A Novel Technique for Energy & Cost Effective Drives for AC & DC Motors

Similar documents
Starting of Induction Motors

EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION

Question Number: 1. (a)

Full Voltage Starting (Number of Starts):

INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF MECHANICAL ENGINEERING ME 6351 ELECTRICAL DRIVES AND CONTROL UNIVERSITY QUESTIONS AND ANSWERS

ESO 210 Introduction to Electrical Engineering

(d) None of the above.

ELECTRICAL MAINTENANCE

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

Soft Start for 3-Phase-Induction Motor

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

2. Draw the speed-torque characteristics of dc shunt motor and series motor. (May2013) (May 2014)

EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1

Reduction of Harmonic Distortion and Power Factor Improvement of BLDC Motor using Boost Converter

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

A Comparative Performance Analysis DCR and DAR Squirrel Cage 3-Phase Induction Motor

2014 ELECTRICAL TECHNOLOGY

PHY 152 (ELECTRICITY AND MAGNETISM)

Regulation: R16 Course & Branch: B.Tech EEE

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier

Chapter 5: DC Motors. 9/18/2003 Electromechanical Dynamics 1

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Induction Generator: Excitation & Voltage Regulation

694 Electric Machines

Development and Analysis of Bidirectional Converter for Electric Vehicle Application


Principles of iers (intelligent

Real And Reactive Power Saving In Three Phase Induction Machine Using Star-Delta Switching Schemes

Abstract- A system designed for use as an integrated starter- alternator unit in an automobile is presented in this paper. The

10. Starting Method for Induction Motors

Just what is an alternator?

DC CIRCUITS ELECTROMAGNETISM

SPEED CONTROL OF THREE PHASE INDUCTION MACHINE USING MATLAB Maheshwari Prasad 1, Himmat singh 2, Hariom Sharma 3 1

Handout Activity: HA773

R07 SET - 1

A matrix converter based drive for BLDC motor Radhika R, Prince Jose

PERFORMANCE AND ENHANCEMENT OF Z-SOURCE INVERTER FED BLDC MOTOR USING SLIDING MODE OBSERVER

CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

DEPARTMENT OF EI ELECTRICAL MACHINE ASSIGNMENT 1


ROTATING MAGNETIC FIELD

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

ECE1750, Spring Motor Drives and Other

Electrical Drives I. Week 11: Three phase Induction Motor Starting

Analysis of Energy Saving Methods in different Motors for Consumer Applications

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Electrical Machines-I (EE-241) For S.E (EE)

PAC TRAINING PUMP MOTORS

QUESTION BANK SPECIAL ELECTRICAL MACHINES

G Prasad 1, Venkateswara Reddy M 2, Dr. P V N Prasad 3, Dr. G Tulasi Ram Das 4

Induction Motor Control

St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad

GENERATION, CONVERSION, OR DISTRIBUTION OF ELECTRIC POWER

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

Performance Analysis of Medium Voltage Induction Motor Using Stator Current Profile

Modeling and Simulation of Firing Circuit using Cosine Control System

Jogging and Plugging of AC and DC Motors. Prepared by Engr. John Paul Timola, LPT

IMPACT OF SKIN EFFECT FOR THE DESIGN OF A SQUIRREL CAGE INDUCTION MOTOR ON ITS STARTING PERFORMANCES

Application Note CTAN #127

Fully Regenerative braking and Improved Acceleration for Electrical Vehicles

SHRI ANGALAMMAN COLLEGE OF ENGINEERING AND TECHNOLOGY (An ISO 9001:2008 Certified Institution) SIRUGANOOR, TIRUCHIRAPPALLI

AC MOTOR TYPES. DESCRIBE how torque is produced in a single-phase AC motor. EXPLAIN why an AC synchronous motor does not have starting torque.

Conference on, Article number 64020

VARIABLE FREQUENCY DRIVE AND ITS INDUSTRIAL APPLICATIONS

SENSORLESS CONTROL OF BLDC MOTOR USING BACKEMF BASED DETECTION METHOD

R13 SET - 1. b) Describe different braking methods employed for electrical motors. [8M]

A Comprehensive Study on Speed Control of DC Motor with Field and Armature Control R.Soundara Rajan Dy. General Manager, Bharat Dynamics Limited

A CURRENT-SOURCE-INVERTER-FED INDUCTION MOTOR DRIVE SYSTEM WITH REDUCED LOSSES

Asynchronous slip-ring motor synchronized with permanent magnets

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR

A Dual Stator Winding-Mixed Pole Brushless Synchronous Generator (Design, Performance Analysis & Modeling)

Speed Control of D.C. MOTOR Using Chopper

SIMULINK Based Model for Determination of Different Design Parameters of a Three Phase Delta Connected Squirrel Cage Induction Motor

GROUP OF INSTITUTIONS :: PUTTUR UNIT I SINGLE PHASE TRANSFORMERS

Induction machine characteristics and operation. Induction Machines

ADVANCES in NATURAL and APPLIED SCIENCES

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Automatic Bidirectional Starter For Induction Motor

CHAPTER 3 EFFICIENCY IMPROVEMENT IN CAGE INDUCTION MOTORS BY USING DCR TECHNOLOGY

Single Phase Induction Motor. Dr. Sanjay Jain Department Of EE/EX

Transient analysis of a new outer-rotor permanent-magnet brushless DC drive using circuit-field-torque coupled timestepping finite-element method

Key words: Consumption of Electrical Energy, Slip Ring Induction Motor, Mine Haulers, Rheostatic, Static Control.

Comprehensive Technical Training

Advance Electronic Load Controller for Micro Hydro Power Plant

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Electrical Machines II. Week 5-6: Induction Motor Construction, theory of operation, rotating magnetic field and equivalent circuit

Syllabus for the Trade of Electrician Duration : Six Month Second Semester Semester Code: ELE: SEM II

SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL ELECTRICAL MACHINES

Contents. Review of Electric Circuitd. Preface ;

FAULT ANALYSIS FOR VOLTAGE SOURCE INVERTER DRIVEN INDUCTION MOTOR DRIVE

PERFORMANCE ANALYSIS OF BLDC MOTOR SPEED CONTROL USING PI CONTROLLER

ENERGY CONSERVATION IN AUTOMATIC FLUID FLOW CONTROL USING VARIABLE FREQUENCY DRIVE

Electrical Machines -II

IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR

INTRODUCTION. I.1 - Historical review.

CHAPTER 6 INTRODUCTION TO MOTORS AND GENERATORS

Isolated Bidirectional DC DC Converter for SuperCapacitor Applications

Transcription:

International Journal of Electrical Engineering. ISSN 0974-2158 Volume 3, Number 3 (2010), pp. 241--250 International Research Publication House http://www.irphouse.com A Novel Technique for Energy & Cost Effective Drives for AC & DC Motors M. Ravindran 1 and V. Kirubakaran 2 1 Research Scholar, 2 Assistant Professor 1,2 Rural Energy Centre, Gandhigram Rural Institute Gandhigram, Tamilnadu, India-624302 E-mail: ravinec99@gmail.com Abstract This paper presents a new approach to reduce the losses of A.C & D.C motor by using the modified system. Energy Conservation is the starting point of an Energy Management plan to reduce the overall cost of production and operation. Normally AC and DC motor consumes large amount of electrical power. Energy conservation in AC motors can be achieved by using voltage control with respect to load current. In the conventional Star-delta starter the motor is switched over to delta mode after fixed starting time delay, the applied voltage remains same independent of the load conditions. Thus even during light load conditions the motor continues to draw the same magnetizing current thereby reducing the power factor and hence the overall efficiency of the motor reduces, this can be avoided by using a modified star-delta starter. If full voltage (rated voltage) is applied at no load condition, then the power consumption for the DC and AC motors will be increased. In this paper we are sensing the load current and changing the star or delta mode of connection at the input of the motor, so that the efficiency and the power factor can be improved. The calculated values are compared with the measurement, in order to evaluate a validity of the proposed method. Introduction An electric motor is usually switched on to the supply through a starter. If it is directly switched on, it draws starting current equal to 5 to 8 times of full load current and develop starting torque only 1 to 1.5 times of full load torque[1]. This amount of starting current is objectionable because it affects the system voltage momentarily. The starting torque developed may not be starting current and to improve the starting torque, we are going for starters.

242 M. Ravindran and V. Kirubakaran A number of starters are available for different electric motors. For three-phase induction motors, Star-delta starter can be used. To improve the starting torque, power factor, to reduce the copper loss, core loss and hence to improve the efficiency, we are adding an external circuit with the existing automatic star-delta starter. This modified automatic star-delta starter is used for variable load three phase induction motor. By use of this starter the efficiency of the AC motor can be improved, when load increases above 50 % of full load current, the motor will run at delta connection and if it s less than 50 % of full load current, it will run at star mode, so that efficiency and power factor can be improved. If low voltage(reduced voltage) is applied to the armature winding of DC motor, then power consumption will be very low and hence overall efficiency of motor is increased[8]. These are applicable to industries where variable load conditions exist. Existing System Starters for 3-phase squirrel-cage Induction motors often use star-to-delta converters. The stator coils of the motor are connected in star configuration at the time of power on and switched to delta configuration when the motor reaches 3/4 th of its full speed, after the stator coils have developed sufficient back electromagnetic force. Losses in Induction Motors Losses in motor are divided into a number of different components. These are friction losses, windage losses, copper and iron losses. The major losses are the iron and copper losses. Worthwhile power savings are only achievable, where the iron losses is in appreciable portion of the total power consumed by the motor and where the amount of the iron loss is significant to the motor rating. Iron Losses Iron Loss (%) 18 16 14 12 10 8 6 4 2 0 0 50 100 150 200 250 300 350 400 Motor Size (kw) Figure 1- Iron losses vs motor size Need for Starters The need for starting devices for motor will become apparent by considering the case of a usual 10 HP, 230 volts motor, which may have a stator resistance about 0.25 ohm. At the moment of starting the motor, the stator is stationary, so no back emf is

A Novel Technique for Energy & Cost Effective Drives 243 there. If the motor is connected directly across a 230 V power source, the only factor which limits the current drawn from the supply is the stator circuit resistance, which is very low and the current drawn will be very large (230/0.25 or 920 A) while the rated current may be only about 30 to 40 A. It will damage the brushes, winding of the motor and blow out the main fuses. Such a large current is not desirable. To guard against that excessive starting current, a resistance may be inserted in series with the motor stator during the starting period, which may gradually be cut-out as the back emf develops. Almost all heavy induction motors make use of star-delta motor starters to reduce the starting current. In simple words, starting current I = (V-E)/Z where V is the applied voltage, E is the back emf and Z is the impedence of the rotor. Since back emf E is directly proportional to the speed of rotation of rotor, initially when the motor starts from rest, this back emf is zero. Thus if full voltage is applied to the motor winding, a very large initial current may be set up in the winding resulting in large copper loss. To prevent this, various kinds of starters are used. The conditions depend on the position of the tapping on the transformer winding, i.e. on the secondary voltage. Usually three or more tappings are provided so that there is a choice of starting conditions such as 40, 60 or 75% of line voltage[2]. The starting torques on these different tappings can be estimated as they are proportional to the square of the voltage. On the 60% tapping the torque will be approximately the same as with stardelta starting, and on the 40 and 75% tapping it will be proportionately lower and higher respectively. Star-Delta Starter At start, the line voltage is applied to one end of each of the three windings, with the other ends bridged together, effectively connecting the windings in star configuration. Under this connection, the voltage across the windings is 1 3 of line-to-line supply voltage and so the current flowing through each winding is also reduced by this factor. Compared to delta connection, the resultant current flowing from the supply, as also the torque, is reduced by a factor of 1/3 is star configuration. Modified System During the light loading conditions the external circuit added will make the starconnection at the input of the induction motor and during heavily loaded conditions,[3] the external circuit added will make the delta connection at the input of the three phase induction motor and hence the overall efficiency and the power factor will be improved. Advantages of reduced voltage to motor under low loading Under reduced voltage conditions the magnetizing current and hence the overall current drawn by the motor is less. This not only reduces the copper loss and core loss, but also improves the power factor and the overall efficiency. It can only be improved when it is dropped considerably below the maximum efficiency of the motor as shown in the figure[6].

244 M. Ravindran and V. Kirubakaran Efficiency at various loads Efficiency(%) 90 80 70 60 50 40 30 20 10 0 0 20 40 60 80 100 120 Load(watts) Fig 2-Efficiency at various loads As the maximum energy that can be saved is the portion of the iron loss, best saving are going to be in motors with high iron losses. Therefore the maximum energy savings can be made below 50% load in small motors of less than 10kw rating. Experimental Setup and Procedure The Star Delta Starter can only be used with a motor which is rated for connection in delta each of the three windings available individually. At start, the line voltage is applied to one end of each of the three windings, with the other end bridged together, effectively connecting the windings is 1/(1/732) of line voltage and so the current flowing in each winding is also reduced by this amount[5]. The resultant current flowing from the supply is reduced by a factor of 1/3 as is the torque. A low voltage is applied to the motor in the initial stage for fixed duration of time. During this interval, the motor gains appreciable speed, thereafter, full voltage is applied. Since line-to-line voltages in Delta mode is 1.732 times in Star mode, the motor is started with star connections, which ultimately change over to Delta mode after a fixed interval of time. The motor remains in Delta mode till next start up. Both ends of each phase of the motor starter windings must be brought out and connected to starter. In the start position the windings are connected in star; in the running position they are reconnected in delta. The voltage across each phase winding in the start position is 58% of line voltage, with consequent reduction of starting current. The starting torque is also reduced to one-third of that which would obtain with D.O.L. starting. With a single-cage or double-cage rotor of average performance, this represent about 80% of full-load torque, assuming normal line voltage, but if there is appreciable line drop the torque will be proportionately lower. These factors must be taken into account when deciding whether star-delta starting is acceptable for the driven machine. It will be acceptable for centrifugal fans and pumps if, in the later case, the friction at starting is not excessive. When the operating handle is placed in the start position the motor stator windings are connected in star across the supply. As the motor approaches normal

A Novel Technique for Energy & Cost Effective Drives 245 running speed the operator must quickly change the handle to run position which changes the motor connection from star to delta. If the operator does not move the handle quickly from start to run the motor may be disconnected from the supply long enough for the motor speed to fall considerably. When the handle is eventually put into the run position the motor will take a large current may be large current and accelerate up to speed again[7]. This surge current may be large enough to cause appreciable voltage dip. To prevent this, a mechanical interlock is fitted to the operating handle. The handle must be moved quickly from start to run otherwise the interlock jams the handle in the start position. Figure 3- Modified Automatic 3-phase induction Motor Starter Three single-phase transformers are used to step-down the 3-phase supply separately. Phases R, Y and B are stepped down by transformers X1, X2 and X3 to deliver the secondary output of 12V at 300mA. The transformer output is rectified by a full-wave rectifier and filtered by a capacitor. The three 12V DC supplies drive relays RL1, RL2 and RL3, respectively. When all the three phases are present, the 12V DC supply derived from the R phase is fed to the coil of relay RL3 and the timer circuit through the contacts of relays RL1 and RL2. As a result, relay RL3 energises. Simultaneously, timer NE555 (IC1), which is configured as a monostable multivibrator, is also triggered. Its time period is determined by capacitor C4, resistor R1 and preset VR1. Preset VR1 is used to set the time period required to reach 3/4 th of the full speed of the motor. The negative triggering pulse for IC1 is provided by the combination of resistor VR1, R1 and capacitor C4. The timer output at pin 3 is connected to the base of transistor T2 via resistor R2. As a result, transistor T2 is driven to saturation and relay RL4 energises (indicated by glowing of LED2). Thus at

246 M. Ravindran and V. Kirubakaran power-on, relay RL3, as also R4, energises (if all three phases are present) to connect the stator windings in star configuration. On tracing the connections you will observe that R phase is connected to R1 end of R windings, Y phase is connected to Y1 end of Y windings and B phase is connected to B1 terminal of B stator windings. The other ends of all the stator windings (i.e., R2, Y2, and B2) gets bridged together to form star connection. After the specified delay, which is provided for the speed of the motor to 3/4 th of its full speed value, the monostable output goes low to cut off transistor T2 and deenergise relay RL4. The motor stator coils now switch to delta configuration. Now you will observe that R phase gets connected to the junction of R1 and B2 terminals, Y phase is connected to Y1 and R2 terminals and B phase is connected to B1 and Y2 terminals of the stator windowing. This connection conforms to delta configuration. Since the output of IC1 is low in this state, pnp transistor T1 is forward biased to light up LED1 and indicate delta configuration[9]. Figure 4: Comparator Figure 5: Over all Block Diagram Energy savings in three phase induction motor by using modified automatic star -Delta starter

A Novel Technique for Energy & Cost Effective Drives 247 Table.1: Result for modified star delta starter. Sl. No. Existing System at no load Modified System at no load Voltage(V) Current(A) Power(W) Voltage(V) Current(A) Power(W) 1. 2. 3. 4. 5. 420 415 400 395 390 3 3.4 4.2 5.6 7 1008 1110 1338 1765 2178 420 415 400 395 390 2.2 2.6 3 3.8 4.2 734 866 958 1198 1310 Energy Savings in DC motor by using PIC Controller The DC motor is a self regulating machine because the development of back emf makes the DC motor to draw as much armature current which is just sufficient to develop the required load torque[4]. Armature current Ia = V - Eb Ra Existing System No Load Conditions When the DC motor is operating on no load condition, small torque is required to overcome the friction and windage losses. Therefore back emf is nearly equal to input voltage and armature current is small i.e., Ia is very low. Eb = V During the light load conditions at the rated voltage the magnetizing current drawn by the DC motor is high. Where the Core losses and Copper losses of a DC motor are not reduced and hence the over all efficiency of the DC motor is reduced. Load Conditions When the DC motor is operating on loaded condition, driving torque of the DC motor is not sufficient to counter the increased retarding torque due to load. Hence, armature slows down (motor speed decreases) and motor back emf Eb also decreases. Corresponding armature current Ia increases. The increase torque, the motor continues to slow down till the driving torque matches the load torque and then steady state conditions are reached. When the load on DC motor is decreased, the driving torque developed is momentarily in excess of the load requirement so that, motor armature is accelerated (motor speed increases). As the motor speed increases, the back emf Eb also increases causing armature current to decrease. The decrease in armature current causes decrease in driving torque and steady state conditions are reached, when the driving torque is equal to the load torque. Under rated Voltage at Load Conditions the magnetizing current drawn by the DC motor is less. Under full load condition efficiency of the DC motor is high. The maximum efficiency of the DC motor is as shown in the following figure

248 M. Ravindran and V. Kirubakaran Modified System No Load Conditions During the light load conditions the PIC controller will reduce the input armature voltage of the DC motor at no load current and hence overall efficiency of the DC motor will be increased. Load Conditions During heavily loaded conditions the PIC controller circuit added will increase the armature voltage of the DC motor at load current and hence overall efficiency of the DC motor will be increased. Figure 7: Modified system using PIC controller on D.C motor Table.2: Result for modified D.C motor converter(armature 190V) Sl. No. Armature Current Torque in N.m Input Power Output Power Efficiency Voltage 1. 2. 3. 4. 170 170 170 170 4.2 5.2 7.5 9.2 0.736 2.06 4.42 6.03 714 884 1275 1564 98.15 270.38 612.61 785.1 13.74 30.58 48.04 50.19 Table.3: for modified D.C motor converter(armature 170V) Sl. No. 1. 2. 3. 4. Armature Voltage 190 190 190 190 Current Torque in N.m 4.2 0.44 5.2 1.18 7.5 4.12 9.2 5.89 Input Power 798 988 1425 1748 Output Power 62.83 168.50 596.99 847.28 Efficiency 7.8 17.05 41.89 48.47

A Novel Technique for Energy & Cost Effective Drives 249 Under the above conditions the magnetizing current and the overall current drawn by the motor is constant. The total power consumed by the motor is very low.this not only reduces the copper loss, but also improves the overall efficiency of the DC motor. Conclusion We can observe that in AC motors the automatic star delta starter circuit presented here offers two main advantages. First one is single phase prevention and next is automatic start Delta conversion. The load sensing circuit is added to this starter. It improves the efficiency of the AC motor because in no load conditions the motor runs in star mode and in loaded condition the AC motor runs in delta mode. So the efficiency is increased. In DC motor the external electronics circuit is very useful to change the voltage with respect to load current for better Energy conservation. Further advantages of these methods are of Less expensive Easy maintenance Noiseless Compact References [1] Wei-Jen Lee; Kenarangui, R.;Energy management for motors, systems, and electrical equipment Industry Applications, IEEE Transactions Volume 38, Issue 2, March-April 2002 Page(s):602 607 [2] Bonnett, A.H.; An update on AC induction motor efficiency Industry Applications, IEEE Transactions Volume 30, Issue 5, Sept.-Oct. 1994 Page(s):1362 1372 [3] Sundareswaran, K.; Jos, B.M.; Development and analysis of novel softstarter/energy-saver topology for delta-connected induction motors Electric Power Applications, IEE Proceedings [4] Zabardast, A.; Mokhtari, H.; Effect of high-efficient electric motors on efficiency improvement and electric energy saving. [5] Hsu, J.S.; Kueck, J.D.; Olszewski, M.; Casada, D.A.; Otaduy, P.J.; Tolbert, L.M.; Comparison of induction motor field efficiency evaluation methods Industry Applications, IEEE Transactions [6] Schachter, N.; Ruesch, U.;Synchronous and slip-ring induction motors drive cement mills Industry Applications Magazine, IEEE [7] Sundareswaran, K.; An improved energy-saving scheme for capacitor-run induction motor Industrial Electronics, IEEE Transactions [8] Bhansali, V.K.; Energy conservation in India - challenges and achievements, Industrial Automation and Control, 1995 (I A & C'95), IEEE/IAS International Conference on (Cat. No.95TH8005)

250 M. Ravindran and V. Kirubakaran [9] Lu Guangqiang; Luo Guangfu; Yu Hongxiang; Ji Yanchao;Energy conservation of a novel soft starter controlled by IGBT for induction motors with minimum current Industrial Electronics, 2004 IEEE International Symposium