1 CONVENTION & EXHIBITION (PUTRAJAYA) SDN. BHD. Co-X/FMD/SOP05 Revision No.: 01 Effective Date: 15 th December 2017 PREPARED BY REVIEWED BY APPROVED BY Name: Name: Name: Designation: Designation: Designation:
2 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 2 of 8 REVISION HISTORY Rev. No DCN No. Description of Changes Effective Date Initial Release 15/12/17
3 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 3 of OBJECTIVE The objective of this procedure is to provide a system flow for the main electrical system from Tenaga Nasional Berhad (TNB) substation incoming power supply to Low Voltage (LV) system inside Putrajaya International Convention Centre (PICC) compound. 2.0 SCOPE 2.1 This procedure shall apply to all High Tension (HT) and Low Voltage (LV) system inside Putrajaya International Convention Centre (PICC) compound High Tension (HT) system including transformer and and all HT subsystem Low Voltage (LV) system including Main Switch Board (MSB), Essential Main Switch Board (EMSB) and all LV sub-system Generator set system. 3.0 DEFINITION 3.1 Co-X : Convention & Exhibition (Putrajaya) Sdn. Bhd. 3.2 PICC : Putrajaya International Convention Centre 3.3 ST : Suruhanjaya Tenaga 3.4 TNB : Tenaga Nasional Berhad 3.5 HT : High Tension 3.6 LV : Low Voltage 3.7 VCB : Vacum Circuit Breaker 3.8 Chargeman B0 : Chargeman certified with B0 level by Suruhanjaya Tenaga 3.9 Chargeman A4 : Chargeman certified with A4 level by Suruhanjaya Tenaga 3.10 Chargeman A0 : Chargeman certified with A0 level by Suruhanjaya Tenaga 3.11 MSB : Main Switch Board 3.12 EMSB : Essential Main Switch Board 3.13 DC : Direct Current 3.14 TX : Tagging code for electric transformer 4.0 RESPONSIBILITY 4.1 The Document Controller shall oversee all documents and records are properly managed at all time. 4.2 Authorized person with minimum competency level Chargeman B0 certified by ST and hired by Co-X to monitor and conduct any activities involving HT system. 4.3 Authorized person with minimum competency level Chargeman A0 certified by ST and hired by Co-X to monitor and conduct any activities involving LV system. 4.4 Authorized person with minimum competency level Chargeman A4 certified by ST and hired by Co-X to monitor and conduct any activities involving generator set.
4 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 4 of REFERENCE 5.1 Electrical Supply Act 1994 Act 447 Act Electrical Regulation Safety Work Procedure Guide For Electrical Work by ST 5.4 Co-X/FMD/SOP01 - Preventive Maintenance & Equipment Management
5 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 5 of PROCEDURE 6.1 Rules And Regulation Only authorised person with minimum allowable competancy level authorised to operate any main electrical equipment or system: Chargeman B0 (All main electical equipment and system) Chargeman A4 (Generator set and LV equipment and system only) Chargeman A0 (LV equipment and system only) Any act of violation of item shall be liable to a fine not exceeding RM10,000 and a fine not exceeding RM1,000 for every day or part of a day during which the violation is continued after the conviction (Section 23, Electrical Supply Act 1994) Any act which may cause harm to life and human limbs, damage to any equipment or property may be fined not exceeding RM100,000 or imprisonment not exceeding 5 years or both (Section 37, Electrical Supply Act 1994) All electrical systems must be certified with Pendaftaran Perpasangan by ST and need to be renewed from time to time (Section 21, Electrical Supply Act 1994). 6.2 HT System HT system function is to receive/cut off 11kV electrical supply from TNB substation Transformer will step down the 11kV electrical supply to 415V (LV system compatible load) Transformer TX1, TX2, TX3 and TX4 applied for PICC building electrical load Transformer TX5 and TX6 applied for chiller plant electrical load Daily round and reading for HT system are as per listed in Table 1 and recorded in High Tension Round & Reading Checklist (Co- X/FMD/SOP03-R01). Any reading exceedin the maximum or minimum limit must be highlighted to HOD.
6 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 6 of 8 NO DESCRIPTION UNIT READING LIMIT MINIMUM MAXIMUM 1. VCB incoming electrical supply: 1.1 Ampere 1.2 Voltage (kilo-volt) A kv DC Battery Charger 2.1 Ampere 2.2 Voltage A V Transformer temperature (Celsius) o c Table 1: HT system equipment for routine monitoring PPM for HT system frequency as per Plan Preventive Maintenance (PPM) (Co-X/FMD/SOP01-R03) schedule. 6.3 LV System LV system function is to distribute the 415V power supply from HT system to MSB and EMSB before further distributed to the building Daily round and reading equipment monitoring for LV system are as per listed in Table 2 and recorded in Low Voltage & Generator Set Round & Reading Checklist (Co-X/FMD/SOP03-R02). Any reading exceeding the maximum or minimum limit must be highlighted to HOD. NO DESCRIPTION UNIT READING LIMIT MINIMUM MAXIMUM 1. MSB reading: 1.1 Ampere 1.2 Voltage A V 1, , EMSB reading: 2.1 Ampere 2.2 Voltage A V , Power Factor Table 2: LV system equipment for routine monitoring PPM for LV system frequency as per Plan Preventive Maintenance (PPM) (Co-X/FMD/SOP01-R03) schedule Maintenance and operation for chiller plant is fully operated by Gas District Cooling (M) Sdn. Bhd.
7 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 7 of Generator Set Generator set function as back-up power supply source and will be run automatically if there are any electrical failure / disruption at HT system Routine monitoring for generator set system are recorded in Low Voltage & Generator Set Routine Checklist (Co-X/FMD/SOP05- R02) Generator Set Duty Switch in AUTO mode at all time ACB Duty Switch must be in AUTO mode at all time Emergency Stop Button released at all time PPM for generator set frequency as Plan Preventive Maintenance (PPM) (Co-X/FMD/SOP01-R03) schedule. 7.0 RECORDS 7.1 Co-X/FMD/SOP01-R03 Plan Preventive Maintenance (PPM) Schedule 7.2 Co-X/FMD/SOP01-R08(a) Standby Diesel Generator Set Checklist 7.3 Co-X/FMD/SOP01-R08(b) LV Capacitor Bank Checklist 7.4 Co-X/FMD/SOP01-R08(c) High Voltage System Checklist 7.5 Co-X/FMD/SOP01-R08(d) Low Voltage Checklist 7.6 Co-X/FMD/SOP05-R01 High Tension Round & Reading Checklist 7.7 Co-X/FMD/SOP05-R02 Low Voltage & Generator Set Round & Reading Checklist 8.0 APPENDIX / ATTACHMENT 8.1 Process Flow
8 REFERENCE NO. Co-X/FMD/SOP05 PAGE NO. Page 8 of 8 PROCESS FLOW RESPONSIBILITY OUTLINE ACTION - TNB 1 TNB 1 TNB - Provide electrical supply for Substation 1 (Semenyih) Substation 2 (Cyberjaya) PICC building - Chargeman B0 (and 2 HT Panel - Receive / cut-off 11kV incoming electrical supply No 3 Power Supply? Yes - Chargeman B0 (and 4 4 Transformer (TX1 to TX4) Transformer (TX5 and TX6) - Step-down electrical supply from 11kV to 415V - Chargeman A0 (and - Gas District Cooling (M) Sdn Bhd 5a LV Panel 5b LV Panel (Chiller Plant) - Distribute electrical supply to MSB / EMSB - Chargeman A4 (and - Gas District Cooling (M) Sdn Bhd 6 Generator Set - Back-up electrical supply when electrical disruption / failure at HT / LV system. - Chargeman A0 (and - Gas District Cooling (M) Sdn Bhd 7a MSB / EMSB 7b MSB / EMSB (Chiller Plant) - Provide electrical supply to electrical distribution system - Gas District Cooling (M) Sdn Bhd 8b Chiller Plant Load - Chiller plant equipment such as chiller, cooling tower etc. 8a Electrical Riser & Distribution - Refer Co-X/FMD/SOP05 Area fully operated by Gas District Cooling (M) Sdn Bhd
Appendix Item Addendum
Addendum to ESAH Version 3 Supply Application Appendix Item Addendum 1 Electrical System Item 1.4.5 Short Circuit Ratings Addendum for type of short circuit rating for system voltage of 275kV. 2 Types
More informationBTE2413: Electrical Power System
For updated version, please click on http://ocw.ump.edu.my BTE2413: Electrical Power System Chapter 1 Introduction to Power System Engineering Dr. Waheb A. Jabbar Faculty of Engineering Technology waheb@ump.edu.my
More informationSYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test)
ANNEXURE I SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) Paper I & Paper II for General Category of S.C.C. Examination Paper I & Paper
More informationAgility in energy Ahead of the challenge, ahead of the change
European Utility Week Vienna, November 3-5, 2015 Agility in energy Ahead of the challenge, ahead of the change Go-ahead application for existing distribution grids combines availability and efficiency
More informationNational Certificate in Electricity Supply (Sub Station Maintainer) (Level 4)
NZQF NQ Ref 1118 Version 2 Page 1 of 7 (Sub Station Maintainer) (Level 4) Level 4 Credits 140 This qualification has been reviewed. The last date to meet the requirements is 31 December 2018. Transition
More informationSubstation LV AC Supplies. Document Number: 1-11-FR-04
Substation LV AC Supplies Document Number: 1-11-FR-04 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-04 LV AC Supplies Asset Class Strategy Intellectual
More informationTenaga Nasional Berhad - SWOT Analysis
Tenaga Nasional Berhad - SWOT Analysis Tenaga Nasional Berhad - SWOT Analysis Sector Publishing Intelligence Limited (SPi) has been marketing business and market research reports from selected publishers
More informationPORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE
PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE Page 1 of 6 1. SUMMARY... 3 1.1 USE OF PORTABLE ELECTRICAL EQUIPMENT... 3 1.2 FAULTY EQUIPMENT... 3 2. PURPOSE & SCOPE... 3 3. DEFINITIONS... 3 3.1
More informationSCHEDULED RATING REVIEWS FOR 2018 (In Monthly Chronological Order)
SCHEDULED RATING REVIEWS FOR 2018 (In Monthly Chronological Order) No Issuer Issue Description Industry Description 1 Jimah East Power Sdn Bhd RM10.0 billion Sukuk Murabahah Programme Power January 2 Konsortium
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationSeremban Gemas Electrified Double Track Project, Malaysia
Seremban Gemas Electrified Double Track Project, Malaysia Electrification Works at a Glance Electrification, the need of time. The need for efficient, eco-friendly and well-integrated public transport
More informationNPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links
Version:- 7.0 Date of Issue:- July 2017 Page 1 of 19 NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links 1. Purpose The purpose of this document is to detail
More informationSCHEDULED RATING REVIEWS FOR 2016 (In Monthly Chronological Order)
SCHEDULED RATING REVIEWS FOR 2016 (In Monthly Chronological Order) No Issuer Issue Description Industry Description 1 The Bank of East Asia, Limited Financial Institution Rating Financial Institution January
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More informationGENERATOR INTERCONNECTION APPLICATION
GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW Also Serves as Application for Category 3 Net Metering (Note:
More informationNational Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance
National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and Guidance WASHING HIGH VOLTAGE INSULATORS USING PORTABLE WASHING EQUIPMENT Copyright National Grid plc 2014, all rights reserved.
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationREFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS
TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3
More informationNational Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance
National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and HIGH VOLTAGE METAL CLAD SWITCHGEAR WITH SPOUTS Copyright National Grid plc 2014, all rights reserved. No part of this publication
More informationBASIC ELECTRICAL PROGRAMME
2017 Proposal on BASIC ELECTRICAL PROGRAMME (Medium Pressure Course) ANOTHER VALUE ADDED PROGRAMME ENTITLED ENHANCING AND EMPOWERING TECHNICAL WORKFORCE Venue KEDAH INDUSTRIAL SKILLS AND MANAGEMENT DEVELOPMENT
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationATTACHMENT - DFO STATEMENT OF NEED
ATTACHMENT - DFO STATEMENT OF NEED Table of Contents Executive Summary... 3 1. Description of the Area... 5 1.1 Geographic Study Area... 5 1.2 Current System Configuration... 7 1.3 Distributed Generation...
More informationSALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-27 CUSTOMER GENERATION PRICE PLAN FOR RESIDENTIAL SERVICE
SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-27 CUSTOMER GENERATION PRICE PLAN FOR RESIDENTIAL SERVICE Effective: April 2015 Billing Cycle AVAILABILITY: The E-27 Price Plan is subject
More informationCouncil of the European Union Brussels, 18 July 2014 (OR. en)
Council of the European Union Brussels, 18 July 2014 (OR. en) 11932/14 ADD 1 TRANS 367 COVER NOTE From: European Commission date of receipt: 9 July 2014 To: General Secretariat of the Council No. Cion
More informationTECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)
TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop
More informationCONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS
LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low
More informationPROCEDURE. Operative Date: 22/12/2016 Department: HSEC. Revision: Author: D Steel CONTENTS
Title: Cranes - Inspection and Maintenance PROCEDURE Procedure No: P314.422 Issue: 1 Revision: 0 Operative Date: 22/12/2016 Department: HSEC Sect./Classification: Safety / Gear & Equipment Author: D Steel
More informationECS CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS
Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 03-0054 CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS EPN, LPN, SPN This standard details the procedures to be undertaken
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION
More informationSNZ TR 6120:2014. New Zealand Technical Report. Low voltage supply earthing systems SNZ TR 6120:2014
New Zealand Technical Report Low voltage supply earthing systems SNZ TR 6120:2014 COMMITTEE REPRESENTATION This technical report was prepared under the supervision of the LV Supply Earthing Systems Review
More informationSALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-21 PRICE PLAN FOR RESIDENTIAL SUPER PEAK TIME-OF-USE SERVICE
SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-21 PRICE PLAN FOR RESIDENTIAL SUPER PEAK TIME-OF-USE SERVICE Effective: April 2015 Billing Cycle Supersedes: November 2012 Billing Cycle
More informationPURPOSE... 1 II. SCOPE... 2 III. REFERENCES... 2 IV. RESPONSIBILITIES...
Reed College 3203 Southeast Woodstock Blvd. Portland Oregon 97202-8199 Crane Safety Policy Effective Date: Revision Dates: February 9, 2011, June 25, 2012, July 2016 Review Dates: I. PURPOSE... 1 II. SCOPE...
More informationMarina Bay Sands Guidelines for Electrical and Wiring Service
Marina Bay Sands Guidelines for Electrical and Wiring Service 1) The supply of electrical mains in the licensed area of the event is an exclusive service offered by Marina Bay Sands (MBS). In the event
More informationElectrical Equipment and Safety: Operation, Control, Maintenance and Troubleshooting
Electrical Equipment and Safety: Operation, Control, Maintenance and Troubleshooting Page 1 of 6 Why Attend This course covers the theoretical and practical operation of common electrical equipment and
More information33kV Connection up to 90MVA
Electricity Specification 217 Issue 2 December 2007 33kV Connection up to 90MVA Contents 1 Scope 2 General 3 Connection Arrangements 4 Equipment Records 5 Documentation 6 Documents Referenced 7 Keywords
More informationMarch 18, Subject: Imperial Irrigation District 2014 Annual Progress Report - Rev 1
Energy Division P.O. Box 937 333 E. Barioni Blvd. Imperial, CA 92251 www.iid.com March 18, 2014 Mr. Tracy Rolstad Chair, WECC Technical Studies Subcommittee Senior Power System Consultant Avista System
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationLIFT TRUCK POLICY AND PROGRAM
LIFT TRUCK POLICY AND PROGRAM Table of Contents 1.0 Policy Statement and Program Overview... 4 2.0 Lift Truck Applicable Legislation, Guidelines and Standards... 4 3.0 Forklift Program Requirements...
More informationUniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions
UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that
More information2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT
41-348.11C SA-1 Generator Differential Relay - Class 1E 2.0 CONSTRUCTION The type SA-1 relay consists of: Restraint Circuit Sensing Circuit Trip Circuit Surge Protection Circuit Operating Circuit Amplifier
More informationAlberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation
Decision 21781-D01-2016 Alberta Electric System Operator Needs Identification Document Application Facility Applications September 7, 2016 Alberta Utilities Commission Decision 21781-D01-2016: Alberta
More informationMedium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient
Medium voltage NEX switchgear Withdrawable circuit breaker Quite simply efficient NEX, a simple and flexible solution NEX is the result of worldwide acquired experience and provides you with a high level
More informationELD Mandate Survival Guide
The Complete ELD Mandate Survival Guide Page 02 What is the Mandate? Page 04 What are ELDs? Page 05 Who is Affected? This rule requires drivers to keep an electronic log of the time they spend driving,
More informationControlling the Speed of Tilting Trains Through Curves
Controlling the Speed of Tilting Trains Through Curves Synopsis This document mandates the means by which Tilting Trains may be operated at higher speeds than nontilting trains around curves. Signatures
More informationThe Road to Safety and Compliance Starts with You! ISRI DOT Self-Audit Checklist
The Road to Safety and Compliance Starts with You! ISRI DOT Self-Audit Checklist ISRI DOT Self-Audit Checklist Disclaimer: The material herein is for informational purposes on and is provided on an as-is
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationTitle High Voltage and 1500 System Earthing References and Definitions. Reference Number PDS 02 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title High Voltage and 1500 System Earthing References and Definitions Reference Number PDS 02 (RIC Standard: EP 12 00 00 01 SP) Document Control
More informationVacuum Circuit Breaker VS1
Vacuum Circuit Breaker VS1 Product features Conform to GB, IEC, DL and JB standards KEMA type test Level A certificate Ideal contact material and shape, ensuring low current carrying value and stable contact
More informationAmendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV).
Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Sr. No. Clause No Existing Proposed 1 8.0 Dischar ge device 2 15.0
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 10/03/17 Specifications for Residential Construction Revision List REVISION Date Page No. Description 8/18/09 T.O.C., 8.1-8.1.5 &
More informationTECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008
NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0
More informationApplied Technology Services Overview
Applied Technology Services Overview Smart Grid Testing i-pggrid Workshop 2013 San Francisco 3/26/2013 Dave Bradley PG&E is a leader in distributed PV >60,000 installations >600 MW (CEC AC) ~ 30% of US
More informationUnitole UP kv Primary substations Motor control centres
Unitole UP 3.6-17.5 kv Primary substations Motor control centres Product Focus Air-insulated withdrawable switchgear with vacuum circuit-breakers and contactors Creating Solutions Eaton Holec creates power-engineering
More informationAUTO CHARGE AMPS DELUXE AUTOMATIC BATTERY CHARGER. Section 1: Single Battery Systems
DELUXE AUTOMATIC BATTERY CHARGER Section 1: Single Battery Systems 10 AUTO CHARGE 1000 SINGLE BATTERY SYSTEM AUTOMATIC BATTERY CHARGER & POWER SUPPLY 10 ELEMENT, WATERPROOF BAR GRAPH DISPLAY 18 AMPS TOTAL
More informationHigh Voltage Operating Rods
High Voltage Operating Rods Summary: This work instruction supports the Power System Safety Rules and its requirements assembled under Making High Voltage Apparatus Safe for Work Category 5.5; and Making
More informationTitle Low Voltage Distribution and Installations Earthing References and Definitions. Reference Number PDS 03 (ARTC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Low Voltage Distribution and Installations Earthing References and Definitions Reference Number PDS 03 (ARTC Standard: EP 12 00 00 02 SP) Document
More informationFor Public Comment DRAFT MALAYSIAN STANDARD
DRAFT MALAYSIAN STANDARD 14E003R0 j STAGE : PUBLIC COMMENT (40.20) DATE : 01/08/2015-30/09/2015 Crimping type hexagon dies for cable lugs, cable links and the rounding dies for sector cable - Installation
More informationCL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES
SERIES E-RATED / MEDIUM VOLTAGE FUSES 5kV AND 15kV CLIP-LOCK MOUNTED FUSES Amp-trap E-rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More information3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.
41-348.1H Type SA-1 2.1. RESTRAINT CIRCUIT The restraint circuit of each phase consists of a center-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are
More informationABB Wind Power Solution
Feng Li, Wind ISI, CNABB, November, 2016 ABB Wind Power Solution November 13, 2016 Slide 1 ABB deliveries from A to Z into the wind industry Wind power generation, transmission and integration, control
More informationAuthorized feedstocks, bulking agents, and additives and classification of composting facilities.
3745-27-40 1 3745-27-40 Authorized feedstocks, bulking agents, and additives and classification of composting facilities. (A) Feedstock types. The following feedstocks, as used in rules 3745-27-40 to 3745-27-47
More informationInvestment Incentive For Rubber Industry
MREPC REGIONAL SEMINAR Investment Incentive For Rubber Industry Present by Mr. Mohd Rasli Muda Director, Food Technology & Sustainable Resources Malaysian Investment Development Authority (MIDA) Contents
More informationGuide to the road TRANSPORT WORKING TIME DIRECTIVE. Údarás Um Shábháilteacht Ar Bhóithre Road Safety Authority
Guide to the road TRANSPORT WORKING TIME DIRECTIVE Údarás Um Shábháilteacht Ar Bhóithre Guide to the Road Transport Working Time Directive This guide explains the main aspects of the EU Directive 2002/15/EC
More informationVariable Frequency Drive Basics
Variable Frequency Drive Basics Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Variable Frequency Drives are
More informationParking Control Bylaw 2014
Parking Control Bylaw 2014 1 Thames-Coromandel District Council - Parking Control Bylaw 2014 1. TITLE 1.1. This Bylaw is the Thames-Coromandel District Council Parking Control Bylaw 2014. 2. EXPLANATORY
More informationDETAILS OF THE EXPRESSION OF INTEREST(EOI) NO.: PL.G03.EOI
DETAILS OF THE EXPRESSION OF INTEREST(EOI) NO.: PL.G03.EOI.09.001 Date: 29/05/2009 For Annual Operation and Maintenance Service Contract of HT/LT Panels,Motors,Transformers,UPS,Air Conditiners,Lightings
More informationCATEGORY 2 GENERATOR INTERCONNECTION APPLICATION
CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering
More informationEH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map
EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids
More informationKCP&L GREATER MISSOURI OPERATIONS COMPANY P.S.C. MO. No. 1 1st Revised Sheet No. 149 Canceling P.S.C. MO. No. 1 Original Sheet No.
P.S.C. MO. No. 1 1st Revised Sheet No. 149 Canceling P.S.C. MO. No. 1 Original Sheet No. 149 AVAILABILITY This schedule is available for all general service use, such as combined lighting and power service
More informationElectric Utility Contact Information Indiana Michigan Power
CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering
More informationSmart Grid Automation and Centralized FISR
Smart Grid Automation and Centralized FISR March 21, 2016 Mike Colby Senior Engineer Distribution Control Center Smart Grid Automation and Centralized FISR Remote Controlled Devices & Communication Distribution
More informationPRO POWER 2 0 A L I T H I U M B AT T E RY C H A R G E R M O D E L : P P - L B C V E R S I O N : V 1. 0
PRO POWER 2 0 A L I T H I U M B AT T E RY C H AR G E R M O D E L : P P - L B C - 1 2 2 0 V E R S I O N : V 1. 0 Contents 1. Revised History... 1 2. Warning... 1 3. Notes... 1 4. Product Number System...
More informationSpecifications, Testing, Inspection, Earthing & Protection. Our Consultant: Ir. Yap Chee Wah. 20 CCD Approved by CIDB
Specifications, Testing, Inspection, Earthing & Protection 29 & 30 NOVEMBER 2017 DORSETT GRAND SUBANG 20 CCD Approved by CIDB Our Consultant: Ir. Yap Chee Wah The course is aimed to cover the basic electrical
More informationSIARAN AKHBAR PRESS STATEMENT
SIARAN AKHBAR PRESS STATEMENT EMBARGO NOT TO BE PUBLISHED BEFORE 5.00 PM S.A. 2011/07/46 (HQ) TNB RECORDS NET LOSS OF RM440.2 MILLION IN 3 RD QUARTER FY2011 DUE TO SEVERE GAS CURTAILMENT 3 months ended
More informationJanuary 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.
3018 Eastpoint Parkway Louisville, KY 40223 (502) 716-7073 January 30, 2006 Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT Re: NFPA 70E Hazard Assessment Date of Visit January 24, 2006
More informationTransmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202
Transmission and Distribution Substation Projects Operating Company: Entergy Gulf States - Texas Customer: PID # 202 Funding Project Number: F4PPGS0386 Facility Study for PID # 202: Study for 146 MW Revision
More informationS H A D E S ELECTRICAL DB MANUFATURING
CORPORATE BROCHURE S H A D E S ELECTRICAL DB MANUFATURING S H D E S ELECTRICAL DB MANUFACTURING L.L.C. www.shadesdb.com I N T R O D U C T I O N Welcome to SHADES, this portfolio has been designed to give
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationMALAYSIAN STANDARD QUALITY MANAGEMENT SYSTEMS - REQUIREMENTS (FIRST REVISION) (ISO 9001:2008, IDT) (PUBLISHED BY STANDARDS MALAYSIA IN 2009)
MALAYSIAN STANDARD MS ISO 9001:2008 QUALITY MANAGEMENT SYSTEMS - REQUIREMENTS (FIRST REVISION) (ISO 9001:2008, IDT) (PUBLISHED BY STANDARDS MALAYSIA IN 2009) ICS: 03.120.10 Descriptors: quality management,
More informationCHANGE NOTICE. 5. Code Ident. 2B945 2B Effectivity All Units
1. The Boeing Company Post Office Box 58747 Houston, TX 77258 2. CHANGE NOTICE Proposed Approved 7. System Designation 8. Related ECP No./Title ISS SSCN 005008 11. Document Title Space Station Electromagnetic
More informationThe Introduction of Euro 5 and Euro 6 Emissions Regulations for Light Passenger and Commercial Vehicles
The Introduction of Euro 5 and Euro 6 Emissions Regulations for Light Passenger and Commercial Vehicles Introduction As a member of the European Union, Ireland is obliged to introduce Regulation (EC) No.
More informationDISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS
Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.
More information3.1 Air Pollution Control Officer (APCO): as defined in Rule 1020 (Definitions).
RULE 4352 SOLID FUEL FIRED BOILERS, STEAM GENERATORS AND PROCESS HEATERS (Adopted September 14, 1994; Amended October 19, 1995; Amended May 18, 2006; Amended December 15, 2011) 1.0 Purpose The purpose
More informationAutomatic DC Power Supply/Battery Charger
Automatic DC Power Supply/Battery Charger PATENTED U.S. 9,270,140; 9,385,556; 9,413,186; 9,509,164 NEW in 2015: Field selectable AC input voltage in high-powered units Automatic battery commissioning mode
More informationR-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism
R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite
More information(Non-legislative acts) DECISIONS
14.5.2011 Official Journal of the European Union L 126/1 II (Non-legislative acts) DECISIONS COMMISSION DECISION of 26 April 2011 concerning a technical specification for interoperability relating to the
More informationEE 456 Design Project
F-2014 EE 456 Design Project PROJECT REPORT MALUWELMENG, CONNIE SHARP, MEGAN Table of Contents Introduction... 2 Assignment I... 2 Setup... 2 Simulation... 2 Assignment II... 3 Problems... 3 Solution...
More informationScale of Inspection Fees of Electrical Inspectorate Schedule. I. Fees for Initial Inspections:
PART 7 Scale of Inspection Fees of Electrical Inspectorate Schedule I. Fees for Initial Inspections: SCALE A For an inspection or test of any generating station, receiving station or other places in which
More informationCORPORATE PROFILE ANPEC GLOBAL CORPORATION SDN BHD ( A)
ANPEC GLOBAL CORPORATION SDN BHD (655269-A) B2-1-36 Jalan Pinggiran 1/3 Taman Pinggiran Putra Seksyen 1 43300 Seri kembangan Selangor Darul Ehsan Malaysia Tel : +6 03 8942 8991 Fax : +6 03 8945 8455 URL
More informationBP OIL -- TOLEDO REFINERY
BP OIL -- TOLEDO REFINERY Document Type: Procedure Effective Date: August 31, 2017 Owner: Dane P. Clark Refinery Wide Electrical Distribution System Switching and Isolation Auth. By: Rick J. Chmelovski
More informationMESP TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION Version: 2 Issued: August 2016 Owner: Head of Engineering
More informationDFO STATEMENT OF NEED REPORT
APPENDIX E DFO STATEMENT OF NEED REPORT Table of Contents 1.0 Executive Summary... 1 2.0 Description of the Area... 2 2.1 Geographic Study Area... 2 2.2 2016 System Configuration... 2 3.0 Area Loading
More informationUpdates and Modifications to Report
QUARTERLY COMPLIANCE REPORT (JULY 2015) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision
More information(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:
10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1
More information37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS
SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 04/25/18 Specifications for Residential Construction Revision List REVISION Date Page No. Description 03/20/00 6.1-6.2 Added Armorcast
More information