0.0 230-3-60 8.3 68.0 13.0 2.3 5.2 0.0 460-3-60 5.1 34.0 8.0 1.3 2.6 0.0 575-3-60 3.2 26.0 5.0 1.3 2.0 0.0 208-1-60 15.4 86.0 24.0 2.3 7.6 0.0 230-1-60 15.4 86.0 24.0 2.3 7.6 0.0 208-3-60 11.5 84.0 18.0 2.3 5.2 0.0 230-3-60 11.5 84.0 18.0 2.3 5.2 0.0 460-3-60 5.8 42.0 9.0 1.3 2.6 0.0 575-3-60 5.1 34.0 8.0 1.3 2.6 0.0 MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 24.6 30 E05 4.0 1 19.2 33.5 35 E07 5.6 1 26.9 43.2 45 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 None - - - 24.6 30 E05 5.3 1 23.0 37.1 40 E07 7.5 1 32.6 48.6 50 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 None - - - 17.9 25 E05 4.0 1 11.1 20.4 25 E07 5.6 1 15.5 25.9 30 E10 8.0 1 22.2 34.3 35 E15 11.9 2 33.0 47.8 50 E20 15.9 2 44.1 61.7 70 None - - - 17.9 25 E05 5.3 1 13.3 22.4 25 E07 7.5 1 18.8 29.1 30 E10 10.6 1 26.6 38.4 40 E15 15.9 2 39.9 54.3 60 E20 21.2 2 53.2 70.2 80 None - - - 10.3 15 E07 6.8 1 8.5 13.5 15 E10 10.1 1 12.7 18.4 20 E15 13.6 2 17.1 23.7 25 E20 19.5 2 24.5 32.6 35 None - - - 7.0 15 E10 10.6 1 10.6 15.2 20 E15 15.9 1 16.0 21.6 25 E20 21.2 2 21.3 28.0 30 None - - - 29.1 35 E05 4.0 1 19.2 33.5 40 E07 5.6 1 26.9 43.2 45 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 None - - - 29.1 35 E05 5.3 1 23.0 37.1 40 E07 7.5 1 32.6 48.6 50 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 None - - - 21.9 30 E05 4.0 1 11.1 21.9 30 E07 5.6 1 15.5 25.9 30 E10 8.0 1 22.2 34.3 35 E15 11.9 2 33.0 47.8 50 E20 15.9 2 44.1 61.7 70 None - - - 21.9 30 E05 5.3 1 13.3 22.4 30 E07 7.5 1 18.8 29.1 30 E10 10.6 1 26.6 38.4 40 E15 15.9 2 39.9 54.3 60 E20 21.2 2 53.2 70.2 80 None - - - 11.1 15 E07 6.8 1 8.5 13.5 15 E10 10.1 1 12.7 18.4 20 E15 13.6 2 17.1 23.7 25 E20 19.5 2 24.5 32.6 35 None - - - 9.4 15 E10 10.6 1 10.6 15.2 20 E15 15.9 1 16.0 21.6 25 E20 21.2 2 21.3 28.0 30 Johnson Controls Unitary Products 35

TABLE 39: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT) Size (Tons) -05 (5.0) -A6 (6.0) Volt Compressors (each) 208-1-60 25.0 150.0 39.0 2.3 7.6 0.0 230-1-60 25.0 150.0 39.0 2.3 7.6 0.0 208-3-60 17.3 123.0 27.0 2.3 5.2 0.0 230-3-60 17.3 123.0 27.0 2.3 5.2 0.0 460-3-60 8.4 70.0 13.1 1.3 2.6 0.0 575-3-60 7.0 53.0 11.0 1.3 2.0 0.0 208-3-60 18.6 156.0 29.0 2.3 5.2 0.0 230-3-60 18.6 156.0 29.0 2.3 5.2 0.0 460-3-60 9.0 75.0 14.0 1.3 2.6 0.0 575-3-60 7.4 54.0 11.5 1.3 2.0 0.0 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 41.2 50 E05 4.0 1 19.2 41.2 50 E07 5.6 1 26.9 43.2 60 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 E30 22.2 2 106.7 142.9 150 None - - - 41.2 50 E05 5.3 1 23.0 41.2 50 E07 7.5 1 32.6 48.6 60 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 E30 29.6 2 128.7 163.7 175 None - - - 29.1 35 E05 4.0 1 11.1 29.1 35 E07 5.6 1 15.5 29.1 35 E10 8.0 1 22.2 34.3 45 E15 11.9 2 33.0 47.8 50 E20 15.9 2 44.1 61.7 70 E30 22.2 2 61.6 83.5 90 None - - - 29.1 35 E05 5.3 1 13.3 29.1 35 E07 7.5 1 18.8 29.1 35 E10 10.6 1 26.6 38.4 45 E15 15.9 2 39.9 54.3 60 E20 21.2 2 53.2 70.2 80 E30 29.6 2 74.3 95.5 100 None - - - 14.4 20 E07 6.8 1 8.5 14.4 20 E10 10.1 1 12.7 18.4 20 E15 13.6 2 17.1 23.7 25 E20 19.5 2 24.5 32.6 35 E30 28.8 2 36.1 46.6 50 None - - - 11.8 15 E10 10.6 1 10.6 15.2 20 E15 15.9 1 16.0 21.6 25 E20 21.2 2 21.3 28.0 30 E30 30.4 2 30.5 39.1 40 None - - - 30.8 40 E05 4.0 1 11.1 30.8 40 E07 5.6 1 15.5 30.8 40 E10 8.0 1 22.2 34.3 45 E15 11.9 2 33.0 47.8 50 E20 15.9 2 44.1 61.7 70 E30 22.2 2 61.6 83.5 90 None - - - 30.8 40 E05 5.3 1 13.3 30.8 40 E07 7.5 1 18.8 30.8 40 E10 10.6 1 26.6 38.4 45 E15 15.9 2 39.9 54.3 60 E20 21.2 2 53.2 70.2 80 E30 29.6 2 74.3 95.5 100 None - - - 15.1 20 E07 6.8 1 8.5 15.1 20 E10 10.1 1 12.7 18.4 20 E15 13.6 2 17.1 23.7 25 E20 19.5 2 24.5 32.6 35 E30 28.8 2 36.1 46.6 50 None - - - 12.3 15 E10 10.6 1 10.6 15.2 20 E15 15.9 1 16.0 21.6 25 E20 21.2 2 21.3 28.0 30 E30 30.4 2 30.5 39.1 40 36 Johnson Controls Unitary Products

TABLE 40: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE HIGH STATIC W/O POWERED CONVENIENCE OUTLET Size (Tons) -03 (3.0) -04 (4.0) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps 208-1-60 11.8 68.0 17.5 2.3 7.6 0.0 230-1-60 11.8 68.0 17.5 2.3 7.6 0.0 208-3-60 8.3 68.0 13.0 2.3 5.2 0.0 230-3-60 8.3 68.0 13.0 2.3 5.2 0.0 460-3-60 5.1 34.0 8.0 1.3 2.6 0.0 575-3-60 3.2 26.0 5.0 1.3 2.0 0.0 208-1-60 15.4 86.0 24.0 2.3 7.6 0.0 230-1-60 15.4 86.0 24.0 2.3 7.6 0.0 208-3-60 11.5 84.0 18.0 2.3 5.2 0.0 230-3-60 11.5 84.0 18.0 2.3 5.2 0.0 460-3-60 5.8 42.0 9.0 1.3 2.6 0.0 575-3-60 5.1 34.0 8.0 1.3 2.0 0.0 MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 24.6 30 E05 4.0 1 19.2 33.5 35 E07 5.6 1 26.9 43.2 45 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 None - - - 24.6 30 E05 5.3 1 23.0 37.1 40 E07 7.5 1 32.6 48.6 50 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 None - - - 17.9 25 E05 4.0 1 11.1 20.4 25 E07 5.6 1 15.5 25.9 30 E10 8.0 1 22.2 34.3 35 E15 11.9 2 33.0 47.8 50 E20 15.9 2 44.1 61.7 70 None - - - 17.9 25 E05 5.3 1 13.3 22.4 25 E07 7.5 1 18.8 29.1 30 E10 10.6 1 26.6 38.4 40 E15 15.9 2 39.9 54.3 60 E20 21.2 2 53.2 70.2 80 None - - - 10.3 15 E07 6.8 1 8.5 13.5 15 E10 10.1 1 12.7 18.4 20 E15 13.6 2 17.1 23.7 25 E20 19.5 2 24.5 32.6 35 None - - - 7.0 15 E10 10.6 1 10.6 15.2 20 E15 15.9 1 16.0 21.6 25 E20 21.2 2 21.3 28.0 30 None - - - 29.1 35 E05 4.0 1 19.2 33.5 40 E07 5.6 1 26.9 43.2 45 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105.1 110 None - - - 29.1 35 E05 5.3 1 23.0 37.1 40 E07 7.5 1 32.6 48.6 50 E10 10.6 1 46.1 64.7 70 E15 15.9 2 69.1 92.3 100 E20 21.2 2 92.2 119.9 125 None - - - 21.9 30 E05 4.0 1 11.1 21.9 30 E07 5.6 1 15.5 25.9 30 E10 8.0 1 22.2 34.3 35 E15 11.9 2 33.0 47.8 50 E20 15.9 2 44.1 61.7 70 None - - - 21.9 30 E05 5.3 1 13.3 22.4 30 E07 7.5 1 18.8 29.1 30 E10 10.6 1 26.6 38.4 40 E15 15.9 2 39.9 54.3 60 E20 21.2 2 53.2 70.2 80 None - - - 11.1 15 E07 6.8 1 8.5 13.5 15 E10 10.1 1 12.7 18.4 20 E15 13.6 2 17.1 23.7 25 E20 19.5 2 24.5 32.6 35 None - - - 9.4 15 E10 10.6 1 10.6 15.2 20 E15 15.9 1 16.0 21.6 25 E20 21.2 2 21.3 28.0 30 Johnson Controls Unitary Products 37

TABLE 40: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE HIGH STATIC W/O POWERED CONVENIENCE OUTLET Size (Tons) -05 (5.0) -A6 (6.0) Volt Compressors (each) 208-3-60 17.3 123.0 27.0 2.3 8.2 0.0 230-3-60 17.3 123.0 27.0 2.3 8.2 0.0 460-3-60 8.4 70.0 13.1 1.3 4.1 0.0 575-3-60 7.0 53.0 11.0 1.3 3.6 0.0 208-3-60 18.6 156.0 29.0 2.3 10.9 0.0 230-3-60 18.6 156.0 29.0 2.3 10.9 0.0 460-3-60 9.0 75.0 14.0 1.3 5.3 0.0 575-3-60 7.4 54.0 11.5 1.3 4.1 0.0 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 32.1 40 E05 4.0 1 11.1 32.1 40 E07 5.6 1 15.5 32.1 40 E10 8.0 1 22.2 38.0 45 E15 11.9 2 33.0 51.5 60 E20 15.9 2 44.1 65.4 70 E30 22.2 2 61.6 87.3 90 None - - - 32.1 40 E05 5.3 1 13.3 32.1 40 E07 7.5 1 18.8 32.8 40 E10 10.6 1 26.6 42.1 45 E15 15.9 2 39.9 58.1 60 E20 21.2 2 53.2 74.0 80 E30 29.6 2 74.3 99.3 100 None - - - 15.9 20 E07 6.8 1 8.5 15.9 20 E10 10.1 1 12.7 20.3 25 E15 13.6 2 17.1 25.6 30 E20 19.5 2 24.5 34.4 35 E30 28.8 2 36.1 48.4 50 None - - - 13.4 20 E10 10.6 1 10.6 17.2 20 E15 15.9 1 16.0 23.6 25 E20 21.2 2 21.3 30.0 30 E30 30.4 2 30.5 41.1 45 None - - - 36.5 45 E05 4.0 1 11.1 36.5 45 E07 5.6 1 15.5 36.5 45 E10 8.0 1 22.2 41.4 50 E15 11.9 2 33.0 54.9 60 E20 15.9 2 44.1 68.8 70 E30 22.2 2 61.6 90.7 100 None - - - 36.5 45 E05 5.3 1 13.3 36.5 45 E07 7.5 1 18.8 36.5 45 E10 10.6 1 26.6 45.5 50 E15 15.9 2 39.9 61.4 70 E20 21.2 2 53.2 77.4 80 E30 29.6 2 74.3 102.6 110 None - - - 17.9 25 E07 6.8 1 8.5 17.9 25 E10 10.1 1 12.7 21.8 25 E15 13.6 2 17.1 27.1 30 E20 19.5 2 24.5 35.9 40 E30 28.8 2 36.1 49.9 50 None - - - 14.4 20 E10 10.6 1 10.6 17.9 20 E15 15.9 1 16.0 24.2 25 E20 21.2 2 21.3 30.6 35 E30 30.4 2 30.5 41.7 45 38 Johnson Controls Unitary Products

TABLE 41: ELECTRICAL DATA - DK-03, -04, -05 & -A6 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET Size (Tons) -03 (3.0) -04 (4.0) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps 208-1-60 11.8 68.0 17.5 2.3 6.0 10.0 230-1-60 11.8 68.0 17.5 2.3 6.0 10.0 208-3-60 8.3 68.0 13.0 2.3 6.0 10.0 230-3-60 8.3 68.0 13.0 2.3 6.0 10.0 208-1-60 15.4 86.0 24.0 2.3 7.6 10.0 230-1-60 15.4 86.0 24.0 2.3 7.6 10.0 208-3-60 11.5 84.0 18.0 2.3 7.6 10.0 230-3-60 11.5 84.0 18.0 2.3 7.6 10.0 MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 33.0 40 E05 4.0 1 19.2 44.0 45 E07 5.6 1 26.9 53.7 60 E10 8.0 1 38.5 68.1 70 E15 11.9 2 57.2 91.5 100 E20 15.9 2 76.4 115.6 125 None - - - 33.0 40 E05 5.3 1 23.0 47.6 50 E07 7.5 1 32.6 59.1 60 E10 10.6 1 46.1 75.2 80 E15 15.9 2 69.1 102.8 110 E20 21.2 2 92.2 130.4 150 None - - - 29.1 35 E05 4.0 1 11.1 33.9 35 E07 5.6 1 15.5 39.4 40 E10 8.0 1 22.2 47.8 50 E15 11.9 2 33.0 61.3 70 E20 15.9 2 44.1 75.2 80 None - - - 29.1 35 E05 5.3 1 13.3 35.9 40 E07 7.5 1 18.8 42.6 45 E10 10.6 1 26.6 51.9 60 E15 15.9 2 39.9 67.8 70 E20 21.2 2 53.2 83.7 90 None - - - 39.1 50 E05 4.0 1 19.2 46.0 50 E07 5.6 1 26.9 55.7 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 None - - - 39.1 50 E05 5.3 1 23.0 49.6 50 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 None - - - 34.3 45 E05 4.0 1 11.1 35.9 45 E07 5.6 1 15.5 41.4 45 E10 8.0 1 22.2 49.8 50 E15 11.9 2 33.0 63.3 70 E20 15.9 2 44.1 77.2 80 None - - - 34.3 45 E05 5.3 1 13.3 37.9 45 E07 7.5 1 18.8 44.6 45 E10 10.6 1 26.6 53.9 60 E15 15.9 2 39.9 69.8 70 E20 21.2 2 53.2 85.7 90 Johnson Controls Unitary Products 39

TABLE 41: ELECTRICAL DATA - DK-03, -04, -05 & -A6 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET (CONT) Size (Tons) -05 (5.0) -A6 (6.0) Volt Compressors (each) 208-1-60 25.0 150.0 39.0 2.3 7.6 10.0 230-1-60 25.0 150.0 39.0 2.3 7.6 10.0 208-3-60 17.3 123.0 27.0 2.3 7.6 10.0 230-3-60 17.3 123.0 27.0 2.3 7.6 10.0 208-3-60 18.6 156.0 29.0 2.3 7.6 10.0 230-3-60 18.6 156.0 29.0 2.3 7.6 10.0 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 51.2 70 E05 4.0 1 19.2 51.2 70 E07 5.6 1 26.9 55.7 70 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 E30 22.2 2 106.7 155.4 175 None - - - 51.2 70 E05 5.3 1 23.0 51.2 70 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 E30 29.6 2 128.7 176.2 200 None - - - 41.5 50 E05 4.0 1 11.1 41.5 50 E07 5.6 1 15.5 41.5 50 E10 8.0 1 22.2 49.8 50 E15 11.9 2 33.0 63.3 70 E20 15.9 2 44.1 77.2 80 E30 22.2 2 61.6 99.0 100 None - - - 41.5 50 E05 5.3 1 13.3 41.5 50 E07 7.5 1 18.8 44.6 50 E10 10.6 1 26.6 53.9 60 E15 15.9 2 39.9 69.8 70 E20 21.2 2 53.2 85.7 90 E30 29.6 2 74.3 111.0 125 None - - - 43.2 60 E05 4.0 1 11.1 43.2 60 E07 5.6 1 15.5 43.2 60 E10 8.0 1 22.2 49.8 60 E15 11.9 2 33.0 63.3 70 E20 15.9 2 44.1 77.2 80 E30 22.2 2 61.6 99.0 100 None - - - 43.2 60 E05 5.3 1 13.3 43.2 60 E07 7.5 1 18.8 44.6 60 E10 10.6 1 26.6 53.9 60 E15 15.9 2 39.9 69.8 70 E20 21.2 2 53.2 85.7 90 E30 29.6 2 74.3 111.0 125 40 Johnson Controls Unitary Products

TABLE 42: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE W/POWERED CONVENIENCE OUTLET Size (Tons) -03 (3.0) -04 (4.0) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps 208-1-60 11.8 68.0 17.5 2.3 7.6 10.0 230-1-60 11.8 68.0 17.5 2.3 7.6 10.0 208-3-60 8.3 68.0 13.0 2.3 5.2 10.0 230-3-60 8.3 68.0 13.0 2.3 5.2 10.0 460-3-60 5.1 34.0 8.0 1.3 2.6 5.0 575-3-60 3.2 26.0 5.0 1.3 2.0 4.0 208-1-60 15.4 86.0 24.0 2.3 7.6 10.0 230-1-60 15.4 86.0 24.0 2.3 7.6 10.0 208-3-60 11.5 84.0 18.0 2.3 5.2 10.0 230-3-60 11.5 84.0 18.0 2.3 5.2 10.0 460-3-60 5.8 42.0 9.0 1.3 2.6 5.0 575-3-60 5.1 34.0 8.0 1.3 2.0 4.0 MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 34.7 45 E05 4.0 1 19.2 46.0 50 E07 5.6 1 26.9 55.7 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 None - - - 34.7 45 E05 5.3 1 23.0 49.6 50 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 None - - - 28.3 35 E05 4.0 1 11.1 32.9 35 E07 5.6 1 15.5 38.4 40 E10 8.0 1 22.2 46.8 50 E15 11.9 2 33.0 60.3 70 E20 15.9 2 44.1 74.2 80 None - - - 28.3 35 E05 5.3 1 13.3 34.9 40 E07 7.5 1 18.8 41.6 45 E10 10.6 1 26.6 50.9 60 E15 15.9 2 39.9 66.8 70 E20 21.2 2 53.2 82.7 90 None - - - 15.3 20 E07 6.8 1 8.5 19.7 20 E10 10.1 1 12.7 24.7 25 E15 13.6 2 17.1 29.9 30 E20 19.5 2 24.5 38.8 40 None - - - 11.2 15 E10 10.6 1 10.6 20.2 25 E15 15.9 1 16.0 26.6 30 E20 21.2 2 21.3 33.0 35 None - - - 39.1 50 E05 4.0 1 19.2 46.0 50 E07 5.6 1 26.9 55.7 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 None - - - 39.1 50 E05 5.3 1 23.0 49.6 50 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 None - - - 31.9 40 E05 4.0 1 11.1 32.9 40 E07 5.6 1 15.5 38.4 40 E10 8.0 1 22.2 46.8 50 E15 11.9 2 33.0 60.3 70 E20 15.9 2 44.1 74.2 80 None - - - 31.9 40 E05 5.3 1 13.3 34.9 40 E07 7.5 1 18.8 41.6 45 E10 10.6 1 26.6 50.9 60 E15 15.9 2 39.9 66.8 70 E20 21.2 2 53.2 82.7 90 None - - - 16.1 20 E07 6.8 1 8.5 19.7 20 E10 10.1 1 12.7 24.7 25 E15 13.6 2 17.1 29.9 30 E20 19.5 2 24.5 38.8 40 None - - - 13.4 15 E10 10.6 1 10.6 20.2 25 E15 15.9 1 16.0 26.6 30 E20 21.2 2 21.3 33.0 35 Johnson Controls Unitary Products 41

TABLE 42: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE W/POWERED CONVENIENCE OUTLET (CONT) Size (Tons) -05 (5.0) -A6 (6.0) Volt Compressors (each) 208-1-60 25.0 150.0 39.0 2.3 7.6 10.0 230-1-60 25.0 150.0 39.0 2.3 7.6 10.0 208-3-60 17.3 123.0 27.0 2.3 5.2 10.0 230-3-60 17.3 123.0 27.0 2.3 5.2 10.0 460-3-60 8.4 70.0 13.1 1.3 2.6 5.0 575-3-60 7.0 53.0 11.0 1.3 2.0 4.0 208-3-60 18.6 156.0 29.0 2.3 5.2 10.0 230-3-60 18.6 156.0 29.0 2.3 5.2 10.0 460-3-60 9.0 75.0 14.0 1.3 2.6 5.0 575-3-60 7.4 54.0 11.5 1.3 2.0 4.0 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 51.2 70 E05 4.0 1 19.2 51.2 70 E07 5.6 1 26.9 55.7 70 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 E30 22.2 2 106.7 155.4 175 None - - - 51.2 70 E05 5.3 1 23.0 51.2 70 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 E30 29.6 2 128.7 176.2 200 None - - - 39.1 50 E05 4.0 1 11.1 39.1 50 E07 5.6 1 15.5 39.1 50 E10 8.0 1 22.2 46.8 50 E15 11.9 2 33.0 60.3 70 E20 15.9 2 44.1 74.2 80 E30 22.2 2 61.6 96.0 100 None - - - 39.1 50 E05 5.3 1 13.3 39.1 50 E07 7.5 1 18.8 41.6 50 E10 10.6 1 26.6 50.9 60 E15 15.9 2 39.9 66.8 70 E20 21.2 2 53.2 82.7 90 E30 29.6 2 74.3 108.0 110 None - - - 19.4 25 E07 6.8 1 8.5 19.7 25 E10 10.1 1 12.7 24.7 25 E15 13.6 2 17.1 29.9 30 E20 19.5 2 24.5 38.8 40 E30 28.8 2 36.1 52.8 60 None - - - 15.8 20 E10 10.6 1 10.6 20.2 25 E15 15.9 1 16.0 26.6 30 E20 21.2 2 21.3 33.0 35 E30 30.4 2 30.5 44.1 45 None - - - 40.8 50 E05 4.0 1 11.1 40.8 50 E07 5.6 1 15.5 40.8 50 E10 8.0 1 22.2 46.8 50 E15 11.9 2 33.0 60.3 70 E20 15.9 2 44.1 74.2 80 E30 22.2 2 61.6 96.0 100 None - - - 40.8 50 E05 5.3 1 13.3 40.8 50 E07 7.5 1 18.8 41.6 50 E10 10.6 1 26.6 50.9 60 E15 15.9 2 39.9 66.8 70 E20 21.2 2 53.2 82.7 90 E30 29.6 2 74.3 108.0 110 None - - - 20.1 25 E07 6.8 1 8.5 20.1 25 E10 10.1 1 12.7 24.7 25 E15 13.6 2 17.1 29.9 30 E20 19.5 2 24.5 38.8 40 E30 28.8 2 36.1 52.8 60 None - - - 16.3 20 E10 10.6 1 10.6 20.2 25 E15 15.9 1 16.0 26.6 30 E20 21.2 2 21.3 33.0 35 E30 30.4 2 30.5 44.1 45 42 Johnson Controls Unitary Products

TABLE 43: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE HIGH STATIC W/POWERED CONVENIENCE OUTLET Size (Tons) -03 (3.0) -04 (4.0) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps 208-1-60 11.8 68.0 17.5 2.3 7.6 10.0 230-1-60 11.8 68.0 17.5 2.3 7.6 10.0 208-3-60 8.3 68.0 13.0 2.3 5.2 10.0 230-3-60 8.3 68.0 13.0 2.3 5.2 10.0 460-3-60 5.1 34.0 8.0 1.3 2.6 5.0 575-3-60 3.2 26.0 5.0 1.3 2.0 4.0 208-1-60 15.4 86.0 24.0 2.3 7.6 10.0 230-1-60 15.4 86.0 24.0 2.3 7.6 10.0 208-3-60 11.5 84.0 18.0 2.3 5.2 10.0 230-3-60 11.5 84.0 18.0 2.3 5.2 10.0 460-3-60 5.8 42.0 9.0 1.3 2.6 5.0 575-3-60 5.1 34.0 8.0 1.3 2.0 4.0 MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 34.7 45 E05 4.0 1 19.2 46.0 50 E07 5.6 1 26.9 55.7 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 None - - - 34.7 45 E05 5.3 1 23.0 49.6 50 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 None - - - 28.3 35 E05 4.0 1 11.1 32.9 35 E07 5.6 1 15.5 38.4 40 E10 8.0 1 22.2 46.8 50 E15 11.9 2 33.0 60.3 70 E20 15.9 2 44.1 74.2 80 None - - - 28.3 35 E05 5.3 1 13.3 34.9 40 E07 7.5 1 18.8 41.6 45 E10 10.6 1 26.6 50.9 60 E15 15.9 2 39.9 66.8 70 E20 21.2 2 53.2 82.7 90 None - - - 15.3 20 E07 6.8 1 8.5 19.7 20 E10 10.1 1 12.7 24.7 25 E15 13.6 2 17.1 29.9 30 E20 19.5 2 24.5 38.8 40 None - - - 11.2 15 E10 10.6 1 10.6 20.2 25 E15 15.9 1 16.0 26.6 30 E20 21.2 2 21.3 33.0 35 None - - - 39.1 50 E05 4.0 1 19.2 46.0 50 E07 5.6 1 26.9 55.7 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117.6 125 None - - - 39.1 50 E05 5.3 1 23.0 49.6 50 E07 7.5 1 32.6 61.1 70 E10 10.6 1 46.1 77.2 80 E15 15.9 2 69.1 104.8 110 E20 21.2 2 92.2 132.4 150 None - - - 31.9 40 E05 4.0 1 11.1 32.9 40 E07 5.6 1 15.5 38.4 40 E10 8.0 1 22.2 46.8 50 E15 11.9 2 33.0 60.3 70 E20 15.9 2 44.1 74.2 80 None - - - 31.9 40 E05 5.3 1 13.3 34.9 40 E07 7.5 1 18.8 41.6 45 E10 10.6 1 26.6 50.9 60 E15 15.9 2 39.9 66.8 70 E20 21.2 2 53.2 82.7 90 None - - - 16.1 20 E07 6.8 1 8.5 19.7 20 E10 10.1 1 12.7 24.7 25 E15 13.6 2 17.1 29.9 30 E20 19.5 2 24.5 38.8 40 None - - - 13.4 15 E10 10.6 1 10.6 20.2 25 E15 15.9 1 16.0 26.6 30 E20 21.2 2 21.3 33.0 35 Johnson Controls Unitary Products 43

TABLE 43: ELECTRICAL DATA - DK-03, -04, -05 & -A6 BELT DRIVE HIGH STATIC W/POWERED CONVENIENCE OUTLET Size (Tons) -05 (5.0) -A6 (6.0) Volt Compressors (each) 208-3-60 17.3 123.0 27.0 2.3 8.2 10.0 230-3-60 17.3 123.0 27.0 2.3 8.2 10.0 460-3-60 8.4 70.0 13.1 1.3 4.1 5.0 575-3-60 7.0 53.0 11.0 1.3 3.6 4.0 208-3-60 18.6 156.0 29.0 2.3 10.9 10.0 230-3-60 18.6 156.0 29.0 2.3 10.9 10.0 460-3-60 9.0 75.0 14.0 1.3 5.3 5.0 575-3-60 7.4 54.0 11.5 1.3 4.1 4.0 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option RLA LRA MCC FLA FLA FLA Model kw Stages Amps MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) None - - - 42.1 50 E05 4.0 1 11.1 42.1 50 E07 5.6 1 15.5 42.2 50 E10 8.0 1 22.2 50.5 60 E15 11.9 2 33.0 64.0 70 E20 15.9 2 44.1 77.9 80 E30 22.2 2 61.6 99.8 100 None - - - 42.1 50 E05 5.3 1 13.3 42.1 50 E07 7.5 1 18.8 45.3 50 E10 10.6 1 26.6 54.6 60 E15 15.9 2 39.9 70.6 80 E20 21.2 2 53.2 86.5 90 E30 29.6 2 74.3 111.8 125 None - - - 20.9 25 E07 6.8 1 8.5 21.6 25 E10 10.1 1 12.7 26.6 30 E15 13.6 2 17.1 31.8 35 E20 19.5 2 24.5 40.7 45 E30 28.8 2 36.1 54.7 60 None - - - 17.4 20 E10 10.6 1 10.6 22.2 25 E15 15.9 1 16.0 28.6 30 E20 21.2 2 21.3 35.0 35 E30 30.4 2 30.5 46.1 50 None - - - 46.5 60 E05 4.0 1 11.1 46.5 60 E07 5.6 1 15.5 46.5 60 E10 8.0 1 22.2 53.9 60 E15 11.9 2 33.0 67.4 70 E20 15.9 2 44.1 81.3 90 E30 22.2 2 61.6 103.2 110 None - - - 46.5 60 E05 5.3 1 13.3 46.5 60 E07 7.5 1 18.8 48.7 60 E10 10.6 1 26.6 58.0 60 E15 15.9 2 39.9 73.9 80 E20 21.2 2 53.2 89.9 90 E30 29.6 2 74.3 115.1 125 None - - - 22.9 30 E07 6.8 1 8.5 23.1 30 E10 10.1 1 12.7 28.1 30 E15 13.6 2 17.1 33.3 35 E20 19.5 2 24.5 42.2 45 E30 28.8 2 36.1 56.2 60 None - - - 18.4 25 E10 10.6 1 10.6 22.9 25 E15 15.9 1 16.0 29.2 30 E20 21.2 2 21.3 35.6 40 E30 30.4 2 30.5 46.7 50 44 Johnson Controls Unitary Products

TABLE 44: PHYSICAL DATA EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FANS CONDENSER COILS COMPRESSOR (Qty. Per Unit) AIR FILTERS CHARGE MODELS DK -03-04 -05 -A6 Centrifugal Blower (Belt Drive) (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 12 X 10 Centrifugal Blower (Direct Drive) (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 12 X 11 Fan Motor HP (Direct Drive) 3/4 1 1 1 Fan Motor HP (Belt Drive) 1 1/2 1 1/2 1 1/2 1 1/2 Fan Motor HP (Belt Drive High Static) 1 1/2 1 1/2 2 3 Rows Deep 3 4 4 4 Fins Per Inch 13 13 13 13 Face Area (Sq. Ft.) 5.1 5.1 5.1 5.1 Propeller Dia. (in.) 24 24 24 24 Fan Motor Hp 1/2 1/2 1/2 1/2 Nom. CFM 4500 4500 4500 4500 Rows Deep 2 2 2 2 Fins Per Inch 18 18 18 18 Face Area (Sq. Ft.) 17.1 17.1 17.1 17.1 Qty / Type 1/Recip 1/Recip 1/Scroll 1/Scroll Quantity Per Unit (15 X 20 X 1 or 2 ) 2 2 2 2 Quantity Per Unit (14 X 25 X 1 or 2 ) 1 1 1 1 Total Face Area (sq. ft.) 6.6 6.6 6.6 6.6 Refrigerant 22 (lbs./oz.) 10/8 10/0 10/0 10/0 TABLE 45: ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAGE kw CAP. MULTIPLIER 208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92 TABLE 46: VOLTAGE LIMITATIONS 1 POWER SUPPLY VOLTAGE MIN. MAX. 208/230-1-60 187 252 208/230-3-60 187 252 460-3-60 432 504 575-3-60 540 630 1. Utilization Range A in accordance with ARI Standard 110. Johnson Controls Unitary Products 45

REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTEC- TION AND WIRING. FIGURE 7 - TYPICAL POWER WIRING TWO STAGE THERMOSTAT SINGLE STAGE HEAT 2 STAGE THERMOSTAT ** = Minimum wire size of 18 AWG R wire should be used for all field installed 24 volt wire. G UNIT CONTROL BOARD TERMINAL STRIP ** R G Y1 Y1 Y2 W C Y/Y2 W C 24 VOLT TRANSFORMER PROGRAMMABLE THERMOSTAT ONLY * DEHUMIDISTAT * DEHUMIDISTAT CLOSES ON RISE IN HUMIDITY Yellow Yellow WIRES LOCATED IN UNIT CONTROL BOX LOW VOLTAGE SECTION TWO STAGE THERMOSTAT TWO STAGE HEAT 2 STAGE THERMOSTAT ** = Minimum wire size of 18 AWG R wire should be used for all field installed 24 volt wire. G UNIT CONTROL BOARD TERMINAL STRIP ** R G Y1 Y1 Y2 W1 Y/Y2 W1 24 VOLT TRANSFORMER W2 W2 C C PROGRAMMABLE THERMOSTAT ONLY * DEHUMIDISTAT * DEHUMIDISTAT CLOSES ON RISE IN HUMIDITY Yellow Yellow WIRES LOCATED IN UNIT CONTROL BOX LOW VOLTAGE SECTION FIGURE 8 - TYPICAL REHEAT CONTROL WIRING 46 Johnson Controls Unitary Products

FIGURE 9 - UNIT DIMENSIONS (3-6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW FIGURE 10 - UNIT DIMENSIONS (3-6 TON COOLING/GAS HEAT) FRONT VIEW Johnson Controls Unitary Products 47

REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTEC- TION AND WIRING. DETAIL A FIGURE 11 - UNIT WITH ECONOMIZER RAINHOOD DETAIL B FIGURE 12 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD 48 Johnson Controls Unitary Products

FIGURE 13 - UNIT DIMENSIONS (REAR VIEW) TABLE 47: UTILITIES ENTRY Filter Access Blower Motor Access Dot Plugs Field-Supplied Disconnect Switch Location Mounting Bracket for Disconnect Switch (Field Supplied) A,B Wiring Entry (See Detail B ) FIGURE 14 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 47: UTILITIES ENTRY Disconnect Switch Location and Motor Access Panel for Unit with Belt-Drive Option Control Box Access HOLE OPENING SIZE (DIA.) USED FOR A 7/8 KO 1 Control Wiring 2 Side Bottom B 2 KO 1 Side Power Wiring Bottom C 1-5/8 KO Gas Piping (Front) HOLE OPENING SIZE (DIA.) USED FOR D 1-1/2 KO Gas Piping (Bottom) 1. Opening in the bottom to the unit can be located by the side in the insulation. 2. Do not remove the 2 knockout ring. TABLE 48: MINIMUM CLEARANCES LOCATION Front Rear CLEARANCE 24 (/Electric Heat) 32 (Gas Heat) 12 (Less Economizer) 36 (With Economizer or Fixed Air/ Motorized Damper) Left Side (Filter Access) 24 (Less Economizer) 36 (With Economizer) Right Side (Cond. Coil) 24 Below Unit 1 0 Above Unit 2 72 (For Condenser Air Discharge) 1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. Johnson Controls Unitary Products 49

FIGURE 15 - TYPICAL APPLICATIONS 50 Johnson Controls Unitary Products