Experimental Study on Heat Enhancement of Helixchanger with Grooved Tubes

Similar documents
ENHANCEMENT OF HEAT TRANSFER RATE AND REDUCTION OF SHELL SIDE PRESSURE DROP IN HELIX HEAT EXCHANGER WITH CONTINUOUS HELICAL BAFFLES

Performance Evaluation Of A Helical Baffle Heat Exchanger

Enhance the Performance of Heat Exchanger with Twisted Tape Insert: A Review

CFD Investigation of Influence of Tube Bundle Cross-Section over Pressure Drop and Heat Transfer Rate

International Journal of World Research, Vol: I Issue XXXVII, January 2017 Print ISSN: X

EXPERIMENTAL INVESTIGATIONS OF DOUBLE PIPE HEAT EXCHANGER WITH TRIANGULAR BAFFLES

CFD Analysis to Study the Effects of Inclined Baffles on Fluid Flow in a Shell and Tube Heat Exchanger

Efficiency Improvement in Shell and Tube Heat Exchanger Using CFD Tool

Comparative Study of Different Configurations of Fuel Oil Heat Exchanger

An Overview of Shell & Tube Type Heat Exchanger Design by Kern s Method

EXPERIMENTAL ANALYSIS AND PERFORMANCE CHARACTERISTIC OF HEAT TRANSFER IN SHELL AND TWISTED TUBE HEAT EXCHANGER

Heat Transfer Enhancement for Double Pipe Heat Exchanger Using Twisted Wire Brush Inserts

A Review on Experimental Investigation of U-Tube Heat Exchanger using Plain Tube and Corrugated Tube

Experimental Analysis and Performance Characteristic Of Heat Transfer In Shell and Twisted Tube Heat Exchanger.

CFD analysis of heat transfer enhancement in helical coil heat exchanger by varying helix angle

Experimental Study of Heat Transfer Augmentation in Concentric Tube Heat Exchanger with Different Twist Ratio of Perforated Twisted Tape Inserts

Design of Shell and Tube Type Heat Exchanger using CFD Tools

Design and Performance Study of Shell and Tube Heat Exchanger with Single Segmental Baffle Having Perpendicular & Parallel-Cut Orientation.

Design and Fabrication of Shell and Tube Type Heat Exchanger and Performance Analysis

Design and experimental analysis of pipe in pipe heat exchanger

CONJUGATE HEAT TRANSFER ANALYSIS OF HELICAL COIL HEAT EXCHANGE USING CFD

Exhaust Gas Waste Heat Recovery and Utilization System in IC Engine

Experimental Investigation of Performance and Exhaust Emission Characteristics of Diesel Engine by Changing Piston Geometry

Effect of Baffle Geometry on Shell and Tube Heat Exchanger-A Review Hardik Tandel 1 Pankaj Ahir 2 Asst. Prof. Y. D. Vora 3

Quality Improvement in Design Process of Shell & Tube Type Heat Exchanger by Computer Integrated 3D Modeling

Analysis to Determine Heat Transfer Using Twisted Tape Inserts In a Horizontal Tube

International Journal of Scientific & Engineering Research, Volume 6, Issue 10, October ISSN

CONSTRUCTION AND ANALYSIS OF TUBE IN TUBE TYPE HEAT EXCHANGER

ABSTRACT I. INTRODUCTION III. GEOMETRIC MODELING II. LITERATURE REVIW

NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] VOLUME 1, ISSUE 1 NOV-2014

REVIEW PAPER ON INVESTIGATION OF PERFOMANCE FOR SHELL AND TUBE HEAT EXCHANGER

Design, Fabrication and Testing of helical tube in tube coil heat exachanger

Heat Transfer in Rectangular Duct with Inserts of Triangular Duct Plate Fin Array

Experimental investigation of shell-and-tube heat exchanger with different type of baffles

Thermal Analysis of Shell and Tube Heat Exchanger Using Different Fin Cross Section

International Journal of Advance Engineering and Research Development

GEOMETRICAL PARAMETERS BASED OPTIMIZATION OF HEAT TRANSFER RATE IN DOUBLE PIPE HEAT EXCHANGER USING TAGUCHI METHOD D.

An Experimental Investigation for the Rate of Heat Transfer in Double Pipe Heat Exchanger with Fins on Inside Surface of Internal Tube

TO STUDY OF PARAMETRIC ANALYSIS OF SHELL AND TUBE HEAT EXCHENGER

CFD ANALYSIS ON LOUVERED FIN

SOLAR FLAT PLATE COLLECTOR HEAT TRANSFER ANALYSIS IN THE RAISER WITH HELICAL FINS Mohammed Mohsin Shkhair* 1, Dr.

CFD analysis of triple concentric tube heat exchanger

THERMAL ANALYSIS OF HELICALLY GROOVED COIL IN A CONCENTRIC TUBE HEAT EXCHANGER

SWIRL MEASURING EQUIPMENT FOR DIRECT INJECTION DIESEL ENGINE

Comparison of Heat transfer Enhancement in Tube in Tube heat exchanger using Different Turbulent Generator.

Review on Comparative Study between Straight Tube Heat Exchanger and Helical Coil Heat Exchanger

REDUCTION OF EMISSIONS BY ENHANCING AIR SWIRL IN A DIESEL ENGINE WITH GROOVED CYLINDER HEAD

An Experimental Study of Thermo-Hydraulic Performance of Modified Double Pipe Heat Exchanger Using Mesh Inserts

International Journal of Advance Engineering and Research Development

Optimization of Seat Displacement and Settling Time of Quarter Car Model Vehicle Dynamic System Subjected to Speed Bump

CFD Analysis of Double Pipe Heat Exchanger with Twisted Tape Insert in Inner Pipe

Single-phase Coolant Flow and Heat Transfer

Comparison of Swirl, Turbulence Generating Devices in Compression ignition Engine

Enhanced Heat Transfer Surface Development for Exterior Tube Surfaces

Visualization of Flow and Heat Transfer in Tube with Twisted Tape Consisting of Alternate Axis

Exhaust Waste Heat Recovery of I. C. Engine by Thermoelectric Generator

THERMAL ANALYSIS OF SHELL AND TUBE HEAT EXCHANGER

An Approach for Enhancement of Heat Transfer Using Conical Convergent Ring Inserts In Tube

Study the Effect of Single Segmental Baffle cut on Overall Heat Transfer Coefficient in Shell and Tube Heat Exchanger

Design Optimization of Cross Flow Heat Exchanger

Lecture 2: Thermal Design Considerations

Experimental Investigation of Heat Transfer characteristics Enhancement through Grooved Tube

DESIGN OPTIMIZATION OF SHELL AND TUBE HEAT EXCHANGER FOR OIL COOLER BY COMSOL MULTIPHYSIS

PERFORMANCE ANALYSIS ON DOUBLE PIPE HEAT EXCHANGER USING WIRE COILED AND PIN WIRE COILED TURBULATOR INSERTS

DESIGN AND ANALYSIS OF CAR RADIATOR BY FINITE ELEMENT METHOD

Effect of Nanofluid on Friction Factor of Pipe and Pipe Fittings: Part I - Effect of Aluminum Oxide Nanofluid

Design and Development of Micro Controller Based Automatic Engine Cooling System

Experimental Investigations on a Four Stoke Diesel Engine Operated by Jatropha Bio Diesel and its Blends with Diesel

Restructuring of an Air Classifier Rotor by Finite Element Analysis

Simulation Studies on the Effect of Porous Twisted Plate Inserts on the Performance of Fire Tube Steam Packaged Boiler

Assistant Professor, Dept. of Mechanical Engg., Shri Ram College of Engineering & Management, Banmore, Gwalior (M.P) 2

EXPERIMENTAL INVESTIGATIONS ON 4- STROKE SINGLE CYLINDER DIESEL ENGINE (C.I) WITH CHANGING GEOMETRY OF PISTON

Thermal Unit Operation (ChEg3113)

CFD Study to Enhance the Heat Transfer in Heat Exchanger by Change the Outer Surface of the Inner Tube and Use Nano Fluid

Generation of Air Swirl through Inlet Poppet Valve Modification and To Enhance Performance on Diesel Engine

Experimental Investigation on Modification of Inlet poppet valve of single cylinder Direct Ignition Four stroke Diesel Engine

Experimental Investigation on Turbulent Flow Heat Transfer in a Horizontal Circular Pipe using Coil and Twisted Tape Inserts

A comparative analysis to enhance the effectiveness of EGR coolers used in diesel engine

Application of Simulation-X R based Simulation Technique to Notch Shape Optimization for a Variable Swash Plate Type Piston Pump

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

ADVANCES in NATURAL and APPLIED SCIENCES

Thermal Analysis Of Counter Flow Shell And Tube Heat Exchanger

Heat transfer enhancement of a single row of tube

The Practical Uses of Computational Fluid Dynamics Not Just a Pretty Picture

EFFECT OF EXTERNAL THREADED INSIDE TUBE ON HEAT TRANSFER RATE IN A CONCENTRIC TUBE HEAT EXCHANGER: A CRITICAL REVIEW

Experimental and CFD Analysis of Exhaust Manifold to Improve Performance of IC Engine

Wind Farm Evaluation and Control

HEAT TRANSFER ENHANCEMENT BY USING TWISTED TAPE INSERTS WITH CIRCULAR HOLES IN FORCED CONVECTION

COMPUTATIONAL ANALYSIS TO MAXIMIZE THE HEAT TRANSFER RATE OF DOUBLE TUBE HELICAL COIL HEAT EXCHANGER

Semi-Active Suspension for an Automobile

FEM Analysis of Combined Paired Effect on Piston & Connecting Rod using ANSYS

Experimental Investigation on Mixing time Analysis of Jet Mixer

AN OVERVIEW OF SHELL AND TUBE HEAT EXCHANGER PERFORMANCE

Performance of Solar Flat plate by using Semi- Circular Cross Sectional Tube

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: METHODOLOGY Design Parameter [250]

PERFORMANCE EVALUATION OF A FOUR STROKE COMPRESSION IGNITION ENGINE WITH VARIOUS HELICAL THREADED INTAKE MANIFOLDS

LOAD SHARING WITH PARALLEL INVERTERS FOR INDUCTION MOTOR DRIVE APPLICATION

THERMAL ANALYSIS OF DIESEL ENGINE PISTON USING 3-D FINITE ELEMENT METHOD

Static Structural and Thermal Analysis of Aluminum Alloy Piston For Design Optimization Using FEA Kashyap Vyas 1 Milan Pandya 2

Fabrication of Shell and Tube Heat Exchanger using Helical Baffles based on Kern s Principle

Transcription:

Experimental Study on Heat Enhancement of Helixchanger with Grooved Tubes Pardeep Kumar Research Scholar, Department of Mechanical Engineering University institute of Engineering & Technology, KUK, Haryana, India Vijay Kumar Research Scholar, Department of Mechanical Engineering University institute of Engineering & Technology, KUK, Haryana, India Sunil Nain Assistant Professor, Department of Mechanical Engineering University institute of Engineering & Technology, KUK, Haryana, India Abstract- Shell and tube heat exchangers with helical baffles are used to improved performance by reducing pressure drop, flow induced vibration and fouling while maintains a higher heat transfer capability. In the present work an experimental Investigation has been carried out to know the thermal performance of Helix -changer with plain copper tubes or with grooved copper tubes of same size and Specification by using co-current flow. During this experimental investigation Attempts were made for both exchangers at same operating conditions and it was found that grooved copper tubes helix changer have a better thermal performance as compared to plain copper tubes helix changer at a particular angle, 25 degree. It was also investigated that the flow pattern inside the grooved tubes has better fluid particle mixing which leads to better heat enhancement. The grooved surface is a passive technique of heat enhancement, the flow pattern gives by these tubes has a significant increase in thermal performance of heat exchangers. Keywords shell and tube heat exchanger, helical baffle, grooved tubes, heat transfer, helix angle, HTRI I. INTRODUCTION Shell and tube heat exchangers are most widely used in various industries such as chemical process, power generation, oil refining, refrigeration and air Conditioning. Among different type of heat exchangers, shell and tube heat exchanger have been commonly used in industries. It has been reported that more than35-40% of heat exchangers are of STHE type, due to their robust construction geometry as well as easy maintenance and possibility of upgrades [1]. Baffle is an important shell side component of STHEs. Besides supporting the tube bundles, the baffles form flow passages for the shell side fluid. The most commonly used baffles are segmental baffle, which forces the fluid in a zig-zag manner, thus improving the heat transfer but with a large pressure drop penalty. This type of exchanger has been developed [2-4] &probably is still the most commonly used types of STHE. The major drawbacks of STHE with segmental baffles are (I) it causes a large side pressure drop. (ii) It results in a dead zone in each component between adjacent segmental baffles, leading to increase of fouling resistance. (iii) zig-zag flow pattern also causes high risk vibration failure on tube bundle To overcome the above mentioned drawbacks of conventional STHE, segmental baffled, a no. of improved structure were proposed for the purpose of higher heat transfer coefficient, low possibility of tube vibration and reduced fouling factor [4-7]. Moreover, the principal shortcomings of the conventional segmental baffle still remain in the above mentioned studies, even though the pressure drop across the heat exchanger has been reduced to some extent. A new baffle called helical baffle, provides further improvement. This type of baffle was first proposed by D.Kral & Nemcansky [8], where they investigated the flow pattern produced by helical baffle geometry with different helix angles. They found that these flow patterns were much close to plug flow conditions, which was expected to reduce shell side pressure drop and to improve heat transfer performance. Vol. 3 Issue 4 March 2014 213 ISSN: 2278-621X

In this work (1) Helix changers were designed by HTRI software, (2) a simple and feasible method was developed to fabricate helical Baffles and grooved surface of copper tubes, (3) an experimental investigation has been carried out for both exchangers with same operating conditions at 25 degree angle. Desirable feature of Heat exchangers- The desirable features of a heat exchanger would be to obtain maximum heat transfer to Pressure drop ratio at least possible operating costs without comprising the reliability. 1.1 Higher heat transfer co-efficient and larger heat transfer area- A high heat transfer coefficient can be obtained by using heat transfer surfaces, which promote local turbulence for single phase flow or have some special features for two phase flow. Heat transfer area can be increased by using larger exchangers, but the more cost effective way is to use a heat exchanger having a large area density per unit exchanger volume, maintaining the Integrity of the Specifications. 1.2 Lower Pressure drop- Use of segmental baffles in a Heat Exchanger result in high pressure drop which is undesirable as pumping costs are directly proportional to the pressure drop within a Heat Exchanger. Hence, lower pressure drop means lower operating and capital costs II.HELIXCHANGER Figure 1. Shell and tube heat exchanger with helical baffles. The concept of helical baffle heat exchangers was developed for the first time Czechoslovakia. The helical baffle heat exchanger also known as HELIXCHANGER is a superior STHE over conventional baffle exchangers. It provides the necessary characteristics to reduce flow dispersion and generate near plug flow condition. It also ensured a certain amounts of cross flow to the tubes to provide high heat transfer coefficient. The Shell side flow configuration offer a very high conversion of pressure drop to heat transfer. The helix changer providesi. Improvement of shell side heat transfer. ii. Less pressure drop for a given mass flow rates. iii. Decreasing of fouling in shell side. iv. Prevention of bundle vibration. v. reducing by pass effect in shell side. Advantages of helix changeri. High thermal & hydraulic performance. ii. High thermal effectiveness. iii. Lower fouling & cleaning ability. Vol. 3 Issue 4 March 2014 214 ISSN: 2278-621X

iv. Vibration elimination. v. Cost saving on total life cycle basis. vi. Improving plant run length. 2.1Concept of Grooved tubes- It is a passive heat enhancement technique generally uses surface or geometrical modification to the flow channel. These geometrical modifications promote higher heat coefficients by disturbing or altering the existing flow behavior. The flow pattern inside the grooved tubes has better fluid mixing particle which leads to better heat enhancement as compare to the plain tubes. Figure shows grooved copper tubes having sine surface of radius 2mm, pitch 100mm, outer dia. of tube 12.7 mm, length 740 mm. Figure 2.Grooved copper tube. III. EXPERIMENTAL STUDY & PROCEDURE In the current paper, comparative thermal performance analysis of helixchanger with plain copper tubes or with grooved copper tubes by using co-current flow at a fixed angle 25 deg. has been carried out. During this experimental investigation attempts were made for both exchangers at same operating conditions to determine the thermal performance. Their results clearly indicate the significant increase in thermal performance of heat exchanger with grooved tubes helixchanger. The process hot fluid was heat-up in the hot water reservoir which has two heating element of capacity 2 KW and heated to prescribed limit. This process fluid was supplied to the tube side part and then to the copper tube of outer diameter of 12.7mm with the help of a pump (0.5 HP) and through the hot flowmeter with different rate of flow. After passing this process fluid through the test section this fluid is fed to the hot water reservoir by a by-pass valve. Similarly, the process cold fluid was supplied to the shell part over the copper tubes by a pump of 0.5 HP and through cold flowmeter with different rate of flow. In the test section the temperature of the process fluid at different location is measured by the use of RTD PT-100 sensor. The total numbers of sensors are 05 used in the test section Figure 3. Experimental set-up layout. Vol. 3 Issue 4 March 2014 215 ISSN: 2278-621X

Figure 4. Photographic view of Experimental set up. The basic experimental procedure is as follows: (1) Filling the system with enough water; (2) Keeping the water valves in full-open state, and running the cool water pump, the hot water pump and the electric heater in turn; (3) Regulating the water flow rate in the hot water loop to a certain value through adjusting the water valve; (4) Regulating the hot water temperature in the tank to a certain stable value through adjusting the power regulator that controls the input power of the heater. (5) Recording the temperatures of the water entering and leaving the heat exchanger (the time interval of the data acquisition system is set as 1s), and meantime, observing the water flow rate in the hot water loop for every minute; (6) After one experimental condition is completed, repeating steps (3)-(5) for the other conditions. The amount of heat transfer (Q=KW in unit) between the hot water flow inside the tubes and cold water outside the tubes can be calculated by Eq. (1) according to the experimental data. Q = mh*cph*(th1-th2) (1) Where, mh mass flow rate of hot water in kg/sec; cph, specific heat of water, J/kg C; th1, th2, inlet and outlet temperature of hot water in C. The heat transfer coefficients (U= w/m2 C) can be written as; U= Q/A (2) Where, A is total flow area of copper pipes, m 2 ; water; C and calculated by Eq. (3) m = (Q1-Q2)/(InQ1/Q2) (3) Where, Q1= th1-tc1; Q2 = th2- tc2, where tc1, tc2, temperature of cold water at inlet and outlet, respectively. The enhancement ratio (ER: %) is used to evaluate the heat transfer enhancement assisted by the grooved tubes. ER = Ug-U/U*100 (4) Where, Ug and U represents, respectively, overall heat transfer coefficient of grooved tube helixchanger and plain tube helixchanger. Vol. 3 Issue 4 March 2014 216 ISSN: 2278-621X

IV.RESULTS 4.1. Influence of water flow rate on Heat Transfer Rate- The heat enhancement brought by the grooved tubes may be influence by water flow rate passing through heat exchanger. In this experimental study, the hot water flow rate inside plain tube helixchanger or grooved tube helixchanger was changed to examine in figure 5.It is clear that the heat transfer has an obvious increase by using grooves. The results also show that the enhanced ratio of heat transfer due to grooves increasing with increasing mass flow rate of hot water (inside tubes). The enhanced ratio for the heat transfer is about 10-27% on different flow rates (0.5, 0.75, 1 kg/sec), as the hot mass flow rate increase rate of heat transfer and overall heat transfer coefficient increase respectively. It is also concluded that there is significant temperature drop in grooved tube as compare to the plain tube helixxchanger with the same operating conditions for both. It indicates that the effect of grooves produce turbulence in flowing fluid which leads to better heat enhancement over plain tube. Therefore it is reasonable to suppose that with the same operating condition heat enhancement of grooved tube helixchanger has better over plain tube helixchanger and it also concluded that heat transfer would increase with increasing flow rate. Figure 5.Effect of different mass flow rates on heat transfer on plain and grooved tube helixchanger Figure 6.Effect of different mass flow rates on heat transfer coefficient on plain and grooved tube helixchanger 4.2 Influence of Inlet hot water temperature on heat transfer enhancement- Hot water temperature produces significant effect on heat transfer coefficient, which influences the efficiency of heat transfer. It is found that enhanced heat transfer efficiency of both, plain tube and grooved tube helixchanger changes with the inlet temperature of hot water. But grooved tube helixchanger has better heat transfer rate over plain tube helixchanger with same operating conditions. The peak point of enhanced ratio occurs at about 60 C where enhanced ratio is about 14%. Temperature may be the most important parameter to be considered in maximizing heat transfer rate. This is because temperature affecting properties of liquid such as viscosity, thermal Vol. 3 Issue 4 March 2014 217 ISSN: 2278-621X

conductivity, and density & specific heat etc. Increasing liquid temperature, on one hand will decrease viscosity of liquid and make it easier to have good heat transfer rate. In this experimental study, temperature 60 C exist a favorable liquid temperature that maximizes the enhanced ratio for grooved tube helixchanger over plain tube helixchanger. Further study ought to be made on this issue and reasonable model be established for guidance. Figure 7.Effect of inlet hot water temperature on Heat transfer rate in plain and grooved tube helixchanger Figure 8.Effect of inlet hot water temperature on Heat transfer coefficient in plain and grooved tube helixchanger 4.3 Influence of grooves on heat transfer enhancement- Temperature drop is directly related to the mass flow rate and groove pattern on tubes. As indicated in figure 7 grooved tube helixchanger, when same operating conditions is taken for both helixchanger, there is a significant temperature drop in grooved tube helixchanger which work in the enhancement of heat transfer. Taking this study for example, at mass flow rate 0.5 Kg/sec and temperature 50 C, the transfer coefficient increase in grooved tubes as compare to plain tubes due to significant temperature drop, about 10% increase in enhanced ratio. When the flow rate of hot fluid is increased to 0.75Kg/sec and 1 kg/sec, enhanced ratio rises 12% and 27% respectively. Therefore it is supposed that the enhanced ratio would further increase if the mass flow rate of hot water increases. Vol. 3 Issue 4 March 2014 218 ISSN: 2278-621X

Figure9. Variation of temperature with mass flow rate in plain and grooved tube helixchanger V. CONCLUSION This study mainly presents some experimental results of heat transfer enhancement of helixchanger assisted by grooved tubes over plain tubes at same operating conditions. The enhancement may be influence by conditions like the fluid temperature, the fluid mass flow rate as well as groove pattern. The effect of groove on the heat enhancement will be more evidence when the fluid mass flow rate is more. The influence of fluid temperature is mainly related to grooves as compare to plain tubes. It can also be concluded that grooves produces a significant drop in temperature of fluid by leading turbulence i.e. mixing of fluid which enhancing heat transfer rate. It is certain that higher the temperature, the higher enhanced ratio will be achieved. The new technology of heat transfer enhancement by using grooves on tubes, which is a passive heat enhancement technique, is still far from the practical application with helix baffle. According to the experimental results, different flow behavior leads to different degree of heat transfer enhancement. The groove pattern on tubes will increase turbulence degree of movement of fluid which leads to better heat enhancement over the plain tube helixchanger. REFERENCES [1] B.I. Master,chungad,A.J Boxma,D.Kral,P.Stheik; Most frequently used heat exchanger from pioneering research to world wide applications, vol.no.6,2008 ppt-8. [2] Young-Gang Lei,Ya-Ling He,Rui,Ya-Fu Crea, Effects of inclination angle on flow and heat transfer of a heat exchanger with helical baffles. Science direct-chemical engineering and processing pp.1-10(2006). [3] B.Peng,Q.W.Wang,C.Zhang, An experimental study of STHE with continuous helical baffles. ASME journal of heat transfer vol.129,pp. 1425-1431(2007). [4] M.R.Jafari and A.Shafeghat, Fluid Flow analysis and extension of rapid design algorithm Science direct- applied thermal engineering,(2006). [5] Bashir Master,K.chunghad, Fouling mitigation using helix changer heat exchanger,.conference on heat exchanger fouling and cleaning. Fundamentals and application.pp 312-317,(2003). [6] Kevin Lunsford, Increasing heat exchanger performance,. Hydrocarbon Engineering,pp1-13,(1998). [7] Sadik Kakaq and Hongfun Lui, Heat exchanger selection rating and thermal design, (2003). [8] D.Kral and J.Nemcansky, The helix changer helically baffled heat exchanger, ICHMT International symposium on new developments in heat exchanger, Portugal, pp 467-477, (1993). [9] R.Mukherjee, effectively design shell and tube heat exchangers, chemical Engg. Progress, pp.1-8 (1998). [10] Prof. sunil kumar shinde,mustanshir hatim pancha, comparative thermal performance Analysis of segmental baffle heat exchanger with continuous helical baffle heat exchanger Using kern s method.. IJERA pp. 2264-2271, (2012). [11] Donald Q.Kern, McGraw hill publication, process heat transfer. Vol. 3 Issue 4 March 2014 219 ISSN: 2278-621X