SATRON VDt differential pressure transmitter. Installation and Setting-Up Instructions Spare Parts List

Similar documents
SATRON VDt Differential Pressure Transmitter

SATRON VTe pressure transmitter

SATRON VVFe Pressure Transmitter

SATRON VT Pressure Transmitter

Page SATRON VT Pressure transmitter 7 SATRON VB Pressure transmitter 15

Smart Pressure Transmitter

Smart Pressure Transmitter

TEK-B AR 3110A. Differential Pressure Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys PRESSURE

Rosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES:

Smart Pressure Transmitter

Smart Pressure Transmitter

Installation and Setting-Up Instructions

ETP80. Electronic Transmitter for Pressure, Differential Pressure and Level

Model 8800C Vortex Flowmeter

JUMO dtrans p20 DELTA

JUMO dtrans p20. Process pressure transmitter. Type Brief description. Key features. Block diagram

UIB3351 Metal Capacitive Pressure/Differential Pressure Transmitters

INTERPLANT STANDARD - STEEL INDUSTRY. Specification for Smart Pressure & Differential Pressure Transmitter

FIELDVUE DLC3000 Series Digital Level Controllers

Differential pressure transmitter PASCAL Ci4 Delta P

Masoneilan Series

PRESSURE TRANSMITTER PYRP-28 INDUSTRIAL & INTRINSICALLY SAFE PRESSURE TRANSMITTER PRESSURE TRANSMITTER

JUMO dtrans p02. Pressure transmitter. General application. Approvals/marks of conformity. Data Sheet Page 1/6. II 1/2G Ex ia IIC T6 Ga/Gb

Installation and Setting-Up Instructions Spare Parts List

mass flowmeter for compressed air

M3500 Industrial Pressure Transmitter

SITRANS P measuring instruments for pressure

Reference Manual Rev AA June Rosemount 3155 Nuclear Pressure Transmitter

Mobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter

Rosemount 3051S Electronic Remote Sensor (ERS) System

Differential Pressure and Flow meters Accessories for the Media Series

Continuous level measurement Capacitance transmitters

Differential pressure transmitter PASCAL Ci4 Delta P

Level Measurement. Continuous level measurement - Capacitance transmitters SITRANS LC500. 5/282 Siemens FI Overview.

Safir-M digital. Features. LCD indicator and controls. Industries. Applications

English Rev. AA. Model 1151 Alphaline Pressure Transmitters

Operating Instructions. Pneumatic Control Valve Low Temperature. Type Series GS3

Rosemount 3051T In-Line Pressure Transmitter

SAVE Sampler. Installation and Setting-Up Instructions Spare Parts List. G800AV Man. revision Contents: 1 Purpose of Use

Rosemount 1151 Pressure Transmitter

JUMO dtrans p20. Process pressure transmitter. Brief description. Special features. Block diagram. Approvals/approval marks (see "Technical data")

Electric Actuated Ball Valves 150 lb Flanged Stainless Steel, Full Port 1/2 to 4 inch Pipe Sizes

Universal Instruction Manual. I/A Series Vortex Flowmeters Models 83F, 83W, and 83S

Monocrystalline silicon smart differential pressure transmitter. High stability, Diaphragm sealed. Benefits. Application

Differential pressure transmitter PASCAL Ci4 Delta P

DL 01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

Pressure transmitter PASCAL CV4

Metal tube variable area flowmeter for gases, liquids and steam

2SGT. Electronic Pressure Instrument. Three Separate Functions in a Single Loop-Powered Device

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT

Hot Tap Insertion Vortex

Electric Actuated Ball Valves 3-Piece Stainless Steel, Full Port 1/4 to 3 inch NPT

Product presentation SITRANS P310

Rosemount 3051CFA Annubar Flowmeter

I/A Series Intelligent Differential Pressure Transmitters

9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER

Pressure transmitter for industrial applications Type MBS 4510

SMART VALVE POSITIONER 4 to 20 ma + HART Digital Communication. smar B87

Valmet Dual Conductivity Measurement Series 3200

XMP ci. Process Pressure Transmitter with HART -communication. Ceramic Sensor. accuracy according to IEC 60770: 0.1 % FSO.

Metal tube flowmeters. Series SC250. Metal Tube Flow Meters. Series SC250. Variable area flowmeter for liquids, gases and steam

C S. Sanitary Differential Pressure Transmitter with Diaphragm Displacement Device CS Range Code. Accuracy. Note 1)

SSI Technologies Application Note PS-AN7 MediaGauge (Model MG-MD) Digital Pressure Gauge Product Overview

Low Profile Insertion Vortex

2010TC for Differential Pressure, Pressure and Temperature (Mass Flow)

EGM5300C MAGMAX. Compact Electromagnetic Flowmeter GENERAL FEATURES STANDARD SPECIFICATION. General Specification

Model CO Compact Orifice for use with Foxboro Differential Pressure Transmitters

L D FB DEVICES FIELDBUS PRESSURE TRANSMITTERS. Features 0 ~125 Pa to 0 ~ 40 MPa. (0 ~0.5 inh 2

Special Purpose Transmitters

KDM ARMORED FLOW METER & SWITCH

MAGPOWR Spyder-Plus-S1 Tension Control

Operating Instructions. Angle Seat Control Valve. Type 7020

SSI Technologies Application Note PS-AN2 MediaSensor Absolute & Gage Pressure Transducers & Transmitters Product Overview

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T

Sentronic PLUS 614 Series

Model TUR-200D Turbine Flowmeter

Industrial Pressure Transmitters

FIELDVUE Type DLC3000 Digital Level Controllers

DPT 200. Differential Pressure Transmitter for Process Industry with HART -Communication. accuracy according to IEC 60770: 0.

Model FVP General Specification. Flanged Vortex Plate. Product Features

LTX RF LEVEL SENSOR. Instruction Manual

STEEMCO Flowmeter for Steam

Data sheet Intoduction. process measurement solutions

JUMO DELOS SI. Precision pressure transmitter with switching contacts and display. Application. Brief description. Key features.

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries

C S. Differential Pressure Transmitter CS Range Code. Accuracy

Selectable ranges and an LCD are a technician s best friend, that s why we make them standard on every dry media differential pressure sensor!

Rosemount 3152K Nuclear Qualified Pressure Transmitter

PRESSURE BENCH OPERATING INSTRUCTIONS

ARI-STEVI 450 / 451 (DN15-150) Control valve - 3-way-form (mixing/diverting valve) (optional with screwed seat ring)

Level Measurement Point level measurement - RF Capacitance switches

Product Data Sheet , Rev GA Catalog Content

Vortex Plate. Model VP General Specification. Product Features

CLA-VAL CPC Position Control 4-20 ma

Rosemount 3095FT MultiVariable Flow Data Logger

DMT PERFORMING UNDER PRESSURE DMT. Pressure Scanner Features. Applications. Description 1/7

TECHNICAL BULLETIN. Logix 510si Series Digital Positioner. Experience In Motion FCD LGENTB /09

BERMAD Waterworks. Insertion Flow Meter Device (IFM)

UIB3351 Metal Capacitive Pressure/Differential Pressure Transmitters

Transcription:

M, revision 4 Installation and Setting-Up Instructions Spare Parts List Contents: INSTALLATION. Mechanical installation. Electrical connections SETTING UP. Using the Hart 75 user interface. Setting up through HART 75 user interface. Using the Hart 75 user interface.4 Setting up through HART 75 user interface.5 Setting up with Satron-pAdvisor Service Software and Satron SI-Toole USB-Hart modem.6 Setting up with local switches.7 Set-up calibration CALIBRATION. Adjustability. Damping. Calibration examples 4 CONSTRUCTION AND OPERATION 5 PARTS LIST DOCUMENTS Technical Specifications: BPdT750 Installation and Setting-Up Instructions: We reserve the right for technical modifications without prior notice. HART is a registered trademark of HART Communication Foundation. Hastelloy is the registered trademark of Haynes International. Teflon is the registered trademark of E.I. du Pont de Nemours & Co Satron Instruments Inc. P.O.Box, FIN-90 Tampere, Finland Tel.int. +58 07 464 800, Telefax +58 07 464 80 www.satron.com, info@satron.com Conmark Systems Inc. Instruments Div. Atlanta, GA 770-00-04 www.conmark.com

INSTALLATION. Mechanical installation.. Impulse piping The process material and the transmitter s location with respect to the process pipe determine how the impulse piping will be installed (Fig. -a). For liquid and steam pressure measurements it is preferable to mount the transmitter below the orifice plate (Fig. -a). This will prevent the formation of unwanted gas bubbles in the impulse piping. In many cases accessibility determines the transmitter s location. As a result the transmitter cannot always be mounted at the best possible location in terms of measurement. For liquid and steam pressure measurements you may have to mount the transmitter above the process pipe, in which case it is recommendable to provide the pipeline with air locks (Fig. -b). Steam should not be admitted to the transmitter s sensing element. Condensate pots are not necessary since the volumetric displacement of the sensor is quite small. For gas pressure measurements (Fig. -c) the transmitter should be mounted above the process pipe. This will eliminate unwanted effects of condensate. For measuring the pressure of sedimenting liquids and for density measurements we recommend the use of purge water when necessary. It can be connected in place of the vent valve on the transmitter s measuring chamber or to the impulse pipeline (Fig. -e and -g). A transmitter with a hydraulic pressure seal can be used for liquid level and density measurements (Fig. -d). The capillary tubes are connected to /4NPT threads or welded at the factory, depending on the type of the pressure seal. Gas and any air dissolved in the fluid are evacuated from the seal fluid when filling the capillaries. Do not open the capillary connections when installing the transmitter! Any opened assemblies have to be sent to the manufacturer for refilling. Table for Figure -, Pipe fittings. Stud coupling Ø mm / G/ male. Stud coupling Ø mm / G/ female 4. Elbow Ø mm / G/4 male 5. T-fitting Ø mm 6. Ball valve G/ 7. Needle valve G/ 8. Pipe x calibrated 9. Needle valve rotameter 0. -stem mounting valve. Condensate pot NOTE! Materials, fittings and seals must be chosen to withstand the pressure and temperature conditions as well as corrosive and chemical effects prevailing at the operating site. Figure -a Liquid and steam

Figure -b Liquid Figure -c Gas Figure -d Density or pressurized vessel level measurement Figure -e Density measurement, transmitter + purge water Figure -g Installation for sedimenting liquids Figure -f Level or filter loss measurement Figure -h Level measurement, cylinder and vacuum

Dimensions (in mm) Pg9 std. housing types H and T Housing types H, T and M 88 Atex transmitter, code, 5 mm 4,±0, 00 Clearace for Cover Removal Ø8.5 +0. 0 /4-8 NPSF A - A +0.5 0.5 4.5 00 5 54±0, 96 A A M0 / deep 4 M / deep 4 7/6-0 UNF / deep 4 Connection to the differential pressure (type) measuring device (IEC 658 / DIN 9 PN00/PN400/PN40) M0 x,5 std. housing type M M0 x,5 std. housing type N 75 Ø48 70 Housing types M 88 Atex transmitter, code, 5 mm Housing types N 8 Atex transmitter, code, 5 mm Esc Enter 4

Dimensions (in mm) Pg9 std. housing type N with DIN 4650 plug connector 90 00 Housing types H, T and M 5 Housing type N 45 Atex transmitter, code, +5 mm 5 70 Housing type N with DIN 4650 plug connector 8 Atex transmitter, code, 5 mm Esc Enter <00 0 min. R75 60 Pg9 std. housing types H and T M0x,5 std. Housing types M and N Remote electronics, connecting cable with protection hose, codes L and K <450 5

.. Recommended mounting positions A differential pressure transmitter s operating environment is often quite demanding in terms of the measurement conditions. For example, the transmitter should be mounted so that the effects of temperature variations will be as small as possible. Different mechanical stresses, such as vibration, should also be avoided as far as possible. 85 50 Direct mounting on the pipe at the measuring point or wall mounting are the possible alternatives for gage pressure and absolute pressure measurement... Mounting valves A mounting valve can be used for mounting a differential pressure transmitter. The valve serves as both isolating valve and mounting base for the transmitter. This method simplifies the connection and disconnection of the transmitter to/from the process...4 Mounting brackets When using a separate isolating valve or flange adapters and two-way valves the transmitter is mounted with a bracket (Fig. -4a) on wall or support pipe. The angle mounting bracket (Fig. -4b) provides the best position for venting and sediment removal. Process connections and vent valves are then at the top and bottom of the measuring chambers. The transmitter body can be rotated on the flanges for the most suitable mounting position. The mounting position (horizontal/vertical) will have a slight effect on the zero point, depending on the transmitter s range. For this reason the zero setting should be checked after installation...5 Hydraulic pressure seal Hydraulic pressure seals are used in applications where the transmitter s wetted parts have to be isolated from the process medium. Such isolation may be necessitated by the process medium s corrosive properties, toxicity, high temperature, sedimentation, crystallization, etc. Figure -4a Flat mounting bracket (M8097) 5 50 Figure -4b Angle mounting bracket (M8096) 5 8 5 50 FLANGE DN40 PN00 DN50 PN40 DN80 PN40 DN00 PN40 ANSI" 50 lbs ANSI" 00 lbs ANSI" 50 lbs ANSI" 00 lbs ANSI4" 50 lbs ANSI4" 00 lbs 50 50 50 ØD 70 65 00 5 5 65 9 0 9 54 0540 0540 b 6 0 4 4 5 6 6 4 50 5 8 Ø50 0540 D ØD 50 b Ø 50 b 5 50 Figure -5a Dimensions: VDtxxxV and hydraulic pressure seals (welded joints) 0540 Figure -5b Dimensions: VDtxxxV and hydraulic pressure seal (welded joints) 6

. Electrical connections Supply voltage and load of the transmitter according to the figure -7. We recommend shielded twisted-pair cable as signal cable. The signal cable should not be installed near high-voltage cables, large motors or frequency converters. The shield of the cable is grounded at the power supply end or according to the recommendations of the manufacturer of the used control system. Figure-6 Removing the PLUG junction box Open. Remove screw. Open 004409 00545 400 50 Load / Ω 000 750 500 50 Operating region 0 0 5 0 5 0 5 Supply voltage /V Min. load using HART - communication 50 Ω 40 Figure -7 Supply voltage and load capacity R max = Supply voltage - V I max I max = 0.5 ma using HART -communication I max = ma (when the alarm current,5 ma is on) Position selection x 90 0.5....5 mm Tighten the screw Pg9 Figure -8 Adjusting the junction box position 004409 7

ma + - ma S P.5 Hart D DN UP 60 Test + - Test - + Load Power Load Power Figure -9, wiring housings H and T 005455 Figure -0, wiring housing M 005455 ma Hart - + ma - + + - Test Test Load Load Power Power Figure -, wiring housing N 005455 Figure -, Wiring housing N with plug DIN 4650, code N-/-P 005455 SETTING UP Setting up is dependent on type of user interface and loaded description VALMET or SATRON. Also must be noted that when the older VAL- MET description is in use then the transmitter must be configured so that it can operate with the old VALMET description. The change from description to another is made by writing to MESSAGE-field either. VALMET or SATRON (Note, capital letters and dot in front). After writing the message the new description will be activated by switching transmitter's power OFF and ON again. 8

SETTING UP. Using the 75 user interface. Setting up through HART 75 user interface Operation keys The six operation keys are located above the alphanumeric keyboard: The ON/OFF key (I/O) switches the user interface on and off. When you switch the user interface on, it starts looking for a HART transmitter connected to it. If the transmitter is not found, the message No Device Found. Press OK will be displayed. The ONLINE menu is displayed when the user interface finds the transmitter. (^) This key allows you to move upwards in menus and scroll lists forwards. (v) This key allows you to move downwards in menus and scroll lists backwards. (<) This two-function key allows you to move the cursor to the left and to go back to a previous menu. (>) This two-function key allows you to move the cursor to the right and to select a menu option. (>>>) The quick-selection key will start the user interface and display the quick-selection menu. You can define the desired menu as quick-selection menu. Function keys With function keys F, F, F and F4 you can perform the program functions displayed above each function key. When you move in the software menus, the functions of these keys will change in accordance with the currently selected menu. After installing and connecting the transmitter, connect the user interface to the transmitter. The following menu is displayed: Measurement Configuration Information 4 Diagnostics To change the measuring range, unit damping time constant to output mode (linear/square-root), select Configuration. The following menu is then displayed: Range values Detailed config To change the measuring range, select Range values. The selection displays the following menu: LRV (lower range value) URV (upper range value) LSL (lower sensor limit) 4 USL (upper sensor limit) 5 Min span (minimum span) 6 Apply values To change the measurement unit, damping time constant or output mode, select Detailed config from the Configuration menu. The selection displays the following menu: Damping Pres. unit Tempr. unit 4 Alarm current 5 Write protect 6 Lin. func 7 Diff El status 8 Burst mode 9 Burst option Poll addr Tag User function User funct. setup After these activities or if the transmitter is supplied with the ready configuration you must correct a zero error of the transmitter in a final installation position. Press Diagnostics and PV ero calibr. Figure - 75 user interface The selection displays the following menu: Give correct value for ero pressure in... The current zero point will be shown in display and the final zero error correction can be done. 9

. Using the 75 user interface The following menu is then displayed: Measurement Configuration Information 4 Diagnostics 5 Review To change the measurement unit, damping time constant or output mod, select Configuration. The following menu is then displayed: Range values Output Tranfer function 4 General setup To change the measurement unit, select Range values. The following menu is then displayed: LRV URV LSL 4 USL 5 Min span 6 Apply values To change the damping time constant, select Output from the Configuration menu. The following menu is then displayed: Damping Alarm current To change the output mode, select Transfer function from the Configuration menu. The following menu is then displayed: Lin. func User function data After these activities or if the transmitter is supplied with the ready configuration you must correct a zero error of the transmitter in a final installation position. The First press Diagnostics and then Sensor trim and then ero trim Figure - 75 user interface.4 Setting up through HART 75 user interface and SATRON description The following text is then displayed : WARN-Loop be removed from automatic control The final zero error correction can be done to select ABORT or OK on the display. After installing and connecting the transmitter, connect the user interface to the transmitter. The following menu is displayed: Main menu. To select the HART Application. 0

www.sat ron.com USB HA RT + 4 V - 00R 0.0% R 8mA 50R R SATRON VDt differential pressure transmitter.5 Setting-up with Satron-pAdvisor Service Software When you will have available all the operations of the Smart transmitter, we recommend the use of Satron-pAdvisor Service Software and Satron SI-Toole USB-Hart-modem in setting-up. Test connections for configuration and pressure/ output current values checking and calibration and for SENSOR TRIM function Recommended equipment for calibration Satron-pAdvisor service software for SATRON Smart transmitter (can be loaded free of charge from www.satron.com) PC: operating system Win-98, Windows 000 or Windows XP) DMM: Digital multimeter, basic DCV accuracy better than 0,0 % of reading (for example Fluke 8840A, Keithley 000) Cal. pressure generation and measurement device (accuracy better than 0,0 % of reading) USB-Hart modem, Satron SI Toole, order no: M000 Digital multimeter for output current measuring Um+ US B Rx Tx +5V Pwr OK Um+ Si-Toole USB / HART Rx HART Tx Um- Ext. power in 4mA = 0.4V 9... 0V 0mA = VDC DC or AC Um+ modem Um- Vsup+ Um- Vsup- IP40 NOTE! Do not switch Vsup ON in live circuit IL Vsup ON/OFF PC VDt Cal. pressure generation and measurement device Figure - Calibration connections window.6 Setting-up with local switches The additional instruction of display menus is enclosed to this manual. Keyboard : Esc = Press Esc move back towards the top of the main menu. = Use the UP arrow key to move up on the current menu level or to increase the selected parameter value. = Use the DOWN arrow key to move down on the current menu level or to decrease the selected parameter value. Enter = Press ENTER to move to a lower level in a menu or to accept a command or parameter value. Figure -4 VDt differential pressure transmitter with display 005454

Measurement PV Pres. AO % rnge LRV Sensor Housing URV LSL USL Configuration Range values Min Span Apply values 75 software tree (Maker code: VALMET) 4 ma 0 ma ON LINE Detailed config Damping Pres. unit Tempr. unit Alarm current Write protect Lin.func Diff El status Burst mode Point pressure Burst option Point output Poll addr... Tag Point6pressure User function Point 6 output User funct. setup Ref. temperature Vol. temp.coeff. Manufacturer Model Information Device info Sensor s/n Message Universal rev Fld dev rev Software rev Hardware rev Descriptor Final asmbly num P-SMART special Selection code P-SMART Process seal Housing type Body/Flange mater Diaph/(+)diaph mat (-)diaphragm mater Diaphragm coating Extension material Fill fluid Explosion proof Diagnostics Device status flags ero device status Loop test Loop calibr. PV ero calibr PV Span calibr Digital inputs Date Tempr calibr. ALARM CPUEE ER ALARM ADSEN ER ALARM ADTS ER ALARM ADTH ER ALARM ELDR ER SCI ERR AD ERR HA FR ERR HA DA ERR ADCEE ERR Reserved Reserved Sensor tempr cal Housing tempr cal

Measurement Configuration PV Press AO % rnge Sensor Housing Range values LRV URV LSL USL Min Span Apply values Damping Alarm current 4 ma 0 ma 75/75 software tree (Maker code: SATRON) ON LINE Output Transfer function General setup Lin. func User function data Pres. unit Temp unit Write protect Tag Descriptor Message Date User point cnt User unit USER Temp correction. Pres. Out... 6. Prs 6. Out Reference temp Vol. temp coeff. Information Measuring point Device info Construction info HART Manufacturer Model Dev Type Serial no. Sensor no. Device no. Software rev Hardware rev Selection code Process connection Housing type Body/flange mater Diaphragm mater (+) Diaphragm mater (-) Diaphragm coating Extension material Ext lenght code Fill fluid Explosion proof Temp code Process connect (-) Universal rev Fld dev rev Poll addr Burst mode Burst option Diagnostics Review Device status Sensor trim Output functions Temperature trim Other functions Self test Error info Statistics ero trim Lower sensor trim Upper sensor trim Loop test Output trim Sensor temp trim Housing temp trim Master reset Factory defaults

.7 Set-up calibration, housing code T (with manual adjuster) The transmitter is factory-calibrated, with sec. electrical damping, for the range specified in the order. If range is not specified, the transmitter will be calibrated for the maximum range. ero and Span adjusters are at the end of the housing, under protective rubber shield. TEST jacks are also under protective rubber shield. Figure -5: housing T with PLUG connector Checkout procedure - See that the ripple on the supply voltage does not exceed.5 V pp on 0-000 Hz frequency range. - Check the nameplate for the factory-calibrated range and zero suppression/elevation. - If necessay, readjust the zero. - Please see quide for zeroing from.. calibration examble. S P.5 Hart D DN UP 60 Test Housing with PLUG-connector, code T Use of selector switch : = working position P = Process value zero D = damping adjustment S = Span adjustment = ero adjustment DN = Down UP = Up Figure -5 005454 CALIBRATION. Adjustability Maximum span is 5 times the minimum span for SATRON VDt transmitter Span adjustments is made from outside the housing, under the protective rubber shield (figure -). ero suppression and elevation Maximum zero suppression is 86 % of max.span, and maximum zero elevation is 00 % of max. span. ero adjustments is made from outside the housing, under the protective rubber shield (figure -). Hart S P.5 D DN UP 60 Test Hart S P.5 D DN UP 60 Test Figure - 005454 Figure - 005454 4

Measuring range The lower and upper range-values cannot differ from zero by more than the maximum span. For example, range 4 transmitter whose measuring range is 0-4/00 kpa cannot be adjusted to measure 00...04 kpa pressure, because maximum span is 00 kpa.. Damping If pulsation occurs in the measured pressure, it can be damped with the damping trimmer position D under the protective rubber shiled on the housing.. Calibration examples S P.5 D DN UP 60 The transmitter is factory-calibrated with minimum electrical damping. To increase the damping, turn the trimmer clockwise. Adjusting the damping does not affect the transmitter's other calibration. Damping adjustment :. Turn the selector switch from to position D. Turn the regulating switch about ±0 so damping adjustment is activated.. Turn the regulating switch to desired value of damping. 0 s on the left side, 60 s in the right side. 4. Turn the selector switch from position D to position. S P.5 D ±0 DN UP 60 Hart 60 Test Figure -4 Process value zero (PV) S P.5 D 005454 First step is process value zero :. Turn the selector switch from position to position P.. PV ERO is done when the damping trimmer is turned once to both edges at least for sec.. Turn the selector switch from position P to position. The maximum correction during one calibration time is limited to 5 % of the sensor maximum range. All the changes made using the P-function can be recalled by turning the calibration trimmer to both edges three times (reset factory settings). DN UP Hart S P.5 D DN UP 60 Test Figure - Damping adjustment 005454 5

±0 Measuring range: 0...500 kpa (range 5 transmitter). Span: 500 kpa S Hart P.5 D S P.5 D DN UP 60 Test DN UP 60 Procedure - Apply zero pressure.. Turn the selector switch from position to position.. Turn the regulating switch about ±0 so adjustment is activated.. Turn the regulating switch to a point where output is closest to 4 ma. (adjustment range on fine adjustment range is ±0.75% of span and speed of adjustment is ±.5% of span / s) 4. Turn the selector switch from position to position. Figure -5 Set the lower range-value ±0 S P.5 D DN UP 005454 60 - Apply full-span pressure.. Turn the selector switch from position to position S.. Turn the regulating switch about ±0 so adjustment is activated.. Turn the regulating switch to a point where output is closest to 0 ma. (adjustment range on fine adjustment range is ±0.75% of span and speed of adjustment is ±.5% of span / s) 4. Turn the selector switch from position S to position. - Apply zero pressure. - Repeat the adjustments to achieve the desired accuracy. Hart S P.5 D DN UP 60 Test Figure -6 Set the upper range-value 005454 Sensor Module CPU Module Analog to Digital Conversion Non-Volatile Memory for Parameters - Correction Coefficients - Transmitter Information - Transmitter Configuration (Range Values, Damping, Lin.Funktion...) Microcontroller with Flash-memory Functions - Range Settings - Damping - Diagnostic - Units - Communication - Transfer function - Correction Calculation for Temperature and Linearization Interface Stage - Failure protection - Test Connections - Cable connections Analog Output HART Digital to Analog Conversion (4... 0mA) HART Digital Communication Module Temperature Temp. Sensor Pressure Sensor Module Abs. or Gage Pressure Sensor Temp. Sensor dp Sensor Module dp Sensor Display Module (optional) Buttons LCD-Display Pressure - + Differential Pressure Figure 4- Functional construction of the SATRON VDt differential pressure transmitter 005456 6

4. CONSTRUCTION AND OPERATION Sensor Module The piezoresistive sensor, which has a silicone oil fill, is isolated from the process with a diaphragm. Sensor pressure and temperature are measured with a 4-bit AD converter. Linearity and temperature effects are digitally corrected with an internal microprocessor connected to the sensor module. The sensor converts pressure to electrical signal. The conversion is carried out through a Wheatstone bridge supplied with direct current. The elastic displacement produced in the bridge by the pressure causes bridge unbalance which is measured as a DC voltage signal. Electronics Module The electronics module converts the process pressure signal from the sensor module to 4-0 ma output signal. The conversion can be made in linear, square root or inverted mode, or it can be done through user-selectable pressure/output point pairs (-6 points). Transmitters provided with own display (code N) is equipped with operating keys that allow you to define the transmitter s all functions. The active functions required for signal shaping are in a customized IC which is divided into two subblocks: amplifier block and standard-signal shaping block. The standard-signal shaping block also includes zero, span and damping adjustments. Compensation includes temperature compensation and linearization. Each sensor is calibrated individually through a resistance network connection. The temperature information required by compensation is derived from a temperature measuring element located by the Wheatstone bridge. 5. PARTS LIST When ordering spares, please quote this document s number and date, the name and The interface stage includes failure protections to ensure the transmitter's operation and nonfailure in possible failure conditions. This stage also includes the TEST and cable connections order number of the required part, and the transmitter s serial number. Parts indicated with asterisk (*) as well as screws, nuts and seals (packings) are spare parts. Number Name Order number Number Name Order number * 4 5 * 6 7 * 8 9 Wiring box GDM009, DIN4650 Seal GDM-7, silicone Sensing element Hex bolt, M0x90 DIN9 A4 Hex bolt, M0x90 DIN9 8.8 ne (PN40) Seal 46/50x.7 PTFE Flange (PN40, M0) Flange (PN400, M) Hex nut, M0 SFS067 A4 Hex nut, M0 SFS067 m 8.8 ne (PN40) Vent/drain valve, ¼-NPT Cylinder-head screw S Mx5 SFS79 A4 7900 79006 54890 5489 T09 T07 T07-M 56080 56087 T587 5705 * * * 5 * 6 7 * 8 9 * 0 * Protection cup, housing H, M and T Protection cup, housing N Mounting clamp Support plate Hex nut M8 SFS067 A4 Mounting bracket S O-ring, 4x FPM (Viton ) Cover M Seal, Silicone rubber Back plate V Fastening screw, M4 T0095 T00400 T54495 T54 560800 T050009 800800 T0056 T0087 T009 T547 7

05400 Figure 5- Parts list: Enclosure H and T, housing with PLUG connector Figure 5- Parts list: Enclosure M, housing with junction box 8 05400

05400 Figure 5- Parts list: Enclosure N, housing with display Figure 5-4 Parts list: Enclosure with remote electronics 05400 9

Satron Instruments Inc. P.O.Box, FIN-90 Tampere, Finland Tel.int. +58 07 464 800, Telefax +58 07 464 80 www.satron.com, info@satron.com Conmark Systems Inc. Instruments Div. Atlanta, GA 770-00-04 www.conmark.com 0