THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES. By M.J. Smart and B. Wadcock

Similar documents
Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

3.2. Current Limiting Fuses. Contents

EMPAC Metal enclosed capacitor bank for wind applications

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

Visual comparison of Plain & Hazy PP Film

HARYANA VIDYUT PRASARAN NIGAM LTD.

FUSES. Safety through quality

Fuse/Var Technical Data

MODVAR Low voltage reactive power compensation modules Installation manual

Paramount HRC Cartridge

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

LOW VOLTAGE CAPACITORS AND CAPACITOR BANKS. Capacitors department

Reviewed: DD Month University Code of Practice for Electrical Safety. PART B - Design and Construction of Electrical Equipment within the University

EUROPEAN HIGH VOLTAGE FUSES

AUTOMATIC CAPACITOR BANK WITH CONTACTOR OPERATIONS

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

Power System Solutions (PSS)

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

LV Capacitor CLMD03 Power Module Instruction manual

Technical Specification For Outdoor Substation Harmonic Filter Banks

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Expulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

CP Automatic capacitor bank

LEVEL SWITCH WITH 1 FLOAT

KD LV Motor Protection Relay

Technical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction

Fuse Link Designation

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

High Reliable Components for Power Factor Correction and Power Quality

Fuses still the best form of overload protection

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

ELECTRICIAN S THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET

Earthing Principles. Symmetra PX 250/500 kw

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Chapter 6 Generator-Voltage System

Guideline for Parallel Grid Exit Point Connection 28/10/2010

18 Industrial and Commercial P ower System Protection

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

LV Capacitor Bank APC

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

Small wonder. Station service voltage transformers for small power requirements

Power Systems Trainer

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

ISTEK-C A 750V DC Contactor

AF series contactors (9 2650)

Modular Capacitor Systems Reactive Compen. sation. Copyright 2002 ABB. All rights reserved.

AF series contactors (9 2650)

Medium voltage products. Fuses

Index Low Voltage Network Quality. Low Voltage Network Quality

Chapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design

Miniature & Moulded Case

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET

Ultravar TM AUTOMATIC POWER FACTOR CORRECTION & HARMONIC SOLUTIONS

Technical Information Solid State Relays. Glossary. Solid State Relays

Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV).

PhiCap Capacitors for Power Factor Correction

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Effective discrimination of protective devices

LV Capacitor Bank APC

CI-TI Contactors and Motor Starters Type CI 6-50

EARTHING YOUR QUESTIONS ANSWERED

Power Factor Correction Capacitors Type LKT

Standby Power Systems

Fault Finding. Standard/Fundamental Faults

Power Factor Correction

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

Modifiable TITAN Horizontal Motors Accessories and Modifications

Q pole Pole Mounted Capacitor System

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

Electrical Power Electric power electrical electric power Electric power electric electric

C1000 Series Automatic Cap Bank

Figure 1. Two and Three-phase MagneX.

Power factor correction Harmonic filtering Dynamic flicker compensation

Unified requirements for systems with voltages above 1 kv up to 15 kv

Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Grounding Of Standby & Emergency Power Systems

Technical information No. 01. IT systems. The basis for reliable power supply

Presented to the IAPMO Standards Review Committee on December 9, 2013

PSNH INTERCONNECTION REQUEST

ELG4125: Flexible AC Transmission Systems (FACTS)

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Electrical Test of STATCOM Valves

Industrial System Protection

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

Film Capacitors Power Factor Correction

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Transcription:

203 THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES By M.J. Smart and B. Wadcock 1.0 INTRODUCTION Capacitors are widely used for industrial power factor correction throughout the world, the advantages of using them being widely appreciated particularly in this era of expensive energy. Capacitors for this application are generally protected by fuses and the application of these fuses presents problems to the fuse and capacitor designer because of the particular phenomena associated with capacitor banks. This paper describes these phenomena and how they are overcome in industrial applications at system voltages up to llkv and bank ratings up to about 3Mvar. 2.0 GENERAL REQUIREMENTS Power Capacitor banks are always made up of series-parallel arrangement of capacitor sections, each section being protected by a fuse. The purpose of this fuse is to disconnect the faulty section in the event of its failure and permit the remaining healthy sections to continue functioning normally. The fuses selected for this duty must take account of the following requirements. Transient Current Withstand On energisation of a capacitor a large inrush current occurs. This inrush current is limited only by the inductance and resistance in the energising circuit. For a single capacitor this source reactance is represented by the system impedance and approximately the peak inrush current can be calculated from the formula. I peak inrush = System Fault level (kva) Capacitor rating (kvar) x capacitor rated peak rated current For a multi-section capacitor bank the inrush current into the first section is as for a single section bank, but for the second and subsequent sections there occurs a large interchange of energy between bank sections resulting in large inrush currents limited only by the inductance and resistance between the bank sections. This transient current is of high frequency and would normally decay within 10-20 milliseconds of inception. Any fuses incorporated in the capacitor circuit must of course withstand this current without deterioration. Continuous Current Withstand Because the impedance of a capacitor is inversely proportional to frequency it will tend to receive a relatively high proportion of currents of frequency higher than system power frequency. This 'fact is particularly important in view of the present increasingly large scale use of power electronic equipment which is Mr. Smart and Mr. Wadcock are with B.I.C.C. Power Cables Limited, Helsby, Warrington, U.K.

204 inherently harmonic generating. It is recognised in the current issues of most national specifications, BS1650 : 1971 typically laying down that the continuous current rating of a power capacitor should be 1.15 x current at rated voltage and frequency for medium voltage capacitors, this factor being increased to 1.3 x for high voltage capacitors. Because a capacitor also normally has a positive capacitance tolerance of 10%, these factors have to be increased respectively to 1.265 x and 1.43 x nominal power frequency current rating. This continuous overcurrent withstand must be incorporated into all associated capacitor equipment, in particular the capacitor fuses. Discharge Withstand When a number of individually fused capacitor sections are connected in parallel, then on failure of one of these sections, the power frequency fusing current in the fuse of the faulty section will be that which results from short-circuiting the complete group of capacitors. In addition if, as is most likely, the short circuit occurs when the group of capacitors is charged to some voltage greater than zero the fuse of the faulty section must clear successfully against the resulting high frequency discharge current, and the fuse of each of the healthy sections must withstand the contribution to this discharge current from its own section. 3.0 FUSE TYPES As stated in Section 2.0 above capacitor banks are made up of series-parallel arrangement of capacitor sections, each section protected by a fuse. In practice capacitors are manufactured in standard unit sizes, these units being connected together to form a bank. Each unit in turn is made up internally of a number of elements or windings. Element voltages at present can be up to about 1.5 to 2kV so that units of voltage rating below this normally have all their elements connected in parallel. These units are generally protected by internal fuses, one fuse being connected in series with each element. Because of the comparatively large number of capacitor elements connected in parallel in this arrangement, it is relatively simple and economical to design an internal fuse to fulfill all the requirements of Section 2.0, above and in fact internal element fuses are usually used at these voltages. These are of course incorporated inside the units at the time of manufacture. Internal fuses can only disconnect dielectric failures, and for other faults, such as failure of the major insulation between the element pack and the unit case, they are not effective. External fuses are therefore normally necessary in addition to the internal fuses, and these are best incorporated in the incoming connections to the complete bank as described in Section 4.0 below. For power factor correction capacitor banks of voltage rating above about 1.5kV to 2kV it is necessary to use capacitor units with two or more windings in series within the unit. Because of this series connection of elements there are correspondingly less elements connected in parallel in each element group within the unit and the design of an element fuse complying with the requirements of Section 2 is more difficult, unless an uneconomically large total number of windings per unit are used. In addition the internal fuse is not effective in disconnecting major insulation faults as described above. It is thus preferred practice to use external fuses for these applications, one fuse for each capacitor unit. The practical choice for an external fuse is then between a noncurrent limiting expulsion fuse and a current limiting h.r.c. fuse. The expulsion fuse is cheaper than the h.r.c. fuse and has a time/current characteristic (time plotted vertically) which is less steep, with the

205 result that for a given ability to withstand high frequency transients its current rating and fusing time with the power-frequency fault current are both less. However the breaking capacity of an expulsion fuse is usually less than the fault level of the system where a capacitor is installed, and therefore the use of such a fuse is limited to those cases where the capacitor units are series connected in such a way that the power frequency fault current occurring upon unit failure is limited by the series connection. Since capacitor units are available with a single phase rating of up to 15kV, series connection of capacitor units is not normally necessary at industrial voltages up to this level unless the bank is sufficiently large to justify the use of the expulsion fuse on economic grounds. Thus capacitor banks of up to 3Mvar and higher at these voltages can be made up of capacitor units connected in parallel directly across the system line connections each with current limiting h.r.c. fuses connected so as to disconnect a faulty unit from the supply upon failure. Since the unit is connected directly across the system, the prespective power-frequency fault current is decided by the system fault level. For banks up to 3Mvar the discharge energy due to the short-circuit of parallel connected capacitors which occurs when a unit fails is negligible, so that only power-frequency fusing current need be considered in choice of fuse. Since the prospective power-frequency fusing current is large, being limited only by system impedance, correct operation of the fuse is ensured even if its rating considerably exceeds its normal operating current. Since a current limiting h.r.c. fuse normally has to be oversized to ensure correct high-frequency transient withstand this is an important advantage. It is emphasised that the connection of capacitors must be such as to ensure that capacitor failure results in system short circuit to obtain this advantage, and arrangements where power frequency fault current is limited by series connection of capacitors, such as in unearthed star arrangements, must be avoided. 4.0 LOW AND MEDIUM VOLTAGE ARRANGEMENTS Capacitor banks in the low and medium voltage range are assembled using capacitor units with individual output ratings up to SOkvar. These units can be two terminal type for single or two phase operation, or, three terminal type for three phase operation. In the case of the two terminal units the elements are all parallel connected. In the three terminal units all elements are arranged in three groups with elements parallel connected, and the three groups arranged in a delta configuration. Fig. 1A indicates the internal connection arrangement of elements for a typical two terminal capacitor unit rated lokvar, 415 volts, 50Hz. Fig. IB indicates the internal connection arrangement of elements for a typical three terminal capacitor unit rated SOkvar, 415 volts, 50Hz. Larger ratings of capacitors are achieved by parallel connection of multiple single unit assemblies. These capacitor banks are usually controlled by suitably rated switches or contactors which are provided with line connected current limiting fuses. Fig. 1C indicates the connection arrangements for a lookvar, 415V,

206 3 phase, 50Hz capacitor bank complete with isolator, contactor, and line connected HRC type fuses. 5.0 HIGH VOLTAGE ARRANGEMENTS In high voltage capacitor banks, capacitor units up to 200kvar 15kV output rating are now commonplace Each unit usually comprises capacitor elements without fuses, these elements being arranged in a series/parallel grouping to meet the specified or required voltage rating. Individual capacitor units of the three terminal type are available for working voltages up to 3.3kV 3 phase, and beyond this up to 15kV, two terminal types only are usually available. Fig. 2A indicates the internal connection arrangement of elements for a typical three terminal ISOkvar, 3.3kV 50Hz capacitor unit, and Fig. 2B the internal connection arrangement of elements for a typical two terminal 200kvar, llkv 50Hz capacitor unit. For capacitor banks of rated voltage above 3.3kV, two terminal capacitor units are used in multiple series/parallel grouped assemblies to achieve the desired rating. For example a 600kvar, llkv 3 phase capacitor bank could be arranged using 3 - two terminal capacitor units of individual rating 200kvar llkv arranged in a delta configuration and protected by 3 line connected fuses. See Fig. 3A. These capacitor units and fuses are normally accommodated in one of three ways. a) Within a welded steel tank type construction complete with cable entry box. This tank is usually oil-filled to aid cooling and is ideal for difficult or exposed environments. b) Within a fabricated sheet, steel cubicle complete with cable entry chamber. c) In an open busbar arrangement where the capacitor units and associated line fuses are supported by a galvanised steel framework. Higher capacitor bank ratings are achieved by addition of further two terminal capacitor units and fuses parallel connected in the delta configuration. For cubicles and open busbar designs the preferred arrangement is, as shown in Fig. 3C, with the units connected in delta in groups of three, with the fuses in the line connection to each delta group of units. An alternative arrangement, is to connect the fuses within the delta as shown in Fig. 3B. Fuses connected in this fashion do not protect the arrangement for earth faults so that line fuses are required in addition for this purpose. This connection arrangement is usually used for oilfilled tank-type capacitors, where the physical arrangement makes it preferable. Where line fuses are provided in addition to unit fuses it is important to ensure discrimination between the unit and line fuses. This can result in large line fuse ratings bearing in mind the 2 x factor which has to be

207 applied to the unit fuse rating in accordance with Section 6.0 below. 6.0 FUSE RATING The fuses used in association with capacitors should have a rating which ensures the following requirements are satisfied a) The fuse rated voltage and interrupting capability corresponds to the rated voltage of the system to which they are connected, and system fault level at the point of connection of the capacitor bank. b) The fuses must be capable of handling the capacitor discharge currents, and also the capacitor bank/unit inrush transients as described in Section 2. On this point it is generally accepted, (based on practical operating experience) that for low and medium voltage capacitor banks line fuses of rating 150% of the capacitor current rating will accommodate without deterioration these discharge and transient inrush currents. Because high voltage capacitors involve the use of fuses with smaller continuous current ratings and the ability of these fuses to withstand transient inrush and discharge currents is disproportionately less than for larger fuses, factors of 200% or more may be necessary. Fuse size can be significantly influenced again if back to back capacitor bank switching is employed. However in general for low and medium voltage capacitor banks because of the relatively small bank sections and high interconnecting inductance a fuse of 150% capacitor current rating will be satisfactory. For high voltage capacitors special steps may have to be taken to ensure sufficient transient withstand is incorporated in the fuses. The consequences of incorrect rating, resulting in partial fuse failure caused by capacitor inrush or discharge current, is that when normal current is returned to the fuse, the fuse is no longer capable of its assigned duty, and overheating followed by complete and probably damaging fuse breakdown occurs. It is particularly important to avoid this in oil-filled tank capacitor designs. c) The line fuses of the capacitor bank should discriminate with the fuses farther back in the supply-system. In particular this may significantly influence the size of cable to a capacitor bank if correct protection of this supply cable is to be achieved. The unit fuses of capacitor units within a capacitor bank should also be rated to achieve discrimination between the fuse protecting the faulty capacitor and those protecting the healthy capacitors. This on delta connected banks as recommended in this paper is easy to achieve as outlined in Section 3.0. 7 - CONCLUSIONS Current limiting fuses offer considerable advantages when used for protection of industrial power factor correction capacitors in that they can generally allow capacitor requirements to be met by a physically small, simple installation. However to ensure reliable and correct operation of the installation it is important that the fuses are applied correctly as outlined in this paper. Capacitor failure rates are considerably less than 0.1% per year and to ensure fuse operation matches this performance is particularly important.

208 Many years of experience of applying fuses in accordance with these guidelines have been acquired, and provided they are followed reliable and trouble free capacitor installations should be achieved. The permission of B.I.C.C. to publish this paper is acknowledged.

209 Parallel connected elements r ] - -»Oi* T- Capacitor element Capacitor element fuse FIG 1A INTERNAL CONNECTIONS FOR 2 TERMINAL LOW VOLTAGE CAPACITOR UNIT. L / \ I ' Capacitor element fuse? Capacitor element T I FIG IB INTERNAL CONNECTIONS FOR 3 TERMINAL LOW VOLTAGE CAPACITOR UNIT. Parallel connected elements Contactor < = cd- -0-0- JL JL t r 71 t Isolator -0-0- f Line fuse I' 's'' I FIG 1C CONNECTION ARRANGEMENT FOR LOW VOLTAGE CAPACITOR BANK. r i"t, \j 1 Parallel connected units

210 h r* FIG 2A INTERNAL CONNECTIONS OF 3 TERMINAL HIGH VOLTAGE CAPACITOR UNIT. FIG 2B INTERNAL CONNECTIONS OF 2 TERMINAL HIGH VOLTAGE CAPACITOR UNIT.

211 Line fuse. v Ml /*f'- - - Capacitor unit internally arranged as FIG 2B. FIG 3A ARRANGEMENT OF 3 PHASE HIGH VOLTAGE CAPACITOR BANK. Line fuse '.v (VA.. ' 'x. v '. < -v,* Capacitor unit internally arranged as FIG 2B Unit fuse I II : FIG 3B ARRANGEMENT OF 3 PHASE HIGH VOLTAGE CAPACITOR BANK WITH LINE & UNIT FUSES. Capacitor unit internally arranged as FIG 2B..<»» Line fuse»cxo I V' oo- J/ I \ FIG 3C MULTIPLE ARRANGEMENTS OF 3 PHASE HIGH VOLTAGE CAPACITOR BANKS. I