1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

Similar documents
1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

Transformer bushings, type GOH. Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide

Bushings for High Voltage AC Applications

Transformer bushings, type GSA-OA Technical guide

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

Transformer bushings, type GOA 250. Installation and maintenance guide

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution

A of 3. Edition : Date : Page : Document No. Amendments :

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide

A of 14. Edition : Date : Page : Document No. Amendments :

DM Condenser bushings, kV DURESCA

DURESCA Busbar system. For indoor and outdoor applications, type DE / type DG DURESCA

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide

en, Rev. 10. Transformer bushings, type GOH Installation and maintenance guide

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual

1ZSC ABH en, Rev. 1. Motor-drive mechanisms, types BUE and BUL2 Maintenance guide

INSTRUCTION MANUAL CRS Combined insulation bushing

B kv Gas-insulated Substations

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

kv А

1ZSC ABE en, Rev. 1. HVDC bushing, type GSD Installation and maintenance guide

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

en, Rev. 7. Transformer bushings, type GOM Installation and maintenance guide

CP Automatic capacitor bank

en, Transformer bushing, type GSA-OA Installation and maintenance guide...

MICAFIL RIP Transformer Bushings AirRIP / RTKF kv

Transformer Bushing Type EKTG

1ZSC AAX EN, Transformer bushing, type GSC Installation and maintenance guide

Current transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv

Transformer Bushing Type EKTO

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R

GAS INSULATED VOLTAGE TRANSFORMERS.

B kv T&D GAS INSULATED SWITCHGEAR

Medium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance

3 TM Cold Applied Barrier Boot System

EMPAC Metal enclosed capacitor bank for wind applications

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

TE S RAYCHEM RSTI-CC-58 SCREENED, SEPARABLE COUPLING SYSTEM

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

Transformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

Zinc Oxide Surge Arrester EXLIM R

15 kv and 25 kv Thru-Bushings

Low voltage bushings for pad-mounted distribution transformers Technical information guide

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

Motor-drive mechanism, type BUL. Technical guide

Power Voltage Transformers for Air Insulated Substations

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

25 kv Apparatus Bushings

Separable Connectors and Kits

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

NXPLUS C Single busbar. Maintenance-free for lifetime

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List

IEC Separable Connectors 17.5 kv/24 kv, 630A

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

High Voltage and Extra High Voltage Cables

MEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance

SERIES TAP-CHANGER

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

Medium Voltage Products. KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance

LV Capacitor CLMD Reliability for Power Factor Correction

TGK Prefabricated Substation Technical Data

Zinc Oxide Surge Arrester PEXLIM Q

MODVAR Low voltage reactive power compensation modules Installation manual

ZX2 Gas-insulated medium voltage switchgear

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Eaton s Cooper Power Systems

Combined instrument transformers

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

High Voltage Surge Arresters Buyer s Guide Section PEXLIM P-Y

MEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance

Transcription:

1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide

Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted.

Content Design... 4 Standards... 4 RIPCOAT... 4 Features and benefits... 4 Transportation and long term storage... 5 General specifications... 5 Testing... 6 Routine testing... 6 Type tests... 6 Special tests... 6 Test tap... 6 Test tap adapter... 6 Electrical data... 7 Dimensions... 8 Connection details... 1 Draw rod system... 1 Fixed bottom contact... 11 SF 6 side terminal... 11 Standard end-shield... 11 Conductor loading... 12 Overloading of bushings according to IEC... 12 Short-time current... 12 Recommendations for positioning... 13 Ordering particulars... 14

Design GSBK is a Resin Impregnated Paper (RIP) bushing intended for immersed oil SF 6 service. The bushing can be mounted in any direction from vertical to horizontal. Outer terminal The insulation core of the GSBK is produced by winding crepe paper onto a center tube, with aluminium foil insert for electrical stress control. The manufacturing process is optimized to give a partial discharge free bushing with low dielectric losses. RIP core As a current conductor, GSBK uses the center tube, which is moulded into the RIP core. The outer terminal is fit to the center tube by a bolted joint. The bottom contact on the transformer side is mounted by a draw rod system or by a bolted joint. Mounting flange Test tap Standards The GSBK bushing is designed and tested according to IEC 6137 and IEC 62271-211. RIPCOAT Water uptake on the RIP bushings during transport, handling and storage leads to increased dielectric losses. At site this means that the bushings might need to be dried before assembling leading to delays. A water barrier RIPCOAT has been developed to solve this problem. The time to reach critical dissipation factor has been stretched by a factor of up to 8 by using RIPCOAT compared to bushings with an unprotected oil-side. Actual time depends highly on level of relative humidity and temperature. Center tube Fig. 1. Transformer bushing type GSBK oil SF 6 connection. Features and benefits Solid Reduced risk of fire. No restriction in mounting angle. Oil leakage from the bushing eliminated. Seals the transformer Reduced risk of fire. Risk of oil leakage from the transformer reduced.. Non-brittle materials Protection of people and equipment. Easy handling. Safe transport - even when mounted on the transformer. High earthquake withstand. Light weight, compact Easy handling, small space requirements inside transformer, low life cycle environmental impact. 4 Technical guide GSBK 1ZSC563-AAA en, Rev. 6

Transportation and long term storage The bushing is surrounded by a sealed moisture-proof wrapping material together with a drying agent upon delivery. The supplied protective wrapping shall not be opened if the bushings are intended to be stored. After transformer test, it is also important to reseal the bushing with the supplied protective wrapping or a similar moisture-proof wrapping, together with a drying agent. The wrapping works as protection for transportation and storage ( 6 months). Note that bushings with standard wrapping shall be stored protected from precipitation. For longer storage times (>6 months) a container have to be ordered separately. General specifications For conditions exceeding the standard specification, please consult the supplier. Application: Transformers Classification: Resin impregnated paper, capacitance graded, completely immersed bushing, temperature class E (12 C) according to IEC 6137 Ambient temperature: +4 C to -4 C, minimum value acc. to temperature class 3 of IEC 6137 Immersion medium on SF 6 gas. Max daily mean temperature +75 C. switchgear side: Max pressure of medium 75 kpa (over pressure) on switchgear side: Immersion medium on Transformer oil. transformer side: Max daily mean oil temperature +9 C. Max temporary oil temperature +115 C. Oil level in transformer: Not lower than 3 mm from the bushing flange. Max. pressure of 1 kpa (over pressure) medium: Angle of mounting: Horizontal to vertical Test tap: Dimensions according to IEEE, Type A. Max. service voltage 6 V. Voltage tap: Dimensions according to IEEE, Type A. Max. service voltage 6 kv. Capacitance C 2 of test < 5 pf tap: Conductor: Integrated tube conductor Markings: Conforming to IEC 1ZSC563-AAA en, Rev. 6 Technical guide GSBK 5

Testing Routine testing The bushing is routine tested according to IEC 6137 and IEC 62271-211. The tests include measurement of partial discharge quantity, tan δ, capacitance and power frequency voltage withstand test. On each bushing, an external pressure test is performed and the tightness between the gas side and the oil side is confirmed. An individual routine test report is issued with each bushing. The routine test is carried out at room temperature with the bushing immersed in transformer oil. Type tests Type tests have been performed according to above standards and are available on request. Special tests A number of tests not specified by the above standards have also been performed and summaries are available on request. Test tap The outer conducting layer of the condenser core is connected to an insulated test tap on the flange. During operation the protective cap must be fitted in order to ground the outer layer to the flange. The maximum test voltage is 2 kv, 5 Hz for 1 minute. The maximum service voltage is 6 V. Voltage tap is available as on request. The maximum test voltage is 2 kv, 5 Hz for 1 minute. The maximum service voltage is 6 kv. The test tap and voltage tap have dimensions according to IEEE, potential tap type A. Test tap adapter For permanent connection of the test tap to the measuring circuits, a test tap adapter (catalog number 2769 522-C) is sometimes required, for example if the IEEE dimension standard for measuring tap is not used.. Fig. 2. Test tap. 6 Technical guide GSBK 1ZSC563-AAA en, Rev. 6

Electrical data Ratings GSBK 17 245 362 42 55 Rated voltage IEC (kv), U m 17 245 362 42 55 Rated phase-to-ground voltage IEC (kv) 98 141 29 242 317 Basic Insulation Level (kv) (Equal to dry lightning impulse withstand voltage.) 75 15 13 155 1675 Dry switching impulse level (kv), SI N.A. 85 15 1175 13 Dry power frequency. Routine test 1 minute (kv) 365 56 63 695 75 Rated current (A), I r Note! Higher current ratings are available on request. Al conductor 16 16 16 16 125 Cu conductor 25 25 25 25 25 Rated frequency (Hz), fr 5/6 5/6 5/6 5/6 5/6 Temporary over voltage (kv) IEC (phase-to-ground voltage) 17 196 29 336 44 Space for current transformer (mm) 3/6 3/6 3/6 3/6 3/6 Nominal capacitance between conductor and test tap C 1 ±1 % (pf) 496/656 5/622 45/494 346/424 286/352 1ZSC563-AAA en, Rev. 6 Technical guide GSBK 7

Dimensions D4 R1 Ø 87 Shield SF 6 side Ø 87 R58 R1 17 72 R58 R58 R1 R1 L1 L5 D1 GSBK 17 GSBK 245-55 Flange SF 6 side 1.6 D7 x n1 L L3 L4 D5 D6 L2 D2 Flange oil side D1 x n2 D8 D9 D3 Dimensions are subject to modification without notice. Fig. 3. Dimensions. Dimensions in mm Space for Rated Cat. No. 1ZSC... current Type current Voltage tap transformer Net mass GSBK (A) Test tap 6 kv (mm) (kg) L L1 L2 L3 L4 L5 17 16 917-AAA 917-ABA 3 68 147 52 75 2 3 378 -AAB -ABB 6 78 177 52 15 2 6 378 17 25 917-ACA 917-ADA 3 96 147 52 75 2 3 378 -ACB -ADB 6 113 177 52 15 2 6 378 245 16 9245-AAA 9245-ABA 3 114 189 77 92 2 3 663 -AAB -ABB 6 128 219 77 122 2 6 663 245 25 9245-ACA 9245-ADA 3 152 189 77 92 2 3 663 -ACB -ADB 6 171 219 77 122 2 6 663 362 16 9362-AAA 9362-ABA 3 178 2285 15 135 2 3 943 -AAB -ABB 6 198 2585 15 1335 2 6 943 362 25 9362-ACA 9362-ADA 3 227 2285 15 135 2 3 943 -ACB ADB 6 253 2585 15 1335 2 6 943 42 16 942-AAA 942-ABA 3 24 234 15 19 2 3 943 -AAB -ABB 6 231 264 15 139 2 6 943 42 25 942-ACA 942-ADA 3 25 234 15 19 2 3 943 -ACB -ADB 6 28 264 15 139 2 6 943 55 125 955-AAA 955-ABA 3 258 2535 15 1285 2 3 943 -AAB -ABB 6 294 2835 15 1585 2 6 943 55 25 955-ACA 955-ADA 3 312 2535 15 1285 2 3 943 -ACB -ADB 6 354 2835 15 1585 2 6 943 8 Technical guide GSBK 1ZSC563-AAA en, Rev. 6

Cantilever load Condenser core D1 D2 D3 D4 D5 D6 D7 x n1 D8 D9 D1 x n2 Max operating load (kn) Test load (kn) 188 18 146 187 335 35 16 x 8 335 29 15 x 12 2 4 188 18 146 187 335 35 16 x 8 335 29 15 x 12 2 4 188 18 146 187 335 35 16 x 8 335 29 15 x 12 2 4 188 18 146 187 335 35 16 x 8 335 29 15 x 12 2 4 214 26 146 187 565 535 16 x 16 45 4 23 x 12 2 4 214 26 146 187 565 535 16 x 16 45 4 23 x 12 2 4 214 26 146 187 565 535 16 x 16 45 4 23 x 12 2 4 214 26 146 187 565 535 16 x 16 45 4 23 x 12 2 4 266 256 146 187 69 64 2 x 16 5 4 23 x 12 2 4 266 256 146 187 69 64 2 x 16 5 4 23 x 12 2 4 266 256 146 187 69 64 2 x 16 5 4 23 x 12 2 4 266 256 146 187 69 64 2 x 16 5 4 23 x 12 2 4 31 29 146 187 69 64 2 x 16 5 45 23 x 12 2 4 31 29 146 187 69 64 2 x 16 5 45 23 x 12 2 4 31 29 146 187 69 64 2 x 16 5 45 23 x 12 2 4 31 29 146 187 69 64 2 x 16 5 45 23 x 12 2 4 355 342 146 187 69 64 2 x 16 55 5 23 x 12 2 4 355 342 146 187 69 64 2 x 16 55 5 23 x 12 2 4 355 342 146 187 69 64 2 x 16 55 5 23 x 12 2 4 355 342 146 187 69 64 2 x 16 55 5 23 x 12 2 4 1ZSC563-AAA en, Rev. 6 Technical guide GSBK 9

Connection details Draw rod system The draw rod system offers the following advantages compared to other connection systems: No hand holes required in the transformer tank. Easy bushing installation and removal no connection work inside the transformer at site. No special supports required in the transformer as is the case with plug contacts. Perfect guiding of the bushing into the transformer. The lower end shield may be fixed to the contact and will thus be correctly positioned with respect to the lower end plate of the bushing. The center tube of the bushing is used as current conductor. The transformer leads are fitted with cable lugs, which are bolted to a bottom contact. This contact is pressed against the bottom end of the bushing tube by a steel draw rod. The upper end of this rod is bolted to a compensating device, which consists of a spring and is so designed that it gives the required contact pressure at all temperatures. The draw rod is divided at the level of the flange. If required by the transport conditions, an additional joint can be positioned below the flange. This must be stated in the order. The lower part with contact end shield can then be secured to the cover during transport and storage of the transformer. Bottom contacts with 4 threaded holes for cable lugs are available. The bottom contacts are made of copper in one piece. To this bottom contact there is a suitable end shield, cat. No. 1ZSC9993. Special bottom contacts are available on request. Catalogue number for draw rod: 1ZSC9994. Threaded hole M8 for pulling wire L 25 Additional joint on request 6 L2 64 45 H1 min 2 M12 (4x) Fig. 4. Draw rod system. 1 Technical guide GSBK 1ZSC563-AAA en, Rev. 6

Fixed bottom contact The fixed bottom contact (Cat. No. 1ZSC9992-AAE) uses the same bottom contact as in the draw rod system, i.e. it is made of copper in one piece and has 4 threaded holes for cable lugs. The fixed bottom contact system also uses the center tube as a current conductor but it is secured to the center tube with a pulling ring instead of the draw rod. The pulling ring is made of aluminum and is threaded on to the center tube. The bottom contact is then fastened to the ring with six M1 bolts. Standard end-shields with Cat. No. 1ZSC9993, is suitable for the bottom contact. 64 45 M12 (4x) Fig. 5. Fixed bottom contact. SF 6 side terminal The dimensions on the SF 6 side terminal fully comply to IEC 62271-211 and include 4 threaded holes for GIS connection. The terminal is fitted to the top end of the conductor tube by means of bolts, screwed into a pulling ring. The terminal surface for GIS connection is silver plated. Special terminals are available on request. Fig. 6. SF 6 side terminal. Standard end-shield The end-shield is made of aluminum and coated with insulating epoxy paint or 3 mm of pressboard. The design enables easy installation and should be used with standard draw rod bottom contact, or with the fixed bottom contact system. Cat. No. Coating 1ZSC9993-AEA 1ZSC9993-AEB Epoxy paint 3 mm pressboard 1ZSC563-AAA en, Rev. 6 Technical guide GSBK 11

Conductor loading The GSBK bushings fulfill the temperature rise test requirements according to IEC for the currents in the table below. The rated thermal short-time current (I th ) is calculated according to IEC 6137. Contact the supplier for current ratings for GSBK in oil - oil applications. Bushing GSBK Rated current A Short-time current (I th ) ka, rms Dynamic current (I d ) ka, peak 1 s 2 s 17 16 57 4 1 17 25 88 63 156 245 16 57 4 1 245 25 88 63 156 362 16 57 4 1 362 25 88 63 156 42 16 57 4 1 42 25 88 63 156 55 125 57 4 1 55 25 88 63 156 Overloading of bushings according to IEC If the conductor for the bushing is selected with 12 % of the rated current of the transformer, the bushing is considered to be able to withstand the overload conditions stated in IEC 676-7 when following the directions: for long time and short time emergency loading the oil temperature must be 115 C max. and the daily mean oil temperature must be 9 C max. For overload conditions other than the above-mentioned IEC overload, contact the supplier for permissible currents and temperatures. Short-time current The rated thermal short-time current (I th ) is calculated according to IEC 6137. 12 Technical guide GSBK 1ZSC563-AAA en, Rev. 6

Recommendations for positioning The maximum stresses in the oil at the surface of the shield and the parts surrounding the bushing must be limited to the normal values for insulated conductors and other similar components in the same transformer. D3 The withstand voltages in a specific case depend upon many factors beyond the control of the bushing manufacturer. Therefore the configurations and distances given in the table and figures are only intended as guidelines. 1 /3 x L4 max L4 Type E (mm) BIL L4 (mm) d3 (mm) d4 (mm) GSBK 17 3 75 52±1 3 22 +3 6 75 52±1 3 22 +3 245 3 15 77±2 45 45 +5 6 15 77±2 45 45 +5 362 3 1175 15±2 54 54 +5 6 1175 15±2 54 54 +5 42 3 155 15±2 54 54 +5 6 155 15±2 54 54 +5 55 3 155 15±2 54 54 +5 3 1675 15±2 58 54 +5 6 155 15±2 54 54 +5 6 1675 15±2 58 54 +5 D4 E 3 R min R5 Fig. 7. Recommendations for positioning. 55 5 R25 Radius (mm) 45 4 35 R296 8 265 3 R35 25 2 3 35 4 45 5 55 6 65 7 75 U (kv) R9 Ø 142 Ø 258 R32 Fig. 8. Recommended minimum distance R, for standard shield at 1 minute power frequency (rms) test. Fig. 9. End shield. 1ZSC563-AAA en, Rev. 6 Technical guide GSBK 13

Ordering particulars When ordering, please state: Type and catalogue number for bushing Connection details: fixed bottom contact or draw rod Catalogue number for shield on oil side Additional accessories or modifications Test required, in addition to the normal routine tests Fig. 13. Nameplate with marking example. 14 Technical guide GSBK 1ZSC563-AAA en, Rev. 6

Contact us ABB AB Components SE-771 8 Ludvika, Sweden Phone: +46 24 78 2 Fax: +46 24 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents Copyright 214 ABB, All rights reserved. 1ZSC563-AAA en, Rev. 6, 214-1-3