1 Quick guide Plug-in fans GPPM with FC101_106 August 2014
2 Fläkt Woods permanent magnet motors and speed controllers for plug fans GPPM 1. General Fläkt Woods offers a wide range of permanent magnet motors (PM) and speed controllers for plug fans. PM motor has high efficiency (IE4) due to the permanent magnets in rotor. Also part load efficiency is better compared to asynchronous motors. When rotor has no losses and stator needs less current, temperature inside the motor is lower and it gives longer running time for bearings. Direct on-line connection is not possible for permanent magnet motors. Speed controller is always needed. This controller has special algorithm for PM motors. Speed controller is programmed with fan and motor specific parameters. 2. Speed controller alternatives Speed controllers can be delivered as an integrated version or separately. Controller integrated to motor is available up to 7.5 kw and separate controllers up to 11 kw. 2
3 IP54 speed controller mounted at AHU casing. Separate speed controller should be mounted near the fan. Motor cable shall not be no longer than 10 m. With longer cables some motor parameters should be changed. Speed controller is delivered with 3.5 m motor cable for fan sizes up to 050. For bigger fans motor cable length is 4.5 m. 3
4 3. Fan and motor data Fan code Motor code including drive Power [kw] Motor Current [A] Frame Size Max speed [rpm] Max freq. [Hz] Nominal speed [min -1 ] Motor weight [kg] GPPM APPM e 0,8 1, ,8 GPPM APPM e 1,5 3, ,4 GPPM APPM e 0,8 1, ,8 GPPM APPM e 1,5 3, ,2 GPPM APPM e 2,2 4, GPPM APPM e 1,1 2, ,4 GPPM APPM e 1,8 3, GPPM APPM e 3 6, ,6 GPPM APPM e 1,1 2, ,4 GPPM APPM e 1,5 3, ,1 GPPM APPM e 2,2 4, ,6 GPPM APPM e 3, GPPM APPM e 1,1 2, , ,1 GPPM APPM e 1,8 3, , ,6 GPPM APPM e 3, GPPM APPM e 4 9, GPPM APPM e 1,1 2, ,1 GPPM APPM e 1,8 3, , ,6 GPPM APPM e 4 9, GPPM APPM e 5, GPPM APPM e 2, GPPM APPM e 3,6 7, GPPM APPM e 4,8 10, ,5 GPPM APPM e 7,5 14, GPPM APPM e 2,2 5, GPPM APPM e 4 9, GPPM APPM e 5,5 10, , GPPM APPM e 7,5 14, , GPPM APPM e 2, GPPM APPM e 5,5 11, , GPPM APPM e 7,5 15, , ,5 GPPM APPM e 11 20, GPPM APPM e 3 8, GPPM APPM e 5, GPPM APPM e 7,5 15, , ,5 4
5 Fan code Motor code including drive Power [kw] Motor Current [A] Frame Size Max speed [rpm] Max freq. [Hz] Nominal speed [min -1 ] GPPM APPM e GPPM APPM e 5,5 11, , GPPM APPM e 7,5 15, GPPM APPM e 11 24, , GPPM APPM e 7,5 16, , GPPM APPM e 11 22, GPPM APPM e 7,5 15, GPPM APPM e 11 22, , kw motors only with separate speed controller Motor weight [kg] 4. Speed controller data for separate and integrated versions Mains supply (L1, L2, L3) Supply voltage V ±10% Supply frequency 50/60 Hz Max. imbalance temporary between mains phases 3.0 % of rated supply voltage True Power Factor (λ) 0.9 nominal at rated load Displacement Power Factor (cosφ) near unity (> 0.98) Switching on input supply L1, L2, L3 (power-ups) maximum 2 times/min. Environment according to EN overvoltage category III/pollution degree 2 Motor output (U, V, W) Output voltage Output frequency for PM motors 0-100% of supply voltage Hz Digital inputs: Programmable digital inputs 4 Logic PNP or NPN Voltage level 0-24 V DC Analog inputs: Number of analog inputs 2 Modes Voltage or current Voltage level 0 to + 10 (scalable) Current level 0/4 to 20 ma (scalable) Analog output: Number of programmable analog outputs 2 Current range at analog output 0/4-20 ma Digital output: Programmable digital 2 Voltage level at digital 17 V 5
6 Max. current at digital output: 20 ma Relay outputs: Programmable relay outputs 2 Max. terminal load (AC-1 Resistive load) 250 V AC, 3 A Control card, 10 V DC output: Output voltage Max. load Control card, 24 V DC output: Max. load 10.5 V ±0.5 V 25 ma 80 ma Surroundings: Enclosure separate unit IP 54 Enclosure integrated unit IP 55 Vibration test separate unit 1.0 g Vibration test integrated unit 2.0 g Max. relative humidity, during operation 5% - 95%(non-condensing) Maximum ambient temperature 40 C Minimum ambient temperature during full-scale operation 0 C separate unit, -10 C integrated unit Fieldbus communication: Modbus RTU BACnet MSTP N2 Metasys FC Protocol Physical layer Built-in Built-in Built-in Built-in RS Separate speed controller dimensions Power Dimensions (mm) Weight (kw) Height Width Depth Hole diam. (kg) A a B b C D IP 54 0, , ,5 5,3 5,5...7, ,5 7, , ,5 13,8 6
7 6. Specification for motor Admissible environmental temperature: from -15 C up to +40 C, with altitudes 1000 m above sea level Mounting: IM B3 Drive operating voltage: 400 VAC Insulation class: "F"; temperature rise to class B (TEFC execution) IP55 degree of protection for the whole range Reduced dimensions 7. Installation Warning: Risk of electric shock. Motor terminals may still be Live if the impeller is rotating, even when the main incoming supplied has been isolated. Ensure the impeller is kept stationary before opening and whilst the terminal box is open. 7
8 Speed controller and motor shall be installed by a qualified electrician with adequate knowledge how to install speed-controlled drive systems (frequency inverters) and EMC safety. All cabling must comply with national and local regulations on cable cross-sections and ambient temperature 8. Connection diagram 9. Cabling 9.1 Supply cable Mount mains supply to terminals L1, L2 and L3 and ground wires to earth terminal and tighten. Short circuit protection: The speed controller must be protected against short-circuit to avoid electrical or fire hazard. The fuses mentioned below are recommended to use to protect service personnel 8
9 and equipment in case of an internal failure in the speed controller. Speed controller provides full short circuit protection in case of a short circuit on the motor output. Over current protection: Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The speed controller is equipped with an internal over-current protection that can be used for upstream overload protection (UL-applications excluded). See par Current Limit. Moreover, fuses or circuit breakers can be used to provide the over-current protection in the installation. Over-current protection must always be carried out according to national regulations. Leakage Current (>3,5mA) EN/IEC (Power Drive System Product Standard) requires special care if the leakage current exceeds 3,5mA. Earth grounding must be reinforced in one of the following ways: Earth ground wire of at least 10mm2 Two separate earth ground wires both complying with the dimensioning rules Isolation switch All speed controllers may be used with an isolated input source as well as with ground reference power lines. 9.2 Recommended fuses on the supply side Power (kw) x VAC Rec. non UL type gg See national/international regulations for selecting an applicable fuse size. 9.3 Motor cable with separate drive Speed controller is delivered with 3.5 m motor cable for fan sizes up to 050. For bigger fans motor cable length is 4.5 m. If it should be shortened or replaced with longer one few rules should be followed. Motor cable should be shielded type. Shield should be grounded 360 at both ends of cable. Motor cable should be no longer than 10 meters to achieve EMC-level EN Class B. Motor is connected to star inside the motor. Phase wires are connected to terminals U1, V1, W1. Terminal connectors are not needed. 9.4 Control cable 9
10 Control cable should be shielded. Keep control cable distance min 200 mm from mains and motor cable. 10 Control signals Start/Stop Fan is started with potential free switch connected between terminals 12 and 18. There is +24 VDC in this circuit. AUTO-mode should be selected from operation panel. Interlock By opening interlock signal between terminals fan can be stopped and then it s not possible to start from operating panel manually or via bus. With this signal fan running can be interlocked to circulating pump alarm or ventilation emergency stop. Speed reference Speed can be controlled with 0 10V signal connected in terminals 53(+) and 55(-). Relay outputs Alarm signal is available in relay1 (terminals 01, 02 and 03). Running indication is available in relay 2 (terminals 04, 05 and 06). Single speed operation: Set constant speed reference (Hz) in parameter 412. Only external start signal is needed. Two speed operation: Lower speed reference (Hz) is set in parameter 412 and higher speed reference (Hz) in parameter 311. Lower speed is activated with start signal (terminals 12-18). Higher speed is activated by closing terminals Modbus RTU Speed controller can be controlled via Modbus RTU. RS-485 cable is connected to the terminals 68 (P), 69 (N) and 61 (COM). If speed controller is last unit in line, it should be terminated by setting switch S801 in ON position. Modbus operation is described in speed controller operation instructions. 11. Start up and functional testing After power up test check motor rotation if separate speed controller is delivered: Set speed controller to Hand on mode from operation panel. Motor will start to rotate. For changing the direction of rotation, disconnect supply voltage and wait for power to discharge. Make sure that motor impeller is not rotating during making connections. Reverse the connection of any two of the three motor cables on the motor or frequency converter side of the connection. 10
11 When direction of rotation is right set speed controller to Auto on mode. Then speed controller will follow control signals. 12. Parameters Speed controller parameters are set at the factory providing for optimal performance of fan and motor. This includes motor parameters, ramp times, starting and stopping methods and speed limitations. Changing of these parameters may result unstable operation or motor won t start. Original parameter values can be downloaded from operation panel in case of losing them: Go to parameter 0-50 LPC Copy Set parameter value to 2 (All from LCP) Wait that copy is completed Parameters are password protected. Changing of motor parameters may cause motor failure. Password for main menu is 100 and for quick menu Operating panel Operating panel is standard in separate speed controller but accessory with integrated motor. 11
12 14. Alarms and warnings If alarm or warning messages appear, consult speed controller operating manual in place fault messages and troubleshooting. Warning! Speed controller tries to restart the motor after alarm so the fan may start automatically Protection and Features: Electronic thermal motor protection against overload. Temperature monitoring of the heatsink ensures that the speed controller trips if the temperature is too high. The speed controller is protected against short-circuits on motor terminals U, V, W. If a mains phase is missing, the speed controller trips or issues a warning (depending on the load). Monitoring of the intermediate circuit voltage ensures that the speed controller trips if the intermediate circuit voltage is too low or too high. The speed controller is protected against earth faults on motor terminals U, V, W. If the speed controller can t find rotor position, Locked Rotor alarm is generated Motor is stopped if motor back voltage is too high. Motor is stopped if 24V supply is too low 12
13 Motor is stopped if motor phase is missing Motor is stopped if inverter overloaded too long 13
FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER
FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when
More informationPhoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP
Phoenix DX Sensorless AC Vector Drive 3 HP to 3500 HP Standard Features: * PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR) * EASY TO USE, SIMPLE SETUP * POWER
More informationBT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
More informationMAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -
MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting
More informationCENTRIFLOW 3D WITH AC MOTOR >> Technical catalogue
CENTRIFLOW 3D plug fan WITH AC MOTOR >> Technical catalogue air comfort Centriflow 3D 2 GMEB CentriFlow 3D - Technical Catalogue Contents GENERAL Description and survey chart Application... 3 General Survey
More informationObserve all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary
More informationCENTRIFLOW 3D WITH AC MOTOR >> Technical catalouge
CENTRIFLOW 3D plug fan WITH AC MOTOR >> Technical catalouge air comfort Centriflow 3D 2 GMEB CentriFlow 3D - Technical Catalouge Contents GENERAL Description and survey chart Application... 3 General Survey
More informationSED2. Variable Frequency Drives. with Conventional Bypass Options. Variable Frequency Drives. Description. Features F-9.
SED2 with Conventional Bypass Options Important Note: VD products are only available through authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies
More information1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp
VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:
More informationDelta Products VFD CP2000 Bypass Control Packages.
Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products
More informationLow voltage AC drives
General machinery drives Main features and dimensions Unique features Fast and extensive I/O PID control Application macros Many installation possibilities 200 to 480 V, 1-phase or 3-phase More value for
More informationMAKING MODERN LIVING POSSIBLE. Instruction Manual. VLT AutomationDrive FC 300, kw
MAKING MODERN LIVING POSSIBLE Instruction VLT AutomationDrive FC 300, 0.25 75 kw Safety Safety WARNING HIGH VOLTAGE! Adjustable frequency drives contain high voltage when connected to AC line power. Installation,
More information1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp
VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:
More informationATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)
Product datasheet Characteristics ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/400...440V(45kW) Complementary Assembly style Function available Supply voltage limits Main Range of product
More informationMAKING MODERN LIVING POSSIBLE. Instruction Manual VLT AutomationDrive FC 300
MAKING MODERN LIVING POSSIBLE Instruction VLT AutomationDrive FC 300 Safety Safety WARNING HIGH VOLTAGE! Adjustable frequency drives contain high voltage when connected to AC line power. Installation,
More informationHigh performance Vector Control. Ratings. System configuration
System configuration High performance Vector Control Low harmonic or regenerative drive IP54 full range Compact design and robustness Built-in filter (according to C3 class) Built-in fuses (from 200 kw)
More informationVariable Frequency Drive NEW! Moving your Control. Forward VFD from Unitronics kW Single Phase kW Three Phase
Variable Frequency Drive Moving your Control NEW! Forward VFD from Unitronics 0.4-2.2kW Single Phase 0.75-110kW Three Phase Total Solution All-in-One software PLC programming HMI design NEW! VFD configuration
More informationROBICON W120 enclosed drive
SINAMICS Drives ROBICON W120 enclosed drive 1 HP to 200 HP Introduction This technical data sheet provides a short overview of the most important characteristics of the ROBICON W120 enclosed standard 6-pulse
More informationHVAC Products. Introducing the SED2 Variable Frequency Drives
HVAC Products Introducing the SED2 Variable Frequency Drives Designed Specifically for HVAC Applications From a global leader in drives technology and innovation, now comes a drive specifically configured
More informationsinamics SINAMICS G110 Variable Speed Drives 0.12 kw to 3 kw SINAMICS G110 Short Form 2004
Variable Speed Drives 0.12 kw to 3 kw Short Form 2004 sinamics SINAMICS Variable Speed Drives 0.12kW to 3kW Product Information Pricing The is a Variable Speed Drive with basic functions for a variety
More informationHIB Enclosed Inverter User Guide
HIB Enclosed Inverter User Guide (0.75kW~22kW) V1.2.0 Contents 1 Safety information...1 2 Technical Data...2 3 Motor Connection...4 4 Operation...5 5 Single phase circuit diagram...7 6 Three phase circuit
More informationSINUS PENTA 2T/4T SINUS PENTA 2T/4T
SINUS PENTA 2T/4T SINUS PENTA 2T/4T Technical Highlights One product, 5 integrated functions - IFD (Inverter Frequency Drive): vector modulation function for general-purpose applications (V/F pattern).
More informationDefender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications
Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting
More informationwww. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide
Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand
More informationDescription 1/8-7.5HP
Description 1/8-7.5HP J1000 In our pursuit to create drives optimized for variable speed needs in compact applications, the J1000 is the solution. This micro-drive is simple and reliable with Yaskawa quality.
More informationRVS-AX Instruction Manual
RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationCobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications
Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System
More informationPower Lynx 3 Uninterruptible Power System (UPS) Technical Specifications
Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible
More informationPresentation Soft starters 0 Altistart 48 soft start - soft stop units
Presentation Soft starters 5 6 7 65_Ver.-EN.fm/ Presentation (continued) Soft starters Applications The Altistart 8 soft start - soft stop unit is a controller with 6 thyristors which is used for the torque-controlled
More informationQUOTATION BLADE 7 LX. Product code GEAL6S2BAA
1 of 10 Mattei rotary vane compressors are the result of 90 years of investments in research and development to improve performance and lessen the impact on the environment. Designed for industrial continuous
More informationShipping volume [ft 3 ] 3 SQF-2 47 * 2.9 1" NPT Dimensions [in] L B S 3 SQF-3 49 * 2.9 1" NPT
Dimensions and weights ø5/16" ø8 S Pump type Dimensions [in] L B S Net weight [lb] Gross weight [lb] Shipping volume [ft 3 ] 3 SQF-2 47 * 2.9 1" NPT 17 21 0.85 3 SQF-3 49 * 2.9 1" NPT 17.5 21 0.85 6 SQF-2
More informationUSERS MANUAL MCD REMOTE OPERATOR
USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3
More informationHoneywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA
Honeywell CORE Drive SPECIFICATION DATA FEATURES APPLICATION The new Honeywell VFD CORE Drive addresses the need to save time for installation, and provides the lower total installed costs with years of
More informationVSD Series II Variable Speed Open Drives
VSD Series II Variable Speed Open Drives Product Bulletin Code No. LIT-12011824 Issued May 5, 2015 Refer to the QuickLIT website for the most up-to-date version of this document. The Johnson Controls VSD
More informationBurden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM
Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0
More informationUL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD
UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you
More informationFortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state
More informationNumber 1 in efficiency
PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter The
More informationModel ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase
Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible
More informationUnidrive M600 High performance drive for induction and sensorless permanent magnet motors
Unidrive M600 High performance drive for induction and sensorless permanent magnet motors 0.75 kw - 2.8 MW Heavy Duty (1.0 hp - 4,200 hp) 200 V 400 V 575 V 690 V Unidrive M600 features Easy click-in keypad
More informationWARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.
SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.
More informationFortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting
More informationA. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings
More informationVarispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES
INVERTER SERIES Varispeed E VARISPEED E YASKAWA INVERTER DRIVE TECHNOLOGY Contents Content Page 2 Experience & Innovation A leader in Drives technology Page 3 Specifications Experience & Innovation For
More informationJC-VSD FP Series II Drives Product Bulletin 1
JC-VSD FP Series II Drives Product Bulletin Code No. LIT-12012081 Issued May 2017 The Johnson Controls VSD FP Series II provides the advanced technology and features of the Johnson Controls VSD Series
More informationPhoenix Inverter
Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC
More informationVTZ variable speed Reciprocating compressors
MAKING MODERN LIVING POSSIBLE Application guidelines VTZ variable speed Reciprocating compressors R404A, R507, R407C, R134a www.danfoss.com CONTENT VARIABLE SPEED COMPRESSORS... 4 Speed control...4 Advantages
More informationALTIVAR FLEX58 Chassis Drive Controller Product Selection
ALTIVAR FLEX58 Chassis Drive Controller Product Selection Class 8806 CONTENTS Description Page General Information and Selection....................................... 2 Specifications and Ratings...........................................
More informationStandard Features 200-600V, 50/60Hz input power supply Built-in run rated (AC1) By-pass contactor up to 820 A * Rated 450% current Conformal coated circuit board Voltage ramp or current limit start modes
More informationMatrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages
More information1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8
Contents : 1. INTRODUCTION...1 2. IMPORTANT SAFETY INSTRUCTIONS...2 3. SYSTEM DESCRIPTION...4 3.1 Front Panel...4 4. CONNECTION AND OPERATION...6 5. TROUBLESHOOTING...8 6. MAINTENANCE...9 6.1 Operation...9
More information3x3x7B Series 80 In-Line Mounted Centrifugal Pumps
SUBMITTAL B-35.2F JOB: REPRESENTATIVE: UNIT TAG: ORDER NO. DATE: ENGINEER: SUBMITTED BY: DATE: CONTRACTOR: APPROVED BY: DATE: SPECIFICATIONS FLOW HEAD HP RPM VOLTS CYCLE PHASE ENCLOSURE APPROX. WEIGHT
More informationSED2 VFD NEMA Type 3R and Type 3R Harsh Environment (3RHE) Bypass
SED2 VD NEMA Type 3R and Type 3R Harsh Environment (3RHE) Bypass Description The NEMA Type 3R Bypasses are companion packages for the family of SED2 Variable requency Drives (VD). NEMA Type 3R/3RHE enclosed
More informationSD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool
FR VARIABLE SPEED DRIVES Regenerative Active Front End icool 4 QUADRANT POWER ELECTRONICS / SD700 SERIES FR SD700FR SERIES goes one step ahead keeping the family unique characteristics. Based on the latest
More informationAQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2
AQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2 INTRODUCTION The Aquavar Intelligent Pump Controller from utilizes an all new Aquavar platform, and combines it with over 20 years of
More informationNumber 1 in efficiency
PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The new device category! The PowerXL DE1 Variable Speed Starter The PowerXL DE1 Variable Speed Starter one device, all the advantages
More informationVSD Series II Variable Speed Enclosed IntelliPass and IntelliDisconnect Drives
VSD Series II Variable Speed Enclosed IntelliPass and IntelliDisconnect Drives Product Bulletin Code No. LIT-12011814 Issued February 4, 2013 The Johnson Controls VSD Series II Variable Speed Enclosed
More informationAxpert-CSS AMTECH DRIVES Axpert-CSS Amtech
The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the
More information3 Internal Frequency Converter Operation 43
High Power Service Manual for VLT FC Series Contents Contents 1 Introduction 11 Purpose 11 VLT FC Product Overview 11 For Your Safety 11 Electrostatic Discharge (ESD) 12 Frame Size Definitions 12 Tools
More informationSYSDrive Frequency Inverter
SYSDrive Frequency Inverter T V/f control T PID control T Standard LED, optional LCD operator T Fieldbus options: DeviceNet T 7 configurable digital inputs T 3 configurable digital outputs T Low audible
More informationSoftstarters. Softstarters Type SSM Medium voltage ,800V 1
Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum
More informationOperating Instructions
MAKING MODERN LIVING POSSIBLE VLT DriveMotor FCP 106 and FCM 106 www.danfoss.com/drives Contents Contents 1 Introduction 3 1.1 Purpose of the Manual 3 1.2 Additional Resources 4 1.3 Product Overview 4
More informationHigh Frequency SineWave Guardian TM
High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation
More informationSDS Enclosed Star-Delta Starter User Guide
SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING
More informationMCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10
Contents Contents 1 Warnings 3 2 Troubleshooting 5 Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10 3 Service Instructions 13 Frame
More information1.1 Caution Statements
USER MANUAL 1.1 Caution Statements Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read and
More informationDrives. Section Rev. 1/10. Publications and Reference: See Section 17 for a complete list of additional product-related publications
AF-60LP Micro Drive Product Description...16-2 Product Number System Diagram...16-2 Pricing, Dimensions and Weights...16-3 Options, Accessories, and Replacement Parts...16-4 Dynamic Braking Resistors...16-5
More informationJ1000. Compact Inverter Series.
J1000 Compact Inverter Series www.yaskawa.eu.com Focus on Application Customer orientation and application focus two attributes of machine equipment YASKAWA offers with its J1000 compact inverter drive
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationThree Phase UPS Systems Range: 10 to 500kVA
Three Phase UPS Systems Range: 10 to 500kVA Three Phase UPS Systems Hitachi Hi-Rel Power Electronics Pvt. Ltd. is in the business of Industrial UPS Systems since 1987 and has rich experience in supplying
More informationM u l t i P o w e r. CM MultiPower. Installation and Operating Manual
M u l t i P o w e r CM MultiPower Installation and Operating Manual Index 1. Introduction of the 4HS submersible pumps range... 3 2. Safety Instructions... 4 3. CM MP installation... 5 3.1 Electric wiring...
More informationUser Manual Rittal PMC UPS 6kVA
User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26 Contents 1. Introduction...
More informationData Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA
Data Bulletin Raleigh, NC, USA ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION The ALTIVAR FLEX58 chassis drive controller offers OEMs, panel builders, integrators, and users a unique
More informationCATALOG. ABB micro drives ACS255, 0.25 to 20 hp / 0.37 to 15 kw
CATALOG ABB micro drives ACS255, 0.25 to 20 hp / 0.37 to 15 kw 2 Select and order your drive Type designation is a unique reference number that clearly identifies the drive by construction, power and voltage
More informationWelcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.
Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the
More informationProducts Tde Macno. User s Manual BRAKING UNIT. Cod. MP00401E00 V_1.0
Products Tde Macno User s Manual BRAKING UNIT Cod. MP00401E00 V_1.0 SUMMARY 1 GENERAL DESCRIPTION... 2 2 USE LIMITATIONS... 2 2.1 Climatic Class... 2 2.2 Resistance To Chemically Active Substances...
More informationVariable Frequency Drives
Table of Contents Variable Frequency Drives PRODUCT PRODUCT CODE RESOURCE DOCUMENTS PAGE # Introduction C-3 BT300 HVAC Drives BT300 149-711 / 154-126 C-5 BT300 HVAC Drives Conventional Bypass (C-Bypass)
More informationOperating Instructions. VLT Soft Starter - MCD 500. Phone: Fax: Web: -
MAKING MODERN LIVING POSSIBLE Operating Instructions VLT Soft Starter - MCD 500 Contents Contents 1 Safety 5 1.1 Safety 5 2 Introduction 7 2.1.1 Feature List 7 2.1.2 Type Code 8 3 Installation 9 3.1 Mechanical
More informationMCD 200 Series Soft Starters
MCD 200 Series Soft Starters AC motors often cause one or more serious problems during startup acceleration. MCD 200 Series electronic soft starters control motor current to provide a smooth start. When
More informationREFERENCE MANUAL FORM: MX-TRM-E REL REV MTE
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation
More informationINVEOR "Smart connections." on five levels
INVEOR "Smart connections." on five levels 1 The Inveor 3 Operation and observation IP65 protection class Integrated soft PLC Pre-fitted cable glands Fan-free design up to 7.5 kw Robust and vibration-resistant
More informationVSD Series II Variable Speed Micro Drives
VSD Series II Variable Speed Micro Drives Product Bulletin Code No. LIT-12011813 Issued March 26, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Johnson Controls VSD
More informationLow Profile DC Power Supply with Zero Voltage Soft Switching
Sorensen XFR Series Low Profile DC Power Supply with Zero Voltage Soft Switching Analog programming Zero voltage soft switching Constant voltage or constant current operation with automatic crossover and
More informationThank you for choosing EATON products. Safety information and operating instructions are included in this manual. Do not attempt to operate the UPS
Thank you for choosing EATON products. Safety information and operating instructions are included in this manual. Do not attempt to operate the UPS until reading through this manual carefully. Observe
More informationSOLSTART Instruction Manual
Solstart Analog Soft Starter 8-58A, 220-600V Instruction Manual Ver. 23/03/2009 2 Table of Content SOLSTART Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationTechnical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage.
INSTALLATI Speed-controlled drive system manufacturer EMS Model Units included S for rotary heat exchanger EURA, size 20 60. Page Content 1 Technical data 1 Units included............motor, Control unit
More informationLIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V
LIFT INVERTER SERIES EN DE ES FR IT 1000V YASKAWA INVERTER DRIVE TECHNOLOGY Contents Page 2 Introduction Experience & Innovation YASKAWA speaks Lift Page 3 YASKAWA Main Features Page 4 Specifications Page
More information1. Product Information
AVS Control Panel 1. Product Information AVS is a pump control panel having 4.3 TFT touch screen, uniquely designed high efficient variable speed control and relay board. The touch control panel is located
More informationLow voltage AC drives. ABB micro drives ACS to 3 hp/0.18 to 2.2 kw Catalog
Low voltage AC drives ABB micro drives ACS55 0.25 to 3 hp/0.18 to 2.2 kw Catalog ACS55 IP20 Overview ACS55 micro drives are designed for use in a wide variety of simple machinery applications where only
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More information690+ Series Integrator
690+ Series Integrator V/F, Sensorless, Vector Inverter from 1 to 1600 DESCRIPTION The 690+ Series is a single range of AC drives designed to meet the requirements of all variable speed applications from
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TLES_040-120_S1_UPS_GE_Floor_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41
More informationSMS PRODUCT CATALOGUE
SMS PRODUCT CATALOGUE CONTENTS 1 TAKEDO 3VF-NXP - LIFT INVERTER Page 3 2 TAKEDO 3VF-V20 - OPEN LOOP LIFT INVERTER Page 6 3 TAKEDO ENERGY - DYNAMIC BRAKING REGENERATIVE UNIT Page 7 4 HYDROVERT VVVF FOR
More informationRVS-DN Digital Reduced Voltage Motor Starter
RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationRegenerative DC Common Bus Supply
Regenerative DC Common Bus Supply The Regenerative DC Common Bus Supply supplies both motoring and regenerative current to the DC bus of one or more AC drives without the need of rectifier front end in
More informationOpen Chassis Star-Delta Starter User Guide
Open Chassis Star-Delta Starter User Guide (7.5kW~90kW) V2.0.1 Contents 1 Safety information... 1 2 Technical Data... 2 3 Supply & Motor Connections & Circuit Diagrams... 5 4 Control Connections & Operation...
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements
More informationHVAC Drives Lenze AC Tech MCH Series Price Book May US Dollars
HVAC Drives Lenze AC Tech MCH Series Price Book May 2015 - US Dollars Document: pcmchusd-0515_a MCH Series Drives: Model Number Designation Code The MCH Series drives are rated for variable torque applications,
More informationVariable speed application guidelines
Variable speed application guidelines Frequency converter VLT 00 SCROLL COMPRESSORS REFRIGERATION AND AIR CONDITIONING www.danfoss.com Introduction The introduction of speed control for refrigeration
More informationApplication Description
-14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....
More information