1 Design & Engineering Services Variable Speed Drive on a Die Casting Machine 0 Report Prepared by: Design & Engineering Services Customer Service Business Unit Southern California Edison December 17, 2010

2 0 Acknowledgements Southern California Edison's Design & Engineering Services (DES) group is responsible for this project. It was developed as part of Southern California Edison s Emerging Technology program under internal project number 0. DES' Charles Kim conducted this technology evaluation with overall guidance and management from Paul Delaney. For more information on this project, contact Charles.Kim@sce.com. Disclaimer This report was prepared by Southern California Edison (SCE) and funded by California utility customers under the auspices of the California Public Utilities Commission. Reproduction or distribution of the whole or any part of the contents of this document without the express written permission of SCE is prohibited. This work was performed with reasonable care and in accordance with professional standards. However, neither SCE nor any entity performing the work pursuant to SCE's authority make any warranty or representation, expressed or implied, with regard to this report, the merchantability or fitness for a particular purpose of the results of the work, or any analyses, or conclusions contained in this report. The results reflected in the work are generally representative of operating conditions; however, the results in any other situation may vary depending upon particular operating conditions. Southern California Edison

3 0 ABBREVIATIONS AND ACRONYMS DCM DES hp Hz IEEE khz kw kwh lb PLC psig PX RMS SCE V VSD Die casting machine Design and Engineering Services Horsepower Hertz Institute of Electrical and Electronics Engineers Kilohertz Kilowatt Kilowatt hours Pound Programmable Logic Control Pounds per square inch (gauge) Power Explorer meter Root-mean-square Southern California Edison Volt Variable speed drive Southern California Edison Page i

4 0 FIGURES Figure 1. Simplified DCM's Hydraulic System... 3 Figure 2. A 40 HP Variable Speed Drive... 5 Figure 3. Snapshot of Baseline Production Cycle (Power vs. Time)... 6 Figure 4. Wiring Diagram and Relay Settings... 7 Figure 5. Typical Casting Cycle (Without VSD vs. With VSD) Figure 6. Histogram of Casting Cycle (Unit: Second) Figure 7. Regression Analysis of The Casting Production (Energy vs. Casting Cycle) Figure 8. Time Series Trend Analysis of Casting Production Cycle (with VSD only) Figure 9. 5-Minute Demand Comparison Figure 10. Monte Carlo Simulation Results of Daily kwh Savings per DCM Figure 11. Monte Carlo Simulation Results of Estimating Daily Casting Production Figure 12. Operating Hours Indicated By DCM kw Recordings from January 7, 2011 Through January 23, Figure 13. Operating Hours Indicated By DCM kw Recordings from January 27, 2011 Through February 10, TABLES Table 1. Descriptive Statistics for A Typical Casting Cycle Shown in Figure 5 (Unit: kw) Southern California Edison Page ii

5 0 CONTENTS EXECUTIVE SUMMARY 1 INTRODUCTION 3 Background... 3 Emerging Technology... 4 Assessment Objectives... 4 TECHNOLOGY/PRODUCT EVALUATION 5 Baseline Technology... 5 Retrofitting a VSD on the DCM... 5 VSD Parameter Settings and Input Signals from DCM... 6 TEST METHODOLOGY 8 Field Testing of Technology... 8 Instrumentation Plan... 9 Error Analysis... 9 Measurement Uncertainty... 9 RESULTS 11 Energy Savings Potential Demand Reduction Estimating Annual Savings RECOMMENDATIONS 18 Southern California Edison Page iii

6 0 EXECUTIVE SUMMARY A die-casting machine (DCM) is typically driven by a complex hydraulic system to produce dimensional metal parts accurately. The design of a DCM is mainly driven by high-volume production and shot capacity 1 ; the low production cost of each casting allows the DCM owner to make a profit. Until the early 90's, high-volume orders enabled DCM owners to invest in advanced die casting machines. Unfortunately, the global economy has changed the nature of the die casting business in the United States, particularly in California, and now other countries produce high-volume orders; therefore, the survival of die casting companies in California heavily relies on frequent customized designs and small-volume orders. Die-casting companies are looking for methods to reduce the production cost per casting by making various improvements such as increasing energy efficiency. The goal of this project is to improve the energy efficiency of existing aging DCMs by retrofitting a variable speed drive (VSD) on the DCM's hydraulic pump motor. This project evaluates the VSD measures' ability to provide energy savings when the speed of the hydraulic pump motor varies, or is controlled based on the DCM's hydraulic pressure and flow rate requirements. Southern California Edison (SCE) conducted a field evaluation where the energy efficiency of an existing aging DCM was measured. A baseline was established by examining the typical operation of an existing DCM's performance after being retrofitted with a VSD while still maintaining the typical operation. The selected DCM is a modified Harvill 2 Model 406 that is over 20 years old. Its locking pressure capacity is 400 tons (US) and the maximum shot capacity is 14.3 pounds (lbs) of (aluminum). The hydraulic pump is driven by a 6-pole, 40 horsepower (hp), 480 Volt (V), and 3-phase motor. In order to establish a fair comparison, we replaced the existing motor with a National Electrical Manufacturers Association (NEMA) Premium motor with the same specifications. Thus, the baseline is the conventional operation mode of an existing DCM when retrofitted with a new hydraulic pump motor. Because the DCM does not produce the same casting for more than 1 or 2 days, low-volume die casting orders created a measurement challenge during this evaluation period. Therefore, one-day measurements were designed in order to capture a fair comparison between a DCM with the VSD installed and one without. The energy consumption of the DCM without the VSD installed while producing the same number of castings as the DCM with the VSD was monitored. The one-day measurement results reveal an approximate 10% reduction in energy consumption and the potential to reduce demand by 15%, which is a significant change. Despite significant energy savings, retrofitting a VSD on an existing aging DCM is a challenge. The VSD can get overloaded and stop working if the accumulator pressure valve is malfunctioning, as experienced in this field evaluation. Additionally, oil leaks are a common maintenance issue that can change the pressure rise-time and present challenges in maintaining pressure levels. The modified DCM, used as the baseline system, created 1 The "shot capacity" is the maximum weight of molten metal that the DCM can inject into the mold. 2 This DCM manufacturer closed its business about 15 years ago. Southern California Edison Page 1

7 0 another challenge since its existing design can be significantly different from the original design specifications (e.g., different size motor, pump, or additional accumulator, a new programmable logic control (PLC), etc.). Because retrofitting a VSD on an existing aging DCM requires a solid understanding of its specific hydraulic system's performance and ability to control the DCM through the PLC, it is highly recommended that a DCM expert be consulted prior to installing a VSD on a DCM. In addition, the study recommends that a bypass switch be installed between the motor and the VSD so the operator can bypass the VSD in the event of a malfunction. Southern California Edison Page 2

8 INTRODUCTION BACKGROUND Die-casting is a fabrication technique that involves a high-pressure injection of molten metal into a cast. The high-pressure injection is driven by a complex hydraulic system that allows a die-casting machine (DCM) to accurately mass produce dimensional metal parts. The DCM's programmable logic control (PLC) allows the hydraulic pump to inject oil into an accumulator until it reaches a desired pressure level (1,500 pounds per square inch (gauge) (psig) to 1,800 psig). Once it reaches the desired pressure level, the accumulator valve closes and the pump is unloaded. The PLC then opens the fluid control valve that causes highly pressured oil to 1) close the die, 2) inject liquefied metal into the die, and 3) open the die. This three-step process takes 9 to 11 seconds. The PCL then 4) controls the DCM and ejects the casting; 5) the DCM operator opens the DCM door and removes the casting, 6) cools the die with the water spray, and 7) closes the DCM door. This process takes 20 to 30 seconds. Therefore, the total cycle takes between 29 and 41 seconds. The production cycle time changes depending on how efficiently the operator removes the cast, cools the die, and opens and closes the die-casting door. The complexity of the casting can also affect the production cycle by adding 1 to 2 seconds to the total cycle time. Figure 1 shows a typical DCM's hydraulic system. FIGURE 1. SIMPLIFIED DCM'S HYDRAULIC SYSTEM The design of a DCM is driven mainly by high-volume production and shot capacity. The low production cost of each casting allows the DCM owner to make a profit. Until Southern California Edison Page 3

9 the early 90's, high-volume orders enabled DCM owners to invest in advanced die casting machines. Unfortunately, the global economy has changed the die casting business in the United States, particularly in California, and now high-volume orders are produced in other countries; therefore, the survival of die casting companies in California heavily relies on frequent customized designs and small-volume orders. Die-casting companies are looking for ways to reduce the production cost of each casting by making various improvements such as increasing energy efficiency. EMERGING TECHNOLOGY A variable speed drive (VSD) is a device that controls the speed or torque of an induction motor by modulating the input frequency to the motor. The VSD requires an input signal related to the load fluctuations. For a DCM, input signals can be obtained from the existing PLC by installing additional logic relays, if necessary. For example, the PLC can send an input signal by opening or closing a relay to the VSD so the VSD can control the motor to run at high, medium, or low speed, depending on the die casting process modes. The different speeds can be determined by monitoring the pressure rise-time (typically 4 to 5 seconds) and understanding the steps in the die casting process. The die casting process is relatively simple and the steps are outlined below: 1. Die closes: The hydraulic system closes the "cover die" and the "ejector die". 2. Shoots forward: A metal piston forces molten metal into the paired die. The injected metal forms to the shape of the die and solidifies rapidly in the cold die.) 3. Die opens: The hydraulic system separates the "cover die" from the "ejector die". 4. Ejects forward: The hydraulic system ejects the newly formed casting from the "cover die". 5. Shoots back: The metal piston moves back to the original position. 6. Ejects backward: The hydraulic system ejects the newly formed casting from the "ejector die". 7. Idles for cooling: The die is cooled by a water spray. ASSESSMENT OBJECTIVES The goal of this project is to improve the energy efficiency of existing aging DCMs by retrofitting a VSD on the DCM's hydraulic pump motor. This project evaluates the VSD measures' ability to provide energy savings when the speed of the hydraulic pump motor is varied or controlled based on the DCM's hydraulic pressure and flow rate requirements. The retrofitted VSD on the DCM is evaluated based on the following objectives: Evaluate the energy savings, if any, after installing a VSD on the existing aging DCM; Evaluate the potential of a peak demand savings during the field test, if any, after installing a VSD; and Estimate the annual energy savings. Southern California Edison Page 4

10 TECHNOLOGY/PRODUCT EVALUATION BASELINE TECHNOLOGY Southern California Edison (SCE) conducted a field evaluation where the energy efficiency of an existing aging DCM was measured. A baseline was established by examining the typical operation of an existing DCM's performance after being retrofitted with a VSD. A typical existing DCM does not use a VSD for controlling the pump speed, as is the case among 17 die casting companies within SCE's service territory. The selected DCM for this study is a modified Harvill 3 Model 406 that is over 20 years old. Its locking pressure capacity is 400 tons (US), and the maximum shot capacity is 14.3 pounds (lbs) (aluminum). The hydraulic pump is driven by a 6-pole, 40 horsepower (hp), 480 Volt (V), and 3-phase motor. In order to establish a fair comparison, the existing motor was replaced with a National Electrical Manufacturers Association (NEMA) Premium motor with the same specifications. Thus, the baseline is the conventional operation mode of the existing DCM driven by a new hydraulic pump motor. RETROFITTING A VSD ON THE DCM Figure 2 displays a 40 hp VSD installed to control the 40 hp motor. The performance of the VSD was compared to the baseline in order to evaluate the amount of energy saved when a DCM is retrofitted with a VSD. FIGURE 2. A 40 HP VARIABLE SPEED DRIVE 3 This DCM manufacturer closed its business about 15 years ago. Southern California Edison Page 5

11 Power (unit: kw) Variable Speed Drive on a Die Casting Machine VSD PARAMETER SETTINGS AND INPUT SIGNALS FROM DCM The VSD parameters were programmed in accordance to the desired DCM performances. The key parameters include: Motor speed Motor acceleration time Motor deceleration time To determine the above parameters, several snapshot power measurements were taken for the baseline condition. Figure 3 shows a snapshot of the baseline production cycle. One Cycle Mode 1 Mode 2 Mode Oil Leaking Time (unit: sec) FIGURE 3. SNAPSHOT OF BASELINE PRODUCTION CYCLE (POWER VS. TIME) The "Mode 1" section of the graph represents the first three steps of the DCM production (1) Die closes, 2) Shoots forward, and 3) Die opens), which require the most energy. During this mode, the pump reaches the peak within 5 seconds (accelerating time) and slows down within 2 seconds (deceleration time). The "Mode 2" section of the graph represents steps 4, 5, and 6 of the DCM production process (4) Ejects forward, 5) Shoots back, and 6) Ejects backward and rebuilds the pressure in the accumulator). During this mode, the pump reaches the peak within 1 to 2 seconds and slows down at the same speed. The "Mode 3" section of this graph represents step 7 of the DCM production process (7) Idle time for die cooling). During this mode, the existing motor still runs at full speed; however, it is unloaded or lightly loaded. Please note that during this mode there is oil leaking from the DCM's accumulator that creates a noticeable pressure drop (about a 150-psig drop within 1 second); therefore, the motor re-runs in order to build up the pressure. Southern California Edison Page 6

12 Although this is a maintenance problem, the operator sees this as the typical operating condition 4 for an existing aging DCM. The energy level for each mode can be determined by totaling the kilowatt (kw) values within the specific mode. After the energy levels for each mode are determined, the speed parameter on the VSD can be set. The following parameters were selected based on the analysis results shown in Figure 3: Mode 1 speed: 40 hertz (Hz) Mode 2 speed: 38 Hz Mode 3 speed: 32 Hz Acceleration Time: 2.5 seconds Deceleration Time: 1.5 seconds After the speed parameters are determined, input signals can be provided to the VSD so the VSD can send the appropriate signals to the motor according to the modes defined in Figure 3. This can be accomplished by reprogramming the existing PLC with three additional relays. A typical VSD allows the user to run at the preset value when it receives a relay signal to its terminal block. Figure 4 shows the wiring and logic diagrams. FIGURE 4. WIRING DIAGRAM AND RELAY SETTINGS The PLC can send signals to the VSD by closing or opening Relay 1 through 3. For example, when the PLC closes Relay 1, the PLC informs the VSD that the DCM is in Mode 1 ("Die closes, Shoots forward, and Die opens"). Once the VSD sees that Relay 1 is "closed", the VSD runs the motor at the "Preset Speed #1". Then Relay 2 "closes" and the VSD runs the motor at the "Preset Speed #2". 4 According to the maintenance supervisor, the accumulator valve is not fixed or replaced unless there is an excessive amount of oil leaking. Southern California Edison Page 7

13 TEST METHODOLOGY FIELD TESTING OF TECHNOLOGY To evaluate the energy savings when retrofitting the VSD onto an existing aging DCM, a power-quality-grade meter was installed to collect kw data. An event data logger was also installed to record the number of castings produced during the test period. Low-volume die casting orders created a measurement challenge because the DCM does not produce the same casting for more than 1 or 2 days. Therefore, two different amounts of measurement time-periods were established: One-day measurements were performed on December 13, 2010 (data is captured every 1 second for 1 to 2 hours.) Four-week measurements (capture data every 30 seconds.) Designed to capture a fair comparison, the one-day measurements monitor energy consumption without the VSD on the DCM while producing the same number of castings. The 4-week measurements are designed to estimate the average energy savings and to determine operating costs. The 4-week monitoring period included 2 weeks with the VSD on the new hydraulic pump motor and 2 weeks without the VSD installed on the DCM. A fair comparison for the 4-week measurement is difficult because of the: Various casting types produced: Some are simple-shaped while others are more complicated; some castings are heavy (over 4 lbs) while others are light (less than 1 lb). Operator performance: Some operators produce more castings than others within a specific shift do. According to the production supervisor, a highly experienced operator can produce approximately 800 castings per shift while most operators produce approximately 600 castings per shift. Wide range of die setup time: When setting up a pair of die (one is called the "cover die" and the other is called the "ejector die"), a simple-shaped die takes 1 to 2 hours while a complicated and specially-designed die can take up to 5 hours. During the die setting, a limited number of castings are produced. Before a die is considered "set", a quality control supervisor must approve the sample casting. Therefore, operators may have to set the die repeatedly, and sometimes only castings can be produced per hour. This is compared to castings per hour during the production mode. Maintenance issues: Operating an existing aging DCM is also a challenge for the operator. For example, after a few hours of operation, the pair of die can become misaligned. The operator may detect this visually by inspecting the produced casting and either shut down the DCM or allow the machine to run while realigning the die. Realigning the die can take anywhere from 15 minutes to 1 hour. If there is a major problem, the machine can be out of commission for 1 to 2 days. Southern California Edison Page 8

14 INSTRUMENTATION PLAN At the first site visit, the size of motor was recorded and the location of the circuit breaker for the DCM was identified. As a result, the following instruments were selected for this project: Power measurement: Dranetz BMI PowerXplorer PX5. This device is designed for monitoring power quality. The accuracy of a meter is 0.1% of the true root mean square (RMS) reading. It complies with IEEE 1159, IEC Class A and EN50160, and captures IEEE 1459 parameters for non-sinusoidal and advanced power systems. Power measurement sensor: Dranflex 3000XL current probes. Its accuracy level for a 300 Ampere (A) Range is ±1% of reading ± 0.1 A. Its frequency range is 10 Hz to 10 kilohertz (khz) (-1 Decibel). It complies with EMC EN :2006 and EN :2001; EN :2002; and EN :2002 safety standards. Event Measurement: Hobo U11. It can record up to 43,000 state changes or events. It is used for recording each casting production cycle. All of the instruments used in this project are up to calibration date. ERROR ANALYSIS Error analysis for a small number of independent variables can be done as follows; the kw reading, for example, is dependent upon two independent variables, voltage (V) and the current (I), then the error in kw measurement is: kw kw V V 2 I I 2 Therefore, the most inaccurate device will drive the error in kw. In this case, the probe is the most inaccurate device. Its accuracy level is 1%, which implies that the kw error will be less than 1.1%. MEASUREMENT UNCERTAINTY Measurement uncertainty is a key issue for this project. The VSD is programmed to save energy and reduce the demand by controlling the acceleration and deceleration time variables in addition to varying the voltage frequency to the motor. Therefore, the DCM, without the VSD, quickly accelerates the motor pump and reaches the predetermined pressure level while the VSD controls the motor pump and reaches the same pressure level relatively slowly, as illustrated in Figure 5. The descriptive statistics of the typical casting cycles shown in Figure 5 are tabulated in Table 1. When comparing the "mean" and "median" values, it can be easily seen that the casting cycle for "without the VSD" is skewed to the right and the casting cycle data for "with the VSD" is skewed to the left while the mean values for both are relatively close. This means that if the measurement is collected by "averaging samples over 30 seconds", for example, the measurement instrument may not see the significant energy savings. Therefore, the meter must have a capability to capture a snapshot, Southern California Edison Page 9

15 kw Variable Speed Drive on a Die Casting Machine not averaging samples over the given interval. Furthermore, the tested DCM was not fully automated but rather controlled by an operator. Therefore, the production time for making a casting can vary greatly from one operator to others. The DCM makes various parts as well. Therefore, the energy needed for making a casting can vary as well. Because of these uncertain factors, the four-week measurement (two weeks without the VSD and two weeks with VSD) is designed to verify operating hours Variable without VSD VSD One Casting Cycle (unit: second) FIGURE 5. TYPICAL CASTING CYCLE (WITHOUT VSD VS. WITH VSD) TABLE 1. DESCRIPTIVE STATISTICS FOR A TYPICAL CASTING CYCLE SHOWN IN FIGURE 5 (UNIT: KW) VARIABLE SAMPLE SIZE MEAN Standard DEVIATION MINIMUM First QUARTILE MEDIAN Third QUARTILE MAXIMUM Without VSD VSD Southern California Edison Page 10

16 Frequency Variable Speed Drive on a Die Casting Machine RESULTS ENERGY SAVINGS Figure 6 shows the production cycles (in seconds) obtained from the 1-day measurement. The sample size was 522 which means 522 castings were made. The mean production cycle was 36.7 seconds. However, there were outliers resulting from the quality-assurance inspector's activities. During the inspector's visual checkup, the casting cycle ranged from 65 to 280 seconds. The total number of outliers was 29 out of 522 samples. Excluding the outlier, the range of the casting cycle was 26 to 58 seconds. (The total number of samples was 493 of which 343 castings were produced with the VSD, and 150 castings were produced without the VSD.) Mean StDev N Casting Cycle FIGURE 6. HISTOGRAM OF CASTING CYCLE (UNIT: SECOND) The energy-savings calculation for the baseline data can be accomplished by performing the following steps: 1. For each casting, add the kw values taken every second during the casting cycle. (The sum of the kw values equals the amount of energy used.) 2. Run a regression analysis to determine the amount of energy used per casting cycle for all of the samples. 3. Repeat steps 1 and 2 for the VSD retrofitting condition. Figure 7 shows the results of the above steps. Southern California Edison Page 11

17 Energy Variable Speed Drive on a Die Casting Machine Variable Baseline VSD Casting Cycle FIGURE 7. REGRESSION ANALYSIS OF THE CASTING PRODUCTION (ENERGY VS. CASTING CYCLE) The regression results are: Baseline (energy) = T (unit: kw seconds/casting) where T is the casting cycle in seconds. VSD (energy) = T When the average casting cycle of 36.7 seconds, obtained from Figure 6, is applied, the result is: Baseline (Energy) = (36.7) = (unit: kw seconds/casting) VSD (Energy) = (36.7) = (unit: kw seconds/casting) Therefore, the average energy savings is the difference of 56.5 (unit: kw seconds/casting) or kilowatt hour (kwh) per casting. This implies that the VSD saves kwh per casting on average. This is equivalent to a 10% energy savings per casting. Figure 7 shows that the casting cycle is reduced for the baseline condition; the average casting cycle in the morning is 37 seconds (using the VSD), and the average casting cycle in the afternoon is approximately 33 seconds (baseline). The average casting cycle difference is mainly due to the operator's performance rather than the performance of the DCM. Because a new production cycle requires new die settings and alignments, the operator spends more time on the visual inspection in the morning than in the afternoon as shown in the Time Series Trend Analysis in Figure 8. Southern California Edison Page 12

18 5-Minute Average Demand (unit: kw) Casting Cycle (unit: Second) Variable Speed Drive on a Die Casting Machine Yt = *t Variable Actual Fits Accuracy Measures MAPE MAD MSD No. of Casting Production in Time Order FIGURE 8. TIME SERIES TREND ANALYSIS OF CASTING PRODUCTION CYCLE (WITH VSD ONLY) POTENTIAL DEMAND REDUCTION A 5-minute demand from the 1-day measurement is shown in Figure 9. For a fair comparison, any data resulting from interruptions (e.g., lunchtime, break-time, and the inspector's activities) was excluded. 20 Variable Demand (without VSD) Demand (VSD) No of Samples in Time FIGURE 9. 5-MINUTE DEMAND COMPARISON The average 5-minute demand for the baseline (e.g., without the VSD) is kw while for the VSD retrofitting is kw; the difference is 2.72 kw. This implies that there is a potential for a 16.8% reduction in the 5-min demand, which is a significant change when the VSD is installed. Southern California Edison Page 13

19 ESTIMATING ANNUAL SAVINGS According to the operation supervisor, daily casting production ranges from 600 to 900 castings. The collected data indicates that the casting production ranges from 675 to 877 castings per day. The average number of work hours per day is 16 hours (from 5:00 a.m. to 10:00 p.m.), excluding breakfast, lunch, and dinner breaks. The plant operates 49 weeks per year; therefore, the annual saving range is: kwh per casting (600 castings per day x 5 days per week x 49 weeks per year = 2,308 kwh per year) When there are 900 castings produced per day, the annual energy savings is 3,462 kwh per year. Therefore, the range of annual energy savings is between 2,308 kwh and 3,462 kwh per DCM. A Monte Carlo simulation (a repeated sampling) can also be used to estimate the savings. This diverts from using a single point of estimating the energy savings per casting (e.g., applying kwh per casting factor). The Monte Carlo procedure is as follows: 1. Find a probability distribution function for one of the casting cycles illustrated in Figure Use a random number generator for the probability distribution function found in step 1; this is a casting cycle from the probability distribution. 3. Calculate the energy savings for a given casting cycle generated from step 2. See Figure Repeat steps 2 and 3 until the total production time per day is between 7 and 11 hours Repeat step 2 through step 4, 5,000 times. The results of the Monte Carlo Simulation reveal an average daily savings of kwh. See Figure 10. When multiplying the daily savings by 5 days per week and 49 weeks per year, the annual savings can be estimated as 3,376 kwh per DCM. This savings is driven by the daily production variation defined in Figure 11 where the daily mean production is 804 castings. This is a conservative estimated value of energy savings and accounts for only 8.5 hours, on average, of continuous production time. This simulation assumes that the die setting takes place daily and will encounter some maintenance issues during the day. Therefore, the actual savings may be greater if the production level increases. 5 The "gamma" function is found to be closest to the casting data collected where the scale is , and the shape is The gamma function is defined as: f ( x) 0 r x x r r 1 1 e e x x dx for r >0, λ > 0 and x > 0 The parameters λ and r are often called the "scale" and "shape". 6 The 7 to 11 hours per day accounts for the continuous production time per day with an average production time of 8.5 hours per day. This excludes die setting time, all breaks (excluding breakfast and lunchtime), various inspections, and maintenance times. Southern California Edison Page 14

20 Frequency Frequency Variable Speed Drive on a Die Casting Machine Currently, there are 17 die casting companies within SCE's service area. If an average of five DCMs per company operates, the estimated annual savings potential can be calculated for retrofitting the VSDs as follows: Market Potential for Retrofitting the VSDs on DCMs = 3,376 kwh per DCM x 5 DCMs per company x 17 companies = 286,960 kwh savings annually. Therefore, the estimated VSD market potential, in the context of energy savings, for retrofitting a VSD is 287,000 kwh annually Mean StDev N Daily kwh Saving per DCM FIGURE 10. MONTE CARLO SIMULATION RESULTS OF DAILY KWH SAVINGS PER DCM Mean StDev N Daily Casting Production FIGURE 11. MONTE CARLO SIMULATION RESULTS OF ESTIMATING DAILY CASTING PRODUCTION Figure 12 illustrates the test site ran the DCM without VSD about 10 to 11 hours per day, 5 days per week from January 7 through January 20, Southern California Edison Page 15

21 1/5/2011 1/7/2011 1/9/2011 1/11/2011 1/13/2011 1/15/2011 1/17/2011 1/19/2011 1/21/2011 1/23/2011 Without VSD (unit: kw) Variable Speed Drive on a Die Casting Machine Date FIGURE 12. OPERATING HOURS INDICATED BY DCM KW RECORDINGS FROM JANUARY 7, 2011 THROUGH JANUARY 23, Figure 13 also shows that the site runs its operation closer to 16 hours a day, excluding breakfast, lunch, and dinner breaks, 5 days a week. The shortest working day is the Friday when the operator turns off the machine around noon. Therefore, the average working hour is about 11 hours a day. Figure 13 also shows that there is a significant peak demand reduction as compared to Figure 12. Therefore, 8.5 hours per day is reasonable for estimating annual savings. Southern California Edison Page 16

22 1/27/2011 1/29/2011 1/31/2011 2/2/2011 2/4/2011 2/6/2011 2/8/2011 2/10/2011 2/12/2011 With VSD (unit: kw) Variable Speed Drive on a Die Casting Machine Date FIGURE 13. OPERATING HOURS INDICATED BY DCM KW RECORDINGS FROM JANUARY 27, 2011 THROUGH FEBRUARY 10, The VSD saves approximately 10% of the energy needed to produce castings from the existing DCMs. The VSD can also reshape the input power to the motor to potentially reduce the peak demand, which is approximately 16.8%, based on the 5-minute average peak demand collected data. Overall, the VSD can be an energy efficient measure for existing DCMs since the energy savings can be much greater for the DCMs that do not have an accumulator valve (e.g., the pump is holding the pressure, not the valve) and two to three times more energy savings than a DCM with an accumulator valve. The estimated VSD market potential, in the context of energy savings for this VSD measure, is 287,000 kwh annually within SCE's service territory. Southern California Edison Page 17

23 RECOMMENDATIONS The VSD saves approximately 10% of the energy needed to produce castings from the existing DCMs. The VSD can also reshape the input power to the motor to potentially reduce the peak demand, which is approximately 16.8%, based on the 5-minute average peak demand collected data. Overall, the VSD can be an energy efficient measure for existing DCMs since the energy savings can be much greater for the DCMs that do not have an accumulator valve (e.g., the pump is holding the pressure, not the valve) and two to three times more energy savings than a DCM with an accumulator valve. The estimated VSD market potential, in the context of energy savings for this VSD measure, is 287,000 kwh annually within SCE's service territory. Despite the significant energy savings it provides, retrofitting a VSD on an existing aging DCM is a challenge. The VSD can be overloaded and stop working if the accumulator pressure valve malfunctions, as experienced in this field evaluation. Additionally, oil leaks are a common maintenance issue that can change the pressure rise-time and cause issues in maintaining pressure levels since its existing design can be significantly different from the original design specifications (e.g., different size motor, pump, or additional accumulator, a new programmable logic control (PLC), etc.). Therefore, a complete field evaluation of the DCM is highly recommended. Because retrofitting a VSD on an existing aging DCM requires a solid understanding of its specific hydraulic system's performance and ability to control the DCM through the PLC, it is highly recommended that a DCM expert be consulted prior to installing a VSD on a DCM. It is also recommended that a bypass switch be installed between the motor and the VSD so the operator can bypass the VSD in the event of a malfunction. Southern California Edison Page 18

DC Power Grid System Lighting for a Typical Conference Room Evaluation

DC Power Grid System Lighting for a Typical Conference Room Evaluation Design & Engineering Services DC Power Grid System Lighting for a Typical Conference Room Evaluation ETO 09.03 Report Prepared by: Design & Engineering Services Customer Service Business Unit Southern

More information

Impact Evaluation of 2004 Compressed Air Prescriptive Rebates

Impact Evaluation of 2004 Compressed Air Prescriptive Rebates Impact Evaluation of 2004 Compressed Air Prescriptive Rebates May 15, 2006 Prepared for: National Grid USA Service Company P.O. 0000027684 DMI# 05006.520 Prepared by: DMI 450 Lexington Street Newton, MA

More information

International Aluminium Institute

International Aluminium Institute THE INTERNATIONAL ALUMINIUM INSTITUTE S REPORT ON THE ALUMINIUM INDUSTRY S GLOBAL PERFLUOROCARBON GAS EMISSIONS REDUCTION PROGRAMME RESULTS OF THE 2003 ANODE EFFECT SURVEY 28 January 2005 Published by:

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

Introduction: Supplied to 360 Test Labs... Battery packs as follows:

Introduction: Supplied to 360 Test Labs... Battery packs as follows: 2007 Introduction: 360 Test Labs has been retained to measure the lifetime of four different types of battery packs when connected to a typical LCD Point-Of-Purchase display (e.g., 5.5 with cycling LED

More information

An Energy Assessment of Fume Hoods with and without Automated Sash Positioning Control Systems at Amgen, Inc.

An Energy Assessment of Fume Hoods with and without Automated Sash Positioning Control Systems at Amgen, Inc. Design & Engineering Services An Energy Assessment of Fume Hoods with and without Automated Sash Positioning Control Systems at Amgen, Inc. Emerging Technologies Final Report Prepared by: Design and Engineering

More information

The reason for higher electric bills

The reason for higher electric bills The reason for higher electric bills William S. Bathgate, BS EE bill.bathgate@gmail.com 1 The new AMI electric meter block diagram The Switched Mode Power Supply, (SMPS) which injects high frequency Oscillations/Harmonics

More information

A Comparative Performance Analysis DCR and DAR Squirrel Cage 3-Phase Induction Motor

A Comparative Performance Analysis DCR and DAR Squirrel Cage 3-Phase Induction Motor A Comparative Performance Analysis DCR and DAR Squirrel Cage 3-Phase Induction Motor 1 Ashish Choubey, 2 Rupali Athanere 1 Assistant Professor, 2 M.E. Student (HVPS Engg) 1,2 Deptt of Electrical Engineering

More information

LOW-VOLTAGE TECHNOLOGY SCOPING STUDY: IMPACT OF SMALL AIR CONDITIONING UNITS ON ELECTRICAL SYSTEM VOLTAGE RECOVERY

LOW-VOLTAGE TECHNOLOGY SCOPING STUDY: IMPACT OF SMALL AIR CONDITIONING UNITS ON ELECTRICAL SYSTEM VOLTAGE RECOVERY Design & Engineering Services LOW-VOLTAGE TECHNOLOGY SCOPING STUDY: IMPACT OF SMALL AIR CONDITIONING UNITS ON ELECTRICAL SYSTEM VOLTAGE RECOVERY Demand Response Emerging Markets and Technologies Program

More information

D6.5 Public report on experience & results from FCEV city car demonstration in Oslo

D6.5 Public report on experience & results from FCEV city car demonstration in Oslo D6.5 Public report on experience & results from FCEV city car demonstration in Oslo Final Report Dissemination level: PU February 2013 Page 1 of 13 Introduction WP6 Deliverable D6.5 Public report on experience

More information

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date: CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in

More information

Oregon DOT Slow-Speed Weigh-in-Motion (SWIM) Project: Analysis of Initial Weight Data

Oregon DOT Slow-Speed Weigh-in-Motion (SWIM) Project: Analysis of Initial Weight Data Portland State University PDXScholar Center for Urban Studies Publications and Reports Center for Urban Studies 7-1997 Oregon DOT Slow-Speed Weigh-in-Motion (SWIM) Project: Analysis of Initial Weight Data

More information

Tolerance-Based Time-Current Coordination

Tolerance-Based Time-Current Coordination S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background....

More information

DRIVER SPEED COMPLIANCE WITHIN SCHOOL ZONES AND EFFECTS OF 40 PAINTED SPEED LIMIT ON DRIVER SPEED BEHAVIOURS Tony Radalj Main Roads Western Australia

DRIVER SPEED COMPLIANCE WITHIN SCHOOL ZONES AND EFFECTS OF 40 PAINTED SPEED LIMIT ON DRIVER SPEED BEHAVIOURS Tony Radalj Main Roads Western Australia DRIVER SPEED COMPLIANCE WITHIN SCHOOL ZONES AND EFFECTS OF 4 PAINTED SPEED LIMIT ON DRIVER SPEED BEHAVIOURS Tony Radalj Main Roads Western Australia ABSTRACT Two speed surveys were conducted on nineteen

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

WIM #41 CSAH 14, MP 14.9 CROOKSTON, MINNESOTA APRIL 2014 MONTHLY REPORT

WIM #41 CSAH 14, MP 14.9 CROOKSTON, MINNESOTA APRIL 2014 MONTHLY REPORT WIM #41 CSAH 14, MP 14.9 CROOKSTON, MINNESOTA APRIL 2014 MONTHLY REPORT In order to understand the vehicle classes and groupings, the MnDOT Vehicle Classification Scheme and the Vehicle Classification

More information

REMOTE SENSING DEVICE HIGH EMITTER IDENTIFICATION WITH CONFIRMATORY ROADSIDE INSPECTION

REMOTE SENSING DEVICE HIGH EMITTER IDENTIFICATION WITH CONFIRMATORY ROADSIDE INSPECTION Final Report 2001-06 August 30, 2001 REMOTE SENSING DEVICE HIGH EMITTER IDENTIFICATION WITH CONFIRMATORY ROADSIDE INSPECTION Bureau of Automotive Repair Engineering and Research Branch INTRODUCTION Several

More information

TECHNOLOGY AND MARKET TRIALS PROGRAM. Final Report Motorboss Motor Controller Field Test

TECHNOLOGY AND MARKET TRIALS PROGRAM. Final Report Motorboss Motor Controller Field Test Las Vegas, Nevada TECHNOLOGY AND MARKET TRIALS PROGRAM Final Report Motorboss Motor Controller Field Test Levi Strauss and McCarran Airport Test Sites Prepared By: Prepared For: Larry Holmes Program Manager,

More information

three different ways, so it is important to be aware of how flow is to be specified

three different ways, so it is important to be aware of how flow is to be specified Flow-control valves Flow-control valves include simple s to sophisticated closed-loop electrohydraulic valves that automatically adjust to variations in pressure and temperature. The purpose of flow control

More information

Sacramento Municipal Utility District s EV Innovators Pilot

Sacramento Municipal Utility District s EV Innovators Pilot Sacramento Municipal Utility District s EV Innovators Pilot Lupe Jimenez November 20, 2013 Powering forward. Together. Agenda SMUD Snapshot Pilot Plan v Background v At-a-Glance v Pilot Schedule Treatment

More information

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any Application Note First trip test A circuit breaker spends most of its lifetime conducting current without any operation. Once the protective relay detects a problem, the breaker that was idle for maybe

More information

Bisnet Solutions for Tomorrow, Today! The Die Casting Process Planner. Users Manual. August 5, A Product By: Bisnet - 1 -

Bisnet Solutions for Tomorrow, Today! The Die Casting Process Planner. Users Manual. August 5, A Product By: Bisnet - 1 - Bisnet Solutions for Tomorrow, Today! The Die Casting Process Planner Users Manual August 5, 2002 A Product By: Bisnet - 1 - DCPP Users Manual Table of Contents CHAPTER 1 PQ 2 4 What is PQ Squared? 4 CHAPTER

More information

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems Farid Katiraei *, Barry Mather **, Ahmadreza Momeni *, Li Yu *, and Gerardo Sanchez * * Quanta Technology, Raleigh,

More information

Technical Papers supporting SAP 2009

Technical Papers supporting SAP 2009 Technical Papers supporting SAP 29 A meta-analysis of boiler test efficiencies to compare independent and manufacturers results Reference no. STP9/B5 Date last amended 25 March 29 Date originated 6 October

More information

Understanding the Performance of Parallel Temporary Protective Grounds

Understanding the Performance of Parallel Temporary Protective Grounds Understanding the Performance of Parallel Temporary Protective Grounds Thomas Lancaster, Shashi Patel, Josh Perkel, & Anil Poda NEETRAC Introduction NEETRAC Test Program Test Results Modeling De-Rating

More information

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric

More information

PATENTED TECHNOLOGY» PROVEN RESULTS» PAYBACK

PATENTED TECHNOLOGY» PROVEN RESULTS» PAYBACK 2328 Bellfort Ave. Houston, Texas 77051 Main 713-821-9600 Fax 713-821-9601 EFFECTS OF ENVIROFUELS DFC ON A LAND DRILLING RIG Oil and Gas Land Drilling Rig PUBLIC VERSION Revision Date February 18, 2008

More information

Product Loss During Retail Motor Fuel Dispenser Inspection

Product Loss During Retail Motor Fuel Dispenser Inspection Product Loss During Retail Motor Fuel Dispenser Inspection By: Christian Lachance, P. Eng. Senior Engineer - ment Engineering and Laboratory Services ment Canada Date: Product Loss During Retail Motor

More information

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC One of the most frequently quoted studies related to electric motor reliability

More information

Performance of Batteries in Grid Connected Energy Storage Systems. June 2018

Performance of Batteries in Grid Connected Energy Storage Systems. June 2018 Performance of Batteries in Grid Connected Energy Storage Systems June 2018 PERFORMANCE OF BATTERIES IN GRID CONNECTED ENERGY STORAGE SYSTEMS Authors Laurie Florence, Principal Engineer, UL LLC Northbrook,

More information

Accelerated Testing of Advanced Battery Technologies in PHEV Applications

Accelerated Testing of Advanced Battery Technologies in PHEV Applications Page 0171 Accelerated Testing of Advanced Battery Technologies in PHEV Applications Loïc Gaillac* EPRI and DaimlerChrysler developed a Plug-in Hybrid Electric Vehicle (PHEV) using the Sprinter Van to reduce

More information

FAN ENGINEERING. Application Guide for Selecting AC Motors Capable of Overcoming Fan Inertia ( ) 2

FAN ENGINEERING. Application Guide for Selecting AC Motors Capable of Overcoming Fan Inertia ( ) 2 FAN ENGINEERING Information and Recommendations for the Engineer Twin City Fan FE-1800 Application Guide for Selecting AC Motors Capable of Overcoming Fan Inertia Introduction Bringing a fan up to speed

More information

Motor Protection Fundamentals. Motor Protection - Agenda

Motor Protection Fundamentals. Motor Protection - Agenda Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection

More information

Copyright Statement FPC International, Inc

Copyright Statement FPC International, Inc Copyright Statement All rights reserved. All material in this document is, unless otherwise stated, the property of FPC International, Inc. Copyright and other intellectual property laws protect these

More information

RRI PERFORMANCE ASSESSMENT OF AFTERMARKET PERFORMANCE MODIFICATION 1 (12)

RRI PERFORMANCE ASSESSMENT OF AFTERMARKET PERFORMANCE MODIFICATION 1 (12) - Road Vehicles - Steady State Test Mode - - Powertrain Performance Comparison Test Code - Performance Assessment of Aftermarket Performance Modification - 1 (12) Status of Document Type Description Publication

More information

INCREASING THE ELECTRIC MOTORS EFFICIENCY IN INDUSTRIAL APPLICATIONS

INCREASING THE ELECTRIC MOTORS EFFICIENCY IN INDUSTRIAL APPLICATIONS Institute for Sustainable Energy, UNIVERSITY OF MALTA SUSTAINABLE ENERGY 12: THE ISE ANNUAL CONFERENCE PROCEEDINGS Tuesday 21 February 12, Dolmen Hotel, Qawra, Malta INCREASING THE ELECTRIC MOTORS EFFICIENCY

More information

SAN PEDRO BAY PORTS YARD TRACTOR LOAD FACTOR STUDY Addendum

SAN PEDRO BAY PORTS YARD TRACTOR LOAD FACTOR STUDY Addendum SAN PEDRO BAY PORTS YARD TRACTOR LOAD FACTOR STUDY Addendum December 2008 Prepared by: Starcrest Consulting Group, LLC P.O. Box 434 Poulsbo, WA 98370 TABLE OF CONTENTS 1.0 EXECUTIVE SUMMARY...2 1.1 Background...2

More information

Brake caliper machining: improve process control and reduce inspection costs

Brake caliper machining: improve process control and reduce inspection costs Case brief Brake caliper machining: improve process control and reduce inspection costs Reduce part costs Full traceability High accuracy automated shop floor gauging Overview Manufacturers of brake calipers

More information

EVALUATION OF DEMONSTRATION PROJECT FOR ICE BEAR THERMAL ICE STORAGE SYSTEM FOR DEMAND SHIFTING. Final Report November 2006

EVALUATION OF DEMONSTRATION PROJECT FOR ICE BEAR THERMAL ICE STORAGE SYSTEM FOR DEMAND SHIFTING. Final Report November 2006 EVALUATION OF DEMONSTRATION PROJECT FOR ICE BEAR THERMAL ICE STORAGE SYSTEM FOR DEMAND SHIFTING Final Report November 2006 Submitted to: Sacramento Municipal Utility District 6301 S Street Sacramento,

More information

A softstarter beyond the ordinary

A softstarter beyond the ordinary A softstarter beyond the ordinary Emotron MSF 2.0 Softstarter More than just Starting an electrical motor involves a number of challenges, such as high start currents and mechanical stress on equipment.

More information

Development of Motor-Assisted Hybrid Traction System

Development of Motor-Assisted Hybrid Traction System Development of -Assisted Hybrid Traction System 1 H. IHARA, H. KAKINUMA, I. SATO, T. INABA, K. ANADA, 2 M. MORIMOTO, Tetsuya ODA, S. KOBAYASHI, T. ONO, R. KARASAWA Hokkaido Railway Company, Sapporo, Japan

More information

Hydrogen Station Equipment Performance Device (HyStEP Device) Specification

Hydrogen Station Equipment Performance Device (HyStEP Device) Specification Hydrogen Station Equipment Performance Device (HyStEP Device) Specification Overview Policies and technology solutions need to be developed and implemented to help reduce the time from when a new hydrogen

More information

High- or Medium-Speed Generator Sets: Which Is Right for Your Application?

High- or Medium-Speed Generator Sets: Which Is Right for Your Application? Our energy working for you. Power topic #6001 Technical information from Cummins Power Generation High- or Medium-Speed Generator Sets: Which Is Right for Your Application? White Paper Joel Puncochar Marketing

More information

A NEW SPIN ON PUMP STATION TESTING AND ANALYIS: WHAT YOU WISH YOU KNEW ABOUT YOUR PUMP STATION

A NEW SPIN ON PUMP STATION TESTING AND ANALYIS: WHAT YOU WISH YOU KNEW ABOUT YOUR PUMP STATION ABSTRACT Zachary G. Purvis, PE Kimley-Horn and Associates, Inc. 3001 Weston Parkway Cary NC, 27513; 919-653-2963; zak.purvis@kimley-horn.com Wastewater collection system owners are becoming increasingly

More information

Analysis of IEC Recommendations in Selected APEC Economies

Analysis of IEC Recommendations in Selected APEC Economies Reducing Losses in Power Distribution through Improved Efficiency of Distribution Transformers (EWG 05 2015A) Analysis of IEC 6007620 Recommendations in Selected APEC Economies 18 December 2017 Bangkok,

More information

Appendix 3. DRAFT Policy on Vehicle Activated Signs

Appendix 3. DRAFT Policy on Vehicle Activated Signs Appendix 3 DRAFT Policy on Vehicle Activated Signs Ealing Council has been installing vehicle activated signs for around three years and there are now 45 across the borough. These signs help to reduce

More information

Project Summary Fuzzy Logic Control of Electric Motors and Motor Drives: Feasibility Study

Project Summary Fuzzy Logic Control of Electric Motors and Motor Drives: Feasibility Study EPA United States Air and Energy Engineering Environmental Protection Research Laboratory Agency Research Triangle Park, NC 277 Research and Development EPA/600/SR-95/75 April 996 Project Summary Fuzzy

More information

Michigan/Grand River Avenue Transportation Study TECHNICAL MEMORANDUM #18 PROJECTED CARBON DIOXIDE (CO 2 ) EMISSIONS

Michigan/Grand River Avenue Transportation Study TECHNICAL MEMORANDUM #18 PROJECTED CARBON DIOXIDE (CO 2 ) EMISSIONS TECHNICAL MEMORANDUM #18 PROJECTED CARBON DIOXIDE (CO 2 ) EMISSIONS Michigan / Grand River Avenue TECHNICAL MEMORANDUM #18 From: URS Consultant Team To: CATA Project Staff and Technical Committee Topic:

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

Shock tube based dynamic calibration of pressure sensors

Shock tube based dynamic calibration of pressure sensors Shock tube based dynamic calibration of pressure sensors C. E. Matthews, S. Downes, T.J. Esward, A. Wilson (NPL) S. Eichstädt, C. Elster (PTB) 23/06/2011 1 Outline Shock tube as a basis for calibration

More information

University of Michigan Health System. Program and Operations Analysis

University of Michigan Health System. Program and Operations Analysis University of Michigan Health System Program and Operations Analysis Analysis of the Sterilization Process of Surgical Instruments to Reduce Turnaround Time in the Central Sterile Supply at the University

More information

LIFTGATE AND 250 WATT SOLAR BATTERY CHARGER

LIFTGATE AND 250 WATT SOLAR BATTERY CHARGER LIFTGATE TEST RESULTS LIFTGATE AND 250 WATT SOLAR BATTERY CHARGER Summary Results A major challenge for commercial trucks is maintaining adequate charge and overall health of batteries that power the truck

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD May 1, 2017 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011-

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011- Proceedings of ASME PVP2011 2011 ASME Pressure Vessel and Piping Conference Proceedings of the ASME 2011 Pressure Vessels July 17-21, & Piping 2011, Division Baltimore, Conference Maryland PVP2011 July

More information

ELECTROMECHANICAL OPTIMIZATION AGAINST TORSIONAL VIBRATIONS IN O&G ELECTRIFIED TRAINS MICHELE GUIDI [GE O&G] ALESSANDRO PESCIONI [GE O&G]

ELECTROMECHANICAL OPTIMIZATION AGAINST TORSIONAL VIBRATIONS IN O&G ELECTRIFIED TRAINS MICHELE GUIDI [GE O&G] ALESSANDRO PESCIONI [GE O&G] ELECTROMECHANICAL OPTIMIZATION AGAINST TORSIONAL VIBRATIONS IN O&G ELECTRIFIED TRAINS MICHELE GUIDI [GE O&G] ALESSANDRO PESCIONI [GE O&G] Topics INTRODUCTION - Mechanical vibrations in electrified trains

More information

Designing for Reliability and Robustness with MATLAB

Designing for Reliability and Robustness with MATLAB Designing for Reliability and Robustness with MATLAB Parameter Estimation and Tuning Sensitivity Analysis and Reliability Design of Experiments (DoE) and Calibration U. M. Sundar Senior Application Engineer

More information

FOR IMMEDIATE RELEASE

FOR IMMEDIATE RELEASE Article No. 7353 Available on www.roymorgan.com Roy Morgan Unemployment Profile Wednesday, 11 October 2017 2.498 million Australians (18.9%) now unemployed or under-employed In September 1.202 million

More information

REAL WORLD DRIVING. Fuel Efficiency & Emissions Testing. Prepared for the Australian Automobile Association

REAL WORLD DRIVING. Fuel Efficiency & Emissions Testing. Prepared for the Australian Automobile Association REAL WORLD DRIVING Fuel Efficiency & Emissions Testing Prepared for the Australian Automobile Association - 2016 2016 ABMARC Disclaimer By accepting this report from ABMARC you acknowledge and agree to

More information

Copyright Statement FPC International, Inc

Copyright Statement FPC International, Inc Copyright Statement All rights reserved. All material in this document is, unless otherwise stated, the property of FPC International, Inc. Copyright and other intellectual property laws protect these

More information

Asian paper mill increases control system utilization with ABB Advanced Services

Asian paper mill increases control system utilization with ABB Advanced Services Case Study Asian paper mill increases control system utilization with ABB Advanced Services A Southeast Asian paper mill has 13 paper machines, which creates significant production complexity. They have

More information

WIM #39 MN 43, MP 45.2 WINONA, MN APRIL 2010 MONTHLY REPORT

WIM #39 MN 43, MP 45.2 WINONA, MN APRIL 2010 MONTHLY REPORT WIM #39 MN 43, MP 45.2 WINONA, MN APRIL 2010 MONTHLY REPORT In order to understand the vehicle classes and groupings the Mn/DOT Vehicle Classification Scheme and the Vehicle Class Groupings for Forecasting

More information

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics Synopsis: This paper describes the use of AC power supplies

More information

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS 2013 NDIA GROUND VEHICLE SYSTEMS ENGINEERING AND TECHNOLOGY SYMPOSIUM POWER AND MOBILITY (P&M) MINI-SYMPOSIUM AUGUST 21-22, 2013 TROY, MICHIGAN HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

More information

Abstract. Background and Study Description

Abstract. Background and Study Description OG&E Smart Study TOGETHER: Technology-Enabled Dynamic Pricing Impact Evaluation Craig Williamson, Global Energy Partners, an EnerNOC Company, Denver, CO Katie Chiccarelli, OG&E, Oklahoma City, OK Abstract

More information

Accelerating the Development of Expandable Liner Hanger Systems using Abaqus

Accelerating the Development of Expandable Liner Hanger Systems using Abaqus Accelerating the Development of Expandable Liner Hanger Systems using Abaqus Ganesh Nanaware, Tony Foster, Leo Gomez Baker Hughes Incorporated Abstract: Developing an expandable liner hanger system for

More information

Improve quality, reduce scrap & determine machine efficiency

Improve quality, reduce scrap & determine machine efficiency Process Monitoring Quality castings, understand variation causes. Improve quality, reduce scrap & determine machine efficiency Monitor, archive, and analyze shot data from multiple machines and give your

More information

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li

More information

Long-Term Costs and Savings of Properly Rewound Motors

Long-Term Costs and Savings of Properly Rewound Motors Long-Term Costs and Savings of Properly Rewound Motors Erin Hope, Bonneville Power Administration Dennis Bowns, Green Motors Practices Group ABSTRACT Industrial facilities send thousands of motors to motor

More information

It s What s Inside that Counts

It s What s Inside that Counts It s What s Inside that Counts Drive Basics Adjustable Frequency Drive Description: Solid State Device Controls the Frequency and Voltage Speed Range Depends on the Motor HP Range - Fractional to 10,000

More information

Appendix B CTA Transit Data Supporting Documentation

Appendix B CTA Transit Data Supporting Documentation RED ED-PURPLE BYPASS PROJECT ENVIRONMENTAL ASSESSMENT AND SECTION 4(F) EVALUATION Appendix B CTA Transit Data Supporting Documentation 4( Memorandum Date: May 14, 2015 Subject: Chicago Transit Authority

More information

SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017*

SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017* SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017* PRODUCT: Screw-Type Superchargers 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for evaluating

More information

1 On Time Performance

1 On Time Performance MEMORANDUM: US 29 Travel Time & OTP To: From: Joana Conklin, Montgomery County DOT James A. Bunch, SWAI Subject: US 29 Travel Time and On Time Performance Analysis Date: This memorandum documents the US

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD June 1, 2018 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

AMS ValveLink SNAP-ON Applications

AMS ValveLink SNAP-ON Applications Product Data Sheet AMS ValveLink SNAP-ON Applications n Communicate with both HART and FOUNDATION fieldbus FIELDVUE digital valve controllers in the same application n Online, in-service performance diagnostics

More information

e-mac Electric. Efficient. Compact & precise.

e-mac Electric. Efficient. Compact & precise. e-mac Electric. Efficient. Compact & precise. All-electric. Best-in-class efficiency and precision to the max. All of the ENGEL e-mac s movements are performed by servo-electric drives. The all-electric

More information

Electromagnetic Fully Flexible Valve Actuator

Electromagnetic Fully Flexible Valve Actuator Electromagnetic Fully Flexible Valve Actuator A traditional cam drive train, shown in Figure 1, acts on the valve stems to open and close the valves. As the crankshaft drives the camshaft through gears

More information

Safe, fast HV circuit breaker testing with DualGround technology

Safe, fast HV circuit breaker testing with DualGround technology Safe, fast HV circuit breaker testing with DualGround technology Substation personnel safety From the earliest days of circuit breaker testing, safety of personnel has been the highest priority. The best

More information

L-force. MF three-phase AC motors. Phone: Fax: Web: -

L-force. MF three-phase AC motors. Phone: Fax: Web:  - L-force MF three-phase AC motors Suheadline TheMix Simply B7 bold multiple negativ Optimised for frequency inverter operation 2 More than a third of newly installed three-phase AC motors are now operated

More information

ENERGY & UTILITIES. Electricity Metering & Sub-Metering Concepts and Applications. BuildingsOne April 30, 2018

ENERGY & UTILITIES. Electricity Metering & Sub-Metering Concepts and Applications. BuildingsOne April 30, 2018 BuildingsOne April 30, 2018 The measurement of base building systems and tenantspecific equipment electricity consumption, through submetering applications, is increasing in importance within the commercial

More information

London calling (probably)

London calling (probably) London calling (probably) Parameters and stochastic behaviour of braking force generation and transmission Prof. Dr. Raphael Pfaff Aachen University of Applied Sciences pfaff@fh-aachen.de www.raphaelpfaff.net

More information

Examples of Electric Drive Solutions and Applied Technologies

Examples of Electric Drive Solutions and Applied Technologies Examples of Electric Drive Solutions and Applied Technologies 2 Examples of Electric Drive Solutions and Applied Technologies Atsushi Sugiura Haruo Nemoto Ken Hirata OVERVIEW: Hitachi has worked on specific

More information

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train K.Ogawa, T.Yamamoto, T.Hasegawa, T.Furuya, S.Nagaishi Railway Technical Research Institute (RTRI), TOKYO,

More information

Generator Efficiency Optimization at Remote Sites

Generator Efficiency Optimization at Remote Sites Generator Efficiency Optimization at Remote Sites Alex Creviston Chief Engineer, April 10, 2015 Generator Efficiency Optimization at Remote Sites Summary Remote generation is used extensively to power

More information

Electric Vehicle Charging Efficiency in Extremely High Temperatures

Electric Vehicle Charging Efficiency in Extremely High Temperatures September 2018 Electric Vehicle Charging Efficiency in Extremely High Temperatures The National Center for Sustainable Transportation Undergraduate Fellowship Report Jon Gordon, Plug-in Hybrid and Electric

More information

SMART Emissions Reducer Trial Program Data Report

SMART Emissions Reducer Trial Program Data Report 150 Main Street Ogdensburg NJ, 07439 Office: 973-209-3450 Fax: 973-209-4796 www.extremeenergysolutions.net SMART Emissions Reducer Trial Program Data Report Philadelphia Parking Authority 3101 Market Street,

More information

Special edition paper Development of an NE train

Special edition paper Development of an NE train Development of an NE train Taketo Fujii*, Nobutsugu Teraya**, and Mitsuyuki Osawa*** Through innovation of the power system using fuel cells or hybrid systems, JR East has been developing an "NE train

More information

Starts, stops and protects. Emotron TSA Softstarter

Starts, stops and protects. Emotron TSA Softstarter Starts, stops and protects Emotron TSA Softstarter First in a new line of CG high performance softstarters Emotron TSA softstarters take motor control to a new level. Soft torque starting, intelligent

More information

Exploring Electric Vehicle Battery Charging Efficiency

Exploring Electric Vehicle Battery Charging Efficiency September 2018 Exploring Electric Vehicle Battery Charging Efficiency The National Center for Sustainable Transportation Undergraduate Fellowship Report Nathaniel Kong, Plug-in Hybrid & Electric Vehicle

More information

Featured Articles Utilization of AI in the Railway Sector Case Study of Energy Efficiency in Railway Operations

Featured Articles Utilization of AI in the Railway Sector Case Study of Energy Efficiency in Railway Operations 128 Hitachi Review Vol. 65 (2016), No. 6 Featured Articles Utilization of AI in the Railway Sector Case Study of Energy Efficiency in Railway Operations Ryo Furutani Fumiya Kudo Norihiko Moriwaki, Ph.D.

More information

PUBLICATION NEW TRENDS IN ELEVATORING SOLUTIONS FOR MEDIUM TO MEDIUM-HIGH BUILDINGS TO IMPROVE FLEXIBILITY

PUBLICATION NEW TRENDS IN ELEVATORING SOLUTIONS FOR MEDIUM TO MEDIUM-HIGH BUILDINGS TO IMPROVE FLEXIBILITY PUBLICATION NEW TRENDS IN ELEVATORING SOLUTIONS FOR MEDIUM TO MEDIUM-HIGH BUILDINGS TO IMPROVE FLEXIBILITY Johannes de Jong E-mail: johannes.de.jong@kone.com Marja-Liisa Siikonen E-mail: marja-liisa.siikonen@kone.com

More information

MIT ICAT M I T I n t e r n a t i o n a l C e n t e r f o r A i r T r a n s p o r t a t i o n

MIT ICAT M I T I n t e r n a t i o n a l C e n t e r f o r A i r T r a n s p o r t a t i o n M I T I n t e r n a t i o n a l C e n t e r f o r A i r T r a n s p o r t a t i o n Standard Flow Abstractions as Mechanisms for Reducing ATC Complexity Jonathan Histon May 11, 2004 Introduction Research

More information

Application of DSS to Evaluate Performance of Work Equipment of Wheel Loader with Parallel Linkage

Application of DSS to Evaluate Performance of Work Equipment of Wheel Loader with Parallel Linkage Technical Papers Toru Shiina Hirotaka Takahashi The wheel loader with parallel linkage has one remarkable advantage. Namely, it offers a high degree of parallelism to its front attachment. Loaders of this

More information

Compressed Air Efficiency: A Case Study Combining Variable Speed Control with Electronic Inlet Valve Modulation

Compressed Air Efficiency: A Case Study Combining Variable Speed Control with Electronic Inlet Valve Modulation 2013-01-0834 Compressed Air Efficiency: A Case Study Combining Variable Speed Control with Electronic Inlet Valve Modulation Author, co-author (Do NOT enter this information. It will be pulled from participant

More information

Southern California Edison Company Demand Response Appendices to SCE-1, Volumes 1-4 ERRATA Replacing Appendix D, Pages D-1 & D-3

Southern California Edison Company Demand Response Appendices to SCE-1, Volumes 1-4 ERRATA Replacing Appendix D, Pages D-1 & D-3 Application No.: Exhibit No.: Witness: A.11-03-003 SCE-1, Volume 5 (Appendices to SCE-1 Volumes 1 4) - ERRATA (U 338-E) Southern California Edison Company Demand Response Appendices to SCE-1, Volumes 1-4

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Legal Metrology Control of a Liquefied Petroleum Gas Transfer Standard and Field Practice

Legal Metrology Control of a Liquefied Petroleum Gas Transfer Standard and Field Practice Legal Metrology Control of a Liquefied Petroleum Gas Transfer Standard and Field Practice Kun-Chih Tsai, Win-Ti Lin, Jiunn-Haur Shaw, Cheng-Tsair Yang, Chun-Min Su Center for Measurement Standards, CMS/ITRI

More information

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS MCD 3000 Soft starter THE PERFECT SOFTENER OF ROUGH STARTS The MCD Soft starter ranging from 7.5 to 800 kw is the optimum solution to a range of

More information

Effect of Sample Size and Method of Sampling Pig Weights on the Accuracy of Estimating the Mean Weight of the Population 1

Effect of Sample Size and Method of Sampling Pig Weights on the Accuracy of Estimating the Mean Weight of the Population 1 Effect of Sample Size and Method of Sampling Pig Weights on the Accuracy of Estimating the Mean Weight of the Population C. B. Paulk, G. L. Highland 2, M. D. Tokach, J. L. Nelssen, S. S. Dritz 3, R. D.

More information

FINAL REPORT AP STATISTICS CLASS DIESEL TRUCK COUNT PROJECT

FINAL REPORT AP STATISTICS CLASS DIESEL TRUCK COUNT PROJECT FINAL REPORT AP STATISTICS CLASS 2017-2018 DIESEL TRUCK COUNT PROJECT Authors: AP Statistics Class 2017-2018 Table of Contents SURVEY QUESTION...p. 2 AIR QUALITY...p. 3-4 TOTAL TRUCK COUNTS.p. 5 TRUCK

More information

FOR IMMEDIATE RELEASE

FOR IMMEDIATE RELEASE Article No. 7433 Available on www.roymorgan.com Roy Morgan Unemployment Profile Friday, 12 January 2018 2.6m Australians unemployed or under-employed in December The latest data for the Roy Morgan employment

More information