MPX-Series Diesel Engine Shut Down Valves (Manual Reset / Air Pressure and Manual Closure Options)

Similar documents
Diesel Engine Shutdown Valves

MVX-Series Diesel Engine Air Shut Down Valves

HVX-Series Diesel Engine Shut Down Valves (Oil Pressure Latched Types with Manual Start Override/Emergency Stop)

SVX-Series Solenoid Actuated Diesel Air Shut Down Valves

Diesel Engine Shutdown Valve

SVX-Series Diesel Engine Shut Down Valves (Solenoid Latched Types with Manual Start Override/Emergency Stop)

Solenoid Actuated Diesel Engine Air Shut Down Valves

SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Stop Types)

D-Series Automatic Engine Overspeed Shut Down Valves (Bendix Types)

SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Run Types for Non-Hazardous Areas)

SVX-Series Solenoid Actuated Diesel Engine Air Shut Down Valves (Energised to Run, Hazardous Area Types without Manual Override)

D200 Spindle Type Automatic Engine Overspeed Air Intake Shut Down Valve (including Manual, Oil and Air Pressure Shut Down Control options)

SELECTION, APPLICATION AND MAINTENANCE

D-Series Automatic Engine Overspeed Shut Down Valves (Mini Range)

D-Series Automatic Engine Overspeed Shut Down Valves (Bendix Types)

SELECTION, APPLICATION AND MAINTENANCE

Diesel Engine Shutdown System

E-M Series. Combined Manual and Automatic Engine Overspeed Shut Down Valves

Air Intake Shut-off Valve

E Series. Automatic Engine Overspeed Shut Down Valves

FS2 Valves. Solenoid Powered to Close / Auto Reset Butterfly Valves

FS3 Valves. Solenoid Powered to Open / Spring to Close (failsafe)

Diesel Engine Safety Solutions. Automatic Engine Overspeed Shut Down Valves - D Series

World class manufacturer of safety solutions SYSTEM SELECTION GUIDE. Safety solutions for vehicles and machines working in petrochemical plants

Automatic Fuel Shut Down Valves

PH1 AIR INTAKE EMERGENCY SHUT-OFF VALVE PULL CABLE ACTUATION.

Thermostatic Valve. Filterstat - Model FJA. Typical applications. Key features and benefits. Mixing Diverting

System Selection Guide

RODADEACO. Diesel Engine Air Intake Shutoff Valves. Model RDB3 Compact Butterfly Valve. by AMOT. Overview. Typical Applications

SELECTION, APPLICATION AND MAINTENANCE

Flameproof Alternators

Diesel Engine Air Intake Shutoff Valves

AIR INTAKE EMERGENCY SHUT-OFF VALVE PH2 C50204 AIR INTAKE SHUT-OFF VALVE DODGE 6.7L CUMMINS.

Intake Air Shut-off Valve

AIR INTAKE EMERGENCY SHUT-OFF VALVE C50203 AIR INTAKE SHUT-OFF VALVES APPLICATION DODGE 5.9L CUMMINS.

C50254A PH3 AIR INTAKE SHUT-OFF VALVE DODGE 6.7L CUMMINS WITH POWERGUARD SMART OVERSPEED LIMITER

Model 4418F. Overview. Typical applications. Key features and benefits. Accreditations. Starting air/gas valve Vented fuel gas valve

AIR INTAKE EMERGENCY SHUT-OFF VALVE C50207 AIR INTAKE SHUT-OFF VALVES APPLICATION FORD 6.7L POWERSTROKE.

PH2 AIR INTAKE EMERGENCY SHUT-OFF VALVES. APPLICATION C ½ DODGE 6.7L CUMMINS C DODGE 6.

Model 4418F. Overview. Typical applications. Key features and benefits. Accreditations. Starting air/gas valve Vented fuel gas valve

by AMOT World class diesel engine safety solutions Automatic Engine Overspeed Shut Down Valves - D Series

Thermostatic Valve. Filterstat - Model FJA. Typical applications. Key features and benefits. Mixing Diverting

PH2 POWERHALT AIR INTAKE SHUT-OFF VALVE C50201A ½ DODGE 6.7L CUMMINS C50202A DODGE 6.

PH2 C50219A AIR INTAKE SHUT-OFF VALVE. T800 KENWORTH / ISX ENGINE WITH POWERGUARD SMART OVERSPEED LIMITER

E1186X Breather Kit. For Yanmar L48N Engines

PH3 AIR INTAKE EMERGENCY SHUT-OFF VALVE WITH POWERGUARD SMART OVERSPEED LIMITER. Generic PH3 Truck Shut-Off Valve Kit.

2-Way Temperature Sensing Valves

Flameproof Alternator

Optimise your temperature control

3-Way Temperature Control Valve

Flameproof Alternator

by AMOT World class diesel engine safety solutions Product Selection Guide

Pressure and Temperature Switches

Flameproof Alternator

Metal Particle Detector

SEries 41 check valve installation, operation & maintenance manual

Pneumatic Indicating Relay

Model J. Thermostatic Control Valves. Typical applications. Key benefits. Key features. Accreditations available

Preventive maintenance 4

Series 900 Minifolds. Aluminium Air Distribution Manifolds. Manifolds & Minifolds. Technical Specifications. hnl-uk.com. Series 900 Minifolds

Pilot Operated 2-Way Gas Valves

Is the heart of your engine protected?

Y690A Series Pressure Reducing Regulators

HYPERMAX ENGINEERING, INC. 7.3L POWER STROKE INTERCOOLER PACKAGE

SECTION J CONTENTS OPTIONAL CONFIGURATIONS DESCRIPTION

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

AIRLINE EQUIPMENT CATALOGUE //

LINED EQUIPMENT // Fort Vale Engineering Ltd CATALOGUE REVISION_

Self-Exciting Flameproof Alternator

D-Series Rack & Pinion Pneumatic Actuators

Installation, Operation and Maintenance Manual DOC.IOM.MO.E October MO-Series Manual Override Gearboxes

SERIES 2000 GAS SAFETY SHUT OFF VALVE

3. Installation and Commissioning 4. Maintenance 5. Spares

Series 100 Slam Shut Valve

M1/M2 POCKET FEEDER. Compact design DESIGN FEATURES. Special ball and seat design. Large ball pocket capacity. Automatic cycling

Model H. Thermostatic Control Valves. Typical applications. Key benefits. Key features. Accreditations

type 122a three-way Switching Valve

BUTTERFLY VALVE CATALOGUE //

Thermostatic Control Valves

167D Series Switching Valves

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

NAF-Triball ball valve

FEATURES. 3 position models can be equipped with special 180 operators offering two 90 steps.

1/4" 2" (DN 8 50) Clincher Series 2000 Threaded-End Ball Valves

Actuators & Surface Safety Valves

6D15 DIGESTER CAPPING VALVES

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822

Keeping You Cool Under Pressure

SUMMARY GENERAL DESCRIPTION... 3 BALL VALVE WITH LEVER OR WITH CAP... 7 FULL BORE FLOW... 7 REDUCED BORE FLOW... 10

KEYSTONE SERIES GR RESILIENT SEATED BUTTERFLY VALVES GRW/GRL INSTALLATION AND OPERATION MANUAL

High Flow Cartridge Valves 2/2 Way Series NG16 NG100

LINED EQUIPMENT // Fort Vale Engineering Ltd CATALOGUE REVISION_

Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual

North. Asia. America. Africa. South. America. Australia. Double Block and Bleed Dual Expanding Plug Valve

PRX Series Pilots for Pilot-Operated Pressure Reducing Regulators

BALL VALVE CATALOGUE //

Bulk Liquid Filtration

Series 1 shaft seal installation instructions

SECTION TWO - INTERMODAL - VENTING

2009 PCED Gasoline Engines SECTION 1: Description and Operation. Intake Air System

Transcription:

MPX-Series Diesel Engine Shut Down Valves (Manual Reset / ir Pressure and Manual Closure Options) Selection, pplication and Maintenance Valve Numbers MPX-300 MPX-301 MPX-302 MPX-303 MPX-500 MPX-501 MPX-502 MPX-503 MPX-800 MPX-801 MPX-802 MPX-803

DESCRIPTION range of 3, 5 and 8 bore slim butterfly air intake shut down valves with air pressure actuated shut down combined with manual reset and the optional addition of manual shut down. Suitable for both hazardous and non-hazardous area applications. MPX valves are available in basic flange mounted form or fitted with hose adaptors. Valve body and disc are manufactured in corrosion resistant hard anodised aluminium with PTFE coating. The valve spindle and mechanism is made from stainless steel. Notes: Maximum temperature of the engine intake air at the MPX valve not to exceed 150 C. (See also Installation - page 5). For alternative types of air pressure actuated Chalwyn valves see brochure CE218. Main Dimensions (mm) Valve Type Nominal ore Diameter C2 minimum & maximum MPX-300 MPX-301 MPX-302 MPX-303 76 (3 ) 190.0 207.0 190.0 223.0 111.5 37.5 82.5 to 112.5 MPX-500 MPX-501 MPX-502 MPX-503 127 (5 ) 246.0 263.0 246.0 279.0 167.0 45.5 102.0 to 157.5 MPX-800 MPX-801 MPX-802 MPX-803 203 (8 ) 346.5 362.0 346.5 377.5 257.0 56.0 136.5 to 185.5 Valve Types MPX-300, MPX-500 and MPX-800 (ir Pressure Shut Down, Manual Reset) 1/8" NPT for connecting air pressure supply Reset Lever Optional Hose daptors C2 (min) C2 (max) page 2

Valve Types MPX-301, MPX-501 and MPX-801 (ir Pressure and Integral Stop utton Shut Down, Manual Reset) 1/8" NPT for connecting air pressure supply Stop utton Reset Lever Optional Hose daptors C2 (min) C2 (max) Valve types MPX-302, MPX-502 and MPX-802 (ir Pressure and Remote Push Stop utton Shut down, Manual Reset Push Type Stop utton ss y RP-100 1/8" NPT for connecting air pressure supply Reset Lever Cable Length Options - see under Selection Optional Hose daptors C2 (min) C2 (max) Valve Types MPX-303, MPX-503 and MPX-803 (ir Pressure and Remote Pull Shut Down, Manual Reset) PULL Type Manual Stop Reset Lever Cable Length Options - see under Selection Optional Hose daptor (One each side) C2 (min) C2 (max) page 3

SELECTION Determine the size and position of the MPX valve to be installed. Within the various constraints imposed in the application, the valve should be as generously sized as possible. Check that the valve can be positioned such that the reset lever and, where applicable, the stop button will be easily and safely accessible. For types with a remote manual stop, position the valve and select the cable length to give a reasonably straight cable run between the MPX valve and the proposed stop button position. ir Pressure clean, dry air supply is required. n air pressure of approximately 2 bar is required to close the valve. Maximum air pressure must not exceed 10 bar. Cable options for use with PUSH button RP-100 To suit valves MPX-302, MPX-502, or MPX-802 Cable options for use with PULL handle RTD-100 To suit valves MPX-303, MPX-503, or MPX-803 Cable part No. Length (meters) Cable part No. Length (meters) CLP-100 1.0 CLP-150 1.5 CLP-200 2.0 CLP-300 3.0 Select the required length of the manual shut down cable from the table. lternative lengths may be available on request. lso order push button assembly RP-100. CLD-100 1.0 CLD-150 1.5 CLD-200 2.0 CLD-300 3.0 Select the required length of the manual shut down cable from the table. lternative lengths may e available on request. lso order handle RTD-100. If the valve is to be fitted into a hose as opposed to flange mounted, suitable hose adaptors may be selected from the table below for ordering with the valve. Hose daptor Options 76mm (3 ) ore Valves daptor To Suit Hose ore Part Number mm (inches) HX-320 38 ( 1 1 / 2 ) HX-322 44.5 (1 3 / 4 ) HX-301 51 (2) HX-303 57 (2 1 / 4 ) HX-304 60 (2 3 / 8 ) HX-305 63.5 (2 1 / 2 ) HX-306 67 (2 5 / 8 ) HX-307 70 (2 3 / 4 ) HX-309 76 (3) HX-314 89 (3 1 / 2 ) HX-319 102 (4) 127mm (5 ) ore Valves daptor To Suit Hose ore Part Number mm (inches) HX-501 89 (3 1 / 2 ) HX-503 95 (3 3 / 4 ) HX-505 102 (4) HX-507 108 (4 1 / 4 ) HX-509 114 (4 1 / 2 ) HX-511 121 (4 3 / 4 ) HX-513 127 (5) HX-518 140 (5 1 / 2 ) HX-523 152 (6) 203mm (8 ) ore Valves daptor To Suit Hose ore Part Number mm (inches) HX-807 178 (7) HX-808 203 (8) page 4

INSTLLTION 1. In the case of a naturally aspirated engine the Chalwyn MPX shut down valve should generally be fitted as close to the engine air intake manifold as possible. If an air intake flame trap is also fitted, the MPX valve must be installed upstream (air cleaner side) of the flame trap. 2. To avoid excessively high intake air temperatures at the MPX valve when fitted to a turbocharged engine, it may be necessary to fit the valve either upstream of the turbocharger or downstream of the intercooler (where fitted). gain, if an air intake flametrap is also installed, the valve must be fitted upstream of the flametrap. 3. Where more than one MPX valve is fitted to an engine, as in the case of an engine with multiple intake pipes, a common pneumatic supply to the valves should be used to ensure that all valves close simultaneously. 4. The MPX valve may be installed either horizontally or vertically. ir flow may be in either direction through the valve. Ensure easy and safe access to the valve reset lever and, where applicable, manual stop control. If the valve is fitted with a cable operated manual stop ensure a reasonably straight run for the cable. 5. If hose adaptors are used, the mating hose should be of a reinforced type, provide adequate support for the valve and prevent excessive vibration. If necessary, additional support brackets mounted from the engine should be considered. kits for various engine types are available from Chalwyn. 8. For valves with the Push button cable operated manual shut down, drill a Ø10mm (3/8 clearance) hole through the bulkhead (or bracket) to which the stop button is to be mounted. Pass cable end through hole. With the MPX valve in the latched open position check that, with the cable inner pressed hard back into the Cable lock nut wound fully back. Check end of inner is burr free cable outer, between 20mm and 22mm of the inner shows With the MPX valve still latched open, use a 2mm /F hexagon key to release the cable grip screw in assembly RP-100 to enable the assembly to be fully screwed onto the cable outer. Then tighten the cable locknut onto the back face of the bulkhead. Finally, fully tighten the cable grip screw (see diagram below). RP-100 20 to 22mm 6. Particular care must be taken to ensure the integrity of the intake pipework between the Chalwyn valve and intake manifold. Ideally metal pipework should be used and any gaps kept as short as possible, (taking into account any relative movement) and closed by reinforced hose. The possibility of a hose collapse on closure of the shut down valve must be avoided. 7. ny engine crankcase breather connections into the intake system between the MPX valve and engine, or any internal crankcase breather arrangement venting directly into the engine intake ports must be sealed and replaced by an external breather system venting either to atmosphere or to the intake system upstream of the shut down valve. External breather system Lock nut - tighten after fully screwing RP-100 onto the cable outer Cable Grip Screw page 5

9. For values with the pull handle cable operated manual shut down, fit the T handle assembly RTD-100 through a suitable Ø20mm (3/4 dia) hole in a bulkhead or mounting bracket as follows. Release the handle locknut. Remove the handle, handle locknut and upper locknut and washer. Thread handle body through the bulkhead/bracket. Refit upper locknut and washer. djust lower and upper locknuts to position handle and tighten. Refit handle locknut and handle. Tighten locknut. 10. Connect shut down air supply using the 1/4NPT tapping on valve. Means must be provided to release any trapped air pressure at the MPX valve connection when the air pressure shut down signal is not being applied. T HNDLE HNDLE LOCKNUT ULKHED MOUNTING RCKET HNDLE ODY UPPER LOCK NUT LOWER LOCK NUT STOP CLE 11. Prior to putting the engine into service the checks listed under Monthly maintenance should first be completed (see page 7). page 6

OPERTION Prior to starting the diesel engine the MPX valve must be latched in the open position by rotating the reset lever clockwise as far as possible. Once latched, the reset lever and valve will remain in the latched open position until released by application of air pressure or by operating the stop button. fter an emergency shut down by air pressure or by operating the stop button, the MPX valve must always be reset before re-starting the engine. fter a normal (diesel fuel only) shut down, the MPX valve will not require reset. MINTENNCE MONTHLY: Check that all intake system fasteners and any associated support bracket fasteners are securely tightened. Check that any intake system hoses between the MPX valve and engine are free from damage and suitable for further service. Run engine, preferably at or just above low idle speed. pply shut down air pressure signal to valve. Check that the valve reset lever immediately rotates to the valve closed position and the engine stops within a few seconds. Run engine, preferably at or just above low idle speed. Operate the manual shut down control. Check that the valve reset lever immediately rotates to the valve closed position and the engine stops within a few seconds. Notes: The engine must not be put back into service until any problems identified by the above checks are rectified. page 7

mericas sia Pacific Europe, Middle East and frica MOT - US Tel: +1 281 940 1800 Fax: +1 713 559 9419 info@amotusa.com MOT - China Tel: +86 (0)21 6279 7700 Fax: +86 (0)21 5237 8560 shanghai@amot.com MOT - UK Tel: +44 (0)1284 715739 Fax: +44 (0)1284 715747 info@amot.com Roda Deaco by MOT - Canada Tel: +1 780 465 4429 Fax: +1 780 469 6275 info@rodadeaco.com MOT - Singapore Tel: +65 6408 6265 Fax: +65 6408 6266 singapore@amot.com MOT - Germany Tel: +49 (0)40 8537 1298 Fax: +49 (0)40 8537 1331 germany@amot.com MOT - Russia Tel: +7 495 617 12 96 Fax: +7 495 913 97 65 russia@amot.com DS-MPX301-803-ShutdownValves-CE236-0712-rev1 www.chalwyn.com by MOT