PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

Similar documents
PPHVC Power Quality Solutions. ABB PQC-STATCON Benefits and advantages

PQC - STATCON The ultra fast Power Quality Compensator

Dynamic Reactive Power Control. By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West)

ABB n.v Power Quality in LV installations

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

&MFDUSJGJDBUJPO Products 1PXFS 2VBMJUZ 'JMUFST 12'* o 12'. o 12'4 )BSNPOJDT NJUJHBUJPO MPBE CBMBODJOH BOE SFBDUJWF DPNQFOTBUJPO PO -7 OFUXPSLT

smartvar Dynamic VAR Compensator

Power Protection Discrete Automation & Motion South Africa

Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic reactive power compensation

Technical News. Power Factor Correction. What technology is best for you? Specialists in electrical and automation products, systems and solutions

ELG4125: Flexible AC Transmission Systems (FACTS)

ADF. Restoring the perfect wave

Power Quality and Energy Management

Power Quality Compensator - Reactive (PQCR) Enhancing power quality and energy efficiency of your electrical network

Power Quality Solutions POWER QUALITY SOLUTIONS: ACTIVE HARMONIC FILTERS

Power IT LV Active Filters PQFI - PQFM PQFK - PQFS

Targeted Application of STATCOM Technology in the Distribution Zone

PQdynaC High speed, flexibility and modularity

Power Factor Correction

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

DYNACOMP. The top-class reactive power compensator

Chapter 3.1: Electrical System

EPRLAB FAQ v1.0 Page 1 / 8 Copyright EPRLAB December 2015

ABB Wind Power Solution

Welcome. Power Survey International

Power Quality. Static Var Generator (SVG) SVG Wallmount & SVG Cabinet Mount

Integration of Large Wind Farms into Electric Grids

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

ABB November 16, 2016 Slide 1

CTU 02. Thyristor switching module for fast PF compensation. User manual

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module

POWER FACTOR CORRECTION USING SHUNT COMPENSATION

Dynamic PFC:Thyristor Modules TSM Series

SINAMICS SM150. Siemens product performance features. Competitor product profile. Components. Power, transport units. Service friendliness

LV Capacitor Bank APC

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Unrivalled in Power Factor Correction.

ADVISE DESIGN IMPLEMENT FOR ELECTROTECHNICAL EXCELLENCE

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Power Factor Correction

ELECTRICAL POWER SYSTEMS 2016 PROJECTS

Diversifying into Marine Energy. ABB March 2015

PQactiF Higher flexibility and modularity for improved power quality

1.1 Block Diagram of Drive Components of Electric Drive & their functions. Power Processor / Modulator. Control. Unit

Power Solutions Manager Generac Power Systems, Inc.

Microcontroller Based Power Factor Correction Using SCR

Est DCM Double Conversion Module 400kVA - 800kVA

SitePro UPS 400Vac / CE. GE Consumer & Industrial August 2004

Transforming Energy.. For Advanced Technology

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

International Journal of Advance Engineering and Research Development. Automatic Power Factor Correction in EHV System

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Chapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

Power Management in a Green Factory. March 20, 2013 Mike Lin Delta Products Corp.

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series

Power Quality Luis Vargas Research Engineer 9/18/2008

kvah Billing - Frequently Asked Questions (FAQs)

Inverter System Accessories

Power Quality innovative SolutionS for industrial and distribution grids.

HIGH POWER RECTIFIER SYSTEMS

ABB n.v PQF LV Active Filters: Bringing energy savings to you

Is Uncorrected Power Factor Costing You Money?

Advanced Protective Relay Training

Switchgear and Distribution Systems for Engineers and Technicians

Technical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction

Machine, Panel, and Plant Level Solutions

Caps unlocked. ABB s new QCap cylindrical capacitor improves power factors

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Application Note. Dynamic PFC: Power Quality at the Docks (China State Shipbuilding Corporation)

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

Dynamic Reactive Power Control for Wind Power Plants

EMPAC Metal enclosed capacitor bank for wind applications

ELECTRICAL POWER and POWER ELECTRONICS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

International Journal of Advance Research in Engineering, Science & Technology

Medium voltage drive for single or multimotor applications, 3 27 MW

Metal enclosed capacitor banks: ABBACUS family

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map

Application manual Dry type power factor correction capacitors

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

POWER QUALITY SEMINAR OF IRAN, 2 ND MARCH 2017 Power Quality Seminar. Abel-Zhang,Power Quality Center Manager

American Traction Systems

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

LOW VOLTAGE WIND CONVERTERS. ABB wind turbine converters ACS880, 800 kw to 8 MW

LV Capacitor Bank APC

Energy Storage and Other Energy Control Solutions

Electrical Power Electric power electrical electric power Electric power electric electric

Qingdao Zener Electric Co., Ltd

POWER FACTOR CORRECTION OF FAST DYNAMICS INDUSTRIAL LOADS

A new static DC drive system with AFE for mining excavators

Product brochure. Medium voltage AC drive ACS2000, kw, kv

4-Day Power System Analysis, Coordination, System Studies

Integrated Plant Control and Q on Demand 24/7 SUNNY TRIPOWER

Transcription:

PQC-STATCON PPHVC-Power Quality Solutions Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

Contents What is poor power quality? Reasons for investing in power quality solutions Reactive power in a power system network Instantaneous stepless compensation Unbalance and reactive power compensation - principle Applications Key benefits Energy efficient operation Technology and features Product portfolio Sizing of PQC-STATCON Conclusions March 7, 2017 Slide 2

What is poor power quality? Any event related to the electrical network that ultimately results in financial loss Power supply failures e.g :breakers tripping, blowing of fuses Utility regulations and penalties System losses Equipment failure, malfunctioning and lifetime reduction, including Equipment overheating (transformers, motors, etc) Damage to sensitive equipment (PCs, UPS systems, drives) Capacitor problems due to resonance Electronic communication interference Personnel issues (illness, poor work efficiency, etc) March 7, 2017 Slide 3

Key elements of poor power quality Reactive power Load imbalance Harmonics High running costs and failures March 7, 2017 Slide 4

Reasons for investing in power quality solutions Traditional reasons Technical problems leading to system downtime Production loss Compliance with regulations (local/iec/company standards) Penalties if no compliance No connection if no compliance Energy savings potential Poor Power Quality results in higher system losses A topic which is becoming more important due to increasing energy prices

Reactive power in a power system network P, Q h LOAD Source Real power Basic Power Flow diagram Responsible for transfer of energy P Real power Q Reactive power h Harmonics Reactive power Enabler for conversion of real power Not a form of energy Flows back and forth, causes loss in the transmission/distribution system Local supply of reactive power improves the system efficiency March 7, 2017 Slide 6

Capacitor & PF Capacitors supply the reactive power component Power Factor is a measurement of how efficiently power is being used. PF is the cosine of the angle of phase displacement between current and voltage. Cos (phi) = P / S M h 7 2017 Slid 7

Power factor vector relationship Power Triangle Power Factor Cos Working or Real Power = KW kva = kw PF kw = kva x PF PF = kw kva Reactive Power = KVAR kva: Total Power required for a given load kw: Working Power required to produce work kvar: Reactive Power needed to generate magnetic fields for inductive loads such as motors Power Factor: The relationship of real power (kw) and total power (KVA) consumed Cosine of angle shown Percentage or decimal expression M h 7 2017 Slid 8

Reactive power in a power system network Conventional solutions of reactive power compensation FC (Fixed capacitor Bank) Source Fixed capacitor APFC (Automatic power factor corrector) CSC (Contactor switched capacitor) Source Contactors Capacitors TSC (Thyristor switched capacitor) Classical reactive power compensation techniques Source Thyristors Capacitors March 7, 2017 Slide 9

Reactive power in a power system network Limitation with conventional schemes Fixed capacitor (FC) Contactor switched capacitor (CSC) Thyristor switched capacitor (TSC) Source Source Fixed capacitor Contactors Thyristors Capacitors Capacitors Q Load demand Q Load demand Q Load demand Q Fixed capacitor Q Q Q TSC/CSC Q 1000 750 time Q TSC/CSC VOLTAGE CURRENT 4000 3000 1000 750 500 time VOLTAGE CURRENT 4000 3000 2000 time Voltage [V] 500 250 0-250 2000 1000 0-1000 Current [A] Voltage [V] 250 0-250 -500 1000 0-1000 -2000 Current [A] -500-2000 -750-3000 -750-1000 0 5 10 15 20 25 30 35 40 Time [ms] -3000-4000 -1000 0 5 10 15 20 25 30 35 40 Time [ms] -4000 March 7, 2017 Slide 10

Instantaneous stepless compensation What is better power quality? March 7, 2017 Slide 11

Power electronics based compensator Instantaneous stepless reactive power compensation I C I R Capacitive current V s Inductive current I R Resistive current Source I g = I Ld -I lq, -I LN VS I I L = I Ld, I lq, I ln Active compensator Active compensator based reactive power compensator technique LOAD I L Load current I Ld Real current I lq Reactive current I ln Negative sequence current IGBT based power electronic current source Fast dynamic response Smooth and step-less Inductive/capacitive reactive power operation Unbalance compensation Operates in shunt with loads March 7, 2017 Slide 12

Basic operating principle Of PQC STATCON PQC-STATCON 2300mm Vs VL Vi 900mm POWER SUPPLY FEED BACK FROM CT REACTOR PQC CONTROLLER (DSP) IGBT Converter CONTROL LOGIC VIA OPTO- TRANSRECEIVERS 1000m m March 7, 2017 Slide 13

Reactive Power Compensation(RPC) by STATCON: CASE-1: When Vi > Vs IL = (Vs-Vi)/jXL = VL/XL (- 90 ) IL leads the Vs by 90 (Capacitive) March 7, 2017 Slide 14

RPC BY STATCON: CASE-2: When Vi < Vs IL = (Vs-Vi)/jXL = VL/XL (- 90 ) IL lags the Vs by 90 (Inductive) March 7, 2017 Slide 15

RPC BY STATCON: CASE-3: When Vi = Vs Is= 0; Hence Supplying Zero Reactive Current March 7, 2017 Slide 16

Unbalance and reactive power compensation Principle Operating boundaries of active compensator March 7, 2017 Slide 17

PQC-STATCON Applications Instantaneous, stepless power electronics based dynamic compensator for reactive power (power factor) and unbalanced loads (<1 cycle response time) For inductive and capacitive loads For highly fluctuating loads e.g. welding loads, rolling mills etc. For industrial loads fed by weak networks, e.g. captive generators For three phase and single phase applications, e.g. railways Suitable for LV networks, and MV networks with step-up transformer March 7, 2017 Slide 18

PQC STATCON Applications ARC FURNACES STEEL ROLLING MILLS TRACTION SUB-STATIONS WELDING LOADS Railway/ traction sub Stations Arc furnaces Automotive / welding plant Steel plants / rolling mills Airports / shipyards / ships Off-shore drilling Process industries Sky lifts / compressor loads Pulp & paper Industries Chemical plants Hydro plants Cement factories Water treatment plants Wind mills March 7, 2017 Slide 19

PQC-STATCON Key benefits Improves power quality Enhanced energy efficiency by reducing system losses Reduced Carbon footprint Improves the reliability of existing capacitor banks under dynamic condition Reduces maintenance need and enhances life of electrical Installations Easy installation & commissioning Easy and convenient operation with touch screen interface No risk of harmonic amplification March 7, 2017 Slide 20

PQC-STATCON Modes of operation Source Grid CT I g VSI Load CT I L LOAD Active compensator 1. Dynamic compensation modes - Open loop (Load CT Mode) - Closed loop (Grid CT Mode), Highest accuracy and the most recommended configuration 2. Fixed Compensation Mode Multiple STATCONs in parallel can share the same CT feedback March 7, 2017 Slide 21

PQC-STATCON technology and features Instantaneous and precise control Green PQC-STATCON Current Blue Supply Voltage Magenta Step Response Response time: 8.062ms (Rise) Instantaneous reaction to step changes Fast dynamic response ( < 1 cycle) Excellent steady state / transient stability Native closed loop operation, open loop operation is also possible Four cascaded control loops Response time: 8.002ms (Fall) March 7, 2017 Slide 22

PQC-STATCON technology and features Energy efficient operation Energy save mode Programmable option IGBT converter is switched off after 30 s, during idle condition Cooling system is turned off, after 2 minutes POC-STATCON enters deep sleep mode Delivers rated kvar within 8 cycles(from sleep mode) of load demand March 7, 2017 Slide 23

PQC-STATCON technology and features Reliability is an important factor! Rugged protections - PQC-STATCON Protection Over current protection DC over voltage protection IGBT short circuit protection Over temperature protection Cooling system failure detection IGBT stack failure detection Supply overvoltage/under voltage protection Switchgear acknowledgement feedback errors Unstable grid detection Door open detection March 7, 2017 Slide 24

Unique advantages of PQC-STATCON Parallel operation PQC-STATCON PQC-STATCON PQC-STATCON PQC-STATCON PQC-STATCON In parallel system of PQC-STATCON, the system reliability will be increased by X times, unlike other ONE MASTER-SLAVE systems where, in the event of master failure the total system gets to shutdown. In PQC-STATCON all individual PQC-STATCONs are capable of being a master and will take over as and when required. March 7, 2017 Slide 25

Unbalance & reactive power compensation Eliminating unbalance - energy efficiency perspective 3 Phase source 2-Ph Load P (kw) 3 Phase Source 3-Ph Load P (kw) (Assuming line Resistance is R) System losses comparison with balance / unbalance loads 50 % Lower line losses March 7, 2017 Slide 26

Operation with parallel fixed capacitor banks Cost effective - more kvar / $ Operation with parallel fixed capacitor banks (existing/new) 200% 100% 100% 100% + 0% = 0% -100% -100% PQC-STATCON Fixed capacitor Total solution PQC-STATCON doubling the dynamic compensation range with parallel capacitor banks. March 7, 2017 Slide 27

Power quality solutions with PQC-STATCON + FC Dynamic compensation MV bus Real Power harmonics + Reactive flow LV bus PQC-STATCON For Harmonics Fixed compensation (FC) LOAD Real power Real + reactive power Harmonics

Typical STATCON SOLUTION Typical HV/MV Applications

PQC-STATCON Product portfolio PQCS - Single Phase Compensator Reactive power compensation PF improvement Main/Auxiliary PF setting (supports Utility/Generator sources) PQCT & PQCT-Light(PQCL) Three Phase Compensator Reactive power compensation PF improvement Main/Auxiliary PF setting (supports Utility/Generator sources) Unbalance compensation Reduction of negative sequence components Priority configuration Reactive power/unbalance compensation March 7, 2017 Slide 30

PQC-STATCON Product portfolio PQCS S. No Type No. Application Voltage kvar Amp (Ir) 1 PQCS-50-V240 1-Ph 240 50 210 2 PQCS-100-V240 1-Ph 240 100 420 3 PQCS-100-V415 1-Ph 415 100 240 4 PQCS-150-V415 1-Ph 415 150 360 5 PQCS-250-V415 1-Ph 415 250 600 PQCT S. No Type No. Application Voltage kvar Amp (Ir) 1 PQCT-100-V415 3-Ph 415 100 140 2 PQCT-150-V415 3-Ph 415 150 210 3 PQCT-250-V415 3-Ph 415 250 350 4 PQCT-300-V415 3-Ph 415 300 420 PQCT-Light (PQCL) S. No Type No. Application Voltage kvar Amp (Ir) 1 PQCL-70-V415 3-Ph 415 70 100 For MV applications: PQC-STATCON supports operation through step-down transformer March 7, 2017 Slide 31

PQC-STATCON Sizing for reactive power and imbalance To quickly calculate the size of a PQC-STATCON based reactive power compensation system, Calculate the required capacity for dynamic compensation through PQC STATCON, which is half of the total dynamic compensation requirement Q PQC-STATCON* = Q dyn /2 = (Q max -Q min )/2 Calculate the required capacity for fixed capacitor based compensation, which is the sum of base compensation requirement and half of the total dynamic compensation requirement. Q capacitor = Q base + Q dyn /2 = Q base + (Q max -Q min )/2 Note: To perform load balancing, add the negative sequence demand of load

PQC-STATCON Sizing for reactive power and imbalance Q max Load Q demand Q dyn =(Q max -Q min ) Q min Q base 0 time Q capacitor = Q base + (Q dyn /2) Q PQC-STATCON* = Q dyn /2 Note: * To perform load balancing, add the negative sequence demand of load.

Conclusions Talk to us for expert advice on solving your power quality problems ABB Has complete range of power quality solutions Has vast amount of experience in instantaneous stepless compensation for reactive power and unbalanced loads (Example: Automobile, rolling mills, railways and furnaces etc.,)