KEWTECH. KT56 digital multi function tester. Instruction manual

Similar documents
1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA KEWTECH

1.Safe testing IMPORTANT:

DIGITAL RCD(ELCB) TESTER

OPERATING INSTRUCTION

OPERATING INSTRUCTION

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL

MARTINDALE MARTINDALE IN2001/IN2003 INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN2001/IN2003 INSULATION & CONTINUITY TESTERS

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

OPERATING INSTRUCTION

POWERED BY KT71 / Portable Appliance Tester. Instruction Manual

3 PHASE TESTER & MOTOR ROTATION TESTER

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA.

BATTERY OPERATED DIGITAL MILLI-OHMMETER

Instruction Manual. Model 307A Analog Insulation & Continuity Meter

Digital Low Resistance Ohm Meter

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

Metrohm E3640 FLASH TESTER INSTRUCTION MANUAL. Martindale Electric Co Ltd.

DIGITAL MULTIMETER INSTRUCTION MANUAL

BM kv Digital Insulation Tester USER MANUAL

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

I I e k ill L ill. INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER BESANTEK BST-ELC01 INSTRUCTION MANUAL

7/05 FORM#347 OPERATING INSTRUCTIONS MULTI FUNCTION TESTER MODEL 6030

HIGH VOLTAGE PROVING UNIT

MY /2-DIGIT DIGITAL MULTIMETER Users Manual

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

INSTRUCTION MANUAL IDM97II DIGITAL MULTIMETER EN FR IT DE

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

SafetyPAT Plus A B P/N:

USER MANUAL. 10KV Digital High Voltage Insulation Tester. Model MG500. Additional User Manual Translations available at

INSTRUCTION MANUAL IDM91E DIGITAL MULTIMETER EN FR IT DE JP

362 Clamp Meter. Users Manual

INSTRUCTION MANUAL IDM93N DIGITAL MULTIMETER EN FR IT DE

OPERATING INSTRUCTIONS

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

INSTRUCTION MANUAL MARTINDALE CM52 CLAMP METER. ELECTRIC Trusted by professionals. Other products from Martindale:

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

KTD30 Digital Insulation and Continuity Tester

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Safety design conforming to the following provisions

MM300. INSTRUCTION MANUAL Manual-Ranging Digital Multimeter

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Initial and Periodic Inspection and Testing of Electrical Installations ( ) Sample Test

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2

Users Manual. Accessories Motor and Phase Rotation Indicator ships with the following items: 3 test leads 3 test probes 3 alligator clips 9 V battery

Table of Contents. Title Page UT501/UT502 OPERATING MANUAL. Introduction. Unpacking the Meter. Safety Information. International Electrical Symbols

323/324/325 Clamp Meter

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

Instruction Manual. Model 310 Digital Milli-Ohm Meter

Model 8 Mk7 AVOMETER USER GUIDE GUIDE DE L UTILISATEUR BEDIENUNGSANLEITUNG GUÍA DEL USUARIO

Autoranging Industrial Multimeter

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)

DX³ RCCBs - ID 4P up to 100 A

INTRODUCTION... 2 ABOUT THE VALHALLA... 2 ABOUT THIS MANUAL... 2 RETAILER & DISTRIBUTOR OBLIGATIONS... 2 HOW TO USE THIS MANUAL...

User Guide. Model Insulation Tester / Megohmmeter. Introduction

DT33B/C/D OPERATOR S MANUAL LIMITED WARRANTY AND LIMITATION OF LIABILITY

Users Manual. Phase Rotation Indicator

707Ex. Users Manual. ma Calibrator

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

User Guide. Model Insulation Tester / Megohmmeter

TES-1601 INSTRUCTION MANUAL AUTORANGING INSULATION TESTER SAFETY INFORMATION TES ELECTRICAL ELECTRONIC CORP. Warnings and Safety symbols:

Digital Multimeter User's Manual

Instruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale:

LH41A. User Manual. Clamp On Ammeter. For detailed specifications and ordering info go to

Volt/mA Calibrator. Manual

EC400 Power Control System

ASTROAI USER MANUAL DIGITAL MULTIMETER. NOTE: Fully read and understand this manual before using this instrument.

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

LRCD200 Series Combined Loop and RCD Tester USER MANUAL

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER

True RMS Autoranging Multimeter

4-WIRE EARTH RESISTANCE TESTER C1 ES P1 S. Max. AC 200V MICROPROCESSOR CONTROLLED TEST. Switch ON, TEST, SCROLL RESULTS 20Ω 200Ω 2000Ω OFF

USER MANUAL 17TH EDITION MULTIFUNCTION INSTALLATION TESTER. Ethos Test Instruments, Distributed by MTI, Victoria Road, Avonmouth, Bristol BS11 9DB

Model Insulation Tester / Megohmmeter. User Manual

RESIDUAL CURRENT CIRCUIT BREAKER

User's Manual. Earth Ground Resistance Tester. Model Introduction

Autoranging Multimeter

Mini Multimeter with Non-Contact Voltage Detector (NCV)

WELDING INVERTER. PEGAS 160 E Smart PEGAS 200 E Smart OPERATING MANUAL. ALFA IN a.s. PEGAS E Smart Manual EN 04

R & D SPECIALTIES ROTROL I USER'S MANUAL

EPS/ELA-Series User Manual EPS/ELA 250W

This instrument is manufactured in the United Kingdom. The company reserves the right to change the specification or design without prior notice.

Effective discrimination of protective devices

INSTRUCTION MANUAL DM5B Fax: (503)

Vol-Con XL (61-086) Voltage/Continuity Tester and Vol-Test (61-085) Voltage Tester Instruction Manual WARNING

Rental Industry Safety Tester Safe Check 5s

KMP Insulation-Continuity Tester. Users Manual

BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet

Go to to register your product and find more information.

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

USER MANUAL. Insulation Tester + DMM. Model MG320

Digital/Analog Megohmmeter Model 1026

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

G72x Series Direct Spark Ignition Controls

i400s Calibration Information Introduction

Calibrator Capabilities Function Range Resolution Measure V dc 28 V 1 mv Measure ma dc Source ma dc

Transcription:

KEWTECH KT56 digital multi function tester Instruction manual

Contents 1 Safety Notice 1 2 Features and Principles of Measurement 3 3 Introduction 6 4 Specifications 7 5 Instrument layout 9 6 Operating instructions 11 7 Servicing & Calibration 15 1 Safety Notice 1.1 This instrument must only be used by a competent, trained person and operated in strict accordance with the instructions. Kewtech will not accept liability for any damage or injury caused by misuse or non-compliance with the instructions or safety procedures. 1.2 It is essential to read and understand the safety rules contained in the instructions. They must always be observed when using the instrument. 1.3 This meter has been designed with your safety in mind. However, no design can completely protect against incorrect use. Electrical circuits can be dangerous and/or lethal when lack of caution or poor safety practice is used. 1.4 Read this instruction manual carefully and completely. 1.5 Double check all switch settings and lead connections before making any measurements. Do not touch exposed wiring, connections or other LIVE parts of an electrical Circuit. 1.6 This instrument is intended to be used on live installations rated at 230V +10% -15% AC phase to earth or phase to neutral. Under NO circumstances must it be connected to higher voltage or phase to phase. Maximum voltage 1

between mains test terminals and ground is 300V. 1.7 Never open the instrument case. There are no user serviceable parts inside. 1.8 Always inspect the unit and test leads for any signs of abnormality or damage. If abnormal conditions exist (e.g. broken lead, cracked case, faulty display, inconsistent reading etc.), do not attempt to take any measurements and return the unit to Kewtech for rectification. 1.9 If the unit does not power up, inspect your leads for damage or a blown fuse. (Never assume the installation is not live). 1.10 If at anytime during testing there is a momentary degradation of reading, this may be due to excessive transients or discharges on the system or local area. Should this be observed, the test should be repeated to obtain a correct reading. If in doubt always contact Kewtech. 1.11For safety reasons always only use accessories (e.g. leads, probes, fuses, cases etc) recommend by Kewtech as they are designed to work with the tester. The use of any other items is prohibited as they may not have the same safety features built in. 1.12 Always keep your hands and fingers behind all finger guards on test leads used with this instruments. 1.13 This instrument is primarily protected by HRC ceramic fuses and other devices. Do not attempt to replace them if they fail. Should they fail please contact Kewtech. 1.14 Users of this equipment and or their employers are reminded that Health and Safety Legislation require them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as from inadvertent short circuits. Where the assessments show that the risk is significant then the use of fused test leads constructed in accordance with the HSE guidance note GS38 Electrical Test Equipment for use by Electricians should be used. 2

2 Features and Principles of Measurement 2-1 Features LED mains status indication. Digital readout of trip time Constant current measurement 0 and 180 phase selection DC test function for testing DC Excessive Fault Voltage (Uf) warning and lockout 2-2 Principles of Measurement (Fault Loop Impedance) The RCD tester is connected between phase and protective connectors on the load side of the RCD after disconnecting the load. A precisely measured current for a carefully timed period is drawn from the phase and returns via the earth, thus tripping the device. The instrument measures and displays the exact time taken for the circuit to be opened. An RCD is a switching device designed for breaking currents when the residual current attains a specific value. It works on the basis of current difference between phase currents flowing to different loads and returning current flowing through the neutral conductor (for a single-phase installation). In the case where the current difference is higher than the RCD tripping current, the device will trip and disconnect the supply from the current. There are two classifications for RCDs: the first one due to the shape of the residual current wave form (types AC and A) and the second due to the tripping time (types G and S). RCD type AC will trip when presented with residual sinusoidal alternating currents whether applied suddenly or slowly rising. This type is the most frequently used on electrical installations. 3

RCD type A will trip when presented with residual sinusoidal alternating currents (similar to type AC) and residual pulsating direct currents (DC) whether suddenly applied or slowly rising. This type of RCD is not commonly used at present, however, it is increasing in popularity and is required by the local regulations in some countries. RCD type G. In this case G stands for general type (without trip-out time delay) and is for general use and applications. RCD type S where S stands for selective type (with tripout time delay). This type of RCD is specifically designed for installations where the selectivity characteristic is required. In order to assure successful protection on an electrical installation using RCDs they should be checked to test trip-out time t. Trip-out time t is the time needed by the RCD to trip at a rated residual operating current of I n. The standard values of tripping time are defined by IEC 61009 (EN 61009) and IEC 61008 (EN 61008) and are listed in the table below for I n and 51 n. Type of RCD l n 5I n 300ms 40ms General (G) max allowed max allowed value value 500ms *150ms max allowed max allowed Selective (S) value value 130ms *50ms max allowed max allowed value value Maximum 5I n tripping time is limited to 50 ms as required by BS7671 when OL is displayed. 4

Typical examples of instrument connection Practical example of 3-phase + neutral ROD test in a TT system. Practical example of single phase RCD test in a TN system. 5

3 Introduction 3.1 Your KT56 Tester uses the latest state of the art Microprocessor Technology to give the best possible performance and accuracy. 3.2 Independent Constant Current Control Constant current circuitry permits accurate and consistent readings even when the voltage fluctuates by 230V+10%- 15% 3.3 DC Sensitive Breakers When the KT56 is switched to the DC mode it will test 30 ma DC sensitive breakers. If the fault current to earth is not a pure sine wave but has a DC current component, it is possible that the breaker will not trip at its rated tripping current. It is only those breakers that are also sensitive to DC fault current that will trip with this type of fault current. The KT56 is capable of testing these breakers by introducing a DC fault current- Fluctuating DC Waveform DC sensitive RCDs will trip To check whether a DC sensitive RCD is functioning a DC fault is injected with the above waveshape (reference IEC1008). 6

4 Specifications Measurement Specification Test Current Settings 10, 20, 30, 100, 300, 500mA Test Current Factors X1/2, X1, X5, DC Fault Trip Current Duration 2000ms (X1/2, X1, DC 50 ms (X5) Rated System Voltage 230+10% -15% Test Current Intrinsic X1/2-8% - 2% Accuracy X1 +2% +8% X5 +2% +8% DC ±10% Trip Time Intrinsic Accuracy ± (0.6% + 4dgts) Reference Conditions Ambient Temperature: 23±5 C Relative Humidity: 60±15% Nominal System Voltage and Frequency: 230V, 50Hz Altitude: Less than 2000m Operating Error (Trip Current) EN61557-6 Function Operating Error x 1/2-10% to 0% x 1 0% to +10% x5 0% to +10% The influencing variations used for calculating the Operating Error are as follows; Ambient Temperature: 0 C and 40 C 7

Earth electrode resistance: Max 50Ω (max 20Ω at x 5 500mA only) System voltage: 230V+10% -15% Relative Humidity: Less than 85% General Specification Storage Temperature: -20 C to +60 C Storage Relative Humidity: 85% maximum Weight: 540g Maximum Altitude: 2000m Dimensions: 175 X 115 X 85.7 mm Over Range indication: OL Input Voltage greater than 260V indication: VP-E Hi Over Temperature indication: Applied Standards Instrument operating standard: - IEC/EN 61557-1, IEC/EN 61557-6 Safety standard: - IEC/EN 61010-1, CAT III (300v) - instrument Protection degree: - IEC 60529 (IP40) Accessories KAMP10 Mains test lead with IEC Connector Test lead carry pouch This manual and product may use the following symbols adopted from international Safety Standards. Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION. Caution, risk of electric shock. Caution (refer to accompanying documents). 8

5 Instrument layout LCD display 0 & 180 phase shift switch Test button Main status indication LED Function switch Rated tripping current switch 9

Test lead Kamp 10 LCD display 10

6 Operating Instructions 6.1 Initial Checks: to be carried out before any testing; a) Always inspect your test instrument and lead accessories for abnormality or damage- If abnormal conditions exist DO NOT PROCEED WITH TESTING. Have the instrument checked by Kewtech. b) Before pressing the test button; always check the LED's for the following sequence: P-E Green LED must be ON P-N Green LED must be ON Red LED must be OFF If the above sequence is NOT displayed or the RED LED is on for any reason, DO NOT PROCEED AS THERE IS INCORRECT WIRING. The cause of the fault must be investigated and rectified. c) If other loads are connected to the test circuit; these may cause erroneous readings. To make the most accurate readings, loads on the circuit should be disconnected. d) Use only the leads supplied with instrument or Kewtech approved equivalents. e) If the fault voltage (Uf) exceeds 50V AC the display will indicate VN-E-Hi and the tester will be unable to continue the measurement. f) If the over temperature symbol appears on the display disconnect the instrument and allow it to cool down. g) If the input voltage is greater than 260V the display will indicate VP-E Hi and the measurement will be halted. h) When making a test with the selected range higher than the rated tripping current of the RCD, the RCD may trip and the display will indicate no. 11

6.2 Preparation:- a) Connect the instrument to the circuit to be tested (see following sections for procedure). Make sure the LED's are lit as per the initial checks. b) If the sequence is not correct, disconnect the instrument and check the installation wiring for a possible fault. 6.3 Testing a) No Trip Test (X1/2) b) The No Trip Test is designed to ensure that the circuit breaker is operating within its specifications and is not too sensitive. c) Set test tripping current to X1/2range and the RCD rated tripping current to the rated trip current of the breaker under test. d) Press and release the Press to Test button. Half the rated tripping current selected will pass through the breaker. The breaker will not trip if it is functioning correctly. e) While the test is being conducted the meter display will be ms. f) If the Press to Test button is released the result will be displayed for 3s before reverting to zero. If the button is held down, the result will be displayed until the button is released. g) If the breaker trips, the display will read the trip time. The display will be held for approx 1Os. h) Reverse the phase angle switch and repeat above. After repeated testing the unit may overheat. This is indicated by the over temperature sign. If this happens disconnect the unit from the mains and allow to cool down. This applies to the No Trip Test, Trip Test, Fast Trip Test and DC Trip Test. 12

6.4 Trip Test (X1) a) Select the X1 test tripping current. b) Press the test button. The RCD should trip and the tripping time will be displayed on the instrument LCD in ms. While the test is being conducted the display will indicate ms. c) Reset the breaker and reverse the phase angle switch. Press the Press to Test button and the breaker should trip. d) Reset the breaker and reverse the phase angle switch again. Press the Press to Test button the breaker should trip. e) The readings obtained in 5-4-d and 5-4-c should both be within the trip time specified for the breaker at its rated tripping current. f) If the breaker does not trip there is a fault. g) To hold the reading press and hold down the Press to Test button. 6.5 Fast Trip Test a) This is a special test required for a circuit breaker that is installed to reduce the risk associated with direct contact for breakers rated up to 30 ma. b) Set the test tripping current function switch to the X5 position. c) Set the RCD rated tripping current switch to 30 ma. d) Set the phase angle switch to the 0 position. e) Press and release the Test button. The breaker should trip. f) Reset the breaker. Change the phase angle switch to the 180 position and press the Test button. g) Rest the RCD to 0 and press the Test button. h) The trip times of the last two measurements should both be less than 40 ms. If the tripping times are greater than 40 13

ms the RCD may be faulty and must be re-checked. 6.6 Testing DC sensitive RCDs a) The following test is designed for those breakers which are sensitive to DC fault currents. It is primarily designed to test breakers of 30 ma rating. b) Set the RCD rated tripping current switch to 30 ma. c) Set the function switch to DC test. d) Select 0 phase angle. e) Press the Press to Test button, the breaker should trip with the trip time displayed in ms. f) Repeat steps 5-6-b-5-6-e but with the phase angle switch to 180. Note If a voltage exists between neutral and earth it may influence the measurements, therefore, the connection between the neutral point of the distribution system and earth should be checked prior to testing. If leakage currents flow in the circuit following the RCD this may influence the measurements. The potential fields of other earthing installations may influence the measurement. Specific requirements of RCD's of a particular design for example S type should be taken into consideration. The earth electrode resistance of a measuring circuit with a probe shall not exceed 50Ω (20Ω at x 5 500mA only). 14

7 Servicing and Calibration If this tester should fail to operate correctly, return it to Kewtech marked for the attention of the Service Department. stating exact nature of fault. Make sure that: a. operating instructions have been followed b. leads have been inspected c. the unit is returned with all accessories Regular re-calibration is recommended for this instrument. We recommend that with normal use, the instrument is calibrated at least once in every 12 month interval. When this is due for re-calibration return it to Kewtech marked for the attention of the Calibration Department and be sure to include all accessory leads, as they are part of the calibration procedure. Optional lead ACCO16E lead is available for testing at distribution boards. This is fused with the fuses rated at 10A/600V high rupture ceramic types. If they should blow always return the instrument and leads to Kewtech for checking. The fuses are special and should only be replaced by equivalent types. Returning the product to Kewtech will ensure this. If other leads are used then reading may not be true unless they are calibrated with the instrument. If this product needs cleaning use a damp cloth to wipe its surfaces. DO NOT use strong cleaning agents as these may damage the plastic surfaces. Kewtech reserve the right to change specifications and design without notice and without obligation. 15

Case, strap, shoulder-pad and test lead pouch assembly Assemble the shoulder strap through the case lugs and the test lead pouch in the following sequence: 1 Pass the strap down through the first lug, under the case and up through the other lug. 2 Slide the shoulder pad onto the strap 3 Feed the strap down through the slots in the back of the test lead pouch. 4 Pass the strap through the buckle, adjust the strap for length and secure. 16

Distributor Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA www.kewtechcorp.com KEWTECH 92-1617 04-03