1 ROCKY MOUNTAIN POWER A DIVISION OF PACIFICORP January 29, South Main, Suite 2300 Salt Lake City, Utah VIA ELECTROl.fiC FILI1VG AND OVERNIGHT DELIVERY Wyoming Public Service Commission 2515 Warren Avenue, Suite 300 Cheyenne, Wyoming Attn: Chris Petrie, Chief Counsel RE: IN THE MATTER OF THE APPLICATION OF ROCKY MOUNTAIN POWER FOR APPROVAL OF A CERTIFICATE OF PUBLIC CONVENIENCE AND NECESSITY TO CONSTRUCT THE BAR NUNN SUBSTATION AND FOUR MILES OF 115 kv TRANSMISSION LINE Dear Mr. Petrie: Enclosed for filing are an original and three (3) copies of an Application of Rocky Mountain Power for Approval of a Certificate of Public Convenience and Necessity to construct the new Bar Nunn substation and the associated 4.16 miles of 115 kv transmission line. The Company has also made the electronic filing of this Application pursuant to the Commission's Rules. Enclosed is the Company's check for the Commission's filing fee in the amount of$ It is respectfully requested that all formal correspondence and Staff requests regarding this matter be addressed to: By (preferred): By regular mail: Data Request Response Center PacifiCorp 825 NE Multnomah, Suite 2000 Portland, OR Informal inquiries related to this application may be directed to David M. Mosier at (307) Very truly yours, Vice President, Regulation & Government Affairs Enclosures
2 Daniel E. Solander 201 South Main Street, Suite 2300 Salt Lake City, Utah Telephone No. (801) Facsimile No. (801) ~~~~~~~~~J;::~~ Attorney for Rocky Mountain Power BEFORE THE PUBLIC SERVICE COMMISSION OF WYOMING IN THE MATTER OF THE APPLICATION OF ) ROCKY MOUNTAIN POWER FOR APPROVAL ) OF A CERTIFICATE OF PUBLIC CONVENIENCE ) AND NECESSITY TO CONSTRUCT THE BAR NUNN ) SUBSTATION AND FOUR MILES OF 115kV ) TRANSMISSION LINE ) Docket No Record No. -EA-14 APPLICATION FOR A CERTIFICATE OF PUBLIC CONVENIENCE AND NECESSITY TO CONSTRUCT THE BAR NUNN SUBSTATION AND FOUR MILES OF 115KV TRANSMISSION LINE Comes now Rocky Mountain Power (the "Company") with the following Application to the \Vyoming Public Service Commission ("Commission") respectfttlly requesting an Order approving a Certificate of Public Convenience and Necessity ("CPCN") for construction of the new Bar Nunn substation and associated 4.16 miles of 115kV transmission line that will serve the new Bar Nunn substation pursuant to W.S and Sections 204 and 205 of the Wyoming Public Service Commission's Procedural Rules and Special Regulations. In support of its Application, the Company represents as follows: 1. Rocky Mountain Power is a public utility in the state of Wyoming and is subject to the jurisdiction of the Commission with regard to its public utility operations, retail rates, service, and accounting practices. The Company also provides retail electricity service under the 1
3 name Rocky Mountain Power in the states of Utah and Idaho and under the name Pacific Power in the states of Oregon, Washington, and California. 2. Rocky Mountain Power's principal place of business in Wyoming is 2840 East Yellowstone Highway, Casper, Wyoming Communications regarding this Application should be addressed to: David M. Mosier Wyoming Regulatory Affairs Manager Rocky Mountain Power 1807 Capitol A venue, Suite 200A Cheyenne, Wyoming Daniel E. Solander Senior Counsel Rocky Mountain Power 201 South Main Street, Suite 2300 Salt Lake City, UT In addition, Rocky Mountain Power requests that all data requests regarding this report be sent in Microsoft Word or plain text format addressed to: By (preferred) Or by regular mail to: Data Request Response Center PacifiCorp 825 NE Multnomah, Suite 2000 Portland, OR Informal inquiries related to this Application may be directed to David M. Mosier at (307) Construction of the new Bar Nunn substation and associated 115kV transmission line are discussed in Sections 26 and 27 of the Stipulation approved by the Commission in the 2010 general rate case (Docket No ER-10). Load growfh in the Town of Bar Nunn 2
4 and at the Casper Airport has created the need for Rocky Mountain Power to apply to the Commission for a CPCN so that the following infrastructure can be added to its substation and transmission systems: A new 115kV three breaker ring bus Bar Nunn substation to be located on five acres approximately one mile west of the town of Bar Nunn. Approximately four miles of 115kV transmission feeder line from the Casper substation to the new Bar Nunn substation. 5. In order to adequately serve existing and new customers in the Casper and Bar Nunn areas and to generally meet the growing energy demands in the vicinity of the Casper Airport, the Company proposes to construct the new Bar Nunn substation with a three circuit breaker ring bus supporting two power transformers and nine distribution circuits. This is explained in detail in Exhibit 1, the master plan of the new Bar Nunn substation. The initial construction will include one circuit breaker, one 115kV 12.5kV, 30MVA power transformer and three distribution circuits. Exhibits 2, 3 & 4 contain the general plan, electrical one-line diagram and profile view illustrating the initial Bar Nunn substation configuration 6. Rocky Mountain Power will finance the proposed new Bar Nunn substation and 115 kv transmission line project as a general system improvement, which is estimated to cost approximately $10.3 million. The Company will use a reasonable balance of debt and equity to finance the project. There are no customer specific financial advances in aid of construction related to this project. 7. The land upon which the proposed new Bar Nunn substation will be located is owned by Rocky Mountain Power. The land on which the 4.16 miles of 115kV transmission line 3
5 will be built is owned by private land owners and all easement across these properties have been successfully secured. 8. The proposed new Bar Nunn substation will be energized from the Casper substation by the new 4.16 mile 115kV transmission line included in this Application. Exhibit 5 contains the plan view of the proposed 115k V transmission line. 9. Requirements of Commission Rule Section 204: (a) The name and address of the applicant: Applicant is Rocky Mountain Power, a division of PacifiCorp. Its principal Wyoming mailing address is 2840 E. Yellowstone Highway, Casper, Wyoming (b) The type of plant, property, or facility proposed to be constructed: The type facility proposed to be constructed is a new 115kV Bar Nunn substation and associated 115kV transmission line extending north from the Casper substation to the new Bar Nunn substation. The Bar Nunn substation will be designed as a three circuit breaker ring bus with two 115 to 12.5kV 30MVA power transformers capable of serving nine distribution circuits (Exhibit 1). The Bar Nunn substation will initially be built with one circuit breaker, one kV 30MVA power transformer and three distribution circuits (Exhibits 2, 3 &4). The new 115kV transmission line will be single pole construction using 795 ACSR conductor and built to avian safe standards. The 115kV transmission line will originate in the Casper substation (Exhibit 5). (c) A complete description of the facilities proposed to be constructed, including preliminary engineering specification in sufficient detail to properly describe the principal systems and components; and final and complete engineering specifications when they become available: The proposed Bar Nunn substation will consist of one 115kV circuit breakers; one 115kV, 420 Amp Trans-Rupter II; one kV 30MVA power transformer; 4
6 one 115kV 1200A TPST, vertical break, motor operated switch; 7-115kV vertical break manually operated switches; 2-self-contained 15.5kV circuit breakers; 27-15kV SPST Hook type disconnect switches; 6-Lightening Arrestors; kV instrument voltage transformers; kV fuses; 1-125V looah Battery System with rack and charger; 1-28X30 control house; and all associated conduit, cable trench, cables, bus work and fencing needed to complete a substation of this size. The new 4.16 mile three phase 115kV transmission line will consist of approximately 60 TF-201 single pole structures, 3 TF-252 single pole dead end structure, 3-TF- 403 H-Frame structures and 3 TF-452 three pole dead end structures. During construction, the Company will raise one structure on the Rocky Mountain Power Claim Jumper line 10 feet in order to provide sufficient clearance for an undercrossing. The conductor on the new 115kV transmission line will be 795 ACSR (Drake). There will be no steel structures or concrete foundations needed for the proposed 115kV transmission line. A general description of the facilities proposed to be constructed is illustrated in the following list of exhibits supporting this Application: Exhibit 1: Exhibit 2: Exhibit 3: Exhibit 4: Exhibit 5: Master Plan of Bar Nunn substation. One-line diagram of the Bar Nunn substation. General plan of the Bar Nunn substation. Plan and elevation drawings of the Bar Nunn substation. Plan and elevation drawings of the 115kV transmission line. The actual plan and profile drawing for the 115kV transmission line are not available at this time. When finished the plan and profile drawings will be sent as an addendum to the application. Exhibit 5 is the plan view imposed on an aerial map. 5
7 Exhibit 6: Exhibit 7: Exhibit 8: Exhibit 9: Exhibit 10: Aerial map of the 115kV transmission line with property owners overlaid. Master list of all property owners. Topographic Survey of the Bar Nunn Location. Transmission line land ownership contact information. Bar Nunn substation land ownership information. (d) List the rates, if any, proposed to be charged for the service that will be rendered because of the proposed construction: The rates proposed to be charged for the service rendered as a result of the construction are the applicable standard service schedules, rules and regulations in the Company's Wyoming tariffs under P.S.C. Wyoming No. 14, which became effective October 1, 2013, and as may be modified and approved by the Commission in the future. (e) State the estimated total cost of the proposed construction: The total estimated cost of the facilities proposed in this Application is $10,278,210. The estimated cost of the Bar Nunn substation (less land purchase) is $5,640,322; the estimated cost of the 115kV transmission line (less right of way costs) is $3,095,684; the estimated cost for the modification to the Casper substation is $1,542,204. (f) State the manner by which the proposed construction will be financed: Rocky Mountain Power will finance the proposed Bar Nunn substation and associated 4.16 miles of 115kV transmission line together with the modifications at Casper substation using a reasonable mix of capital designed to provide a competitive cost, predictable capital market access and to allow the Company to remain financially stable. The Company may use operating cash flows, long-term and short-term debt and, if necessary, equity capital to fund this expansion project. When 6
8 completed and in service, the actual cost of the project will be recorded as plant-in-service and the Company will apply for rate-base treatment in a future Wyoming general rate case. (g) State the financial condition of the applicant: Rocky Mountain Power's current financial condition is on file with the Commission in response to the annual reporting requirements in Commission Rule 226 and through Rocky Mountain Power's semi-annual earnings reports or its general rate case application in Docket No ER-11. Rocky Mountain Power is financially capable of funding this project. (h) State the estimated annual operating revenues and expenses that are expected to accrue from the proposed construction: The initial estimated annual operating revenue related to service provided from the additional capacity made available as a result of the proposed Bar Nunn substation and associated 115kV transmission line is approximately $1 million. These revenues will increase as the loads in the Bar Nunn and Casper Airport area increase. The estimated annual cost of service related to the proposed additional facilities is $1.5 million. (i) State the estimated starting and completion date of the proposed construction: The Company proposes to begin site development construction work for the Bar Nunn substation in the third quarter of This work will consist of completing the grubbing, grading, fencing and access road. The remainder of the substation and the transmission line will be constructed in The current estimated completion date of the project, under normal construction circumstances, weather conditions, labor availability and materials delivery is approximately October 31,2015. (j) This provision shall not be construed to require the filing of an application for construction necessary in the ordinary course of business or for a contiguous extension; proving that this exception does not apply to a person who will become a public utility after 7
9 such construction: The proposed Bar Nunn substation and supporting 4.16 miles of 115kV transmission line are major facilities as defined by the Commission's Rules and are not construction necessary in the ordinary course of business or for a contiguous extension. (k) If the project is a major utility facility, the application shall also contain the information required by Section 205 and 206 (where applicable) below: The proposed Bar Nunn substation and associated 4.16 miles of 115kV transmission line are major utility facilities as defined by the Commission's Rules and the applicable information required by Commission Rules Section 205 is provided below. (1) Each utility which proposes to extend utility service on a contiguous basis under W.S (1977) to a person not located within its certificated service area shall file a letter request and obtain authority from the Commission therefore prior to such extension, unless an emergency exists requiring immediate extensions: The proposed Bar Nunn substation and associated 4.16 miles of 115kV transmission line are not an extension of utility service on a contiguous basis to a person located outside the Company's certificated service area. 10. Requirements of Commission Rule Section 205: (a) The proposed site by an appropriate description of the involved properties and the county or counties in which the major facility will be located and where possible a metes and bounds description; a description of the route of line or lines in the project and the number of route miles located in each county; a description of the various types of country in or through which the facility will be constructed: The proposed Bar Nunn substation and associated 4.16 miles of 115kV transmission line are located entirely located in Natrona County, Wyoming on private lands. The Bar Nunn substation is located in the SEI/4 of the NW1/4 of Section 7, 8
10 Township 34 North, Range 79 West of the 6th Principal Meridian, Natrona County, Wyoming. The land was purchased by Rocky Mountain Power in December of2012. The proposed 4.16 miles of new 115k V transmission line will start at the Casper substation in Township 34 North, Range 79 West in Section 31 and proceed north to the Bar Nunn substation in section 7, Township 34 North, Range 79 West. The line will be located on portions of Sections 31, 30, 19, 18 and 7 in Township 34 North, Range 79 West in Natrona County, Wyoming. All Right-of-Way for the proposed 115kV transmission line has been obtained. Contact information regarding land ownership is included in Exhibit 9. (b) A brief report on the surrounding scenic, historical, archaeological and recreational locations, natural resources, plant and animal life, land reclamation, possible safety hazards, and plans for protecting the environment: The proposed new Bar Nunn substation is located four miles north of the Casper substation and approximately one mile west of the town of Bar Nunn. The proposed 115kV transmission line will originate at the Casper substation and terminate at the new Bar Nunn substation. The new Bar Nunn substation will be located on a five acre site in an agriculture area which has not been previously developed. The property is currently zoned UA (urban agriculture). The Company contracted with an environmental engineering firm to perform a Phase 1 Environmental Study which concluded that further environmental assessment is not needed. The immediate area around the proposed Bar Nunn substation is uninhabited and undisturbed flatland with little or no grass vegetation. The Company's Environmental Group conducted a high level survey of the proposed substation site and transmission line routing and determined that there are no known historical or archaeological resources on the properties. If cultural resources are encountered during construction, the crews will be instructed to stop work pending a qualified archaeologist evaluation of any discovery. 9
11 There are no known wetlands or riparian areas near the project. Wildlife may include pronghorn antelope, mule deer and raptors. The proposed Bar Nunn substation and associated 115k V transmission line are not in a greater sage grouse core area. The proposed 115kV transmission line has the same type of environmental surroundings as the proposed Bar Nunn substation, with proximity to commercial build up approximately one mile to the east and unrestricted open range to the north, west and south. The Company will develop a Storm Water Pollution Prevention Plan (SWPPP) for this project and all construction will comply with the Company's Avian Safe Standards. Construction of this project will employ industry Best Management Practices to protect water, air and wildlife resources. (c) Land, mineral, and water requirements for the major utility facility, the status of the acquisition of land, or rights-of-way or of minerals and water for the project, the sources of locations thereof, and proposed methods of transportation and utilization: The proposed Bar Nunn substation in this Application will be located entirely within property owned by Rocky Mountain Power as indicated in Exhibit 10. The associated 115kV transmission line will be located in new right-of-way which has been acquired by Rocky Mountain Power as indicated in Exhibits 8 and 9. There is no further land, mineral, or water right required. A conditional use permit has been applied for from Natrona County. Water may be used during the course of construction for dust control, soil compaction and other construction needs and will be acquired from an acceptable location identified by the construction contractor. (d) A statement setting forth the need for the project in meeting present and future demands for service, in Wyoming or other states, and the proposed sale of the utility commodity or service which the construction of this facility will make available: The Bar 10
12 Nunn substation and associated 115kV transmission line is needed to provide additional electrical distribution capacity to support growing residential, commercial and industry growth in the Casper, Bar Nunn and Casper Airport areas all located in Natrona County, Wyoming. (e) A statement of the effect of the project on applicant's and other systems' stability and reliability, if applicable: The proposed Bar Nunn substation and associated 115kV transmission line is needed to serve load growth in Natrona County. The facilities proposed in this Application will support and serve area residential, commercial and industrial load growth and will not adversely affect any other utility's system. (f) The estimated cost of and plans for financing the project, and a statement of the estimated effects of the project on applicant's revenues and expenses: The estimated cost and financing plans for the project described in this Application have been addressed above in response to requirements of Section 204 (e) and (f). The estimated effect ofthe project on Rocky Mountain Power's revenues and expenses is described above in response to the requirements of Section 204 (h). (g) A list of local, state, Indian, or federal governmental agencies having requirements which must be met in connection with the construction or operation of the project, and the status before those agencies; and applicant shall file such agency'sfinal order when entered: The only local, state, Indian, or federal governmental agencies having requirements of which Rocky Mountain Power is aware that must be met in connection with the construction or operation of the proposed Bar Nunn substation and associated 115kV transmission line are the Wyoming Public Service Commission, pursuant to Commission Rules Sections 204 and 205; the Federal Energy Regulatory Commission; the state Board of Land Commissioners with consultation with the Wyoming Game and Fish Department; and the Department of 11
13 Environmental Quality which will issue a Storm Water Pollution Prevention Plan (SWPPP). 11. Rocky Mountain Power plans to bid the initial site development portion of the proposed Bar Nunn substation work in May 2014 and authorize construction in mid-july, 2014, or as soon as approval has been received from the Commission. The remainder of the substation and the transmission line are planned to be constructed beginning January All construction is dependent upon the Commission's approval of this Application. In order to facilitate the regulatory consideration of this Application by the Commission, the Company has included with this Application a printed and electronic copy of a proposed Notice. WHEREFORE, Rocky Mountain Power respectfully requests that the Commission issue an Order approving a CPCN for construction of the new Bar Nunn substation and associated 4.16 miles of 115kV transmission line that will serve the new Bar Nunn substation pursuant to W.S and Sections 204 and 205 of the Wyoming Public Service Commission's Procedural Rules and Special Regulations. Dated this 29th day of January, Respectfully submitted, Daniel E. Solander Attorney for Rocky Mountain Power 12
ROCKY MOUNTAIN POWER A DIVISION OF PACIFICORP
ROCKY MOUNTAIN POWER A DIVISION OF PACIFICORP 1407 W. North Temple, Suite 330 Salt Lake City, Utah 84116 January 28, 2016 VIA ELECTRONIC FILING AND OVERNIGHT DELIVERY Wyoming Public Service Commission
More informationThe cost estimation methodology used to update the charges and credits is the same methodology the Company utilized in the prior year s filing.
LISA D. NORDSTROM Lead Counsel lnordstrom@idahopower.com December 28, 2018 Public Utility Commission of Oregon Filing Center 201 High Street SE, Suite 100 P.O. Box 1088 Salem, Oregon 97301 Re: Tariff Advice
More informationwelcome to the BC Hydro community open house
welcome to the BC Hydro community open house Dawson Creek/ Chetwynd Area Transmission ProjecT Open House welcome Dawson Creek/Chetwynd Area Transmission Project (DCAT) The purpose of this open house is
More informationDecision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L82
Decision 21447-D01-2016 August 23, 2016 Decision 21447-D01-2016 Proceeding 21447 Application 21447-A001 August 23, 2016 Published by the: Fifth Avenue Place, Fourth Floor, 425 First Street S.W. Calgary,
More informationSTATE OF NEW HAMPSHIRE Inter-Department Communication
STATE OF NEW HAMPSHIRE Inter-Department Communication DATE: February 11, 2010 AT (OFFICE): NHPUC FROM: Torn Frantz Director, Electric Division SUBJECT: DE 09-277: Petition by Public Service Company of
More informationAlberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation
Decision 21781-D01-2016 Alberta Electric System Operator Needs Identification Document Application Facility Applications September 7, 2016 Alberta Utilities Commission Decision 21781-D01-2016: Alberta
More informationElbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI
Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility
More informationDecision D ATCO Electric Ltd. Decommissioning of Transmission Line 6L79. October 18, 2016
Decision 21481-D01-2016 October 18, 2016 Alberta Utilities Commission Decision 21481-D01-2016 Proceeding 21481 Application 21481-A001 October 18, 2016 Published by the: Alberta Utilities Commission Fifth
More informationELECTRIC RATE SCHEDULES ROCKY MOUNTAIN POWER. Salt Lake City, Utah. for ELECTRIC SERVICE. in the STATE OF UTAH. Under
Original Sheet No. A ELECTRIC RATE SCHEDULES of ROCKY MOUNTAIN POWER Salt Lake City, Utah for ELECTRIC SERVICE in the Under PUBLIC SERVICE COMMISSION OF UTAH TARIFF NO. 50 CANCELS ALL PREVIOUS SCHEDULES
More informationPlease Refer to Attached Sample Form
Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 32105-E Cancelling Revised Cal. P.U.C. Sheet No. 28313-E Electric Sample Form No. 62-0686 Application for Service
More informationNEW ECTOR COUNTY NORTH TO MOSS 138 kv TRANSMISSION LINE PROJECT PUBLIC OPEN HOUSE MEETING
NEW ECTOR COUNTY NORTH TO MOSS 138 kv TRANSMISSION LINE PROJECT PUBLIC OPEN HOUSE MEETING TUESDAY AUGUST 17, 2010 4:00 PM 8:00 PM CAVAZOS ELEMENTARY SCHOOL CAFETERIA 9301 WEST 16 TH STREET ODESSA, TEXAS
More informationPublic Information Workshop
Public Information Workshop Charlotte County-Punta Gorda MPO - Meeting Rooms A and B March 29, 2018 Welcome to the Public Information Workshop for Harborview Road Project Development and Environment (PD&E)
More informationBEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) APPLICATION
BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA Application of Great Oaks Water Company (U-162-W for an Order establishing its authorized cost of capital for the period from July 1, 2019
More informationAppendix D Black Hills Project Summary
Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain
More informationMemorandum. This memorandum requires Board action. EXECUTIVE SUMMARY
California Independent System Operator Memorandum To: ISO Operations (MRTU) Committee From: Armando J. Perez, Director of Grid Planning cc: ISO Board of Governors ISO Officers Date: April 29, 2005 Re:
More informationv Deborah Flint - Chief ecutive e, ficer
Date 6/30/2017 6/30/2017: 6/26/2017: Approval EY MY By RW AE MT BY...jil 0.'1 1 Los Angeles World Airports REPORT TO THE B A - e OF AIRPORT COMMISSIONERS Meeting Date:, A irdro, /. Approved : aiph -,...
More informationSeptember 9, Ms. Kimberly D. Bose, Secretary Federal Energy Regulatory Commission 888 First Street, N.E., Room 1A Washington, DC 20426
Mark D. Patrizio Attorney at Law 77 Beale Street, B30A San Francisco, CA 94105 Mailing Address P.O. Box 7442 San Francisco, CA 94120 (415) 973.6344 Fax: (415) 973.5520 E-Mail: MDP5@pge.com September 9,
More informationFrequently Asked Questions Leander-Round to Rock 138-kV Transmission Line Project Williamson County
Frequently Asked Questions Leander-Round to Rock 138-kV Transmission Line Project Williamson County Q. What is the Leander-Round Rock 138-kV Transmission Line Project? A. The Leander-Round Rock project
More informationAlberta Electric System Operator Saleski Transmission Project Needs Identification Document
Decision 2013-127 Alberta Electric System Operator Saleski Transmission Project Needs Identification Document ATCO Electric Ltd. Saleski 901S Substation and 144-kV Transmission Line 7L142 Facility Application
More informationDecision Blaze Energy Ltd. Application for an Exemption under Section 24 of the Hydro and Electric Energy Act.
Decision 2014-108 Application for an Exemption under Section 24 of the Hydro and Electric Energy Act April 17, 2014 The Alberta Utilities Commission Decision 2014-108: Application for an Exemption under
More informationCoalspur Mines (Operations) Ltd.
Decision 22744-D01-2017 Application for an Exemption Under Section 24 of the Hydro and Electric Energy Act October 5, 2017 Alberta Utilities Commission Decision 22744-D01-2017 Application for an Exemption
More informationHighway 18 BNSF Railroad Overpass Feasibility Study Craighead County. Executive Summary
Highway 18 BNSF Railroad Overpass Feasibility Study Craighead County Executive Summary October 2014 Highway 18 BNSF Railroad Overpass Feasibility Study Craighead County Executive Summary October 2014 Prepared
More informationQ. Are you familiar with the matter which is the subject of this petition? A. Yes, I am.
October, 0 0 0 Q. Please state your full name and occupation. A. My name is Dean Benton. I am employed as the Plant Supervisor at the New Hampshire Electric Cooperative, Inc. ( NHEC ), Tenney Mountain
More informationBEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION
BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION IN THE MATTER OF THE APPLICATION FOR A CUSTOMER RELEASE FROM WOODRUFF ELECTRIC COOPERATIVE CORPORATION TO OF PIVOT WELLS BELONGING TO WAYNE WILKISON PREPARED
More informationIncluded in this Stakeholder Information Package:
Who can you contact for more information? Yellowhead Area Transmission Reinforcement: TERA Environmental Consultants Dave Sare Phone: 403-538-5734 Email: dsare@teraenv.com Drayton Valley Area AltaLink
More informationTariff cover sheets reflecting all rates approved for April 1 in Dockets 4218 (ISR) and 4226 (Reconciliation Filing).
Thomas R. Teehan Senior Counsel April 4, 2011 VIA HAND DELIVERY & ELECTRONIC MAIL Luly E. Massaro, Commission Clerk Rhode Island Public Utilities Commission 89 Jefferson Boulevard Warwick, RI 02888 RE:
More informationSalt Lake County Electrical Plan Task Force October Douglas N. Bennion, P.E. Vice President Rocky Mountain Power
Salt Lake County Electrical Plan Task Force October 2009 Douglas N. Bennion, P.E. Vice President Rocky Mountain Power 1 Rocky Mountain Power s Bright History In 1881, Salt Lake City became the fifth city
More informationWest Station-West Cañon 115 kv Transmission Project
West Station-West Cañon 115 kv Transmission Project Project Sponsor: Additional Project Participants: Project Description: Black Hills Colorado Electric New 115 kv line from West Station to West Cañon
More informationJanuary 18, 2002 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION
Akbar Jazayeri Director of Revenue and Tariffs January 18, 2002 ADVICE 115-G (U 338-E) PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION SUBJECT: Decrease in Santa Catalina Island
More information(2) Scope. 220 CMR applies to all Distribution Companies subject to the jurisdiction of the Department.
D.P.U. 11-10-A 220 CMR 18.00: NET METERING Section 18.01: Purpose and Scope 18.02: Definitions 18.03: Net Metering Services 18.04: Calculation of Net Metering Credits 18.05: Allocation of Net Metering
More informationUS 81 Bypass of Chickasha Environmental Assessment Public Meeting
US 81 Bypass of Chickasha Environmental Assessment Public Meeting March 14, 2013 Introductions ODOT FHWA SAIC Meeting Purpose Present need for bypass Provide responses to 10/04/11 public meeting comments
More informationFITCHBURG GAS AND ELECTRIC LIGHT COMPANY NET METERING SCHEDULE NM
Sheet 1 FITCHBURG GAS AND ELECTRIC LIGHT COMPANY SCHEDULE NM Applicability The following tariff provisions shall be applicable to a Host Customer, as defined herein, that requests net metering services
More informationCase 13-M Edic to New Scotland 345 kv Transmission Line and Hurley Avenue PARs Project (ED-NS/HA) Article VII Filing ED-NS/HA
Submission of Indicated New York Transmission Owners For Authority to Construct and Operate Electric Transmission Facilities in Multiple Counties in New York Case 13-M-0457 Edic to New Scotland 345 kv
More informationJanuary 20, 2004 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION
Akbar Jazayeri Director of Revenue and Tariffs January 20, 2004 ADVICE 123-G (U 338-E) PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION SUBJECT: Increase in Santa Catalina Island
More informationD.P.U A Appendix B 220 CMR: DEPARTMENT OF PUBLIC UTILITIES
220 CMR 18.00: NET METERING Section 18.01: Purpose and Scope 18.02: Definitions 18.03: Net Metering Services 18.04: Calculation of Net Metering Credits 18.05: Allocation of Net Metering Credits 18.06:
More informationApplicable California Vehicle Code Sections, 2015 Edition
Applicable California Vehicle Code Sections, 2015 Edition Speed limits in California are governed by the California Vehicle Code (CVC), Sections 22348 through 22413; also, pertinent sections are found
More informationFORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5
ALANNA GILLIS ACTING COMMISSION SECRETARY Commission.Secretary@bcuc.com web site: http://www.bcuc.com SIXTH FLOOR, 900 HOWE STREET, BOX 250 VANCOUVER, BC CANADA V6Z 2N3 TELEPHONE: (604) 660 4700 BC TOLL
More informationNOTICE OF PUBLIC HEARING ANAHEIM PUBLIC UTILITES BOARD IS HOLDING A PUBLIC HEARING ON THE FORMATION OF UNDERGROUND DISTRICT No. 66 (BEACH) TO UNDERGROUND OVERHEAD FACILTIIES, INCLUDING POWER AND COMMUNICATION
More informationHONORABLE CHAIRPERSON AND MEMBERS OF THE AZUSA UTILITY BOARD
SCHEDULED ITEM TO: FROM: HONORABLE CHAIRPERSON AND MEMBERS OF THE AZUSA UTILITY BOARD GEORGE F. MORROW, DIRECTOR OF UTILITIES DATE: JANUARY 28, 2013 SUBJECT: APPROVAL OF POWER SALES AGREEMENT ( PSA ) WITH
More informationWOLVERINE TO BHP JANSEN NEW TRANSMISSION LINE PROJECT FALL 2017
WOLVERINE TO BHP JANSEN NEW TRANSMISSION LINE PROJECT FALL 2017 TODAY WE LL TALK ABOUT Our challenges and how we re meeting them Why we re building this project Our planning process and considerations
More informationFebruary 13, Docket No. ER ; ER Response to Request for Additional Information
California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California Independent System
More informationPlease Refer to Attached Sample Form
Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 32104-E Cancelling Revised Cal. P.U.C. Sheet No. 28312-E Electric Sample Form No. 62-0685 Application for Service
More informationBEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA SOUTHERN CALIFORNIA EDISON COMPANY S (U338-E) NOTICE OF EX PARTE COMMUNICATION
BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA Application of Southern California Edison Company (U 338-E) for Approval of Electric Vehicle Charging at Schools, State Parks and Beaches
More informationProject Location. Purpose and Need for Action. File Code: 1950 Date: September 14, Dear Interested Party,
United States Department of Agriculture Forest Service Idaho Panhandle National Forests Sandpoint Ranger District 1602 Ontario Street Sandpoint, ID 83864 File Code: 1950 Date: September 14, 2016 Dear Interested
More informationUpdates and Modifications to Report
QUARTERLY COMPLIANCE REPORT (JULY 2015) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision
More informationHigh Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007
High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM-2006-02) Interconnection Facility Study Final Report November 2, 2007 Prepared by: Public Service Company of New Mexico Electric Services
More informationContact Person for questions and approval letters: Alain Blunier
CALIFORNIA PUBLIC UTILITIES COMMISSION ADVICE LETTER FILING SUMMARY ENERGY UTILITY MUST BE COMPLETED BY LSE (Attach additional pages as needed) Company name/cpuc Utility No. Liberty Utilities (CalPeco
More informationSTATE OF NEW HAMPSHIRE PUBLIC UTILITIES COMMISSION DE PUBLIC SERVICE COMPANY OF NEW HAMPSHIRE
STATE OF NEW HAMPSHIRE PUBLIC UTILITIES COMMISSION DE 07-071 PUBLIC SERVICE COMPANY OF NEW HAMPSHIRE Petition for License to Construct and Maintain Electric Lines and a Fiber Optic Communications Cable
More informationBEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES
EXHIBIT JC-2 BEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES IN THE MATTER OF THE PETITION OF JERSEY CENTRAL POWER & LIGHT COMPANY PURSUANT TO N.J.S.A. 40:55D-19 FOR A DETERMINATION THAT THE OCEANVIEW
More informationPlan and Profile for the Black Dog Natural Gas Pipeline Project Docket No. G002/GP
414 Nicollet Mall Minneapolis, MN 55401 March 13, 2017 Daniel P. Wolf Executive Secretary Minnesota Public Utilities Commission 121 7 th Place East, Suite 350 St. Paul, MN 55101 Via Electronic Filing RE:
More informationSTATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS ENERGY FACILITY SITING BOARD
STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS ENERGY FACILITY SITING BOARD In re : : Docket No. SB-00-0 () : Testimony of David M. Campilii, P.E. June, 00 PROV-- 0 0 TESTIMONY OF DAVID M. CAMPILII,
More informationThank you for your time and attention to this matter. Please feel free to contact me if you have any questions regarding the filing.
Mary L. Cottrell, Secretary March 27, 2009 Page 1 Stacey M. Donnelly Counsel September 23, 2009 Mark D. Marini, Secretary Department of Public Utilities One South Station Boston, MA 02110 Re: D.P.U. 09-03
More informationSANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT
SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT This Net Metering and Interconnection Agreement ( Agreement ) is made and entered into as of this day of, 2018, by the City of Santa
More informationTABLE OF CONTENTS FIGURES: MAP EXHIBITS: TABLES:
TransWest Express Transmission Project TABLE OF CONTENTS 7.0 DESIGN OPTIONS... 7-1 7.1 OVERVIEW OF DESIGN OPTIONS... 7-1 7.2 DESIGN OPTIONS PURPOSE AND NEED AND DESIGN CHARACTERISTICS... 7-4 7.2.1 Design
More informationRE: January 9, Electronic Service Only. Marc Weintraub, Esq. Counsel, Applicants Bailey & Glasser, LLP 209 Capitol Street Charleston, WV 25301
c IC 201 Brooks Street, P.O. Box 812 Phone: (304) 340-0300 Charleston, West Virginia 25323 Fax: (304) 340-0325 Electronic Service Only Marc Weintraub, Esq. Counsel, Applicants Bailey & Glasser, LLP 209
More informationSTATE OF MICHIGAN COUNTY. ORV ORDINANCE No. 24 AMENDMENT 2/10/16
STATE OF MICHIGAN COUNTY ORV ORDINANCE No. 24 AMENDMENT 2/10/16 An ordinance authorizing and regulating the operation of Off Road Vehicles (ORVs) on roads in Lake County, providing penalties for the violation
More informationCUSTOMER/ TWIN ARROWS PROJECT
A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset
More informationAgenda. Utility Undergrounding Strategies & Laguna Canyon Road Master Plan
Utility Undergrounding Strategies & Laguna Canyon Road Master Plan January 17, 2017 City Council Meeting 2 Agenda Progress since March 2016 Status of undergrounding and road widening between El Toro Rd.
More informationNational Grid. Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES. 2 nd Amended Compliance Filing
National Grid Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES 2 nd Amended Compliance Filing Attachment 1: Book 2 of 2 April 2010 Submitted to: Rhode Island
More informationScope of Services January 26, Project Development and Conceptual Engineering for City of Lake Forest Amtrak Station
203 North LaSalle Street, Suite 2100 Chicago, IL 60601 (312) 558-1345 Fax: (312) 346-9603 E-Mail: cquandel@quandelconsultants.com www.quandel.com Scope of Services January 26, 2010 Project Development
More informationLink LRT: Maintenance Bases, Vehicles and Operations for ST2 Expansion
Project Number SYS-LRT Subareas All Primary Mode Impacted Link Facility Type Link Service Version Number 4.0 Date Last Modified 7/24/2008 Project Locator Map Short Project Description Construct new light
More informationAugust 18, 2016 NWN OPUC Advice No A / UG 309 SUPPLEMENT A (UM 1766)
ONITA R. KING Rates & Regulatory Affairs Tel: 503.721.2452 Fax: 503.721.2516 Email: ork@nwnatural.com August 18, 2016 NWN OPUC Advice No. 16-13A / UG 309 SUPPLEMENT A (UM 1766) VIA ELECTRONIC FILING Public
More informationCITY COUNCIL OF THE CITY OF NOVATO ORDINANCE NO. 1620
G-12 CITY COUNCIL OF THE CITY OF NOVATO ORDINANCE NO. 1620 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF NOVATO AMENDING THE NOVATO MUNICIPAL CODE BY ADDING SECTION 4-19 (ELECTRIC VEHICLE CHARGING SYSTEMS)
More informationSeptember 2, Ms. Kimberly D. Bose, Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C.
TEXAS EASTERN TRANSMISSION, LP Mailing Address: 5400 Westheimer Court P. O. Box 1642 Houston, TX 77056-5310 Houston, TX 77251-1642 713.627.5400 main Ms. Kimberly D. Bose, Secretary Federal Energy Regulatory
More informationAttached is Idaho Power s 2013 WECC Annual Progress Report. Please contact me if you have any questions.
March 8, 2013 David Franklin Chair, Technical Studies Subcommittee Southern California Edison 1 Innovation Way Pomona, CA 91768 MHanson@idahopower.com (208) 388-2253 Enoch Davies Western Electricity Coordinating
More information79th OREGON LEGISLATIVE ASSEMBLY Regular Session. House Bill 3157
th OREGON LEGISLATIVE ASSEMBLY--0 Regular Session House Bill Sponsored by Representatives DOHERTY, MCLAIN (at the request of Radio Cab Company) SUMMARY The following summary is not prepared by the sponsors
More informationBlack Hills Project Summary
2016 Rule 3627 Report Black Hills Project Summary Page 1 of 38 Black Hills Project Summary Colorado PUC E-Filings System D 1 2016 Rule 3627 Report Black Hills Project Summary Page 2 of 38 Category Transmission
More informationMerger of the generator interconnection processes of Valley Electric and the ISO;
California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson Vice President, Policy & Client Services Date: August 18, 2011 Re: Decision on Valley Electric
More informationDecision on Merced Irrigation District Transition Agreement
California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson, Vice President Policy & Client Services Date: March 13, 2013 Re: Decision on Merced Irrigation
More informationUNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) )
UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION The Nevada Hydro Company, Inc. Docket No. EL18-131-000 SOUTHERN CALIFORNIA EDISON COMPANY'S COMMENTS AND PROTEST TO THE NEVADA HYDRO
More informationTurnpike Mitigation Program Application
Ohio Department of Transportation & Ohio Turnpike and Infrastructure Commission Turnpike Mitigation Program Application Please note the following eligibility criteria: 1) Projects must be sponsored by
More informationApplication for Service Residential Subdivision / Development
Application for Service Residential Subdivision / Development Please complete this application and submit the completed form and attachments to PG&E Application for Service at P.O. Box 24047 Fresno CA
More informationPacific Gas and Electric Company TM
Pacific Gas and Electric Company TM Evelyn C. Lee Mailing Address P.O. Box 7442 San Francisco, CA 94120 Street/Courier Address Law Department 77 Beale Street San Francisco, CA 94105 (415) 973-2786 Fax:
More informationTAUSSIG. Public Finance Public Private Partnerships Urban Economics. Newport Beach Riverside San Francisco Dallas ASSOCIATES, INC.
DAVID TAUSSIG & ASSOCIATES, INC. MONTECITO ESTATES PUBLIC IMPROVEMENT DISTRICT FISCAL YEAR 2015-2016 FINAL BUDGET JULY 27, 2015 Prepared on Behalf of: MONTECITO ESTATES PUBLIC IMPROVEMENT DISTRICT Department
More informationMAP OR PHOTO. Public Meeting & Open House July 23, Project Roadway Limits From: FM 1957 To: FM 471. Counties Bexar & Medina
Public Meeting & Open House July 23, 2013 Project Roadway Limits From: FM 1957 To: FM 471 MAP OR PHOTO Counties Bexar & Medina 1 I. Project History II. III. IV. Project Overview Project Alternatives Response
More informationSTATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION PUC DOCKET NO. E002/TL OAH DOCKET NO.
Direct Testimony and Schedules Grant Stevenson STATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION IN THE MATTER OF THE APPLICATION FOR A ROUTE PERMIT FOR THE PLEASANT
More informationCHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.
25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements
More informationRevised Cal. P.U.C. Sheet No E Cancelling Revised Cal. P.U.C. Sheet No E
Revised Cal. P.U.C. Sheet No. 33883-E Cancelling Revised Cal. P.U.C. Sheet No. 28182-E ELECTRIC SCHEDULE LS-2 Sheet 1 APPLICABILITY: TERRITORY: RATES: This schedule is applicable to services for lighting
More informationRequest for Expressions of Interest (Phase I - Preliminary) PUBLIC-PRIVATE PARTNERSHIP. for the. Big Chino Water Delivery System
CITY OF PRESCOTT Request for Expressions of Interest (Phase I - Preliminary) PUBLIC-PRIVATE PARTNERSHIP for the Big Chino Water Delivery System City Manager s Office Water Resource Management Section 201
More informationUM 1810 Cross-Examination Statement and List of Stipulated Exhibits
November 6, 2017 VIA ELECTRONIC FILING Public Utility Commission of Oregon 201 High Street SE, Suite 100 Salem, OR 97301-3398 Attn: Filing Center RE: UM 1810 Cross-Examination Statement and List of Stipulated
More informationCurrant Lake Transmission Project
Currant Lake Transmission Project September 2010 Why are you receiving this project information package? New transmission facilities are needed in the Monitor area of southeastern Alberta. ATCO Electric
More informationJCP&L Verbatim Response to Middletown Township s Questions
JCP&L Verbatim Response to Middletown Township s Questions Township officials sent 13 questions about the proposed Monmouth County Reliability Project to JCP&L on June 10 th. JCP&L provided direct responses
More informationTurnpike Mitigation Program Application
Ohio Department of Transportation & Ohio Turnpike and Infrastructure Commission Turnpike Mitigation Program Application Please note the following eligibility criteria: 1) Projects must be sponsored by
More informationTHE NARRAGANSETT ELECTRIC COMPANY LARGE DEMAND RATE (G-32) RETAIL DELIVERY SERVICE
Sheet 1 AVAILABILITY Electric delivery service shall be taken under this rate for all purposes by any customer who is placed on the rate by the Company in accordance with this paragraph. The Company shall
More informationFund and 2015 revenue bonds Est. State and Local Taxes: $2,810,000
PORT OF SEATTLE MEMORANDUM COMMISSION AGENDA Item No. 6b ACTION ITEM Date of Meeting August 4, 2015 DATE: TO: FROM: Dave Soike, Director, Aviation Facilities and Capital Programs Wayne Grotheer, Director,
More informationBohn to Kettle River Transmission Project
April 2012 Why are you receiving this project information package? New transmission facilities are needed in the Fort McMurray area. ATCO Electric has been directed by the Alberta Electric System Operator
More informationKettle River Transmission Project
April 2012 Why are you receiving this project information package? New transmission facilities are needed in the Fort McMurray area. ATCO Electric has been directed by the Alberta Electric System Operator
More informationMONRO MUFFLER BRAKE, INC. PROVIDES FOURTH QUARTER AND FISCAL 2017 FINANCIAL RESULTS
CONTACT: John Van Heel Chief Executive Officer (585) 647-6400 Robert Gross Executive Chairman (585) 647-6400 FOR IMMEDIATE RELEASE Brian D Ambrosia Senior Vice President Finance Chief Financial Officer
More informationPortland General Electric Company Second Revision of Sheet No. 122-1 P.U.C. Oregon No. E-18 Canceling First Revision of Sheet No. 122-1 PURPOSE SCHEDULE 122 RENEWABLE RESOURCES AUTOMATIC ADJUSTMENT CLAUSE
More informationOff-Road Vehicle Recreation Report
Wyoming Comprehensive Off-Road Vehicle Recreation Report Summary of Key Findings 2012 Report by University of Wyoming, Department of Agricultural and Applied Economics The University of Wyoming Department
More informationEast Avenue and Queen City Substation Improvement Project
East Avenue & Queen City Substation Improvement Project VIA FIRST CLASS MAIL August 29, 2017 Judith C. Whitney, Clerk Vermont Public Utility Commission 112 State Street, 4 th Floor Montpelier, VT 05620-2701
More informationMUNICIPAL CLASS EA PROCESS 1
PHASE 1 PROBLEM OR OPPORTUNITY PHASE 2 PHASE 3 PHASE 4 PHASE 5 ALTERNATIVE SOLUTIONS ALTERNATIVE DESIGN CONCEPTS FOR PREFERRED SOLUTION ENVIRONMENTAL STUDY REPORT IMPLEMENTATION 1. Identify problem or
More informationOn June 11, 2012, the Park Board approved the installation of three electric vehicle charging stations along Beach Avenue.
January 8, 2017 TO: Park Board Chair and Commissioners FROM: General Manager Vancouver Board of Parks and Recreation SUBJECT: Electric Vehicle Charging Stations New Park Board Locations RECOMMENDATION
More informationCompetitive Electricity Market Concepts and the Role of Regulator
Competitive Electricity Market Concepts and the Role of Regulator Scott R. Storms Chief Administrative Law Judge Indiana Utility Regulatory Commission October 18, 2005 Tirana, Albania Oversight and Regulation
More informationSTATE OF MINNESOTA ENVIRONMENTAL QUALITY BOARD MEQB DOCKET NO. MP-HVTL-EA-1-99
STATE OF MINNESOTA ENVIRONMENTAL QUALITY BOARD In the Matter of the Exemption Application by Minnesota Power for a 345/230 kv High Voltage Transmission Line Known as the Arrowhead Project. MINNESOTA ENVIRONMENTAL
More informationFebruary 4, 2019 VIA ELECTRONIC FILING. Public Utility Commission of Oregon 201 High Street SE, Suite 100 Salem, OR Attn: Filing Center
February 4, 2019 VIA ELECTRONIC FILING Public Utility Commission of Oregon 201 High Street SE, Suite 100 Salem, OR 97301-3398 Attn: Filing Center RE: Advice No. 19-003 Schedule 12 Quarterly Meter Reading
More informationFLEET SERVICES OVERVIEW and ACCOMPLISHMENTS Public Works Commission August 10, 2017
FLEET SERVICES OVERVIEW and ACCOMPLISHMENTS Public Works Commission August 10, 2017 DESCRIPTION OF FLEET OPERATION Fleet operations include vehicle and equipment maintenance, procurement and surplus services,
More informationNovember 16, Ms. Kimberly D. Bose, Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C.
November 16, 2012 Ms. Kimberly D. Bose, Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C. 20426 ANR Pipeline Company 717 Texas Street, Suite 2400 Houston, Texas 77002-2761
More informationCOUNTY ROAD COMMISSION RULES FOR THE MOVEMENT OF OVERSIZE OR OVERWEIGHT VEHICLES AND LOADS
COUNTY ROAD COMMISSION RULES FOR THE MOVEMENT OF OVERSIZE OR OVERWEIGHT VEHICLES AND LOADS General instructions, information and rules governing the issuance of special permits for the movement of oversize
More informationApril 6, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426
414 Nicollet Mall Minneapolis, MN 55401 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 RE: Public Service Company of Colorado Docket
More information