Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

Similar documents
Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

PV Grid Integration Research in the U.S.

Renewable Grid Integration Research in the U.S.

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

Using Hosting Capacity Methodology to Develop Simplified Screens for New Solar PV Interconnections

Essential Reliability Services From PV Plants

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

DISTRIBUTED GENERATION FROM SMALL HYDRO PLANTS. A CASE STUDY OF THE IMPACTS ON THE POWER DISTRIBUTION NETWORK.

Y9. GEH2.3: FREEDM Cost Benefit Analysis based on Detailed Utility Circuit Models

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

Distribution System DER Hosting Capacity IEEE34 PV

The Role of Electricity Storage on the Grid each location requires different requirements

Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

DEMONSTRATION OF ESSENTIAL RELIABILITY SERVICES BY A 300-MW SOLAR PV POWER PLANT

Analysis of Grid Connected Solar Farm in ETAP Software

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Characterization of Voltage Rise Issue due to Distributed Solar PV Penetration

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

By Mahesh Morjaria, Dmitriy Anichkov, Vladimir Chadliev and Sachin Soni First Solar, Tempe, Arizona

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Implementation of Distributed Generation

ENOW SOLAR TEST RESULTS:

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

Impact of High Photo-Voltaic Penetration on Distribution Systems. Design Document

Grid Stability Analysis for High Penetration Solar Photovoltaics

Behaviour of battery energy storage system with PV

POWER FLOW MODELLING IN ELECTRIC NETWORKS WITH RENEWABLE ENERGY SOURCES IN LARGE AREAS

Potential Negative Impact on Reliability of Distributed Generation under Temporary Faults

Rate Impact of Net Metering. Jason Keyes & Joseph Wiedman Interstate Renewable Energy Council April 6, 2010

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

The North Carolina solar experience: high penetration of utility-scale DER on the distribution system

Voltage Control Strategies for Distributed Generation

Increasing PV Hosting Capacity in Distribution Networks: Challenges and Opportunities. Dr Andreas T. Procopiou

INTEGRATING PLUG-IN- ELECTRIC VEHICLES WITH THE DISTRIBUTION SYSTEM

Essential Reliability Services Engineering the Changing Grid

An Integrated Grid Path for Solar. Thomas Key, EPRI Senior Technical Executive. ISES Webinar. April 22, 2016

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

Solar Development in New Jersey, and PV Impacts on the Distribution System Carnegie Mellon Conference on the Electricity Industry - March 9, 2011

Georgia Transmission Corporation Georgia Systems Operations Corporation

Assessing Feeder Hosting Capacity for Distributed Generation Integration

Power System Analysis for a Utility with Localized Wind Generation: Southern Negros Oriental Case

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

Residential Lighting: Shedding Light on the Remaining Savings Potential in California

PES Cook Islands KEMA Grid Study Final Report

The future role of storage in a smart and flexible energy system

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Smart- Grid Ready PV Inverter

Possibilities of Distributed Generation Simulations Using by MATLAB

Optimal and Modular Configuration of Wind Integrated Hybrid Power Plants for Off-Grid Systems

Sensitivity Analysis of Photovoltaic Hosting Capacity of Distribution Circuits

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Targeted Application of STATCOM Technology in the Distribution Zone

Group 3: Pricing from 1 April 2018 and load management

MILLIGAN SOLAR PROJECT

Stability Study for the Mt. Olive Hartburg 500 kv Line

Impacts of Fast Charging of Electric Buses on Electrical Distribution Systems

DC Power Grid System Lighting for a Typical Conference Room Evaluation

Modeling Distribution System Impacts of Solar Variability and Interconnection Location

Generator Interconnection System Impact Study For

Distribution System Analysis Tools for Studying High Penetration of PV with Grid Support Features. Raja Ayyanar

ABB POWER SYSTEMS CONSULTING

To Shift or not to Shift?

Solar Photovoltaic Inverter Current Distribution during Fault on Distribution and Transmission System

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

Implementing a Microgrid Using Standard Utility Control Equipment

Small Electrical Systems (Microgrids)

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Current State of the Renewable Energy in Kyushu Electric Power and Our Future Plan. Kyushu Electric Power Co. Inc. June 8, 2017

Impact Analysis of Fast Charging to Voltage Profile in PEA Distribution System by Monte Carlo Simulation

STOCHASTIC ESTIMATION OF FEEDER-SPECIFIC DISTRIBUTED GENERATION (DG) HOSTING CAPACITY

Control System for a Diesel Generator and UPS

C PER. Center for Advanced Power Engineering Research C PER

INCREASING THE ELECTRIC MOTORS EFFICIENCY IN INDUSTRIAL APPLICATIONS

Available online at ScienceDirect. Energy Procedia 36 (2013 )

Effect of Compressor Inlet Temperature on Cycle Performance for a Supercritical Carbon Dioxide Brayton Cycle

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Gateway South Transmission Project

United Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation

Autonomous Voltage and Frequency Control by Smart Inverters of Photovoltaic Generation and Electric Vehicle

Industry Recommendation Loss of Solar Resources during Transmission Disturbances due to Inverter Settings - II

USAGE OF ACCUMULATION TO SUSTAIN THE DAILY DIAGRAM OF ELECTRICITY PRODUCTION IN PHOTOVOLTAIC POWER PLANT

Interconnection System Impact Study Report Request # GI

High speed, closed loop frequency control using PMU measurements for power grids

Cumulative Impacts of High Penetration of Electric Vehicle Charging and Photovoltaic Generation on Distribution Circuits

Reactive Power Compensation for Solar Power Plants. Andy Leon IEEE PES Chicago Chapter December 12 th, 2018

Comments on the Solar Alliance Proposal for Changes to New Jersey Interconnection Rules

Patrick Lee and Chuck Wells

Generation Increase on Distribution Feeders using Electronic Voltage Regulators

LOW-VOLTAGE TECHNOLOGY SCOPING STUDY: IMPACT OF SMALL AIR CONDITIONING UNITS ON ELECTRICAL SYSTEM VOLTAGE RECOVERY

21st European Photovoltaic Solar Energy Conference, 4-8 September 2006, Dresden, Germany

PV and opportunistic electric vehicle charging in a Swedish distribution grid

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

Energy storage projects for smart distribution grids

Regenerative Utility Simulator for Grid-Tied Inverters

Transcription:

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems Farid Katiraei *, Barry Mather **, Ahmadreza Momeni *, Li Yu *, and Gerardo Sanchez * * Quanta Technology, Raleigh, NC 27607, USA ** National Renewable Energy Laboratory (NREL), Golden, CO 80401, USA Abstract This paper describes a methodology for field evaluation of large PV system impacts on distribution systems based on data collected from several phasor measurement devices deployed on two distribution feeders. The method utilizes a series of performance indicators and pattern trending approaches to process large amounts of granular data gathered from fielded data acquisition instruments (1 second GPS time-synchronized phasor measurements). A summary of key observations and findings from data analysis approach and field verified effects are provided in the paper to explain key operational concerns and future design challenges. The approach mainly focuses on analysis of voltage and current profiles of distribution feeders at primary feeder level (e.g. 12 kv) for various daily and seasonal conditions to identify and evaluate events with adverse power quality impacts. Event categories are proposed and used to classify types of events based on the level of severity in the range or rate of voltage or frequency variations. The proposed approach was proven to be very effective to investigate field issues and to capture events. Index Terms power distribution systems, PV integration impact study, power quality in feeders, analysis of field data. I. INTRODUCTION As part of the high penetration PV projects funded by Department of Energy (DOE) SunShot Program, three distribution feeders with large utility-scale PV systems were selected to deploy voltage and current measurement devices at several locations on the feeders [1]. Two types of measurement devices were deployed on the feeders for granular voltage and current phasor measurements at 1 and 5 second intervals respectively over a period of several months. Data measurements from each set of data acquisition instruments were communicated to a centralized location via the cellular communications network and collected in a database server for off-line analysis. Data analyses were extensively performed for two distribution circuits, based on availability and quality of the data (For some other related studies from the authors, see [2] and [3]). The data set utilized for this study included voltages and currents gathered in a period of approximately 17 months from April 2013 to September 2014. The analyzed circuits are named Feeder 1 and Feeder 2 in this paper for simplicity. Feeder 1 is a 12.47 kv rural feeder supplied from a 66 kv substation. This feeder supplies mostly agricultural lands and farm area. There are two switched capacitor banks on the feeder which are operating with time-biased and voltage override. A 5 MW ground mounted PV plant is interconnected to this feeder toward the end of the feeder. During light load condition of the feeder, reverse power flow can be observed at feeder head. Feeder 2 is a 12.47 kv rural feeder supplied from a 66 kv substation. Two 1.5MW ground mounted PV plants are interconnected to this feeder on the middle of one of the main branches. Feeder is very lightly loaded, causing significant reverse power flow toward the substation. There are no voltage control devices on this feeder. II. DATA ANALYSIS METHODOLGY To visualize the impact of PV plants and to detect potential issues, several power quality indicators are suggested. The indicators deal with duration and severity of voltage deviations as well as the extent of power flow and reactive power variations in the circuit. Examples of the indicators are defined below. Rapid voltage variation is defined as the maximum voltage variations in periods of one hour or less. This indicator is of interest to quantify the level of voltage disturbances introduced either by normal changes in load, or by the cumulative action of load changes and PV output variations for cloud movement. Slow voltage variations V due to PV Generation is another indicator that was used to determine the average difference in voltage between the cases when the PV plant output is not generating power, to moments of maximum PV generation. Similarly, the maximum and the minimum voltages registered through specific days were recorded as indicators of interest. Other indicators that were monitored in this study are the maximum current supplied by the PV plant in a given season, the maximum power output incursions due to cloud movements, the daylight span for specific seasons, and the duration of reverse power flow at the respective substation. Analysis of measurements was done for several specific days that let see the most important effects of meteorological conditions on the PV plant, and on the rest of the circuit where

the solar PV plant is connected. The days analyzed were selected according to extremes in the amount of solar irradiation, cloud patterns, and load characteristics. This lead to consider days in summer and winter seasons, with high and low load conditions, and characterized by their respective cloud patterns that are linked to variations in solar irradiance. (Figure 5). III. FIELD DATA ANALYSIS RESULTS AND OBSERVATIONS FOR PV IMPACT STUDY In this section, a detailed discussion on the observations and examples of event captures for both Feeders 1 and 2 on February 1, 2014, are described. These two days are a sample of the days on which the impact of the reverse power flow on the feeder voltage is significant, and there are important power quality concerns Case Study I: Feeder 1, on February 1, 2014 February 1, 2014 had a sunlight span of approximately 10 hours, negligible cloud variations, and moderate solar intensity, as shown in Figure 1. PV output variations due to cloud movement were negligible. As seen in this figure, the maximum current provided by the PV branch was 150A, where an approximate load between 3A and 6A was being supplied in the same branch. Fig. 2. Current profile at the substation of Feeder 1 (Date: Fig. 3. Duration of reverse power flow at the substation of Feeder 1 (Date: Fig. 1. Current profile close to the PV plant on Feeder 1 (Date: The amount of PV generation caused a reverse power flow at the substation that lasted 8.1 hours as can be seen in Figures 2 and 3. The largest voltage sensitivity on PV generation is roughly about 3% (Figure 4). This happens in a location close to the PV plant, where the short circuit capacity is 24 MVA. The smallest dependency on PV variations occurs at the substation, where the voltage variation is roughly about 1.8% in average (Figure 5), and the short circuit capacity is 191 MVA. Disregarding some voltage variations attributed to night and early morning load behavior that is not observed during the rest of the day, rapid voltage variation caused by normal load variations is observed to be below 0.7% in a location close to the PV plant (Figure 4), and below 0.7% at the substation Fig. 4. Voltage profile close to PV plant on Feeder 1 (Date: Fig. 5. Voltage profile at the substation on Feeder 1 (Date:

When cloud movement is considered, the rapid voltage variation is below 1% in a location close to the PV plant (Figure 4), and below 1% at the substation (Figure 5). Additionally, variations shown in Figures 4 and 5 do not imply capacitor operations; voltage at the PV plant, close to a capacitor bank, surpasses the 1.05 pu level from approximately 9:30 to 15:30, at times when the PV output is high. However no capacitor operation is observed. Through the rest of the day, voltage remains within the ±5% limits. It is noted that this 5% permissible voltage level is chosen according to IEEE 1547.a standard [4]. Case Study II: Feeder 2, on February 1, 2014 February 1, 2014 had a sunlight span of approximately 9.5 hours with almost no variations in solar irradiance caused by cloud movement, as shown in Figure 6. As seen in this figure, the maximum current provided by the PV branch was 133A, where there was no load supplied to the PV branch. output is 1.8%, where the short circuit capacity is 35 MVA. This is shown in Figure 10, where the voltage variations are attributed to high load switching operations. At the end of the lateral branch on Feeder 2, voltage dependency on PV variations is about 1.5% in average (Figure 11), and the short circuit capacity is 22MVA. Fig. 8. Duration of reverse power flow at the substation of Feeder 2 (Date: Fig. 6. Current profile close to the PV plant on Feeder 2 (Date: The amount of PV generation caused reverse power flow for about 9.5 hours at the substation as can be seen in Figures 7 and 8. Fig. 9. Voltage profile close to PV plant on Feeder 2 (Date: Fig. 7. Current profile at the substation of Feeder 2 (Date: The voltage sensitivity on PV generation is roughly about 3% in allocation close to the PV plant (Figure 9). At the end of the main branch on Feeder 2, when high load operations are disregarded, the approximate voltage variation due to PV Fig. 10. Voltage profile at the end of the main branch on Feeder 2 (Date: From the analysis of the voltage profile in Figure 12, it can be observed that the PV system utilizes power factor adjustment or power curtailment to reduce the voltage, once

the voltage at Point 1 (PV system point of interconnection) is above 1.05 pu. It seems that the control approach has some delay in sensing voltage and determination of power factor or curtailment level. It could be also that control was only applied once the voltage exceeded 1.06 pu, and terminated when voltage fell below 1.045 pu. The control scheme has been selected such that the voltage at the PV system point of interconnection (POI) can be limited to about 1.05 pu. Fig. 11. Voltage profile at the end of the lateral branch on Feeder 2 (Date: Fig. 12. Additional reactive power demand from PV plants for Feeder 2. Disregarding some voltage variations that are attributed to large load switching operations, rapid voltage variation caused by normal load variations is observed to be below 1.3% in a location close to the PV plant (Figure 9), below 1.3% at the end of the main branch (Figure 10), and below 1.3% at the end of lateral branch (Figure 11). When cloud movement is considered, the voltage variation is below 1.3% in a location close to the PV plant (Figure 9), below 1.2% at the end of the main branch (Figure 10), and below 0.8% at the end of the lateral branch (Figure 11). In addition, as shown in Figure 9, voltage in a location close to the PV surpasses 1.05 pu between about 9:00 and 15:00 hrs. As observed, voltage has the potential to exceed the permissible level of 1.05 per unit during high PV production time of the day. In the case of feeder 2, both PV curtailment and operation at a very low leading power factor of 0.85 have to be applied to keep the voltage close to 1.05 pu. This has added extensive reactive power flow to the feeder, causing additional loses. III. CONCLUSIONS ON THIS PV IMPACT STUDY A summary of the major observations concluded for the two feeders in this study, based on the analysis of the voltage and current data collected from the field is given below: The short circuit capacity (SCC) at different points of the circuit, demonstrated to be a good indicator of voltage robustness, where locations with higher SCCs were showing less voltage deviations due to PV generation intermittency, and lower SCCs corresponded to points in the circuit more susceptible to large voltage fluctuations. The maximum PV generation in Feeder 1 was decreased from 100% in summer to 68% in winter. In Feeder 2, the maximum generation was the same for both seasons. In cloudy and windy days, highly variable cloud patterns typically caused PV fluctuations with up to 70% depth of changes in the power output. Reverse power flow occurred consistently in both feeders. At the feeder head for feeder 1, the reverse power flow can last for up to 8.1 hours approximately. In the case of feeder 2, the reverse power flow can last for up to 10.9 hours approximately. In case of feeder 1, there were occasional and infrequent overvoltage conditions (voltages greater than 1.05pu), however, no capacitor operation that could be associated with the PV plant output fluctuations was detected. In case of feeder 2, voltage surpassed the 1.05 pu limit typically at all times when PV generation was relatively high (above 60-70% of rated capacity). Operation with leading power factor at all time, as well as PV power curtailment under extreme voltage conditions were observed to be used as a measure to limit large overvoltage to about 1.06 pu. Feeder 2 does not have capacitors installed. Average voltage deviations (throughout the day) in feeder 1 are typically in 4% range for the area closer to the PV plant. In case of feeder 2, average voltage variations are typically in 3% range. To put into perspective, it should be noted that SCC close to the PV site in feeder 1 is about 27 MVA, while the corresponding SCC for feeder 2 is about 62 MVA. In addition, feeder 1 has a 5 MW PV system operating

closed to unity power factor, where feeder 2 PV system is 3 MW in size and most of the time is operated with a low leading power factor (absorbing reactive power), and at reduced output (power curtailment) under extreme voltage conditions. Rapid voltage variations occurring in periods less than one hour, and caused by PV intermittency, are in the range of 3.5% for both feeders. Sudden voltage changes in feeder 2 could be much higher, but they are managed by operating at off-unity leading power factor. ACKNOWLEDGEMENTS This work was supported by the U.S. Department of Energy under Contract No. DOE-EE0002061 with the National Renewable Energy Laboratory. The authors would also like to acknowledge the California Solar Initiative (CSI) RD & D Program and Itron for past support of the NREL/SCE Hi- Penetration PV Integration Project that provided data for this analysis. REFERENCES [1] U.S. Department of Energy (DOE), "SunShot Initiative," http://www1.eere.energy.gov/solar/sunshot/index.html. [2] B. Mather, B. Kroposki, R. Neal, F. Katiraei, A. Yazdani, J. R. Aguero, T. E. Hoff, B. L. Norris, A. Parkins, R. Seguin, and C. Schauder, "Southern California Edison High-Penetration Photovoltaic Project - Year 1 Report," NREL Technical Report: TP5500-50875, 2011. [3] F. Katiraei, D. Paradis and B. Mather, "Comparative Analysis of Time-series Studies and Transient Simulations for Impact Assessment of PV Integration on Reduced IEEE 8500 Node Feeder," IEEE Power and Energy Soc. Gener. Meet., 2013. [4] IEEE-P1547a, "Standard for Interconnecting Distributed Resources with Electric Power Systems - Amendment 1," IEEE Standard Working Group.