Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Similar documents
8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

K-Limiter high ampere Companion II fuse

Edison modular fuse, vault application products

TEMPERATURE RISE TESTS

ELF -LR current-limiting fuse

Eaton s Cooper Power Systems

X-Limiter full-range current-limiting fuse

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

BUSSMANN. Pre-production and sample electric vehicle power fuses 500 Vdc, A SERIES. Technical Data Effective December 2018.

Effective March 2015 Supersedes S August 2012

NX indoor current-limiting fuses

Direct-connected capacitor fuse

Fusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses

A 1.2 kv class externally removable secondary bushing

600 A 15 kv class Cleer loadbreak connector system

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Faulted Circuit Interrupting Tests on Type CMU Power Fuses

600 A 35 kv class BT-TAP deadbreak connector

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

3.2. Current Limiting Fuses. Contents

Product Selection Guide

Faulted Circuit Interrupting Tests on Type CMU Power Fuses

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

600 A 28 kv class Cleer loadbreak connector system

Figure 1. Two and Three-phase MagneX.

Electric vehicle auxiliary fuses 500 Vdc, A

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Figure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION

Mica Element Support. Compacted Quartz Sand. Length B

PT Medium voltage fuses for potential and small power transformers

Low-Peak LPJ Class J 600Vac/300Vdc, 1-60A, dual element, time-delay fuses

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

PROTECTION AND CONTROL

6.3 mm reverse quick connect

FRNR A 250V TD Class RK5 Dual Elem Fuse-Fusetron

CERTIFIED TEST REPORT

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

M-Force three-phase switch

BUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

100 A externally operated one-, twoand three-phase tap-changer switch

600 A 15 kv class T-OP II deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults.

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

CMU medium voltage power fuses

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

LKN A 250V Super-Lag Fuse Link. Features amperage rating 200 class Voltage Rating 250. Long Description. Manufacturer Information

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

Technical Specification For Outdoor Substation Harmonic Filter Banks

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Single-phase step voltage regulators

FX Full-Range Current-Limiting Fuse

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

M-Force three-phase switch

COOPER POWER CA280012EN

25 kv class fused loadbreak elbow connector

Single-phase pad-mounted step voltage regulator

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

NOVA three-phase, microprocessorcontrolled

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Type NR oil switch installation and operation instructions

600 A 15 and 25 kv class Cleer grounding elbow

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products

FUSE TECHNOLOGY Ambient temperature

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

600 A 35 kv class deadbreak accessories, tools, and replacement parts

High-voltage primary bushings installation instructions

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Single-Phase Step Voltage Regulators

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

Specification made simple for selective coordination in a compact size

EE 741 Over-voltage and Overcurrent. Spring 2014

Section 1 Introduction to the Presentation

Loadbreak Apparatus Connectors

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION

600 A 35 kv class separable splices

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

BH-1 modular fuse blocks, 700 V, 400 A

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

INSTALLATION PRODUCTION TESTS

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

The easiest and fastest way to select and specify the right control circuit fuse

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

Bussmann series Quik-Spec Power Module Switch elevator disconnect

Transcription:

Page:1 of 9 CERTIFIED TEST REPORT Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C37.41-2008 REV. 00 August 11, 2014 Original Report Date: August 11, 2014 Eaton s Cooper Power Systems

Page:3 of 9 INTRODUCTION The 38kV ELSP fuses are designed to be applied as backup type current-limiting fuses. In this application, the ELSP fuse provides protection against high current faults and limits the peak current and the amount of let-through energy to the protected equipment. The ELSP fuse is typically applied in series with an expulsion device. When applied with an expulsion device or another type of low current interrupting device, the combination provides full range protection. The dielectric tests specified by C37.41-2008 are a function of the fuse mounting and enclosure rather than of the particular fuse design. Therefore this report does not include these tests. Contact Eaton s Cooper Power Systems for additional information. Scope of Testing Interruption Testing at Line-to-Neutral Rated Voltage Series 1 Rated Maximum Interrupting Current Series 2 Critical Current Series 3 Rated Minimum Interrupting Current Time Current Characteristics Thermal Cycle Seal Radio-Influence Voltage Temperature Rise

Page:4 of 9 INTERRUPTION TESTING Requirements Backup current-limiting fuses are required to operate on high available fault currents and limit the fault current magnitude and energy. They must interrupt these fault currents so that the other pieces of connected equipment are isolated from the distribution system. Verify the interrupting performance of the 38 kv ELSP current-limiting backup fuse according to the requirements specified in ANSI/IEEE C37.41-2008, clause 6.6 and C37.47-2011, clause 4.2. procedures. Testing was conducted at ambient temperature for Series 1 and Series 3. For Series 2, testing was performed at the RMAT (140 C) for the maximum current rating of each homogeneous series (65A, 100A, 120A, & 140A) and at ambient temperature for all other ratings (50A & 80A). Peak arc voltages were measured and recorded during all testing. Series 1 testing was performed at the KEMA Laboratories, Arnhem, Netherlands, in May 2014. All other testing was performed at Powertech Labs in Surrey, BC and the Edison Technical Center in Franksville, WI. Results The 38 kv ELSP fuses successfully interrupted each respective test current. The performance parameters are detailed in the Table below. Base Catalog # Fuse Rating Min. Melt I 2 t 38.0 kv Ratings Total Clear I 2 t Rated Minimum Interrupt Level Amps Maximum Interrupting Rating (Amps symmetric) kv Amp CBUC38050D100 38.0 50 3,870 30,600 450 50,000 CBUC38065D100 38.0 65 7,160 39,300 490 50,000 CBUC38080D100 38.0 80 11,450 60,700 625 50,000 CBUC38100D100 38.0 100 16,100 80,500 635 50,000 CBUC38120D100 38.0 120 21,200 118,000 700 50,000 CBUC38140D100 38.0 140 36,240 163,000 800 50,000 Conclusions The tested fuses successfully interrupted the required current and voltage, and were within the required peak arc voltage levels as specified in C37.47-2011.

Page:5 of 9 TIME CURRENT CHARACTERISTICS TESTS Requirements Time current characteristics curves are primarily used for application, selection, and system coordination studies. The minimum-melt and total-clearing curves detail the operational performance for a particular fuse design. Establish time-current characteristic curves for the 38 kv ELSP current-limiting fuses per ANSI/IEEE C37.47-2011 requirements. procedures. Minimum-melt and total-clearing time-current characteristic curves were developed using ANSI/IEEE C37.41-2008, Clause 11 requirements as a guideline. Testing was performed by placing the fuses in mineral oil in the horizontal position to simulate actual field application. The fuses were tested by applying current and measuring the time until the fuses opened. The curves were developed by utilizing curve-fitting techniques and applying the appropriate tolerances. An allowance for arcing time is also added to the total-clearing curve to determine the fuse s total clearing characteristics. Testing was performed at ambient temperatures. Results and Conclusions The minimum-melt and total-clearing TCC curves for the 38 kv ELSP backup current-limiting fuses were developed using the procedure described above and are detailed in ECPS product literature R240-91-170.

Page:6 of 9 THERMAL CYCLE SEAL EVALUATION Requirements Oil leaking into the sand fuse can adversely affect fuse operation. It is essential, therefore, to verify seal integrity of the fuse design. Testing per ANSI/IEEE standards was performed as detailed below. Verify seal integrity of the 38 kv ELSP fuse per ANSI/IEEE C37.41-2008 requirements. procedures. The highest ampere rating of the 38kV ELSP family (140A) was chosen so as to provide the highest thermal stress. Testing was conducted per ANSI/IEEE C37.41-2008, Clause 13 requirements. The test involved placing five fuses in mineral oil with thermocouples placed at selected locations on the fuses and within the surrounding oil medium to monitor temperatures. Ten cycles were run from room ambient (25 C) to a maximum temperature of 140 C. Current was passed through each fuse sample for two hours after the oil reached 140 C. The fuses were then allowed to cool down to room ambient, completing one cycle. Following the conclusion of the ten cycles, the fuses were dissected and examined for any oil ingress. Results The 38kV 140A ELSP fuse assemblies successfully passed the thermal cycle seal test, maintaining seal integrity when cycled per ANSI/IEEE C37.41-2008 requirements. Conclusion The 38kV ELSP family of fuses meets the ANSI/IEEE C37.41-2008 requirements for seal integrity.

Page:7 of 9 RIV TESTS Determine RIV performance levels for the 38 kv ELSP current-limiting fuse. procedures. Testing was performed as detailed in ANSI/IEEE C37.41-2008, Clause 8. Fuses were secured to a three-phase transformer mounting board (2624086B0305) and tested in an appropriate tank filled with mineral transformer oil. The mounting board assembly provides a clearance of 3.25 to the nearest ground plane, and 5.75 to the nearest adjacent phase (center-to-center). Three 38kV ELSP fuses were tested. Minimum test voltage was 23.0 kv as required by Table 4 of ANSI/IEEE C37.47-2011. This is based on line-to-line application of the fuses with voltages equal to or less than the rated maximum voltage. Measurements were taken with one fuse energized and the other two grounded. Each configuration (three total) was tested. Results The inception voltage for each configuration was less than the 250 V requirement as specified in ANSI/IEEE C37.47-2011. Conclusion All samples tested met RIV levels as required per ANSI/IEEE C37.47-2011 Table 4 requirements.

Page:8 of 9 TEMPERATURE RISE TESTS Requirements For applications at ambient temperatures greater than 40 C, ANSI/IEEE C37.47-2011 does not specify temperature rise and total temperature limits. Eaton s Cooper Power Systems requires that under-oil backup fuses achieve temperature stability while carrying rated current continuously in a suitable enclosure filled with oil. Determine temperature rise characteristics when tested as specified in ANSI/IEEE C37.41-2008. Verify that temperature stability is achieved. procedures. The fuses under test were mounted in a tank of oil in an appropriate holder to simulate actual field installation. Testing was conducted following ANSI/IEEE C37.41-2008, Clause 10 requirements. Testing was conducted at room ambient. Current was supplied from a regulated source. Temperature levels of current carrying parts were recorded throughout the test. Final temperature readings were taken at stabilization. Results and Conclusions The 38 kv ELSP backup current-limiting fuses reached temperature stability while carrying rated current continuously.

Page:9 of 9 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53188 United States Cooperpower.com 2014 Eaton All Rights Reserved Eaton and Cooper Power Systems are valuable trademarks of Eaton, in the US and other countries. You are not permitted to use these trademarks without prior written consent of Eaton.