1 Product Guide An Invensys company

2 Contents Page I/ The principle of the gas-recombination battery... 2 II/ Charge characteristics... 4 III/ Electrical performance tables... 5 IV/ Battery calculations Float applications Accidental deep discharge Effect of temperature on capacity V/ Installation of the battery Warning Unpacking the battery Setting up the battery stands Installing in a cabinet Connection of the cells Installation on standard metallic stand VI/ Battery storage Storage conditions Storage time Determining the state of charge of the battery Recharging stored batteries VII/ Commissioning VIII/ Maintenance... 16

3 POWERSAFE VE Range 1 TYPE voltage (Volts) Capacity (Ah) to 1.80V at 10 h rate at 20 C Capacity (Ah) to 1.75V at 20 h rate at 20 C Length in mm Width in mm Heigth over protection in mm 12 VE 38(3) M5 6+/-10% 12 VE 38(3) 8 mm wrench 12 VE M6 9+/-10% 12 VE mm wrench 12 VE M6 9+/-10% 12 VE mm wrench 12 VE M6 9+/-10% 12 VE mm wrench 12 VE 90(3) M6 9+/-10% 12 VE 90(3) 10 mm wrench 6 VE 110(3) M8 16+/-10% 6 VE 110(3) 6 VE 140(3) M8 16+/-10% 6 VE 140(3) 2 VE M6 9+/-10% 2 VE mm wrench 6 VE 155(3) M8 16+/-10% 6 VE 155(3) 6 VE 180(3) M8 16+/-10% 6 VE 180(3) 2 VE M8 16+/-10% 2 VE VE M8 16+/-10% 2 VE VE M8 16+/-10% 2 VE VE M8 16+/-10% 2 VE VEO 450(1) M8 16+/-10% 2 VEO 450(1) 2 VE 540(2)(3) M8 16+/-10% 2 VE 540(2)(3) 2 VE M8 16+/-10% 2 VE 550 Weigth in kg Connexion Screw Torque (Nm) TYPE (1) cells with 4 posts - (2) Cells with 6 posts - (3) with integral handles

4 I/ The principle of the gas-recombination battery In a gas-recombination battery, the quantity of active materials in the plates and the alloys used in the manufacture of the grids which support the active materials, are such that oxygen is first released from the positive plate. The internal design of the battery ensures that this oxygen diffuses toward the negative plates where it reacts chemically with the spongy lead of the negative active material to form lead oxide. The sulphuric acid contained in the electrolyte is composed then reacts with this lead oxide to form lead sulphate and water. The lead sulphate thus formed is transformed electrochemically into lead to return sulphuric acid. This state of equilibrium will remain for as long as the battery remains fully charged. Schematically, we then have the following reactions : At the end of the charge or if overcharging, oxygen is released at the positive plate in the form of a gas. H 2 O 2H + + 1/2O 2 + 2e - The oxygen diffuses across the separator to the negative plate The oxygen reacts chemically with the spongy lead of the negative plate to form lead oxide. Pb + 1/2O 2 PbO The sulphuric acid reacts with the lead oxide to give lead sulphate and water, and so part of the spongy lead is chemically discharged to the lead suplhate state and the water consumed at the positive plate is regenerated. PbO + H 2 SO 4 PbSO 4 + H 2 O The spongy lead which was chemically discharged at the negative plate is re-charged chemically. PbSO 4 + 2H + + 2e - Pb + H 2 SO 4 These reactions occur within each cell, and an equilibrium is thus achieved. Electrolyte Conventional cell Oxygen and hydrogen escape to the atmosphere Powersafe Oxygen evolved from positive plate transfers to negative and recombines to form water. Separator 2

5 Construction : These reactions can take place only by using : - plates composed of special alloy with several components which provide the plate grids with high mechanical strength and a high level of hydrogen overvoltage. - an appropriate ratio between positive and negative active materials. - fiberglass separators manufactured from borosilicate, giving them excellent resistance to high temperatures and to sulphuric acid.the high level of porosity of these separators is used to retain the quantity of electrolyte necessary for cell operation, but without any free electrolyte. - a pressure relief valve which allows gas to be released if necessary in the case of an accidental overcharge. ➀ Grey lid in ABS heat-welded to the container ➄ Terminals with threaded insert for maximum conductivity and ease of installation ➅ Gas-relief system ➆ Negative plate ➁ ABS container highly resistant to impact and vibration ➂ Positive plate ➃ Separator 3

6 II/ Charge characteristics The cells in the Powersafe VE product range must be charged at a constant voltage At an ambient temperature of 20 C, the batteries should be charged at volts per cell. It is not necessary to limit the current as this will be governed by the maximum output available from the charger until the voltage limit is reached. Increased maintenance is recommended as the battery approaches end of useful life. The charging voltage of volts should also be used for float charging. To achieve nominal performance characteristics, it is recommended to adjust this value to suit the ambient temperature, as indicated in the following table : Temperature 0 C 10 C 20 C 25 C 30 C 35 C (reference T ) Float charge voltage V V V V V V Under these conditions a full recharge will be completed in approximately 72 hours. Fast recharge : Recharge time can be reduced by increasing the charge voltage to 2.40 Volts per cell and it is possible, depending on the depth of discharge, to halve the recharge time. Under these conditions, however, the charge must be monitored and must be terminated when the charge current remains reasonably steady for 3 hours after the voltage limit has been reached.at the beginning of charge the current must be limited to 0.10C10 : 0.125C3(A). Ripple current : The ripple content of the charging current affects the life of the battery. It is recommended to limit the continuous ripple current to 0.05 C10 (in amperes) as recommended value (never exceed 0.10C10). Transient and other ripple type voltage excursions can be accommodated provided that, with the battery disconnected, the system peak to peak voltage including regulation limits falls within % of the recommended float voltage of the battery. 4

7 III/ Tables of performances Powersafe VE Discharge current in amperes End voltage : 1.60 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE Discharge current in amperes End voltage : 1.65 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE

8 Discharge current in amperes End voltage : 1.70 V 12 VE VE VE VE , VE , VE VE VE VE VE VE VE , VE , VE , VEO VE VE , Discharge current in amperes End voltage : 1.75 V 12 VE VE , VE VE VE VE VE VE , VE VE VE VE , VE VE ,0 34, VEO VE VE

9 Discharge current in amperes End voltage : 1.80 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE Discharge current in amperes End voltage : 1.85 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE

10 Discharge current in amperes End voltage : 1.90 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE Tables of available power Power per cell in watts End voltage : 1.60 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE

11 Power per cell in watts End voltage : 1.65 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE Power per cell in watts End voltage : 1.70 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE

12 Power per cell in watts End voltage : 1.75 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE Power per cell in watts End voltage : 1.80 V 12 VE , , VE ,3 35, VE VE , VE VE VE , VE VE VE , VE VE VE VE VEO VE VE

13 Power per cell in watts End voltage : 1.85 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE Power per cell in watts End voltage : 1.90 V 12 VE VE VE VE VE VE VE VE VE VE VE VE VE VE VEO VE VE

14 IV/ Battery calculations a. Floating applications A battery application is characterised by : - a voltage which must be held within certain limits, - a power level which must be delivered - a set capacity to maintain the load in terms of time. By the use of these three parameters, calculations can be effected as follows : - A situation requires : a maximum voltage of 484 volts a minimum voltage of 383 volts - The ambient temperature is 20 C - The float voltage is to be 2.27 volts per cell. Preliminary calculation : The maximum number of cells : 484 V / 2.27 V = 213 cells The minimum voltage per cell at the end of discharge : 383 V / 213 = 1.80 volts. Case 1 : discharge with a surge at the start of discharge - The surge power is to be kw for 10 minutes, followed by 25.7 kw for 4 hours. Discharge current : During the surge : W/383 V = 403 amps And then :25700 W/383 V = 67 amps Determining the cell required for the current required Current flow during surge : ( 403 A x 10 mins)/60 mins= 67 Ah Current flow for 4 hours : 67 A x 4 h = 268 Ah Total capacity drawn : 67 Ah Ah = 335 Ah. Equivalent discharge time at 67 amps to supply 335 Ah : 335/67 = 5 hours From the table of performance characteristics, expressed in terms of the discharge current in amps for 1.80 V end voltage, the cell to give a current of 67 amps for 5 hours is the 2VE 450. Conclusion : In this example; it is the total number of Ah required which determines the battery to be used, i.e. 213 cells of type 2 VE 450. Case 2 : discharge with a surge at the end of discharge (here again, it is the surge which dictates the battery to be used) The continuous power is to be 25.7 kw for one hour, followed by a surge of 138 kw for 20 minutes. P P 154,3 KW 138 KW 25,7 KW 25,7 KW 10 4h10 T 1h20 T 12

15 Discharge current : - During the surge : W/383 V=360 amps - Before the surge : W/383 V= 67 amps Capacity drawn in 1 hour : 67 A x 1 h = 67 Ah Capacity drawn during surge (20 mins) (360 amps x 20 mins)/60 mins=120 Ah Total capacity drawn : 187 Ah Equivalent discharge time at 360 amps to supply 187 Ah (187/360)x 60 min=31 min From the table of performance characteristics, expressed in terms of the discharge current in amps for 1.80 V end voltage, the cell to give a current of 360 amps for 31 minutes is the 2 VE 450. The battery to be used will consist of 213 cells of type 2 VE 450. b) Accidental deep discharge This may involve discharge of the battery into indicator lamps, a lower load on the battery than that initially planned, a failure of the charging system, a discharged battery not recharged immediately, etc On a full battery discharge : All of the sulphuric acid has been consumed, and the electrolyte is now entirely water. Sulphation of the plates is at a maximum, thus increasing greatly the internal resistance of the accumulator. The aqueous solution in which the battery now finds itself can give rise to the development of metal flakes on the separator during recharging, and this may cause the cell to short-circuit internally. Important note : This type of deep discharge will still result in the premature deterioration of the battery, and a significant effect on its life expectancy. c) Effect of temperature on capacity The following table gives the correction factor according to temperature, where the reference temperature is 20 C. Discharge time 5 minutes to 59 minutes 1 hour to 24 hours 0 C 5 C 10 C 15 C 20 C 25 C 30 C 35 C 40 C

16 V/ Installation of the battery Warning : - The cells of the Powersafe VE Series batteries are already charged when delivered, and are fitted with a protective cap on each terminal.they should be unpacked with care. - Avoid short-circuiting terminals of opposite polarity, because these units are capable of discharging at a very high current especially if the lid or the container is damaged. Unpacking the battery - Each shipment of Powersafe VE Series batteries is accompagnied by a packing list. - The packing list should be checked, and the Sales Department Telecoms/IT should be told immediately of any missing items. Setting up the battery stands - The structure should be assembled in accordance with instructions supplied with the equipment. Wooden stands - Ensure that the stretchers and cross-members are correctly interlinked. - Take up any irregularity in floor surface using shims Metal stands - Ensure that all frame members are correctly interlinked - Use the adjustable feet to take up irregularities in the floor surface - Recommend stands over 3 tiers high are wall mounted - Metal stands should always be connected to the building earth in accordance with current regulations. Place the duckboarding around the battery stand as shown in the figure on p.15. Mounting in a cabinet Ensure that the cabinet : - is sufficiently strong to cope with the weight of the battery - is covered with a layer of insulation - is naturally ventilated. Connection of cells All connections should be insulated In series : The number of cells in series will determine the total float of voltage : U = v x N Total float Float voltage Number of cells Voltage for one cell In parallel : VE cells of the same Ah rating may be connected in parallel to give higher current capability. This connection in parallel will be preferably carried out through an equipotential wiring for an equal current distribution in each string. There is no technical reason for limiting the number of strings but for practical installation reasons, it is recommended not to exceed 4 strings in parallel especially if the battery is used in high discharge rates (Standby time lower than 1 hour). General recommendations - Do not wear clothing of synthetic material, to avoid the generation of static potentials. - Use insulated tools. - Place the cells beginning with the least accessible rows, spacing the cells as shown on the drawing. - Consult the drawing for the correct position of the cell poles ( positive=red washer, negative = blue washer). - Before attaching the inter-cell flexible cables, check that all terminals are in the correct position. - The battery cells are connected in series, that is with a positive pole connected to a negative pole. - Use only a damp cotton cloth for cleaning purposes - THE TIGHTENING TORQUE FOR CONNECTION SCREWS VARIES ACCORDING TO THE IR DIAMETER : M5 screws : torque from 5.5 Nm to 6.5 Nm maximum M6 screws :torque from 8Nm to 10 Nm maximum M8 screws : torque from 15 Nm to 17 Nm maximum (see table on p.1 of the brochure) Safety : All installations must comply with the current regulations and norms. 14

17 Length Installation on standard metallic stand - in vertical position Width of stand of cells 2 levels 3 levels 4 levels 2 levels 3 levels 4 levels 2 levels 3 levels 4 levels 12 VE 38 Max. No of cells Total height (mm) VE 50 Max. No of cells Total height (mm) VE 60 Max. No of cells Total height (mm) VE 75 Max. No of cells Total height (mm) VE 90 Max. No of cells Total height (mm) VE 110 Max. No of cells Total height (mm) VE 140 Max. No of cells Total height (mm) VE 170 Max. No of cells Total height (mm) VE 180 Max. No of cells Total height (mm) VE 225 Max. No of cells Total height (mm) VE 310 Max. No of cells Total height (mm) VE Max. No of cells Total height (mm) VEO 450 Max. No of cells Total height (mm) VE 540 Max. No of cells Total height (mm) VE 550 Max. No of cells Total height (mm) VE 155 is design primarily in a cabinet. If stand details are required, please consult the sales departement. Ferrule Stand drawing. Constructional details and dimensions Schelf 425 Total height 10 - in horizontal position (please contact our sales departement) Width 410,510 or 610

18 VI/ Battery storage Storage conditions : The battery should be stored away from any moisture or source of heat. Storage times : The self-discharge of Powersafe VE Series batteries as a function of temperature is as follows : 3 % per month at 20 C 6 % per month at 30 C 10 % per month at 40 C In order to ensure that the battery can be charged easily after a long period of storage, it is recommended that batteries should not be stored for more than the following periods without recharging : 6 months at 20 C 4 months at 30 C 2 months at 40 C Failure to comply with these recommendations may compromise the life expectancy of the battery. Determining the state of charge of the battery The state of charge of the battery can be determined by measuring the off-load voltage after the battery has been allowed to rest for 24 hours. % of Voltage per cell at differents temperatures capacity at 20 C 0 C 10 C 20 C 30 C 40 C 100% 2,16 2,15 2,14 2,13 2,13 80% 2,09 2,09 2,09 2,09 2,09 60% 2,06 2,06 2,06 2,06 2,06 40% 2,02 2,02 2,02 2,02 2,02 20% 1,97 1,97 1,97 1,97 1,97 Recharging stored batteries The batteries should be recharged at the float charge voltage to suit the temperature volts at 20 C per cell for example) for a minimum period of 96 hours. The battery will be charged when the charging current has remained constant for a period of 3 hours. VI/ Commissioning - Ensure that batteries are kept at all times in clean and dry conditions. - Before commissioning, the batteries must be charged at a constant regulated voltage to match the prevalling temperature for a minimum period of 48 hours. VII/Maintenance - Check the tightening of connections. - Every month, it is recommended that the total voltage at the battery terminals be measured. It should be Nx at a temperature of 20 C, where N is the number of cells in the battery. - Once each year, it is recommended that the voltage of each cell in the battery should be read off. - A difference of plus or minus 2.0% between these individual voltages and the average voltage may be observed. This is due to the gas- recombination process. - A check on capacity (independent operation on load) can be performed once or twice per year. Safety : When carrying out any work on the battery, the applicable safety standards should be followed. 16 Note : it is recommended that a battery log be maintained, and that records should be kept of the total voltage measurements, any mains failures, major battery discharges (current and time) etc. The main factors causing reduction in the life expectancy of Powersafe VE Series cells : - deep discharges - poor regulation on the float voltage - cycling or micro-cycling - poor quality ( smoothing) of the charging current - high ambient temperature.

19 Hawker S.A. Rue Alexander Fleming ZI EST BP Arras Cedex France Tel: Fax: hawker.france@hawker.invensys.com Ref. DCE0009G/ Hawker reserves the right to change or revise without notice any specification or other details given in this publication. Please refer to the website address for details of your nearest Hawker office

OPzV Technical Manual. An Invensys company

OPzV Technical Manual. An Invensys company OPzV Technical Manual An Invensys company Contents Page I/ The principle of the gas recombination tubular gel battery 1 Operating principle... 3 2 Conclusion... 3 3 Construction... 4 4 The OPzV range...

More information

PRODUCT GUIDE RESERVE POWER

PRODUCT GUIDE RESERVE POWER PRODUCT GUIDE RESERVE POER Contents Page I/ The principle of the gas recombination tubular gel battery 1 Operating principle... 3 2 Conclusion... 3 3 Construction... 4 4 The PowerSafe OPzV Battery range...

More information

F R O N T T E R M I N A L PRODUCT GUIDE Publication No: EN-VFT-PG-001 February 2003

F R O N T T E R M I N A L PRODUCT GUIDE Publication No: EN-VFT-PG-001 February 2003 F R O N T T R M I N L PRODUCT GUID Contents Introduction Introduction 2 Range Summary 3 Technology 4 Construction 5 Selection of Battery Size 6 Performance Data 7-14 Operating Characteristics 15 Operating

More information

Product Guide. An Invensys company

Product Guide. An Invensys company Product Guide An Invensys company Contents Introduction Introduction 2 Range Summary 3 Technology 4 Construction 5 Selection of Battery Size 6 Performance Data 7-26 Operating Characteristics 27 Operating

More information

1. Introduction Technical Features Construction Standards Certification Technology...

1. Introduction Technical Features Construction Standards Certification Technology... 1. Introduction...01 2. Technical Features...01 3. Construction...02 4. Standards...03 5. Certification...03 6. Technology...04 7. General Specifications...05 8. Performance Data...06 9. Selection of battery

More information

Battery. Student booklet

Battery. Student booklet Battery Student booklet Battery - INDEX - 2006-04-07-12:51 Battery Batteries are all over the place, in our cars, our PCs, laptops, portable MP3 players and cell phones. A battery is essentially a can

More information

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. Gelled Electrolyte Range. Monobloc

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. Gelled Electrolyte Range. Monobloc Haze Company Ltd Sealed Lead Acid 6 & 12 Volt Monobloc Gelled Electrolyte Range CONSTRUCTION - Gel battery construction is as shown in the diagram. The positive and negative grids are cast from a calcium/tin

More information

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service POWER FOR TOMORROW TODAY The Eternity Technologies range is built using only the highest quality and most efficient production processes at our state-of-the-art manufacturing centre in the UAE. It is this

More information

Haze Battery Company Ltd

Haze Battery Company Ltd Haze Battery Company Ltd Sealed Lead Acid 2 Volt Bloc Gelled Electrolyte Range CONSTRUCTION - Gel battery construction is as shown in the diagram. The positive and negative grids are cast from a calcium/tin

More information

Power to keep you on the move

Power to keep you on the move Power to keep you on the move Electric Vehicle Gel ELECTRIC VEHICLE applications are wide and varied with many durability & power demands placed firmly on the batteries shoulders. HAZE ELECTRIC VEHICLE

More information

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003 PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003 Contents Introduction Introduction 2 Range Summary 3 Recombination Technology 4 Construction 5 Features and Benefits 6 Battery Sizing 7-8 Performance

More information

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc Haze Battery Company Ltd Sealed Lead Acid 6 & 12 Volt Monobloc AGM Range CONSTRUCTION - AGM battery construction is as shown in the diagram below. The positive and negative grids are cast from a calcium

More information

Technical Manual. An Invensys company

Technical Manual. An Invensys company Technical Manual An Invensys company Content Page Application Areas for OPzS Batteries... 1 Cell Design... 2 The Electrolyte... 3 Basic Electrochemical Function of the Lead-Acid Cell... 4 Discharge Properties...

More information

Haze Battery Company Ltd

Haze Battery Company Ltd Haze Battery Company Ltd Sealed Lead Acid 6 & 12 Volt Monobloc Gelled Electrolyte Range CONSTRUCTION - Gel battery construction is as shown in the diagram. The positive and negative grids are cast from

More information

Haze Battery Company Ltd. Sealed Lead Acid 2 Volt Bloc. Gelled Electrolyte Range

Haze Battery Company Ltd. Sealed Lead Acid 2 Volt Bloc. Gelled Electrolyte Range Haze Battery Company Ltd Sealed Lead Acid 2 Volt Bloc Gelled Electrolyte Range CONSTRUCTION - Gel battery construction is as shown in the diagram. The positive and negative grids are cast from a calcium/tin

More information

Valve regulated sealed industrial battery. HAGEN OPzV

Valve regulated sealed industrial battery. HAGEN OPzV Valve regulated sealed industrial battery HAGEN OPzV HAGEN OPzV The OPzV range of valve regulated cells is a subsequent development of the well proven OPzS range and complies with DIN 40742. The cell containers

More information

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1 OPERATING CHARACTERISTICS 2 2 INSTALLATION 4 3 CHARGING 6 4 STORAGE AND REFRESH CHARGING 8 5 MAINTENANCE AND TESTING 9 6 SAFETY 10 7 APPLICABLE STANDARDS 10 8 RECORDS DATA 10 FIAMM.

More information

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc Haze Battery Company Ltd Sealed Lead Acid 6 & 12 Volt Monobloc AGM Range CONSTRUCTION - AGM battery construction is as shown in the diagram below. The positive and negative grids are cast from a calcium

More information

Pure Lead-Tin Technology

Pure Lead-Tin Technology Pure Lead-Tin Technology Pure Lead-Tin technology offers many advantages which include: High overall efficiency High energy density Excellent high rate performance Excellent low temperature performance

More information

INSTALLATION OPERATING AND ENGINEERING MANUAL. Range Umtb. Valve Regulated Recombination Batteries

INSTALLATION OPERATING AND ENGINEERING MANUAL. Range Umtb. Valve Regulated Recombination Batteries INSTALLATION OPERATING AND ENGINEERING MANUAL Range Umtb Valve Regulated Recombination Batteries Table of Contents 1. INTRODUCTION... 4 2. FEATURES... 4 No topping-up...4 Compatibility...4 High energy

More information

Valve Regulated Pocket Plate Nickel Cadmium Battery. Technical Manual

Valve Regulated Pocket Plate Nickel Cadmium Battery. Technical Manual Valve Regulated Pocket Plate Nickel Cadmium Battery Technical Manual Contents Pages 1.0. Introduction to VRPP battery 2.0. VRPP - Solution to varied applications 3.0. xygen recombination cycle - A technological

More information

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems Technical Note Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems Automation Products Introduction As more and more remote monitoring is installed on sites ranging

More information

The introduction of Lead Crystal Battery

The introduction of Lead Crystal Battery The introduction of Lead Crystal Battery (1). Brief Introduction of Lead Crystal Battery Lead crystal battery is based on an in-depth study of both lead acid batteries and gel batteries features and defects,

More information

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL) Batteries and more Powered by (CE, UL & ISO9001 APPROVAL) 1. Feature 1) Maintenance free-operation. There is no need to check the special gravity of the electrolyte or to add water during the service life.

More information

SUBSTATION EQUIPMENT - Page 1 of 8

SUBSTATION EQUIPMENT - Page 1 of 8 BATTERY BANKS 1. GENERAL: JEA utilizes a 125 volt DC system for the control and operation of its transmission and distribution substations. JEA has standardized on lead acid type battery banks to supply

More information

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A) A Complete solution for small battery-backed dc instrument power systems. DATASHEET Supply 12Vdc 8A or 24Vdc 6A loads Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where

More information

Valve regulated Batteries for Stationary Applications. HAGEN dc plus. An EXIDE Company

Valve regulated Batteries for Stationary Applications. HAGEN dc plus. An EXIDE Company Valve regulated Batteries for Stationary Applications HAGEN dc plus An EXIDE Company The new! HAGEN dc plus The new battery generation dc plus is based on the proven flat plate series HAGEN drysafe compact.

More information

OPERATION MANUAL. GFM-Series. Storage Battery Systems, Inc. N56 W16665 Ridgewood Dr. Menomonee Falls, WI (262)

OPERATION MANUAL. GFM-Series. Storage Battery Systems, Inc. N56 W16665 Ridgewood Dr. Menomonee Falls, WI (262) OPERATION MANUAL GFM-Series Version:V3.0 Storage Battery Systems, Inc. N56 W16665 Ridgewood Dr. Menomonee Falls, WI 53051 (262) 703-5800 Content Chapter One: Introduction to the Product 1. Product Characters

More information

Technical Manual. E-trek DM Series SHANDONG SACREDSUN POWER SOURCES CO.,LTD

Technical Manual. E-trek DM Series SHANDONG SACREDSUN POWER SOURCES CO.,LTD Technical Manual E-trek DM Series Version:V3.0 SHANDONG SACREDSUN POWER SOURCES CO.,LTD Security Instruction Please read these instructions carefully in order to make correct, safe, and effective operation.

More information

Pb battery. Chemical equation: Pb+2 H 2 SO 4. + PbO 2 <charge. 2 PbSO 4 +2 H 2. discharge>

Pb battery. Chemical equation: Pb+2 H 2 SO 4. + PbO 2 <charge. 2 PbSO 4 +2 H 2. discharge> Pb battery Chemical equation: discharge> Pb+2 H 2 SO 4 + PbO 2 state of charge can be determined

More information

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar Chapter 6 Batteries Types and Characteristics Functions and Features Specifications and Ratings 2012 Jim Dunlop Solar Overview Describing why batteries are used in PV systems. Identifying the basic components

More information

Valve Regulated Lead Acid Batteries

Valve Regulated Lead Acid Batteries Motors I Automation I Energy I Transmission & Distribution I Coatings Batteries - VRLA Valve Regulated Lead Acid Batteries User Manual User Manual Series: Sealed Batteries Language: English Document:

More information

VRLA Batteries. Battery Installation And Start up Guide

VRLA Batteries. Battery Installation And Start up Guide TECHNICAL MANUAL 41-7525 VRLA Batteries 26-206 Ampere-Hour Capacity Battery Installation And Start up Guide (For Rack Mounted Systems) 41-7525/0514/CD www.cdtechno.com Table of Contents 12V VRLA Battery

More information

VALVER REGULATED SEAL LEAD ACID BATTERY. MP Series OPERATION MANUAL. Version:V4.2. Narada Power Source Co., Ltd.

VALVER REGULATED SEAL LEAD ACID BATTERY. MP Series OPERATION MANUAL. Version:V4.2. Narada Power Source Co., Ltd. VALVER REGULATED SEAL LEAD ACID BATTERY MP Series OPERATION MANUAL Version:V4.2 Email: intl@narada.biz Narada Power Source Co., Ltd. Website: www.naradabattery.com Contents Security Instructions... 3 Chapter

More information

Features and Benefits

Features and Benefits C&D Tubular GEL (OPzV) Series For Standby & Cyclic Applications C&D Tubular GEL (OPzV) Series range of valve regulated lead acid stationary batteries combine the benefits of recombination technology (i.e.

More information

SBS T HE P OWER P LATE T HIN T ECHNOLOGY S PECIFIERS M ANUAL

SBS T HE P OWER P LATE T HIN T ECHNOLOGY S PECIFIERS M ANUAL TM SBS T HE P OWER OF T HIN P LATE T ECHNOLOGY S PECIFIERS M ANUAL CONTENTS Introduction 3 Specifications & Dimensions 4 Gas Recombination Mechanism 5 Battery Sizing 6-7 Service & Float Life 8-9 Energy

More information

Deep Cycle AGM Range VRLA

Deep Cycle AGM Range VRLA 01 DEEP CYCLE AGM RANGE 18Ah to 400Ah @ C20 SEALED MONOBLOC AGM BATTERIES The extremely powerful, compact AGM batteries of EverExceed Deep Cycle AGM Range are an ideal energy Source for durability in Photovoltaic,

More information

PowerSafe OPzV Operation Guide for Solar Applications

PowerSafe OPzV Operation Guide for Solar Applications Sustainable solutions PowerSafe OPzV Operation Guide for Solar Applications Operation Guide > PowerSafe OPzV < 2 Safety precautions Batteries give off explosive gasses. They are filled with dilute sulphuric

More information

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell UPS 12-1121 PURE LEAD PLUS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications 305-545 Watts per APPLICATIONS Data Centers Network Operations Centers Industrial Process Control

More information

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications EverExceed power your applications Maintenance free VRLA design Leak proof / Spill proof Gas recombination Absorbed electrolyte Float / Cycle use Low self-discharge rate Reliable one-way safety valve Lead

More information

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES EUROBAT, the Association of European Storage Battery Manufacturers, has 36 regular and associate member companies and represents more than 85 % of

More information

Valve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications FEATURES & BENEFITS

Valve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications FEATURES & BENEFITS 12-1079 HIGH RATE MAX UPS 12-355MRF APPLICATIONS Data Centers Network Operations Centers Industrial Process Control Facilities Internet Housing Sites Semiconductor Manufacturing Banks & Financial Markets

More information

FIAMM. stationary batteries J^^^^^^^IRP^ FIAMM

FIAMM. stationary batteries J^^^^^^^IRP^ FIAMM V FIAMM stationary batteries J^^^^^^^IRP^ FIAMM Progress runs fast, and its race is based on energy. Energy that is generated and used, not always at the same time. To supply it right when it is needed,

More information

Battery Storage Systems

Battery Storage Systems Battery Storage Systems Agenda System Components Applications How to Size Batteries System Components Basic battery theory Electro-chemical reaction Two dissimilar metals Positive electrodes Negative electrodes

More information

Small Traction powerbloc powerbloc dry

Small Traction powerbloc powerbloc dry Small Traction powerbloc powerbloc dry Bigger Power for small tracti powerbloc powerbloc dry Powerbloc and powerbloc dry are ranges of bloc batteries for all applications in small traction, from cleaning

More information

WORKSHOP MANUAL ELECTRICITY

WORKSHOP MANUAL ELECTRICITY WORKSHOP MANUAL ELECTRICITY GB reference : 754282 DC/ATR 04/2000 1. Electric units:...2 2. Key formulae to remember:...2 3. Definitions:...3 4. Elements:...4 Resistances:...4 Lights:...5 Condensers:...5

More information

V3.4. Vantage. Ultra-low maintenance batteries. Technical manual

V3.4. Vantage. Ultra-low maintenance batteries. Technical manual V3.4 Vantage Ultra-low maintenance batteries Technical manual Contents 1 Introduction 3 2 Benefits of the Vantage battery 4 3 Battery applications 5 4 Principles of the oxygen recombination cycle 6 5 Construction

More information

Operation Manual. For GTS-L Range Stationary VRLA Batteries

Operation Manual. For GTS-L Range Stationary VRLA Batteries Operation Manual For GTS-L Range Stationary VRLA Batteries CONTENT 1 Operation Principle 2 Construction and Technical Characteristics 3 Product Model and Specification 4 Discharge and Charge Curve 5 The

More information

VALVE REGULATED SEALED LEAD ACID BATTERY

VALVE REGULATED SEALED LEAD ACID BATTERY VALVE REGULATED SEALED LEAD ACID BATTERY (Front access design) OPERATION MANUAL Version 3.0 NARADA POWER SOURCE CO., LTD Email: intl@narada.biz Website: www.naradabattery.com Contents Important safety

More information

Stationary Batteries and Battery Management

Stationary Batteries and Battery Management Stationary Batteries and Battery Management Author can be written as under- Discharge cycle Pb+2H 2 SO 4 +PbO 2 Pbso 4 +2H 2 O+PbSO 4 Charge Cycle Pbso 4 +2H 2 O+PbSO 4 Pb+2H 2 SO 4 +PbO 2 Mr. Manish Naha

More information

SPA AGM VRLA batteries

SPA AGM VRLA batteries SPA AGM VRLA batteries for Stationary Applications SPA OVERVIEW Valve Regulated AGM batteries The SPA range of SUNLIGHT Valve Regulated Lead Acid batteries has been developed as general purpose batteries,

More information

PowerSafe OPzV Operation Guide for Solar Applications

PowerSafe OPzV Operation Guide for Solar Applications Sustainable solutions PowerSafe OPzV Operation Guide for Solar Applications Operation Guide > PowerSafe OPzV < 2 Safety precautions Batteries give off explosive gasses. They are filled with dilute sulphuric

More information

INSTALLATION GUIDE HEALTH AND SAFETY NOTICE FOR SEALED LEAD ACID BATTERIES

INSTALLATION GUIDE HEALTH AND SAFETY NOTICE FOR SEALED LEAD ACID BATTERIES EXIDE TECHNOLOGIES NETWORK POWER INSTALLATION GUIDE & HEALTH AND SAFETY NOTICE FOR SEALED LEAD ACID BATTERIES HEALTH AND SAFETY NOTICE FOR SEALED LEAD ACID BATTERY TYPES S300, S500, P300, P500, SP300,

More information

EcoSafe EOPzV. Operation Guide for Solar Applications

EcoSafe EOPzV. Operation Guide for Solar Applications EcoSafe EOPzV Operation Guide for Solar Applications 2 Ecosafe EOPzV Specific Abilities The specific abilities of this type of battery for renewable energy applications are as follows: Cycling (one cycle

More information

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell -11 PURE LEAD PLUS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications 305-545 Watts per Cell FEATURES & benefits APPLICATIONS Data Centers Network Operations Centers Industrial

More information

Duracell Battery Glossary

Duracell Battery Glossary Duracell Battery Glossary 1 Duracell Battery Glossary AB Absorption Alloy Ambient Humidity Ambient Temperature Ampere-Hour Capacity Anode Battery or Pack Bobbin C-Rate (also see Hourly Rate) Capacity Capacity

More information

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity...

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity... Table of Contents Features of Power-Sonic Sealed Lead Acid Batteries...1 Battery Construction...2 Theory of Operation...3 & 4 Battery Capacity...5 & 6 Battery Capacity Selector...7 Performance Data...8

More information

GLOSSARY: TECHNICAL BATTERY TERMS

GLOSSARY: TECHNICAL BATTERY TERMS GLOSSARY: TECHNICAL BATTERY TERMS AB5 Absorption Alloy Ambient Humidity Ambient Temperature Ampere-Hour Capacity Anode Battery or Pack Bobbin C-Rate (also see Hourly Rate) Capacity Capacity Retention (or

More information

Applications. EMC tested

Applications. EMC tested SOLAR Applications Photovoltaic power supply of: Power plants of remote villages Signal Installations of the air-, sea-, road and railway transport Radio relay stations of telecounication services Cellular

More information

[Charge] [Lead dioxide] [Lead] [Sulfuric acid] [Lead sulfate] [Lead sulfate] [Water]

[Charge] [Lead dioxide] [Lead] [Sulfuric acid] [Lead sulfate] [Lead sulfate] [Water] Sunstone VRLA Battery Family //SPT series - -Standard Series with 5 years design life //ML series - -High Tin alloy design with 10 years design life //MLG series - - 12V Gel Series with 15 years design

More information

Modular Max AGM Range VRLA

Modular Max AGM Range VRLA Innovative Features Valve Regulated Lead Acid (V.R.L.A.) design Fully tank formed plates Never needs addition of water Spill-proof and leak-proof Proprietary Fixed Orifice Plate Pasting technology applying

More information

Installation Manual. An Invensys company

Installation Manual. An Invensys company Installation Manual An Invensys company Contents 2 1 Scope and safety warnings 2 2 Cell identification 3 3 Unpacking 4 4 Storage 4 5 Installation instructions 4 6 Filling with acid 5 7 General battery

More information

Charging of HOPPECKE OPzV solar.power battery in Solar Applications

Charging of HOPPECKE OPzV solar.power battery in Solar Applications Charging of HOPPECKE OPzV solar.power battery in Solar Applications Preface: This document provides hints for charging of HOPPECKE OPzV solar.power battery cells and blocs in solar applications. Note:

More information

X600. Technical Sheet

X600. Technical Sheet X600 Technical Sheet 2 Inverter + Charge Controller + X600 1 Photovoltaic Modules Stand Alone Technical Sheet Electric Diagram 3 Technical Characteristics Contacts X600: Electric Diagram 1 2 3 Photovoltaic

More information

SEC. MICROLYTE +Plus. Industrial Battery Co. Supplied Worldwide by: Visit our website on Features. Application

SEC. MICROLYTE +Plus. Industrial Battery Co. Supplied Worldwide by: Visit our website on   Features. Application MICROLYTE +Plus Maintenance-Free Rechargeable Sealed Lead Acid Batteries 6 volt 1.3 Ah to 12 volt 25 Ah R MH2528 Features * Maintenance free * Leak proof / spill proof * Gas recombination * Absorbed electrolyte

More information

VGS. series (OPzV) GLOBAL OPzV Valve Regulated Sealed Industrial Battery

VGS. series (OPzV) GLOBAL OPzV Valve Regulated Sealed Industrial Battery VGS series (OPzV) GLOBAL OPzV Valve Regulated Sealed Industrial Battery Head Office Chang-Won Factory Industrial battery & Motive Power, EV(Electric Vehicle) - Capacity : 1.5 Million/year - Gross Area

More information

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX DATASAFE HX TOP TERMINATED BATTERIES DataSafe HX Top Terminated Batteries 6 and 12 Volt HX Available exclusively from EnerSys, the world leader in stored power solutions. DataSafe HX Top Terminated Batteries.

More information

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date:

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date: Application Manual and Product Information for NorthStar Battery Company Table of Contents Introduction...3 NSB Blue Series Benefits...4 ISO Certifications...5 NSB Blue Product Specifications...6 Leak

More information

Modular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications

Modular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications EverExceed power your applications Modular Max Range BATTERY SOLUTIONS NEBS qualified Reliable capacities CADMIUM FREE FULLY RECYCLABLE LEAD ACID BATTERIES CONFORMS TO THE EUROPEANE.C.1992 DIRECTIVE ON

More information

1. Production Features

1. Production Features 1. Production Features LEOCH Battery adopt unique plate grid alloy formula with a high corrosion resistance and the active material formula,while the use of advanced production technology and the special

More information

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries RS-2046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES.

More information

1. What is the principle of a brush less alternator? Explain with figure?

1. What is the principle of a brush less alternator? Explain with figure? 1. What is the principle of a brush less alternator? Explain with figure? 1. Stator 2. North pole 3. South Pole 4&5 Field coil 6. Armature Winding 7. Rotor The brushless alternator consists of 3 phase

More information

IEEE IAS Atlanta Chapter

IEEE IAS Atlanta Chapter Stationary Battery Sizing IEEE IAS Atlanta Chapter Presented by: Lesley Varga, P.E. Quality Standby Services, LLC 1649 Sands Place, SE, Suite C Marietta, GA 30067 (770) 916-1747 lesley@qualitystandbyservices.com

More information

12-Batteries and Inverters. ECEGR 452 Renewable Energy Systems

12-Batteries and Inverters. ECEGR 452 Renewable Energy Systems 12-Batteries and Inverters ECEGR 452 Renewable Energy Systems Overview Batteries Lead-Acid Batteries Battery Specifications Battery Charge Controllers Inverters Dr. Louie 2 Batteries Incorporation of a

More information

Operation manual for Ares (Tubular Gel) series VALVE REGULATED TUBULAR GEL BATTERY OPERATION MANUAL. Ares(OPzV) series OPERATION MANAUL. Version 3.

Operation manual for Ares (Tubular Gel) series VALVE REGULATED TUBULAR GEL BATTERY OPERATION MANUAL. Ares(OPzV) series OPERATION MANAUL. Version 3. Operation manual for Ares (Tubular Gel) series VALVE REGULATED TUBULAR GEL BATTERY Ares(OPzV) series OPERATION MANUAL OPERATION MANAUL Version 3.0 NARADA POWER SOURCE CO., LTD Email: intl@narada.biz Website:

More information

INTRODUCTION As illustrated in Figure 1, the discharge reactions of a lead acid battery yield lead sulfate at both the positive and negative plates.

INTRODUCTION As illustrated in Figure 1, the discharge reactions of a lead acid battery yield lead sulfate at both the positive and negative plates. Global Energy Innovations, Inc 2901 Tasman Drive, Suite 111 Santa Clara, California 95054 USA Tel: +1.415.354.5688 Fax: +1.415.354.5738 TECHNOLOGY BRIEF Dynapulse Systems Principles of Desulfation This

More information

Charge Voltage(V/cell) Set point (V) (V)

Charge Voltage(V/cell) Set point (V) (V) Temperature compensation is not necessary when the battery is charged at an ambient temperature of 5 (41 F) to 35 (95 F). At a temperature below 5 (41 F) or above 35 (95 F), however, temperature compensation

More information

Features of Power-Sonic Sealed Lead Acid Batteries Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity...

Features of Power-Sonic Sealed Lead Acid Batteries Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity... Table of Contents Features of Power-Sonic Sealed Lead Acid Batteries... 1 Battery Construction...2 Theory of Operation...3 & 4 Battery Capacity...5 & 6 Battery Capacity Selector...7 Performance Data...8

More information

XLR Energy Storage Module

XLR Energy Storage Module Technical Note 19 XLR Energy Storage Module XLR Energy Storage Module Safety The XLR 48 V module contains stored energy of 54 watt-hours and can discharge up to 97 amps if short circuited. Only personnel

More information

C&D Technologies, Inc. Dynasty Division 900 East Keefe Avenue Milwaukee, WI53212 Phone: Fax:

C&D Technologies, Inc. Dynasty Division 900 East Keefe Avenue Milwaukee, WI53212 Phone: Fax: , C&D Technologies, Inc. Dynasty Division 900 East Keefe Avenue Milwaukee, WI53212 Phone: 800-396-2789 Fax: 414-961-6506 Form 41-7525 (Rev.6100) Printed in U.S.A. Inter-tier, Inter-Unit Inter-row Cables,

More information

Technical data Smart chargers Hawker Lifeplus Powertech

Technical data Smart chargers Hawker Lifeplus Powertech Technical data Smart chargers Hawker Lifeplus Powertech 2 Lifeplus chargers Matching table of capacity and recharge time Recharge time in hours for a 80 % discharged battery, discharged battery at a electrolyte

More information

Sealed Rechargeable VRLA Batteries

Sealed Rechargeable VRLA Batteries Sealed Rechargeable VRLA Batteries poweronaustralia.com.au 2 435 AGM VRLA Batteries Engineered With Vision. Built With Care. The Power-Sonic Corporation has been a leading force since 197 in the supply

More information

PS-Series General Purpose Batteries

PS-Series General Purpose Batteries PS-Series General Purpose Batteries All PS Series batteries feature: Absorbent Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction allows safe operation in any

More information

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity...

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity... Table of Contents Features of Power-Sonic Sealed Lead Acid Batteries...1 Battery Construction...2 Theory of Operation...3 & 4 Battery Capacity...5 & 6 Battery Capacity Selector...7 Performance Data...8

More information

Maintaining the operating temperature of the battery at 20 C to 25 C will maximize its service life and efficiency.

Maintaining the operating temperature of the battery at 20 C to 25 C will maximize its service life and efficiency. 5.1.3 Reliability In most cases, the reliability of a VLA is better than VRLA cells given similar environments. VLA batteries are also more robust to environmental conditions such as temperature and ripple

More information

6 & 12 Volt Monobloc GEL Range

6 & 12 Volt Monobloc GEL Range 6 & 12 Volt Monobloc GEL Range Haze Battery Company Ltd Q The Haze HZY - GEL range covers Ah capacities from 7Ah to 230Ah (C10) with dimensions suitable for racking systems for maximum space utilisation.

More information

Polymer Gel Standby Battery (Front Access Design) OPERATION MANUAL

Polymer Gel Standby Battery (Front Access Design) OPERATION MANUAL Polymer Gel Standby Battery (Front Access Design) OPERATION MANUAL Version 3.2 NARADA POWER SOURCE CO., LTD Website: www.naradapower.com Operation manual V3.2 for AcmeG series Contents Important Safety

More information

Batteries. Eric Harris, Colin Hepton, Steven Hodgson, Martin Holland, Michael Hudson and Jonathan Ridyard. 14/11/2005

Batteries. Eric Harris, Colin Hepton, Steven Hodgson, Martin Holland, Michael Hudson and Jonathan Ridyard. 14/11/2005 Batteries Eric Harris, Colin Hepton, Steven Hodgson, Martin Holland, Michael Hudson and Jonathan Ridyard. 14/11/2005 A Brief History Alessandro Volta. Voltaic Pile. 1800s. Silver and Zinc Plates separated

More information

K50. Technical Sheet

K50. Technical Sheet K50 Technical Sheet 2 Inverter + Charge Controller + K50 1 Photovoltaic Modules Stand Alone Technical Sheet Electric Diagram 3 Technical Characteristics Contacts Battery Pack K50: Electric Diagram Inverter

More information

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1.

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1. -1029 Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications. APPLICATIONS Data Centers Network Operations Centers Industrial Process Control Facilities Internet Housing Sites Semiconductor

More information

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries RS02046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES.

More information

Central Battery Systems Loadstar AC/DC Systems

Central Battery Systems Loadstar AC/DC Systems The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources of emergency power for escape

More information

IEC APPROVAL TESTS

IEC APPROVAL TESTS IEC61427-1 APPROVAL TESTS Edition 1.0 : 2013-04 Secondary cells and batteries for renewable energy storage General requirements and methods of test Part 1 : Photovoltaic off-grid application Flooded lead-acid

More information

PERFORMANCE SPECIFICATIONS

PERFORMANCE SPECIFICATIONS PERFORMANCE SPECIFICATIONS Introducing the PowerSafe DDm Range The PowerSafe DDm range of valve regulated lead acid batteries further demonstrates EnerSys' commitment to supplying those high quality products

More information

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. ANNEXURE XI (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. Sr. No Technical Particulars Confirmation to be given by bidder (Please strike out which ever not applicable)

More information

CELLS AND BATTERIES Understand the general features of cells and batteries Describe the relationship between cells and batteries. Describe the basic

CELLS AND BATTERIES Understand the general features of cells and batteries Describe the relationship between cells and batteries. Describe the basic Cell & Batteries CELLS AND BATTERIES Understand the general features of cells and batteries Describe the relationship between cells and batteries. Describe the basic operation of a battery. Compare between

More information

FlexCharger Battery Chargers

FlexCharger Battery Chargers FlexCharger Battery Chargers Operating Instructions Definitions (as used in these instructions) Flooded Battery Lead-acid battery with liquid electrolyte that requires open-venting and regular water replacement.

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 1 Battery Fundamentals EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with various types of lead-acid batteries and their features. DISCUSSION OUTLINE The Discussion

More information

Stationary Batteries OPzS Cells

Stationary Batteries OPzS Cells General Features High Capacity Long Life Reduced Maintenance Low Self-Discharge Quick and Simple Acid Level Control Economical Water Consumption Low, Constant Maintenance Current MTI s Stationary OPzS

More information

NCPP. Nickel Cadmium Pocket Plate Batteries. Block Cell Dimensional and Electrical Data

NCPP. Nickel Cadmium Pocket Plate Batteries. Block Cell Dimensional and Electrical Data NCPP Nickel Cadmium Pocket Plate Batteries Block Cell Dimensional and Electrical Data Nickel Cadmium Pocket Plate Batteries HBL's Nickel Cadmium Pocket Plate Battery designs are based on the superior Pocket

More information