MS Application. Features. Proportional Valve Actuator General Instructions

Similar documents
MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

MA-5200 Series MA-5300 Series

MF4E MF4E

AV-430. Application. Features. Applicable Literature. Valve Linkage for Pneumatic Actuators General Instructions

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

CP (Vdc) CP (Milliamp) CP (Slidewire)

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

Application. Features

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

MAx1-720x Two Position Series MFx Floating Series MSx Proportional Series

CP CP

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions

VB-8000 Series VB-9313 Series. Selection Guide. Applications. Applicable Literature. Selection Guide Contents. Valve and Actuator Selection Procedure

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

MC-351, 421, 431, MC-4311

CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

AV-497. Application. Features. Valve Linkage for MK-6811 and MK-6911 General Instructions

AV-401. Application. Features. Applicable Literature. Pneumatic Actuator Valve Linkage Kit General Instructions

MK-6600 Series, MK-6800 Series, and MK-6911

MS41-634X Series. Features. SmartX Actuators Non-Spring Return Proportional General Instructions

Non-Spring Return EconoDrive Floating Actuator

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

VB-9323 Series. Application. Features. Applicable Literature. 2-1/2" to 6" 125 Lb. Flanged Three-Way Diverting Valves General Instructions

AV-608 Linkage Adapter Kit

NETSIAN TECHNOLOGY VALVE SCHEDULE

TS Series TS Series

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

MA/F/S 4D-xxxx-xxx Two Position, Floating and Proportional Series SmartX Actuators Rotary Overshaft Actuators

TS , -850 Series TS , -850 Series TS-57031, TS

MA40-704X Series MA41-707X Series MA41-715X Series

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None

VA-8020 Floating Valve Actuator

MS Series MS Series MS Series

VA-640GSX024P. Overview. Applications. Features & Benefits. Datasheet. Large Globe Valve Actuators

Features Globe Valve 2-Way & 3-Way Assembly Features:

TK-6024, TK-6124, TK-8024, TK-8124

MX4X-6XXX-20X Series MX4X-7XXX-20X Series

TAC DuraDrive Product Guide Direct Coupled Actuators

453X Series. Application. Features. Two-Position Damper Actuator General Instructions

SAX Electronic Valve Actuator

AV-611. Application. Applicable Literature. Schneider Electric DuraDrive Globe Valve Linkage General Instructions

NV Direct Coupled Globe Valve Actuator

AV-8020 Series Floating Control Actuated Valve

SAV Electronic Valve Actuator

VB-9213 Series. Application. Features. Applicable Literature

MF /MS Series

3-Way Linked Globe Valve Assemblies with Linear Series Actuators

Flare Valves 1/2 inch 2-Way and 3-Way

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

Erie VT/VS PopTop Series Two Position Spring Return Valves

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

TSMN-90xxx Series TSMN TSMN TSMN Electronic Room Temperature Sensor General Instructions

MF Series MF Series MF Series

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

Electronic Globe Valves

Selection Guide. Vx-7000 & Vx-9000 Series Mx4x-6xxx & Mx4x-7xxx Series. Globe Valve Assemblies. Actuator/Linkage Assemblies

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

2211 Series. Application. Features. One-Pipe Pneumatic Room Thermostats General Instructions SPECIFICATIONS

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

Powermite 599 MT Series SQS Electronic Valve Actuator, 24 Vac, Floating Control (3-position)

VB-9313 Series. Application. Features. Applicable Literature

AV-602. Application. Globe Valve Linkage General Instructions

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

IMP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning. Hyciraulic Actuator General Instructions SIEBE

Flowrite EA 599 Series SQX Electronic Valve Actuator 24 Vac, 3-Position Control

System 350 P352AB Electronic Pressure Control Series

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

M100F Incremental Motor Actuator R81F Interface Board

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

VA-4233-GGx Series Electric Valve Actuators

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

VE VVG Series Electronic Two-way Valves Normally Closed

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

AM-751, AM-752, AM-753, AM-754, AM-755. Applications. Applicable Literature

VA-715x Electric Valve Actuator

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

Erie VM PopTop Series Modulating Valves

LF Series Spring Return Direct Coupled Actuator

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac 3-Position (Floating) Control

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

Zone Valves and Parts (Honeywell)

B2 Series Characterized Control Valve, Non-Spring Return Actuator

Technical Instructions Document No EA GQD May 6, OpenAir GQD Series. Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

Transcription:

Proportional Valve Actuator Application The Proportional Valve Actuator is a non-spring return actuator used with proportional to 10 Vdc or 4 to 0 ma controllers and standard 1/" to 1-1/4" two-way and three-way valve bodies for control of heating and cooling coils. Typical applications include VAV terminals with reheat coils, fan coil units, and unit ventilators. Features Proportional actuator controlled by to 10 Vdc or 4 to 0 ma 45 pounds (00 newtons) of output force with automatic load limit for self-adjusting travel and long motor life Synchronous motor for consistent timing Manual override with automatic release to 10 Vdc actuator position feedback signal Integral linkage for all standard 1/" to 1-1/4" two-way stem-up open and three-way valve bodies for a wide variety of applications Compact size for application flexibility Rugged construction with die cast housing 100Ω input impedance for the 4 to 0 ma input Printed in U.S.A. 8-08 Copyright 008 TAC All Rights Reserved. F-663-6

Applicable Literature F-Number Description Audience Purpose F-3638 TAC Environmental Control Cross-Reference Guide F-1683 TAC Environmental Control Reference Manual F-1335 TAC Environmental Controls Application Manual F-6363 F-630 F-6075 F-5675 F-6077 F-4388 F-4390 F-439 F-6074 F-4394 EN-06 Guidelines for Powering Multiple Full-Wave and Half-Wave Rectifier Devices from a Common Transformer VS-7XXX Series Valve Selection Guide for the Actuator VB-713 Series 1/" to " Screwed NPT Stem Up Open, Two-Way Valves VB-714 Series 1/" to " Union Sweat, Solder Joint Stem Up Open, Two-Way Valves VB-715 Series 15 mm to 50 mm Screwed Rp Stem Up Open, Two-Way Valves VB-753 Series 1/" to " Screwed NPT Stainless Steel Trim with Teflon Disc Stem Up Open, Two-Way Valves VB-773 Series 1/" to " Screwed NPT Stainless Steel Trim Stem Up Open, Two-Way Valves VB-731 Series 5/8" O.D., 45 SAE Flared Three-Way Mixing Valves VB-7313 Series 1/" to " Screwed NPT Three-Way Mixing Valves VB-7314 Series 1/" to " Union Sweat, Solder Joint, Three-Way Mixing Valves Provides a listing of TAC Environmental Control HVAC component products to assist in the selection of product replacement. The components are cross referenced to compatible older components and/or competitive components. A collection of currently published component General Instruction literature in a two volume format. Provides theory of operations for numerous HVAC applications. Describes the proper wiring guidelines associated with full-wave and half-wave rectifier devices from a common transformer to avoid equipment damage. Provides a listing of VS-7XXX Series valve bodies and their characteristics as used with the actuator. This document assists in the selection of appropriate valve body for product ordering or replacement. Describes the VB-713 Series valve features, Describes the VB-714 Series valve features, Describes the VB-715 Series valve features, Describes the VB-753 Series valve features, Describes the VB-773 Series valve features, Describes the VB-731 Series valve features, Describes the VB-7313 Series valve features, Describes the VB-7314 Series valve features, Copyright 008 TAC All Rights Reserved. F-663-6

F-Number Description Audience Purpose F-6078 F-4396 F-661 VB-7315 Series 15 mm to 50 mm Screwed Rp Three-Way Mixing Valves VB-733 Series 5/8" O.D. 45 SAE Flared Three-Way Sequencing Valves AV-64 Valve Linkage Kit for Controlli Valve Bodies Describes the VB-7315 Series valve features, Describes the VB-733 Series valve features, Describes the AV-64 valve linkage kit features, specifications, and possible application. Also provides step-by-step mounting, installation, and checkout instructions. SPECIFICATIONS Inputs Operating Range: to 10 Vdc or 4 to 0 madc, Proportional control signals (fixed span and start point). Input Impedance, 100kΩ minimum for voltage input. 100Ω for current input. Power Input: See Table-1. Connections: 4 foot (1. m) color coded 18 AWG, plenum cable rated for UL. Outputs Position Feedback Signal: to 10 Vdc non-adjustable. Connections, 4 foot (1. m) color coded 18 AWG, plenum cable rated for UL. Mechanical: Force, 45 pounds (00 N) minimum with automatic load limit. See Table-3. Stroke, Up to 9/16" (14.3 mm) maximum, self-adjusting. Timing, See Table-1. Manual Operator: Allows actuator to be manually set at any position upon loss of power. Releases automatically when power is restored. Environment Ambient Temperature Limits: Shipping and Storage, -40 to 160 F (-40 to 71 C). Operating, Minimum 40 F (4 C). Maximum See Table-. Fluid Temperature Limits: See Table-. Humidity: 5 to 95% RH, non-condensing. See Table- for maximum dew point temperature. Location: NEMA Type 1. Enclosure Protection Class: IP31 according to EN 6059, BS EN 6059. Agency Listings UL 873: Underwriters Laboratories (File # E949 Category Temperature-Indicating and Regulating Equipment). CUL: Certified for use in Canada by Underwriters Laboratories. Canadian Standards C. No. 4-93. European Community: EMC Directive (89/336/EEC). Low Voltage Directive (7/3/EEC). F-663-6 Copyright 008 TAC All Rights Reserved. 3

Table-1 Actuator Model Chart. Part Number Application Chilled/Hot Water/Steam b Actuator Power Input Voltage (+0%, -15%) 4 Vac (Class Power Supply) Feedback Hz VA to 10 Vdc a Typical Timing in Sec. @ 75 F for 1/" (1.7mm) Stroke 60 Hz 50 Hz 50 60 4 Yes 16 151 a Running or manually adjusting the actuator before it is mounted to a valve changes the potentiometer setting and could also cause damage. b Refer to Table- for maximum allowable temperature. Max. Stroke in in. (mm) 9/16 (14.3) Table- Restrictions on Ambient Temperature for Valve Actuators. a b Actuator Part Number Temperature of Media in the Valve Body (Check Rating of the Valve) Minimum Maximum 40 F (4 C) b 81 F (138 C) 0 F (104 C) Dew point temperature applies only to chilled water applications. The dew point temperature cannot be more than 48 F (6.7 C) above the fluid temperature. Maximum Ambient Temperature of Actuator 115 F (46 C) 140 F (60 C) Dew Point Temperature a 88 F maximum with 40 F fluid (31 C maximum with 4 C fluid) b Table-3 Close-off Pressure Ratings. Valve Body Part Number a Two-Way Valves VB-711 VB-71 VB-713 VB-714 VB-715 c Three-Way Mixing Valves VB-731 VB-7313 VB-7314 VB-7315 c Valve Sizes Close-off Pressure (psi) b Nominal 1/" 130 3/4" 80 1" 40 1-1/4" 5 1/" 130 3/4" 80 1" 40 1-1/4" 5 a actuators may also be used with VB-9000 valves. Refer to TAC Environmental Controls Catalog, F-5683, for available valves. b Close off ratings describe only the differential pressure which the actuator can close with adequate seating force. Consult valve body specifications for other limitations, see "Applicable Literature" for document listing. c Metric thread 15 to 3 mm (Rp 1/ to Rp 1-1/4). ACCESSORIES AV-641 AV-64 AV-644 FRAC-55 Valve linkage kit (replacement parts only, order separately, see F-6588) Four-way valve linkage kit for Controlli valve bodies (see F-661) Valve linkage kit (included with actuator) (see Figure-6) Metric male 0 mm conduit fitting (m0 x 1.5-8g) 11 mm nominal thread length Note: If the actuator drive screw (Figure-7) has a round opening in the center, then the center section of the stem extension should also be round to match. AV-641 Valve Linkage Kit contains the round stem extension. (Valve/actuator assemblies using the AV-641 valve linkage kit are assembled similar to the AV-644 illustration shown in Figure-6.) 4 Copyright 008 TAC All Rights Reserved. F-663-6

TYPICAL APPLICATION (wiring diagrams) Basic Actuator The actuator provides a to 10 Vdc position feedback output to indicate the actuator s stroke position. Figure-1 and Figure- illustrate typical wiring diagrams, Figure-3 illustrates a typical wiring configuration using multiple actuators with one controller, and Figure-4 illustrates a typical wiring configuration for multiple actuators in parallel. Note: When the is assembled on a valve, the feedback signal may not reach exactly Vdc (0%) or 10 Vdc (100%) at the ends of valve stroke. Caution: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-isolated full-wave rectifier power supplies. Refer to EN-06, Guidelines for Powering Multiple Devices from a Common Transformer, F-6363 for detailed information. Each actuator can accept either a to 10 Vdc or 4 to 0 ma signal. The unused control input lead ( or ) must be taped, capped with a wire nut, or cut off to provide only one input signal. If the actuator position feedback signal lead (Blue) is not used, the lead must be taped, capped with a wire nut, or cut off. L1 L 4 Vac Transformer 4H 4G 4H 1 4G Earth 4 to 0 ma DC Controller (+) VDC IN (+) 4 to 0 ma DC Output (+) ma DC IN 3 Feedback Input Blue 4 (+) VFB Feedback Signal 1 The actuator contains a half-wave rectifier power supply. When connecting multiple devices to a common transformer, connect 4H and 4G with half-wave rectifier or isolated power supplied devices, only. For actuator models manufactured prior to date code 991X (e.g. 9910, 9911, etc.), see Table 4 for wire colors and numbers. 3 The input impedance between and for each actuator is 100 ohms nominal. 4 Optional connection for controllers with feedback input. If unused, wire nut. Figure-1 Wiring Diagram for 4 to 0 ma DC Proportional Control. F-663-6 Copyright 008 TAC All Rights Reserved. 5

L1 L 4 Vac Transformer 4H 4G 4H 4G 1 Earth 0 to 10 Vdc Controller (+) ma DC IN 4 (+) 0 to 10 Vdc Output (+) VDC IN Feedback Input Blue (+) VFB 3 Feedback Signal 1 The actuator contains a half-wave rectifier power supply. When connecting multiple devices to a common transformer connect 4H and 4G with half-wave rectifier or isolated power supplied devices, only. For actuator models manufactured prior to date code 991X (e.g. 9910, 9911, etc.), see Table 4 for wire colors and numbers. 3 Optional connection for controllers with feedback input. 4 Although the controller in this example has an output of 0 to 10 Vdc, the only operates over its input span of to 10 Vdc. Figure- Wiring Diagram for to 10 Vdc Proportional Control. 4 to 0 ma DC Controller (+) 4 to 0 ma DC DC 3 (+) ma DC 1 4 Vac Transformer L1 L 3 (+) ma DC 1 4 Vac Transformer L1 L 1 Separate transformer required for each actuator. 3 (+) ma DC 1 4 Vac Transformer L1 L For actuator models manufactured prior to date code 991X(e.g. 9910, 9911, etc.), see Table 4 for wire colors and numbers 3 The input impedance between and for each actuator is 100 ohms nominal. Figure-3 Wiring Diagram for Series Combination of Actuators Using One 4 to 0 ma Control Input. 6 Copyright 008 TAC All Rights Reserved. F-663-6

0 to 10 Vdc Controller 3 (+) 0 to 10 Vdc DC (+) VDC IN (+) VDC IN 1 4 Vac Transformer L1 L (+) VDC IN 1 The actuator contains a half-wave rectifier power supply. When connecting multiple devices to a common transformer, connect 4H and 4G with half-wave rectifier or isolated power supplied devices, only. For actuator models manufactured prior to date code 991X (e.g. 9910, 9911, etc.), see Table 4 for wire colors and numbers. 3 Although the controller in this example has an output of 0 to 10 Vdc, the only operates over its input span of to 10 Vdc. Figure-4 Wiring Diagram for Parallel Combination of Actuators Using One to 10 Vdc Control Input. INSTALLATION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Requirements Job wiring diagrams Tools (not provided): 5/3" (4 mm) Allen wrench Appropriate wrenches for stem extension and lock nut TOOL-37, 1-5/8" (4 mm) open-ended wrench Volt-ohm meter Caliper or 1/" (1 mm) wide scale Training: Installer must be a qualified, experienced technician Warning: Disconnect the power supply (4 Vac power) before installation to prevent electrical shock and equipment damage. Caution: Make all connections in accordance with the wiring diagram and in accordance with national and local electrical codes. Use copper conductors only. Do not remove cover of actuator. There are no user serviceable parts inside. Do not exceed ratings of the device(s). Avoid locations where excessive moisture, corrosive fumes, or vibration is present. F-663-6 Copyright 008 TAC All Rights Reserved. 7

Mounting Wiring Requirements Position the actuator above center line of valve to prevent damage from condensation and dripping water. 1. Allow 3" (76 mm) above the actuator valve assembly for removal and reattachment of actuator to installed valve.. Install all two-way valves so that they close against the flow. An arrow on the valve body or tag indicates proper flow direction. 3. Always install three-way mixing valves with two inlets and one outlet. 4. Always install three-way diverting valves with one inlet and two outlets. 5. Always install four-way Controlli valves per manufacturers instructions. 6. Valve actuators are to be mounted in any upright position above the center line of the valve body. For steam applications only, position the valve body so the valve stem and actuator are at least at 45 from vertical. Power and Control Leads See Table-4 for lead identification. Table-4 Power and Control Wiring Color Codes. Actuator Power Proportional Control Signals Feedback Control Signal Actuator Label Description Color Only (Current Models) Wire Codes Color with Numbers (Older Models a ) Earth Earth Ground ( ) 4 H 4 Vac (1) 4 G 4 Vac b () +VDC (IN) to 10 Vdc Input / (3) -COMMON DC Common Ground / (4) +madc (IN) 4 to 0 madc Input / (6) +VFB Actuator Feedback Blue /Blue (5) a Actuator models manufactured prior to date code 991X (e.g. 9910, 9911, etc.) have multi-color, numbered wires. b Actuator power wire may be Violet on some models. Make all electrical connections in accordance with the job wiring diagram and in compliance with national and local electrical codes. See Table-5 and Table-6 for maximum wiring lengths. Table-5 Proportional Control Wiring Data (Leads,,, Blue). Wire Size (GA) Maximum Wire Run in ft. (m) 0 500 (15) 18 1000 (305) 16 50 (686) 14 4000 (119) Caution: Use multi-conductor twisted shielded cable when it becomes necessary to install the input, common, and feedback signal leads in the same conduit with power wiring or when RFI/EMI generating devices are near. Table-6 Power Wiring Data (,, ). Wire Size (GA) Maximum Wiring Run in ft. (m) (5% voltage drop) 14 5500 (167) 16 3600 (1094) 18 100 (638) 8 Copyright 008 TAC All Rights Reserved. F-663-6

Low voltage actuators installed to NEC (National Electrical Code) codes may use Class wiring. The total length of power wiring [black, red leads] should not exceed the maximum length shown for given wire size in Table-6. Wiring Connections Assembly/Adjustment Instructions Note: Use flexible conduit only. Rigid conduit cannot be used. Actuator housing must be free to move. Caution: Damage could occur if an actuator is run or manually adjusted without being mounted to a valve. This will also cause the potentiometer output to be out of specification and will require the actuator position to be re-established. If an actuator is run or adjusted without being mounted to a valve, see Re-establishing Actuator Position below. Re-establishing Actuator Position If an actuator is run or adjusted without being mounted to a valve, the actuator position can be re-established by applying 4 Vac to the actuator (refer to Figure-5 and Table-4): 1. Remove actuator position indicator nut and stem extension.. Apply 9.0 Vdc between +VDC (IN) and COMMON. When the actuator has stopped moving remove power from the actuator. or Depress the manual override button and turn the manual override screw so that the position feedback voltage, (VFB), is 9.0 Vdc. Then remove power from the actuator before releasing the override button. Now follow the assembly steps listed below. Actuator Assembly See Figure-5 for parts identification. 1. Position the valve stem in the down position. Place the lock nut onto the valve stem.. Remove the stem extension from the actuator. Screw the stem extension onto the valve stem. Adjust the height of the stem extension to 1-3/3" (7.8 mm). This dimension is the distance from the top of the packing nut to the shoulder of the stem extension (see Figure-5). Distance between top of packing nut and stem extension shoulder is measured with valve stem down. 1-3/3" (7.8 mm) Top of Packing Nut Figure-5 Valve and Stem Extension Assembly. 3. Tighten the lock nut against the stem extension to make the stem extension secure to the valve stem. F-663-6 Copyright 008 TAC All Rights Reserved. 9

4. Position the valve stem in the fully down position. Position indicator nut* Manual override screw (use 5/3" (4mm) Allen wrench) Manual override button Actuator/Valve mounting opening Optional FRAC-55 Metric Conduit Fitting (Sold Separately) Stem extension* AV-644 Lock nut* Valve Stem Packing nut Mounting nut * These parts are shipped with the MF-3XX3 actuator. Additional accessories may be ordered separately, see "ACCESSORIES", on page 3. Figure-6 Assembly Diagram. 5. Confirm that the drive screw is at the required distance from the top of the actuator case. See Figure-7. If the drive screw is not in position, insert a tapered pencil or pen into the drive screw and rotate. 55/64" ( mm) to top of drive screw Drive screw Actuator case Figure-7 Proper Drive Screw Position Before Mounting. 6. Insert the valve stem extension through the bottom of the actuator. If necessary, rotate the drive screw slightly to align the hex in the drive screw to the square in the lower bearing to match the stem extension hex and square. 7. Screw the valve mounting nut into the actuator and tighten. 8. Insert the position indicator nut into the hole at the top of the actuator. 9. Position the indicator nut on top of the actuator and tighten against the shoulder on the stem extension. 10 Copyright 008 TAC All Rights Reserved. F-663-6

Caution: The hex shaped interface between the stem extension and drive screw does not require high indicator nut tightening torque. Do not tighten the indicator nut beyond the hex shoulder on the stem extension or a reduction in the actuator output may result. See Figure-6 for parts identification. Manual Override Operation All models are provided with a means of manual positioning the valve without power to the actuators. See Figure-6 for the location of the manual override button and manual override screw. Rotating manual override screw clockwise as seen from the top of the actuator, extends the actuator shaft. 1. Disengage the gear train by depressing the manual override button.. While holding the button turn manual override screw with 5/3" or 4 mm hex Allen wrench until the desired valve stem position is obtained, then release the manual override button. Note: When power is applied to the actuator/valve assembly control is automatically resumed. No manual reset required. CHECKOUT Positioning with Controller Go, No Go Test MAINTENANCE After the entire system has been installed and the actuator has been powered up, the following checks can be made for proper system operation. If the sensed media is within the controller s setpoint range, the actuator can be positioned by adjusting the controller setpoint up and down. Check for correct operation of valve while the actuator is being stroked. 1. Override the controller s output to 10 Vdc or 0 ma and the actuator should extend.. Override the controller s output to Vdc or 4 ma and the actuator should retract. The actuator requires no maintenance. Regular maintenance of the total system is recommended to assure sustained optimum performance. Note: When the is installed in an exceptionally dirty environment, the internal feedback potentiometer may, after several years of use, exhibit some error due to contamination. The performance of the potentiometer can be restored to its original quality by manually cycling the actuator for 10 full-stroke cycles. This procedure is only necessary in those applications where normal control action does not frequently operate the actuator over its full stroke of travel. FIELD REPAIR Caution: Do not remove cover of actuator. No user serviceable parts inside. Replace with a functional actuator. The AV-641 valve linkage kit can be ordered separately as a replacement part for the parts that were included with the actuator. The following instructions are for disassembling the actuator from the valve for actuator replacement or valve repacking. See Figure-6. F-663-6 Copyright 008 TAC All Rights Reserved. 11

Disassembly Instructions 1. Turn off power to the actuator and disconnect wires at the junction box. Warning: Disconnect the power before disassembly to prevent electrical shock. Note: Do not remove actuator cover to disconnect wires.. Unscrew the position indicator nut. 3. Unscrew the mounting nut and lift the actuator from the valve. DIMENSIONAL DATA Dimensions for Figure-8 are shown in inches with millimeters in brackets. 3-5/16 (84) 3 (76) 5-9/16 (141) Dimensions shown are in inches (mm). Optional metric conduit fitting (FRAC-55) adds 37/64" (15 mm) to overall length. Figure-8 Actuator Dimensions Copyright 008, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-663-6 TAC 1354 Clifford Avenue P.O. Box 940 Loves Park, IL 6113-940 www.tac.com