TRAINING BULLETIN APPARATUS P-2 January 22, 1998 FLOWMETERS

Size: px
Start display at page:

Download "TRAINING BULLETIN APPARATUS P-2 January 22, 1998 FLOWMETERS"

Transcription

1 TRAINING BULLETIN APPARATUS P-2 January 22, 1998 FLOWMETERS 1. INTRODUCTION 1.1 The intention of this bulletin is to describe the operation and calibration of the SPAN FLOWMINDER, the flowmeter presently in use. 1.2 Flowmeters provide added safety. With pressure gauges, pressure at the end of the line where firefighters need it, differs from pressure at the beginning of the line where it is measured. Pressure is reduced because of friction loss, head pressure, etc., and complicated formulas must be used to determine the water flow at the nozzle. Flowmeters measure flow in gallons per minute (GPM), which is the same at the beginning and the end of a hose line. As water is not compressible, what the display shows at the pumper is what the firefighters are receiving at the nozzle. This enables the motor pump operator to know the volume of water (in GPM) that is being delivered to the nozzle. 1.3 Flowmeters can be used with any type of nozzle to show the water flow. This is especially important with the Automatic Fog Tip (FT-2) to insure adequate water for fire extinguishment and firefighter safety. 1.4 These meters can also provide the total amount of water used with the totalizer feature. (Refer to Section 6). 2. EQUIPMENT AND SCHEDULE 2.1 Divisions will be issued a test kit consisting of a pitot gauge, a set of pitot nozzles, and a stream shaper for use during calibration. 2.2 Units shall calibrate their flowmeters semi-annually and/or when necessary to insure proper working order. 1

2 3. CALIBRATING THE FLOWMETER 3.1 Calibration is setting the electronics in a flowmeter to match the water flow in a pipe (as measured in psi by a pitot gauge). Flow is determined by the size of the pipe, the velocity in the pipe, and the size of the nozzle. 3.2 Zeroing sets the zero point with no flow. Calibrating sets a setpoint in the middle range of the flow. A low checkpoint and a high checkpoint are also used during calibration. 3.3 The Discharge Table For Water-Flow Test Kit-Style 9015 lists the suggested setpoints (in psi and GPM) for various pressures and pitot nozzles sizes. The following step-by-step instructions explain how to zero and calibrate the flowmeter. 4. ZEROING THE DISPLAY 4.1 Each time you calibrate a flowmeter, you should zero the display using the following procedure: Connect the pumper to a hydrant using an inlet on the side of the apparatus opposite the control panel Connect the stream shaper to the discharge gate to be tested Connect the test kit body swivel to the stream shaper and rotate the pitot blade out of stream position Open the By-Pass cooler on the pump panel, run a short 20 to 30 second spurt of water at full flow, and then shut the water off Remove the cover screw labeled S Push the SET bottom. If the display reads other than 0 while holding the SET button, insert a small screwdriver into the S hole to turn the potentiometer. If the display shows -0, or a negative number, turn clockwise until the minus sign barely turns off, leaving 0. Turn the potentiometer slowly; it takes a few seconds for the display to change and it is easy to turn it too far. If the display shows a positive number, turn the potentiometer counterclockwise until you see -0. Then slowly turn the potentiometer clockwise until the minus sign barely turns off, leaving 0.

3 January 22, 1998 T.B. APPARATUS P-2 FLOWMETERS If the flowmeter display can not be zeroed, notify The Division of Fleet Maintenance Reinstall the S cover screw, checking to be sure the O-ring is under the screw. The display is now set at zero. 5. PROCEDURE FOR CALIBRATING SPAN FLOWMETERS WITH A 2 1/2 INCH DISCHARGE USING THE AKRON WATER FLOW TEST KIT 5.1 TEST NUMBER SETPOINT # Install the 1 1/8 inch test barrel into the pitot test gauge assembly and secure the retaining lock nut Rotate pitot blade into center steam position and tighten thumbscrews Fully open the discharge gate that you are checking and obtain a reading of 50 psi on the pitot gauge by increasing or decreasing the fire pump panel throttle control (or closing the discharge gate if necessary). The flowmeters display should read 260 gpm. If it does not read 260 gpm go to Section Remove the cover screw labeled F on the flowmeters display. If the display reads a higher number, turn the set screw counterclockwise to obtain 260 gpm reading on the display gauge. If the display reads a lower number, turn the set screw clockwise to obtain 260 gpm reading on the display gauge When pumper must continue to operate (e.g. endurance test), rotate blade out of stream position to reduce wear and avoid damage. 5.2 TEST NUMBER SETPOINT # Install the 1 1/4 inch test barrel into the pitot test gauge assembly and secure the retaining lock nut Rotate pitot blade into center stream position and tighten thumbscrews Operate the Fire Pump in the normal safe manner. Fully open the discharge gate that you are checking and obtain a reading of 50 psi on the pitot gauge by increasing or decreasing the fire pump panel throttle control, the display should read 330 gpm. If it does not read 330 gpm go to Section

4 If the display reads a higher number, turn the setscrew counterclockwise to obtain 330 gpm reading on the display gauge. If the display reads a lower number, turn the set screw clockwise to obtain 330 gpm reading on the display gauge Reinstall the cover screw labeled F. NOTES: 1. As the flowmeter s last digit is designed to stay at 0, set GPM in ten digit increments such as 230, 240, 250, etc. 2. Decrease the number below the desired GPM then make small adjustments clockwise until you reach the desired reading. 3. Flowmeter readings should be within approximately 3% of maximum flow. Example: When the pitot shows 50 psi (l 1/8 inch tip), the flowmeter should read 260. It can read between 250 and 270 and be within the allowable range, which is 3% of the maximum flow. 4. If the flowmeter can not be calibrated for any reason (i.e.: display lights missing) or it becomes obvious the calibration will not hold, The Division of Fleet Maintenance should be notified. 6. TOTALIZER 6.1 The Totalizer feature allows you to check the total flow from each discharge at any time. To know how many total gallons of water have been pumped since the unit was cleared, do the following: Push and hold the TOTAL button located on the flowmeters front panel; a number is displayed Multiply the number by 100 for the total gallons of water pumped since the flowmeter was reset or turned on. For example, if 23 is shown, 2300 gallons have been pumped on that line. 6.2 Anytime the batteries are turned off the Totalizer automatically resets to zero.

5 January 22, 1998 T.B. APPARATUS P-2 FLOWMETERS SAFETY FIRST AND HELPFUL TIPS 1. When pumping always make certain that the maxi brake is on and you have chocked the rear wheels. 2. Cap all discharge gates that are not in use at the time of this test. 3. Make certain that you are in pumps and the green O.K. to pump light is on. 4. Never operate the fire pump without flowing water (open a drain valve). 5. Extreme caution must be used when calibrating flowmeters while the stream of water is flowing. 6. When adjusting the setscrew on the flowmeter, make slow 1/8 turns and pause to check the display reading. Potentiometers are located beneath the cover screws marked S and F. After using the potentiometers for calibrating, make certain the cover screws and O-rings are in place to keep water out of the interior. 5

6

Essentials of Fire Fighting

Essentials of Fire Fighting Essentials of Fire Fighting 6 th Edition Certified Volunteer Firefighter Chapter 16 Fire Streams Learning Objectives Explain the way vaporization and steam relate to the extinguishing properties of water.

More information

AKRON NEW YORKER MULTIVERSAL NOZZLE

AKRON NEW YORKER MULTIVERSAL NOZZLE TRAINING BULLETIN TOOLS 17 June, 1983 1. INTRODUCTION 1.1 This training bulletin is issued to govern the operation, use, and maintenance of the Akron New Yorker Multiversal Nozzle. 1.2 Information contained

More information

REAR MOUNT AERIAL LADDER USED AS A WATER TOWER

REAR MOUNT AERIAL LADDER USED AS A WATER TOWER EVOLUTION 21A January 1, 1997 REAR MOUNT AERIAL LADDER USED AS A WATER TOWER 1. EQUIPMENT: 2. COMMAND: 1 Rear Mount Aerial Ladder 1 Portable Ladder Pipe (Note B) 1 Halyard and Reel (Note C) 1 Siamese 3"

More information

DATE Updated November 30, 2007

DATE Updated November 30, 2007 DATE Updated November 30, 7 PURPOSE: To insure all Fire Apparatus pumps are tested annually and after extensive repair in compliance with NFPA Standard 1901 and the Insurance Service Office (ISO). BACKGROUND:

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 10 Apparatus Service Tests Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 10 Apparatus Service Tests Revised DRIVER OPERATOR Page 1 of 10 APPARATUS SERVICE TESTING Pump Testing Pumps test are generally classified into two types based on when they are performed. The first is the Acceptance Test. The Acceptance

More information

ZTM AND ZTMB ZENNER TURBINE METERS INSTALLATION, MAINTENANCE AND SERVICING

ZTM AND ZTMB ZENNER TURBINE METERS INSTALLATION, MAINTENANCE AND SERVICING ZTM AND ZTMB ZENNER TURBINE METERS INSTALLATION, MAINTENANCE AND SERVICING INSTALLATION 1. The meter is intended for measuring potable, cold water in one direction. 2. The meter is to be installed in a

More information

Head to Head Demo Comparison Sheet

Head to Head Demo Comparison Sheet Head to Head Demo Comparison Sheet Task Force Tips Handline Full Range Automatic Nozzle The purpose of this document is to encourage you to compare models head to head, apples to apples, with like models

More information

Head to Head Demo Comparison Sheet

Head to Head Demo Comparison Sheet Head to Head Demo Comparison Sheet Task Force Tips Quadrafog and Thunderfog Selectable Gallonage Nozzle The purpose of this document is to encourage you to compare TFT products head to head, apples to

More information

STYLE 3463 FireFox. With Position Feedback Potentiometer

STYLE 3463 FireFox. With Position Feedback Potentiometer STYLE 3463 FireFox INSTALLATION, OPERATING and MAINTENANCE INSTRUCTIONS With Position Feedback Potentiometer The following is intended to provide the basic instructions for installation, operating and

More information

( Versions Available)

( Versions Available) STYLE 494 ELECTRIC LADDER PIPE INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS ( Versions Available) The following is intended to provide the basic instructions for installation, operating and maintenance

More information

Main Fire Pump Engagement. Shifting Into Pump 2006 / 2007 KME

Main Fire Pump Engagement. Shifting Into Pump 2006 / 2007 KME Main Fire Pump Engagement Shifting Into Pump 2006 / 2007 KME 1 Battery Switch Ensure battery switch is turned on to BOTH. 2 Ensure Maxi (Parking) Brake Set Maxi (Parking) Brake must be set or the Pump

More information

ESCONDIDO FIRE DEPARTMENT TRAINING MANUAL DRIVER OPERATOR PUMPING PAGE 1 OF 6 Nozzles & Hose Revised

ESCONDIDO FIRE DEPARTMENT TRAINING MANUAL DRIVER OPERATOR PUMPING PAGE 1 OF 6 Nozzles & Hose Revised PUMPING 06-30-17 PAGE 1 OF 6 TFT Task Force Tip Combination Nozzles There are two sizes of hand line nozzles, 1 ½ and 2 ½. Our 1 ½ nozzles are Task Force Tip (TFT) combination nozzles. They are primarily

More information

To establish a standardized procedure for Class B foam application by engine companies.

To establish a standardized procedure for Class B foam application by engine companies. PURPOSE: DATE Reviewed June 27, 2013 SARASOTA COUNTY GOVERNMENT EMERGENCY SERVICES DIRECTIVE VOLUME #2 FIRE OPERATIONS NUMBER #223 CATEGORY RECOMMENDED OPERATING GUIDELINE SUBJECT Class B FOAM EQUIPMENT

More information

June Drill of the Month Instructor Guide. Topic: Review of Hydraulics and Pump Components

June Drill of the Month Instructor Guide. Topic: Review of Hydraulics and Pump Components Course: Pumps Refresher Course Session Reference: 1 June Drill of the Month Instructor Guide Topic: Review of Hydraulics and Pump Components Level of Instruction: Time Required: 3 hours Materials: Chalkboard

More information

Pump Acceptance Test Data

Pump Acceptance Test Data Customer Location: 500 Base Ave East Venice, Fl. 34275 941-485-5402 941-483-3321 Fax Pump Acceptance Test Data Division: Customer Number: Date: City & State Work Order: Technician: PUMP IF VERTICAL TYPE

More information

STYLE 3462 FORESTRY BUMPER MONITOR INSTALLATION, OPERATING and MAINTENANCE INSTRUCTIONS

STYLE 3462 FORESTRY BUMPER MONITOR INSTALLATION, OPERATING and MAINTENANCE INSTRUCTIONS STYLE 3462 FORESTRY BUMPER MONITOR INSTALLATION, OPERATING and MAINTENANCE INSTRUCTIONS The following is intended to provide the basic instructions for installation, operating and maintenance of the 3462

More information

Hose & Apparatus Test Equipment

Hose & Apparatus Test Equipment Hose & Apparatus Test Equipment Akron Brass Company PH. 800.228.1161 (330.264.5678) FAX 800.531.7335 (330.264.2944) www.akronbrass.com The Hose Tester HT-15-C A fast, easy, safe way to test fire hose.

More information

Chapter Quiz. Directions: Write the correct letter on the blank before each question.

Chapter Quiz. Directions: Write the correct letter on the blank before each question. Chapter 12 Quiz Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe dry-barrel and wet-barrel hydrants. 1. Most fire hydrants are made of: (605) A.

More information

32 quarts Transmission Allison HT 740 Automatic Fluid

32 quarts Transmission Allison HT 740 Automatic Fluid BOOK: Blue Book I SECTION: E-One Engine (SGT) Page 1 of 6 E-ONE CYCLONE TABLE OF CONTENTS SPECIFICATIONS... 2 DAILY CHECKS... 2 SAFETY CHECKS... 3 START ENGINE... 3 STOP ENGINE... 3 EMERGENCY SHUTDOWN

More information

Draft Commander 3000 Mobile Fire Pump Testing & Training Specifications Municipal/County/Rural/Commercial/Industrial

Draft Commander 3000 Mobile Fire Pump Testing & Training Specifications Municipal/County/Rural/Commercial/Industrial Draft Commander 3000 Mobile Fire Pump Testing & Training Specifications Municipal/County/Rural/Commercial/Industrial MODEL NUMBER DC1911-3000 AT/AL/MC Draft Commander 3000 Specifications MODEL NUMBER DC1911-3000

More information

Pump Service Testing

Pump Service Testing Pump Service Testing SCOPE This guideline shall apply to all members of the Stoney Point Fire Department (SPFD) and shall be adhered to by all members responsible for conducting pump service testing. PURPOSE

More information

Display Installation. page 1 of 9 pages. Engineering Standards. Engineering Standard Number C A. Name Identifier

Display Installation. page 1 of 9 pages. Engineering Standards. Engineering Standard Number C A. Name Identifier Installation and Calibration Information Display Installation The flowmeter display mounts in a 2.84 by 1.51 cutout. Overall area necessary for installation is 2.5 by 3.2. Two 0.201 diameter holes are

More information

S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions

S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions Table of Contents Read through the safety information and operating instructions carefully before using your S200-P Series Fire

More information

AVK SAUDI VALVES MANUFACTURING COMPANY

AVK SAUDI VALVES MANUFACTURING COMPANY AVK SAUDI VALVES MANUFACTURING COMPANY AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS EXPLODED ASSEMBLY / PARTS LIST INTRODUCTION / DESCRIPTION

More information

ATP-2040 Electric Damper Actuator/Transmitter

ATP-2040 Electric Damper Actuator/Transmitter ATP-2040 Electric Damper Actuator/Transmitter Kit Includes 1. Actuator/Transmitter package: factory assembled Actuator (EDA-2040) and Transmitter (DPT-2000). Product Code Number Coupler Size Differential

More information

A Methane Sample-Draw Detector Operator s Manual

A Methane Sample-Draw Detector Operator s Manual 35-3001A-01-01 Methane Sample-Draw Detector Operator s Manual Part Number: 71-0310RK Revision: A Released: 8/7/17 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

Ford Meter Box Test Bench Installation Instructions

Ford Meter Box Test Bench Installation Instructions DQS Inc. 12/12/18 THE FORD METER BOX COMPANY, INC. CERTIFIED TO ISO 9001:2015 10004466 Ford Meter Box Test Bench Installation Instructions Table of Contents Installation Instructions for Standard, Akron

More information

AMERICAN AVK COMPANY AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS

AMERICAN AVK COMPANY AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS AMERICAN AVK COMPANY AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS EXPLODED ASSEMBLY / PARTS LIST INTRODUCTION / DESCRIPTION RECEIVING AND

More information

Test Stand Preparation Data Collection

Test Stand Preparation Data Collection General Description Objective ability Stand Description ability Procedures Water Calibration Check Stand Preparation Data Collection Retardant Retardant Mixing Stand Preparation Data Collection Clean-Up

More information

PORTABLE FLOWTESTER MODELS: FTA400 GPM, FTA410 LPM

PORTABLE FLOWTESTER MODELS: FTA400 GPM, FTA410 LPM Document Number: XE-FTA4PM-R0A FTA400 Rev180131 PORTABLE FLOWTESTER MODELS: FTA400 GPM, FTA410 LPM FIRE RESEARCH CORPORATION www.fireresearch.com 26 Southern Blvd., Nesconset, NY 11767 TEL 631.724.8888

More information

TRAINING BULLETIN TOOLS 7 December, 1978 HOSE NOZZLES (HAND HELD) 1. NOZZLE NOMENCLATURE AND IDENTIFICATION

TRAINING BULLETIN TOOLS 7 December, 1978 HOSE NOZZLES (HAND HELD) 1. NOZZLE NOMENCLATURE AND IDENTIFICATION TRAINING BULLETIN TOOLS 7 December, 1978 1. NOZZLE NOMENCLATURE AND IDENTIFICATION 1.1 A nozzle identification and nomenclature system is established to insure that issuance and recall of equipment as

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of Sutphen Aerial Operations Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of Sutphen Aerial Operations Revised DRIVER OPERATOR Page 1 of 10 1997 Sutphen Aerial Operations Revised 12-11-17 PROCEDURES FOR ELEVATING THE PLATFORM Placing the aerial platform into service requires qualified personnel trained in the proper

More information

Darley UHP-HV Diesel Specification 1

Darley UHP-HV Diesel Specification 1 Darley UHP-HV Diesel Specification 1 This dual pump is designed for either a powerhead type unit or a full module. The module provides a self-contained diesel powered slide-in type ultra high pressure

More information

GENERAL FEATURES / SPEC M&H AWWA C502 FIRE HYDRANTS Style 929 Traffic Model 250 PSI Working Pressure 500 PSI Hydrostatic Test AWWA UL / FM Approval Type: Compression type, opening against line pressure.

More information

Maximum Flow: 600 GPM (3800 LPM) Portable Base 1250 GPM (4800 LPM) Direct Mount. Maximum Pressure: 200 PSI (1380 Kpa, 13.8 BARS)

Maximum Flow: 600 GPM (3800 LPM) Portable Base 1250 GPM (4800 LPM) Direct Mount. Maximum Pressure: 200 PSI (1380 Kpa, 13.8 BARS) STYLE 3414 Apollo S.I. Monitor with FoldING Legs OPERATING & MAINTENANCE INSTRUCTIONS WITH SPECIAL L.A. COUNTY SPECIFICATIONS The Akron Style 3414 Apollo Monitor is designed to provide efficient trouble-free

More information

AccuMax 3060 Multi-Point Detailed Specifications

AccuMax 3060 Multi-Point Detailed Specifications AccuMax 3060 Multi-Point Detailed Specifications A FoamPro AccuMax, part number S111-3060A electronic/hydraulic foam proportioning system shall be provided. The system shall be demand based, fully automatic

More information

High Accuracy Mechanical Fuel meter FM-100

High Accuracy Mechanical Fuel meter FM-100 INSTRUCTION MANUAL S190, Rev A High Accuracy Mechanical Fuel meter FM-100 Congratulations on purchase of this World Class High Accuracy Mechanical Fuel Meter! Worldclass Mechanical Fuel Meter, extremely

More information

Troubleshooting Guide

Troubleshooting Guide Troubleshooting Guide diesel - gasoline - LPG diesel - gasoline - LPG diesel - gasoline - LPG P/N 0191681 May, 1999 An ISO 9001 Registered Company P.O. Box 1160 St. Joseph, MO 64502-1160 1-800-255-0317

More information

Trailer Sprayer Owner s Manual

Trailer Sprayer Owner s Manual Trailer Sprayer Owner s Manual Models: T4052B, T40D53B, T40D52BL 1910 Lookout Drive North Mankato, MN 56003 2011 Model Year 40 GALLON 12-VOLT TRAILER SPRAYER OWNER S MANUAL OPERATION: 1. Partially fill

More information

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B2000 M-D 1 HIGH PRESSURE FIRE FIGHTING SPECIFICATIONS Scope and General Design Requirements A fire fighting system shall

More information

Check the following fluid levels daily or prior to starting unit:

Check the following fluid levels daily or prior to starting unit: PNEUMAX MODEL 60-GM OPERATING INSTRUCTIONS Check the following fluid levels daily or prior to starting unit: Engine oil Compressor system oil (oil level should be visible within the pump panel mounted

More information

oubleshooting Guide diesel - gasoline - LPG electric P.O. Box 1160 St. Joseph, MO Fax:

oubleshooting Guide diesel - gasoline - LPG electric P.O. Box 1160 St. Joseph, MO Fax: Troub oubleshooting Guide diesel - gasoline - LPG electric P/N 0162737 October 2005 P.O. Box 1160 St. Joseph, MO 64502-1160 1-800-255-0317 Fax: 785-989-3075 www.snorkelusa.com GENERAL INFORMATION This

More information

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER FH Series The FH-series line of fire hose testers, offers testing pressures up to 1,000 PSI, with flow rates up to 10 GPM. Gas, Electric, and Diesel driven models, designed to safely test fire hose up

More information

Troubleshooting Guide

Troubleshooting Guide Troubleshooting Guide diesel - gasoline - LPG P/N 0172021 June 1999 P.O. Box 1160 St. Joseph, MO 64502-1160 1-800-255-0317 Fax: 816-360-9379 www.snorkelusa.com GENERAL INFORMATION This manual contains

More information

Product Ratings Electrical Specifications

Product Ratings Electrical Specifications STYLE 3440 DECKMASTER ELECTRIC MONITOR FOR STANDARD CONFIGURATION WITH POTENTIOMETERS & U2 LOGIC BOX INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS The following is intended to provide the basic

More information

BASIC FOAM FIREFIGHTING OPERATIONS Red and Green Systems

BASIC FOAM FIREFIGHTING OPERATIONS Red and Green Systems BASIC FOAM FIREFIGHTING OPERATIONS Red and Green Systems Page 730.60 Each of the Red and Green Foam Systems consists of one 3000 gallon foam concentrate storage tank, two foam concentrate pumps, a balanced

More information

of Fire Pump Assemblies

of Fire Pump Assemblies A.1.0 A.1.1 A.2.0 A.2.1 A.2.2 A.2.3 A.2.4 A.2.5 A.2.6 A.3.0 A.3.1 A.4.0 A.4.1 Report of Inspection, Testing & Maintenance System in service before conducting tasks Pertinent parties notified before conducting

More information

MODEL GS. Check the following fluid levels daily or prior to starting unit:

MODEL GS. Check the following fluid levels daily or prior to starting unit: PNEUMAX MODEL 90-45-GS OPERATING INSTRUCTIONS Check the following fluid levels daily or prior to starting unit: Engine oil Compressor system oil (oil level should be visible within the sump mounted sight

More information

Other significant updates include:

Other significant updates include: THE NEW N.F.P.A. 1962 The NFPA recently revised its standard on fire hose. The newest edition requires that hose manufactured before July 1987 be removed from service. This makes sense given all the changes

More information

8296 Portable Monitor Operating & Maintenance Instructions

8296 Portable Monitor Operating & Maintenance Instructions 8296 Portable Monitor Operating & Maintenance Instructions PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM MAILING: P.O. BOX 1127 ELKHART, IN 46515 1-574-295-8330 1-800-346-0250

More information

Dethatcher Kit Greensmaster 3000 Series

Dethatcher Kit Greensmaster 3000 Series Form No. 338 944 Dethatcher Kit Greensmaster 3000 Series Model No. 04493 Serial No. 3000000 and Up Operator s Manual English (EN) Contents Page Specifications............................... General Specifications.....................

More information

FIXED DEPTH INSERTION METER INSTRUCTIONS

FIXED DEPTH INSERTION METER INSTRUCTIONS UNPACKING Please open and inspect your package upon receipt. Your package was packed with great care and all the necessary packing materials to arrive to you undamaged. If you do find an item that is broken

More information

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER FH Series The FH-series line of fire hose testers, offers testing pressures up to 1,000 PSI, with flow rates up to 10 GPM. Gas, Electric, and Diesel driven models, designed to safely test fire hose up

More information

INSTALLATION/OPERATION/MAINTENANCE INSTRUCTIONS FOR ARCHON MODELS WD2010L, WD2010, WD2010H WASHDOWN STATIONS. ARCHON Industries, Inc.

INSTALLATION/OPERATION/MAINTENANCE INSTRUCTIONS FOR ARCHON MODELS WD2010L, WD2010, WD2010H WASHDOWN STATIONS. ARCHON Industries, Inc. ARCHON Industries, Inc. Washdown Stations Models WD2010L, WD2010, WD2010H Installation / Operation / Maintenance Instructions 1 This manual has been prepared as an aid and guide for personnel involved

More information

Troubleshooting Guide

Troubleshooting Guide Troubleshooting Guide P/N 0153180 July 1999 P.O. Box 1160 St. Joseph, MO 64502-1160 1-800-255-0317 Fax: 816-360-9379 www.snorkelusa.com GENERAL INFORMATION This manual contains procedures for locating

More information

ALLSTAR DILUTION CONTROL SYSTEM MODEL 639AG-4-1ABC

ALLSTAR DILUTION CONTROL SYSTEM MODEL 639AG-4-1ABC MODEL 639AG-4-1ABC 1. PARTS: A. Blend Center assembly B. 5 pc. 1/4 ID x 8 ft. long vinyl supply tubing, with foot valve & ceramic weight C. 1 pc. 1/2 ID x 6 ft. long vinyl outlet tubing D. 2 pc. #8 pan

More information

KEES, INC. BALANCING MANUAL

KEES, INC. BALANCING MANUAL KEES, INC. Products for Sheet Metal HVAC, Food Service, & Architectural Construction Industries 400 S. INDUSTRIAL DRIVE ELKHART LAKE, WISCONSIN 53020 920 876-3391 FAX 920 876-3065 FORWARD: BALANCING MANUAL

More information

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation.

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation. Industrial Turbo Meters Sizes 2" through 6" Installation & Operation Manual IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation. BadgerMeter,Inc. IOM-003-15 Part No.

More information

VALVES, FIRE HYDRANTS, AND APPURTENANCES

VALVES, FIRE HYDRANTS, AND APPURTENANCES VALVES, FIRE HYDRANTS, AND APPURTENANCES PART 1 - GENERAL 1.01 SECTION INCLUDES A. Butterfly Valves B. Gate Valves C. Tapping Valve Assemblies D. Fire Hydrant Assemblies E. Flushing Devices (Blowoffs)

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of Sutphen Aerial Operations Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of Sutphen Aerial Operations Revised DRIVER OPERATOR Page 1 of 12 2014 Sutphen Aerial Operations Revised 12-11-17 PROCEDURES FOR ELEVATING THE PLATFORM Placing the aerial platform into service requires qualified personnel trained in the proper

More information

1 MECHANICAL FUEL METER

1 MECHANICAL FUEL METER 1 MECHANICAL FUEL METER USER S MANUAL WARNING: Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions may result in serious

More information

TABLE OF CONTENTS. 3 Outlet Stainless Steel Body. 3 Outlet Ductile Body. 2 Outlet Ductile Body 2 Outlet Bronze Body

TABLE OF CONTENTS. 3 Outlet Stainless Steel Body. 3 Outlet Ductile Body. 2 Outlet Ductile Body 2 Outlet Bronze Body AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS EXPLODED ASSEMBLY / PARTS LIST INTRODUCTION / DESCRIPTION RECEIVING AND STORAGE INSTALLATION

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

Cummins 6.7 Litre 2500/3500 Diesel EGR System. Always wear gloves and safety glasses when performing this service

Cummins 6.7 Litre 2500/3500 Diesel EGR System. Always wear gloves and safety glasses when performing this service Cummins 6.7 Litre 2500/3500 Diesel EGR System Always wear gloves and safety glasses when performing this service EGR System Consists of: Cold side EGR valve (after EGR cooler) controls exhaust gases for

More information

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER FH Series The FH-series line of fire hose testers, offers testing pressures up to 1,000 PSI, with flow rates up to 10 GPM. Gas, Electric, and Diesel driven models, designed to safely test fire hose up

More information

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve Technical Bulletin TB-ACV-LFF11RFP LEAD FREE * LFF11RFP Flood Protection Shut Down Valve Installed upstream of Reduced Zone Backflow Preventer. Normally Open Valve - Closes when continuous discharge from

More information

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE PIERCING AND FIRE FIGHTING SYSTEM L 1000 W-D

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE PIERCING AND FIRE FIGHTING SYSTEM L 1000 W-D SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE PIERCING AND FIRE FIGHTING SYSTEM L 1000 W-D 1 SPECIFICATIONS FOR FIRE FIGHTING SYSTEM FIRE FIGHTING AND PIERCING SPECIFICATIONS Scope and General

More information

Driver/Operator Program Part III - Tanker

Driver/Operator Program Part III - Tanker Driver/Operator Program Part III - Tanker Overview The Driver/Operator Preparation Program Part II is designed to standardize the training and release of driver/operators within the company; the intent

More information

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING CONTROL VALVE PRESSURE REDUCING CONTROL VALVE 06/08 Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Reducing setpoint is adjustable 2 (AOS) X P/L Standard Components 1 Main

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST

More information

TFT HAND HELD AUTOMATIC PRESSURE CONTROL NOZZLES

TFT HAND HELD AUTOMATIC PRESSURE CONTROL NOZZLES ULTIMATIC, INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE TFT HAND HELD AUTOMATIC PRESSURE CONTROL NOZZLES MID-MATIC & HANDLINE Read instruction manual before use. Operation of this nozzle without understanding

More information

FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions FAIRCHILD T5420 DIGITAL-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions Figure 1. T5420 Outline Dimensions. INSTALLATION The Model T5420 can be mounted directly onto a flat surface

More information

Instructions for Installation, Operation Care and Maintenance

Instructions for Installation, Operation Care and Maintenance Model A Dry Pipe Valve Bulletin 353 Rev.K Bulletin 353 Rev.K Instructions for Installation, Operation Care and Maintenance 2 1 2 (65mm) Valve With Model A Trim Listed by Underwriters Laboratories, Inc.

More information

STYLE 3491 Severe Duty Electric Mining Water Cannon INSTALLATION, AND OPERATING INSTRUCTIONS

STYLE 3491 Severe Duty Electric Mining Water Cannon INSTALLATION, AND OPERATING INSTRUCTIONS STYLE 349 Severe Duty Electric Mining Water Cannon INSTALLATION, AND OPERATING INSTRUCTIONS Australian Only The following is intended to provide the basic instructions for installation, operating and maintenance

More information

3. Fuel System FUEL SYSTEM FUEL INJECTION (FUEL SYSTEM) A: GENERAL. FU(STi)-7

3. Fuel System FUEL SYSTEM FUEL INJECTION (FUEL SYSTEM) A: GENERAL. FU(STi)-7 W1860BE.book Page 7 Tuesday, January 28, 2003 11:01 PM 3. Fuel System A: GENERAL The fuel pressurized by the fuel tank inside pump is delivered to each fuel injector by way of the fuel pipe and fuel filter.

More information

INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES

INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES SYSTEM CONCEPT When not transferring fuel, the pressure in the underground closed piping system of a gasoline station may fall due

More information

1½ Diameter Aluminum Pipe. Standard 2 1/2 shut-off with 1 1/8 MST T-handle allows members control of the nozzle.

1½ Diameter Aluminum Pipe. Standard 2 1/2 shut-off with 1 1/8 MST T-handle allows members control of the nozzle. T.B. TOOLS 7 DATA SHEET 17 1. DESCRIPTION FDNY Designation Material Weight Misc. High Rise Nozzle 1½ Diameter Aluminum Pipe Approx 10 lbs Standard 2 1/2 shut-off with 1 1/8 MST T-handle allows members

More information

LNW-5. Installation... 2 Lift Truck Conditions Indicator Installation Hose Installation

LNW-5. Installation... 2 Lift Truck Conditions Indicator Installation Hose Installation Table Of Contents Important Notice... ii Caution... iii DC Power Filters... iv Introduction & Description... 1 Principle of Operation Pressure Transducer Digital Indication Housing Power Requirements Installation...

More information

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING VALVE with LOW-FLOW BY-PASS FEATURE Main Line valve

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-3 Venturi Tubes EXERCISE OBJECTIVE In this exercise, you will study the relationship between the flow rate and the pressure drop produced by a venturi tube. You will describe the behavior of

More information

ENGINE TUNE-UP INSPECTION OF ENGINE COOLANT INSPECTION OF ENGINE OIL INSPECTION OF BATTERY. INSPECTION OF AIR FILTER (Paper Filter Type)

ENGINE TUNE-UP INSPECTION OF ENGINE COOLANT INSPECTION OF ENGINE OIL INSPECTION OF BATTERY. INSPECTION OF AIR FILTER (Paper Filter Type) ENGINE MECHANICAL - Engine Tune-Up EM-17 ENGINE TUNE-UP INSPECTION OF ENGINE COOLANT (See steps 1 and 2 on page CO-4) INSPECTION OF ENGINE OIL (See steps 1 and 2 on page LU-5) INSPECTION OF BATTERY (See

More information

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING VALVE with LOW-FLOW BY-PASS FEATURE Main Line valve

More information

NSGV EVE-ER I, O, & M MANUAL

NSGV EVE-ER I, O, & M MANUAL TABLE OF CONTENTS Rail Layout.. Page 1 Support Placement...Page 1 Rail Assembly.Page 1 Rail Duct Connections.. Page 2 Rubber Lip Installation.. Page 3 Pneumatic End Stop. Page 4 End Stop. Page 4 End Cap..

More information

HL Series Centrifugal Fire Pumps Operation and Maintenance Instructions

HL Series Centrifugal Fire Pumps Operation and Maintenance Instructions HL Series Centrifugal Fire Pumps Operation and Maintenance Instructions Table of Contents Read through the safety information and operating instructions carefully before using your Waterous HL Series Fire

More information

Operation and Maintenance Manual

Operation and Maintenance Manual BM / BMA Hydrometers ½ Operation and Maintenance Manual i This manual is intended for use by the users of this equipment. The information contained herein is the property of the Arad Ltd. Dalia and may

More information

534HS Pressure Transmitter

534HS Pressure Transmitter These instructions provide information for installation, process connection, electrical connection and field calibration of SOR 534HS Pressure Transmitters. The 534HS Pressure Transmitter consists of a

More information

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Closes quickly when downstream pressure exceeds reduced pressure setpoint 3 PRESSURE REDUCING VALVE with SURGE

More information

STYLE 5148 MERCURYMASTER OSCILLATING NOZZLE INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS

STYLE 5148 MERCURYMASTER OSCILLATING NOZZLE INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS STYLE 5148 MERCURYMASTER OSCILLATING NOZZLE INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS The following is intended to provide the basic instructions for installation, operation, and maintenance.

More information

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST Date Documents Submitted: Log No.: File No.: Plan Examiner: Permit No.: Property Information Building Name: Building Address: Building Manager's Name: Building Manager's Phone: Fax: System Designer/Contractor

More information

BIG SPRING FIRE DEPARTMENT STANDARD OPERATING PROCEDURES SOG 417: LADDER TRUCK OPERATIONS SOP: 417. Ladder Truck Operations.

BIG SPRING FIRE DEPARTMENT STANDARD OPERATING PROCEDURES SOG 417: LADDER TRUCK OPERATIONS SOP: 417. Ladder Truck Operations. BIG SPRING FIRE DEPARTMENT STANDARD OPERATING PROCEDURES SOG 417: LADDER TRUCK OPERATIONS SOP: 417 Ladder Truck Operations Table of Contents 1. Purpose... 1 2. Safety... 1 3. Normal Operation... 2 1. Purpose

More information

PLEASE READ THESE INSTRUCTIONS THOROUGHLY BEFORE BEGINNING INSTALLATION. Part No. A7SOCA700

PLEASE READ THESE INSTRUCTIONS THOROUGHLY BEFORE BEGINNING INSTALLATION. Part No. A7SOCA700 SPIN-ON High Pressure Fuel Air Separator INSTALLATION MANUAL For Engines with 136-5017 Filter Head PLEASE READ THESE INSTRUCTIONS THOROUGHLY BEFORE BEGINNING INSTALLATION Part No. A7SOCA700 Revised 8/17/17

More information

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited. SERVICE MANUAL ELECTRIC BRAISING PANS (30 & 40 GALLON) VE30 VE40 ML-126849 ML-126850 VE40 SHOWN - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 13 Pumps and Accessory Equipment Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 13 Pumps and Accessory Equipment Revised DRIVER OPERATOR Page 1 of 13 PUMPS AND ACCESSORY EQUIPMENT Pumps are designed for many different purposes. In order to understand the proper application and operation of a pump in a given situation, firefighters

More information

Portable CAFSystem. Operating Instructions

Portable CAFSystem. Operating Instructions Portable CAFSystem Operating Instructions Applies to the Pneumax model 70-35-E Unit Serial Number Pneumax, Inc. 8557 North 78th Ave. Peoria, Arizona 85345 623-979-3398 Fax: 623-979-6949 www.pneumaxcafs.com

More information

Driver/Operator - Mobile Water Supply

Driver/Operator - Mobile Water Supply CDC 10028W Driver/Operator - Mobile Water Supply Performance Test Extension Course Program (A4L) Air University Air Education and Training Command Acknowledgement Preparation of this volume was aided through

More information

Installation Instructions

Installation Instructions Instructions Aerada 900 Series Futura Faucet With Battery (BIR) Infrared Control S53-284 4" Centerset/Centershank S53-289 Centerset/Centershank w/plate Table of Contents Pre- Information............2 900

More information

CUMMINS N-14 Pump Mount to Frame Filter Conversion

CUMMINS N-14 Pump Mount to Frame Filter Conversion CUMMINS N-14 Pump Mount to Frame Filter Conversion For Trucks Equipped with Cummins N-14 Engines Kit No. 905-02-0200-H PLEASE READ THESE INSTRUCTIONS THOROUGHLY BEFORE BEGINNING INSTALLATION Providing

More information

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER

The EL-FHT is a. The FH-series line of fire hose testers, offers testing. Pressure Wands Fire Hose Testers Hose Restraints Hand Pumps MINI HOSE TESTER FH Series The FH-series line of fire hose testers, offers testing pressures up to 1,000 PSI, with flow rates up to 10 GPM. Gas, Electric, and Diesel driven models, designed to safely test fire hose up

More information

R & D SPECIALTIES ROTROL I USER'S MANUAL

R & D SPECIALTIES ROTROL I USER'S MANUAL R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL

More information