1 STATEMENT OF TECHNICAL REQUIREMENTS FOR GT/GTG STARTING RECTIFIER EED May 2005 M A T E R I A L B R A N C H I N T E G R A T E D H E A D Q U A R T E R S M O D ( N A V Y ) D WING, SENA BHAWAN N E W D E L H I i

2 EED I. AMENDMENT RECORD Amendment No. Date Text Affected Signature/Dat e NIL NIL II. REVISION NOTE No revision incorporated. III. HISTORICAL RECORD This standard supersedes the following:- NIL. CONTENTS ii

3 Sl No Description Page No 1 Introduction. 1 2 System Configuration 1 3 System Design 1 4 Requirements of System Design 1 to 3 5 Switching Controls 3 6 Duty Cycle 3 7 Technical Specifications 4 to 5 8 System Performance 6 9 Reparability Aspects 6 10 Quality Assurance, Quality Control and 6 to 7 Inspection 11 EMI/EMC Specifications 7 12 Naval Specifications 7 13 Maintenance 7 14 Equipment spares 8 15 Documentation 9 16 Weight and dimensions Warranty Technical Services Training 11 iii

4 1. Introduction. The Gas Turbines are main prime movers for propulsion and power generation on board IN ships. Each gas turbine is fitted with a DC motor to give initial torque and pre defined speed essential to fire the self sustained turbine ignition chamber. Further each GT/GTG is provided with a dedicated DC starting unit which is intended for converting 380 V 50 HZ ships mains power supply to DC supply to power the DC starting motor of the connected turbine. 2. System Configuration. The input supply to the rectifier unit is 380 V 50 HZ 3 phase ships mains supply. The DC out put of the rectifier through a set of cables shall be connected to the DC motor fitted on the turbine. The starting circuit of the rectifier be integrated with the gas turbine starting controls system. The switching on of the rectifier will be from remote Turbine Control Room and the rectifier shall cut off automatically by the turbine control system after elapse of set time. 3. System Design. The system should be modular in design and should be modular extension of a few basic building blocks. The rectifier should be dual channel and the change over from channel I to channel II should be through a suitable switch provided on the unit itself. The design of both the channels should be similar. The unit shall convert alternating current into direct current and adjust output parameters in conjunction with the automatic equipment system. The commonality between the PCBs may be maintained in form fit and function to the extent feasible. The DC rectifier should be state of the art using Gate Turn off thyristers /MOS Turn off thyristers/ MOS Controlled Thyrister / Isolate Gate Bipolar transistors (IGBTs). 4. Requirements of System Design. The rectifier unit shall confirm to following design/functional requirements:- (a) The design of rectifier to meet the out put characteristics as specified by the NSM under most adverse environmental and the electric conditions. (b) Input supply interruption during the operation of the rectifier must be cause malfunction of the unit. Further the equipment shall be automatically ready for normal performance on restoration of the input supply. (c) distortion (d) operating load. Switching on of the rectifier should not cause harmonic to the input supply more than maximum. The equipment is to be capable of withstanding for the time when running at any load between full load to no 1

5 (e) shall be limit of Sufficient cooling arrangement by natural air convection provided in the rectifier in order to meet the permissible temperature rise. (i) Further damage within the equipment, subsequent to a fault. (ii) Damage to the converted power loads. (iii) Prevent the primary supply going out of specification. (iv) Damage to the equipment, subsequent to a fault external to the equipment. (v) Conditions under which the equipment shall trip be specified. (g) All control supplies for the operation of the rectifier be derived from the main input power supply to the equipment and the rectifier should be self sustained. (h) Power supplies to control circuits are to be protected by fuse. Fuses for control and protection circuits are to be kept separate. (j) Closed loop voltage control is to be provided in the rectifier for controlling the rectifier output voltage characteristics within the specified limit. (f) The rectifier shall be provided with protection circuit to protect the unit against impermissible over currents and short circuit currents. Further, protection against damage to the equipment both internal and external under following conditions be also provided:- (l) The equipment shall be provided with following indications:- (i) Equipment supply available - Lamp (Green) (ii) Equipment ON - Lamp (Green) (iii) Trip -Lamp (Red) (iv) Local /Remote control available (v) 3 phase Input supply voltmeter (v) DC Voltmeter and Ammeter. 5. Switching Controls. The rectifier shall have a starting circuit to provide connection and disconnection of the rectifier unit and selection of current and voltage duty. The rectifier unit will be remotely controlled by commands from the control station by means of closing and opening contacts whose circuits are connected to the remote control panel. In manual mode the rectifier could be switched on and off by push button S1 and S2 mounted on front panel of the rectifier. 6. Duty Cycle. The rectifier shall be provided with suitable stabilisation circuit to maintain the out put parameters at the preset 2

6 values and ensures a continuous smooth rise in current during starting of the article. The rectifier out put shall have a provision to select current of 1800, 1200, 900 A duties and voltage 70, 60, 50 V values. The rectifier will be tested to meet the starting current envelope of the system as given below:- (a) When the system is started the rectifier ensures smooth adjustment of the output current from 0 to the value being set within 5-6 seconds. By the time current stabilizes the output current voltage should be 15 to 30 V. (b) The rectifier shall withstand the complete starting cycle of 70 seconds duration. (c) The rectifier should be capable to supply designed output for consecutive three starts within 120 seconds which constitute the one operating cycle of the rectifier. Further the rectifier will be tested for its normal operation for four such operating cycles continuously. STARTING CURRENT ENVELOPE OF THE RECTIFIER Time (Seconds) Output Voltage(Amps) Out put Current (Volt) Rectifier cuts off - 7. Technical Specifications. Sl PARAMETERS VALUES N o (i) Input Supply 380V±19V, 50Hz±1.5Hz, 3Ph (ii) Power Consumption at 1800A 175 KVA & O/P Voltage 70V (iii) Max. Output Current 2000A (iv) Max. Output Voltage 70V (v) Output Power at Max. Current 140 KW 3

7 (vi) (vii) Sl N o (viii) (ix) (x) & Voltage Output voltages limitation stages Limits of Output and Current regulation PARAMETERS Output Current estimated deviation from given level %, not more Output Voltage stages established deviation from given level % Electrical Insulation resistance and normal climatic conditions In cold state MΩ not less 50V, 60V, 70V A VALUES ±7% 10% to 3% 50 MΩ (xi) Efficiency at Output current 85% 1800A, Output Voltage 70V (xii) Service life of the Units 20 Years (xiii) Middle Service life 06 Years (xiv) Mean Time Between Failure 10,000 Cycles (Starts) (xv) Overall Dimensions: The dimensions should not be more than those specified. However the smaller dimension unit meeting the operational and technical specifications is acceptable. Height: 1256 mm Width: 740 mm Depth: 660 mm Weight: Not exceeding 675 Kg (xvi) Environmental Conditions - Ambient Temp C -Relative Humidity at 50 0 C: 98%. (xvii) Shocks Tilts up to 45 0 to either side or rolling up to 45 0 with rocking period of 16S (xviii) Control facility The control desk/panel would have facility for local control 4

8 and monitoring of the system. (xix) Cables Suitable LFH cables would be required to ensure EMI/EMC compatibility. (xx) Starting cycle During starting of the turbine (active load operation) the rectifier is required to with stand a specific time verses current output cycle required for smooth and trouble free starting of the gas turbine as mentioned at para 6 (c) above. 5

9 Sl PARAMETERS VALUES N o (xxi) Vibration and Noise The self induced airborne noise and vibration level (xxii) Short circuit and over current protection:- must not exceed 60 db. The rectifier should have short circuit and over current protection which should actuate at 2200 to 2400 Amperes. The protection circuit shall also have a provision of adjustment. 8. System Performance (a) Reliability. The system performance will degrade in the event of failure. The system will contain no single point control, whose malfunctioning would result in complete failure of the system. The functional redundancy will be available in the shortest possible time through hardware reconfiguration within shortest possible time. The design will cater for adequate fail safe features. (b) Maintainability. The system has a System Control Panel to run online and off-line maintenance diagnostics. The monitor panel along with built-in test equipment (BITE) of individual units will be capable of selecting and localizing faults down to a single replaceable PCB/Module within 5 minutes of the fault occurrence. The monitoring system will also be designed to indicate corrective action either by a display or through a fault detection code, with amplifying notes used in conjunction with the maintenance manual. The hardware maintenance system will be designed as an off-line one and isolation of faulty units in the maintenance mode will be on a not-to interfere basis with healthy system. The manufacturer will prepare and submit the following data on maintainability:- (i) (ii) Maintainability programme. Calibration Programme. 9. Reparability Aspects. The repair facilities for the PCB level repairs would be eventually set up in the naval dockyards. The test jigs and repair facilities may also have to be provided by the OEM. The other aspects that would be applicable as and when equipment developed by a particular firm is cleared for induction in Navy are enumerated in the succeeding paragraphs. 6

10 7

11 Quality Assurance, Quality Control and Inspection 10. The system and units would be required to undergo type testing as per JSS at CQAE Bangalore and technical evaluation will be carried out by ETMA (Mumbai) followed by actual on board performance trials. Inspection and acceptance tests will be jointly carried out by the representative of the Indian Navy and the manufacturer. A Quality Acceptance Procedure document containing the following details will be provided to the Indian Navy:- (a) The details of Test Procedure and method of proving the performance of the system both in factory and on board ship. (b) Factory Acceptance Test (FAT) plan. (c) List of relevant hardware specifications to which the testing/acceptance would conform to and the performance parameters required to be checked during the various acceptance phases. (d) List of specifications that cannot be conclusively demonstrated /proved during System Acceptance Tests and for which documentary evidence will be furnished by the manufacturer. The manufacturer will undertake to make good, free of cost, any defects noticed during ship-borne tests/trials/operations. 11. EMI/EMC Specifications. The equipment should confirm to MIL STD 461 C. 12. Naval Specifications. The system should confirm to Naval Engineering Specifications NES-501, 511, 536 and 537 for design, testing and general specifications. Logistic Support 13. Maintenance. (a) On Board Repair/Maintenance. The system is to be susceptible to first level of preventive/repair maintenance by replacement up to PCB level. (b) Shore Repair /Maintenance. Shore repairs/maintenance on the rectifier will be carried out at Naval Dockyards. The firm will be required to provide and install necessary test jigs /facilities required to carry out complete repairs / maintenance. 8

12 14. Test Equipment. The OEM to provide details of following test equipment that would be required:- (a) Onboard Test Equipment. This should be adequate to meet the requirement of all repairs/ maintenance expected to be carried out on board the ship by the ship staff. (b) Special Test Equipment. Certain special to-type test equipment shall be available in the shore base for specific tests/ checks on the equipment. 15. Equipment Spares (a) Manufacturers Recommended Spares. The manufacturer will prepare the list of spares taking into account the IN s maintenance philosophy and test equipment policy. The basis for ranging and scaling of the spares will be clearly indicated. Unit cost with Pattern numbers of each item is required to be specified. The Part Identification List should conform to the Integrated Logistic Management System format of the Indian Navy. The lead-time for the supply of items is also to be specified. The following are the requirements of the Indian Navy in so far as the spares are concerned: (i) Provision of On Board spares based on two year s requirement with a maximum mission time of 90 days. (ii) Scope, modalities and pricing for long term supply of pares during the life of the system and undertake to maintain the supply of same for at least a period of 12 years. (iii) Provide working substitutes for those components becoming obsolete during a period of 12 years. 16. Documentation. The manufacturer will deliver 10 sets of documentation along with the first system with one of the above sets as a reproducible master. The delivery of documentation may be phased during the execution of the project, as mutually agreed. The scope and contents of documentation will be as per JSS 0251 specification. Documents are also to be supplied on electronic media as per EED-P-23 specifications. Basic content break-down of the requirement is as follows:- (a) (b) (c) System description. Operating Instruction. Technical description. 9

13 (d) (e) (f) Maintenance instruction along with drawings. Repair instructions along with drawings. Fault location procedures and service diagrams. and (g) Electrical spares parts catalogue including those for test measuring equipment. (h) (j) Interface Control Document. Test and Calibration procedure Non Electrical Catalogue and General Data (k) (l) (m) ESD control and protection. Installations instructions /schedules. Instructions for setting to work, testing and tuning. (n) Test procedures/plans for factory acceptance and HATS and SATs. (p) (q) (r) (s) Comprehensive parts lists and parts identification list List of on board spares Performance figures including MTBF and MTTR EMI/EMC protection 17. Weight and Dimensions. Details are to be intimated as part of the documentation. 18. Warranty. On site warranty for hardware will be for a period of 18 months from the date of commissioning. 19. Technical Services. The system is to be fitted on board the ship at India. This would entail additional requirements as follows: (a) Installation Supervision. The representative of OEM is to be positioned at the ship during the installation of the system. This is required for supervision of the installation process and to assist to resolve any technical holdups. (b) STW and Commissioning. The OEM is responsible for Setting to Work, and commissioning of the system. 10

14 20. Training. The OEM is to provide on site training for Indian Naval personnel as follows. (a) for of the Operators.Training for one day duration is to be imparted minimum of 20 personnel on the operation and exploitation system. (b) Maintainers. Training for five days duration is to be imparted for minimum of 10 personnel on the first and second level of maintenance of the system. 11

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5 Columbia City, Indiana Page 1 of 5 SCHEDULE DG-2 LARGE POWER DISTRIBUTED GENERATION I. AVAILABILITY This Distributed Generation Rate is available to any member in good standing of Northeastern REMC (Northeastern)

More information

For BIS Use Only Doc: CED 50(7436) BUREAU OF INDIAN STANDARDS

For BIS Use Only Doc: CED 50(7436) BUREAU OF INDIAN STANDARDS For BIS Use Only Doc: CED 50(7436) BUREAU OF INDIAN STANDARDS DRAFT FOR COMMENTS ONLY (Not to be reproduced without the permission of BIS or used as an Indian Standard) Draft Indian Standard SPECIFICATION

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO BILL 1 MAINS POWER DISTRIBUTION 2-1 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Supply, install, test, commission and set to work the following:- 1.01 Free-standing purpose made front access sub main switchboard

More information

Knowledge of Diagnosis and Rectification of Light Vehicle Engine Faults

Knowledge of Diagnosis and Rectification of Light Vehicle Engine Faults Unit 157 Knowledge of Diagnosis and Rectification of Light Vehicle Engine Faults UAN: F/601/3733 Level: Level 3 Credit value: 6 GLH: 45 Relationship to NOS: This unit is linked to LV07 Diagnose and Rectify

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates

More information

532: 2006 Bicycle tube valves and valve tubing Specification (third revision) 2414: 2005 Cycle and rickshaw pneumatic tyres (fourth revision)

532: 2006 Bicycle tube valves and valve tubing Specification (third revision) 2414: 2005 Cycle and rickshaw pneumatic tyres (fourth revision) For BIS use only Draft Indian Standard CYCLE RUBBER TUBES (MOULDED/JOINTED) SPECIFICATION (fourth revision of IS 2415) Not to be reproduced without the permission Last date for receipt of comments is of

More information

Unit MC07K Knowledge of Diagnosis and Rectification of Motorcycle Engine Faults

Unit MC07K Knowledge of Diagnosis and Rectification of Motorcycle Engine Faults Assessment Requirements Unit MC07K Knowledge of Diagnosis and Rectification of Motorcycle Engine Faults Content: Single cylinder and multi-cylinder fuel injection systems a. The operation and construction

More information

INPUTS FOR FEASIBILITY STUDY FOR MAKE PROJECTS : AUXILIARY POWER UNIT (APU) FOR TANK T-90 S/SK

INPUTS FOR FEASIBILITY STUDY FOR MAKE PROJECTS : AUXILIARY POWER UNIT (APU) FOR TANK T-90 S/SK Appendix A (Refer Para 3 of Mod (AC), DGMF letter No A/35854/PPP/Make/GS/ Mod (AC)/2016 dt 10 May 2016) INPUTS FOR FEASIBILITY STUDY FOR MAKE PROJECTS : AUXILIARY POWER UNIT (APU) FOR TANK T-90 S/SK 1.

More information

Knowledge of diagnosis and rectification of light vehicle engine faults

Knowledge of diagnosis and rectification of light vehicle engine faults Unit 157 Knowledge of diagnosis and rectification of light vehicle engine faults UAN: F/601/3733 Level: No Level Credit value: 6 GLH: 45 Relationship to NOS: This unit is linked to LV07 Diagnose and Rectify

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 7 SCHEDULE LPDG-1 LARGE POWER AND COMMERCIAL MEMBER-OWNED GENERATION I. AVAILABILITY This Generation rate is available to any member in good standing of Noble REMC (Noble) who

More information

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Northeastern Rural Electric Membership Corporation Columbia City, Indiana Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),

More information

Proposed Special Condition for limited Icing Clearances Applicable to Large Rotorcraft, CS 29 or equivalent. ISSUE 1

Proposed Special Condition for limited Icing Clearances Applicable to Large Rotorcraft, CS 29 or equivalent. ISSUE 1 Proposed Special Condition for limited Icing Clearances Applicable to Large Rotorcraft, CS 29 or equivalent. ISSUE 1 Introductory note: The hereby presented Special Condition has been classified as important

More information

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. ANNEXURE XI (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. Sr. No Technical Particulars Confirmation to be given by bidder (Please strike out which ever not applicable)

More information

Number 24 of 2008 MOTOR VEHICLE (DUTIES AND LICENCES) (NO. 2) ACT 2008 ARRANGEMENT OF SECTIONS. 3. Amendment of Part I of Schedule to Act of 1952.

Number 24 of 2008 MOTOR VEHICLE (DUTIES AND LICENCES) (NO. 2) ACT 2008 ARRANGEMENT OF SECTIONS. 3. Amendment of Part I of Schedule to Act of 1952. Number 24 of 2008 MOTOR VEHICLE (DUTIES AND LICENCES) (NO. 2) ACT 2008 Section 1. Definitions. ARRANGEMENT OF SECTIONS 2. Application of sections 3 to 5. 3. Amendment of Part I of Schedule to Act of 1952.

More information

DEPARTMENT OF THE ARMY TECHNICAL MANUAL TECHNICAL MANUAL OPERATOR AND ORGANIZATIONAL MAINTENANCE MANUAL TRUCK, LIFT, FORK, POWER SHIFT G.E.D.

DEPARTMENT OF THE ARMY TECHNICAL MANUAL TECHNICAL MANUAL OPERATOR AND ORGANIZATIONAL MAINTENANCE MANUAL TRUCK, LIFT, FORK, POWER SHIFT G.E.D. TM 10-3930-624-12 DEPARTMENT OF THE ARMY TECHNICAL MANUAL TECHNICAL MANUAL OPERATOR AND ORGANIZATIONAL MAINTENANCE MANUAL TRUCK, LIFT, FORK, POWER SHIFT G.E.D., 6,000 LB CAPACITY, SRT. 180 IN. LIFT (ALLIS

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS INTER PLANT STANDARD STEEL INDUSTRY SOFT STARTER FOR VOLTAGE UP TO 690 V AC IPSS: 1-10-040-15 IPSS NO CORRESPONDING IS 0. FOREWORD 0.1 This interplant standard has been prepared by the Standard Committee

More information

INTELEPOWER CXS SWITCHING SYSTEMS

INTELEPOWER CXS SWITCHING SYSTEMS INTELEPOWER CXS SWITCHING SYSTEMS INTELEPOWER CXS SWITCHING SYSTEMS Intelepower DC UPS - CXS Range Designed For Switching The demands for quality power in switching applications are placing new demands

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

AD Table 3.--Goodrich Evacuation Systems Installed on Certain Airbus Model Airplanes

AD Table 3.--Goodrich Evacuation Systems Installed on Certain Airbus Model Airplanes Table 3.--Goodrich Evacuation Systems Installed on Certain Airbus Model Airplanes Goodrich evacuation system having P/N - (i) 4A3928-1 (ii) 4A3928-2 (iii) 4A3931-1 and 4A3931-3 (iv) 4A3931-2 and 4A3931-4

More information

Number 10 of 2012 MOTOR VEHICLE (DUTIES AND LICENCES) ACT 2012 ARRANGEMENT OF SECTIONS. 3. Amendment of Part I of Schedule to Act of 1952.

Number 10 of 2012 MOTOR VEHICLE (DUTIES AND LICENCES) ACT 2012 ARRANGEMENT OF SECTIONS. 3. Amendment of Part I of Schedule to Act of 1952. Number 10 of 2012 MOTOR VEHICLE (DUTIES AND LICENCES) ACT 2012 Section 1. Definitions. ARRANGEMENT OF SECTIONS 2. Application of sections 3 to 5. 3. Amendment of Part I of Schedule to Act of 1952. 4. Amendment

More information

A Research, Science and Discovery based Polyurethane Technology company

A Research, Science and Discovery based Polyurethane Technology company HAMISAR HEALTHCARE Polyurethane Education, Contract research and Training ANNOUNCEMENT: SHORT TERM COURSES 1) Course: INTRODUCTION TO FLEXIBLE POLYURETHANE MOULDED FOAMS AND TROUBLE SHOOTING 1) DATE :

More information

EU RO Mutual Recognition Technical Requirements

EU RO Mutual Recognition Technical Requirements 1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.

More information

TECHNICAL MANUAL DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE MANUAL CRANE, WHEEL MOUNTED: 20 TON AT 10 FOOT RADIUS;

TECHNICAL MANUAL DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE MANUAL CRANE, WHEEL MOUNTED: 20 TON AT 10 FOOT RADIUS; DEPARTMENT OF THE ARMY TECHNICAL MANUAL TM 5-3810-232-34 TECHNICAL MANUAL DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE MANUAL CRANE, WHEEL MOUNTED: 20 TON AT 10 FOOT RADIUS; 2 ENGINES, DIESEL ENGINE

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

BULLDOZER, EARTH MOVING: TANK MOUNTING, M9 ( )

BULLDOZER, EARTH MOVING: TANK MOUNTING, M9 ( ) TECHNICAL MANUAL OPERATOR, ORGANIZATIONAL, DIRECT SUPPORT, AND GENERAL SUPPORT MAINTENANCE MANUAL (INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST) FOR BULLDOZER, EARTH MOVING: TANK MOUNTING, M9 (2590-00-708-3563)

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1 30 August 2011 Agreement Concerning the adoption of uniform technical prescriptions for wheeled vehicles, equipment and parts which can be fitted and/or be used on wheeled vehicles and the conditions for

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / 2005-06 SR.NO ITEM PAGE 1. SCOPE 2 2. WEATHER CONDITIONS 2 3. RATED VOLTAGE & FREQUENCY 2 4. GENERAL REQUIREMENT

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

REQUEST FOR INFORMATION ON ENVIRONMENTAL CONTROL (EC) WITH AUXILIARY POWER UNIT (APU) IN TANK T-72

REQUEST FOR INFORMATION ON ENVIRONMENTAL CONTROL (EC) WITH AUXILIARY POWER UNIT (APU) IN TANK T-72 REQUEST FOR INFORMATION ON ENVIRONMENTAL CONTROL (EC) WITH AUXILIARY POWER UNIT (APU) IN TANK T-72 1. The Indian Army is in the process of upgrading T-72 tank fleet with Environmental Control (EC) with

More information

LIFE INSURANCE CORPORATION OF INDIA

LIFE INSURANCE CORPORATION OF INDIA Annexure - VI LIFE INSURANCE CORPORATION OF INDIA Divisional Office. 1 st West Patel Nagar, Circuit House Road, Jodhpur ( Rajasthan)-342011 PRICE BID TO BE SUBMITTED IN ENVELOPE II Re : Tender for SITC

More information

PERFORMANCE SPECIFICATION SHEET BATTERY, STORAGE, AIRCRAFT, MAINTENANCE-FREE, 24-VOLT, 1.5-AMPERE-HOUR

PERFORMANCE SPECIFICATION SHEET BATTERY, STORAGE, AIRCRAFT, MAINTENANCE-FREE, 24-VOLT, 1.5-AMPERE-HOUR METRIC MIL-PRF-8565/6A (AS) 25 June 2001 SUPERSEDING DOD-B-8565/6(AS) 26 June 1987 PERFORMANCE SPECIFICATION SHEET BATTERY, STORAGE, AIRCRAFT, MAINTENANCE-FREE, 24-VOLT, 1.5-AMPERE-HOUR This specification

More information

FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1

FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1 THE SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1 OVERVIEW : 1. Introduction to Distribution, Transmission and Generation

More information

Number 5 of 2003 MOTOR VEHICLE (DUTIES AND LICENCES) ACT 2003 ARRANGEMENT OF SECTIONS. 4. Amendment of Part I of Schedule to Act of 1952.

Number 5 of 2003 MOTOR VEHICLE (DUTIES AND LICENCES) ACT 2003 ARRANGEMENT OF SECTIONS. 4. Amendment of Part I of Schedule to Act of 1952. Number 5 of 2003 MOTOR VEHICLE (DUTIES AND LICENCES) ACT 2003 ARRANGEMENT OF SECTIONS Section 1. Interpretation. 2. Application of sections 3 to 6. 3. Amendment of section 1 of Act of 1952. 4. Amendment

More information

7 The revised IS 8034:2002 and revised STI be implemented w.e.f. 1 Feb 2005.

7 The revised IS 8034:2002 and revised STI be implemented w.e.f. 1 Feb 2005. BUREAU OF INDIAN STANDARDS (CENTRAL MARKS DEPARTMENT-III) Our Ref: CMD-III/16:8034 25 Oct 2004 Subject: Implementation of revised IS 8034:2002 Submersible Pump Sets and revised STI (Doc:STI/8034/5 ) IS

More information

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has

More information

INDIAN MARITIME UNIVERSITY KOLKATA CAMPUS

INDIAN MARITIME UNIVERSITY KOLKATA CAMPUS INDIAN MARITIME UNIVERSITY KOLKATA CAMPUS No. IMU-KC/Laboratory Equipment/16-17 Date: 17.02.2017 Sub: Quotation for procurement of Instruments for Electrical Machine Laboratory at IMU-Kolkata Campus Sealed

More information

DRAFT SUPPLEMENT 1 TO THE 05 SERIES OF AMENDMENTS TO REGULATION No. 83. (Emissions of M1 and N1 categories of vehicles)

DRAFT SUPPLEMENT 1 TO THE 05 SERIES OF AMENDMENTS TO REGULATION No. 83. (Emissions of M1 and N1 categories of vehicles) UNITED NATIONS Economic and Social Council Distr. GENERAL 20 December 2000 ENGLISH Original: ENGLISH and FRENCH ECONOMIC COMMISSION FOR EUROPE INLAND TRANSPORT COMMITTEE World Forum for Harmonization of

More information

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED GUIDELINES FOR EMPANELMENT OF GRID TIED INVERTER MANUFACTURERS FOR IMPLEMENTATION OF SRTPV PROGRAM IN BESCOM. I. NEW EMPANELMENT 1. The grid tied inverter manufacturer shall register their application

More information

DETAIL SPECIFICATION

DETAIL SPECIFICATION INCH-POUND 19 September 2006 SUPERSEDING MIL-C-17361F(SH) 10 March 1989 DETAIL SPECIFICATION CIRCUIT BREAKER TYPES AQB/NQB, AIR, ELECTRIC, LOW VOLTAGE, INSULATED HOUSING (SHIPBOARD USE), GENERAL SPECIFICATION

More information

CETOP POSITION PAPER PP 07

CETOP POSITION PAPER PP 07 CETOP POSITION PAPER PP 07 MACHINERY DIRECTIVE 2006/42/EC Valid since 26 th May 2010 CETOP General Secretariat Lyoner Straße 18 D-60528 Frankfurt am Main Phone: +49 69 6603 1201 Fax: +49 69 6603 2201 E-mail:

More information

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module EFFECTIVE DATE JULY 28 204 OF 8 Dual Hybrid Ship Propulsion System 750V BUS Generator Generator Propulsion Propulsion Bus Capacitorss 50,000µF Total Traction Inverter Dual Inverterr e Power Inverter L

More information

HARYANA VIDYUT PRASARAN NIGAM LTD.

HARYANA VIDYUT PRASARAN NIGAM LTD. HARYANA VIDYUT PRASARAN NIGAM LTD. TECHNICAL SPECIFICATION SSD/S-03/R-1/DGM-605 TECHNICAL SPECIFICATION FOR 33 KV CAPACITOR BANKS CHIEF ENGINEER/MM HVPNL, PANCHKULA TELEPHONE & FAX: 0172-2583724 MARCH-2017-0

More information

DETAIL SPECIFICATION SHEET

DETAIL SPECIFICATION SHEET INCH-POUND MIL-DTL-17361/4B(SH) 19 September 2006 SUPERSEDING MIL-C-17361/4A(SH) 13 March 1995 DETAIL SPECIFICATION SHEET CIRCUIT BREAKERS, AIR, ELECTRIC, INSULATED HOUSING (SHIPBOARD USE) TYPES AQB-A101,

More information

MGE TM Galaxy TM 7000 GFC

MGE TM Galaxy TM 7000 GFC MGE TM Galaxy TM 7000 GFC Grid Frequency Converter (GFC) for Shore Connection solution 500 kva Performance 3 Phase Power Protection with high adaptability to meet the unique requirements of Shore Connection

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

EDS REPLY. Point No.2 Past-production details duly authenticated by DMG since Reply

EDS REPLY. Point No.2 Past-production details duly authenticated by DMG since Reply INDEX S. No. PARTICULARS PAGE NO. A EDS REPLY 1-3 ANNEXURE I ESSENTIAL DETAILS SOUGHT (EDS) 4-5 ANNEXURE II LEASE DOCUMENTS 6-58 ANNEXURE III AUTHENTICATED PAST PRODUCTION DATA 59 ANNEXURE IV CTE (AIR)

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT 33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

Lloyd s Register Type Approval System Test Specification Number GT04

Lloyd s Register Type Approval System Test Specification Number GT04 Lloyd s Register Type Approval System Test Specification Number GT04 Gas Turbines Performance and test specifications for Gas Turbines to be used in Marine, Offshore and Industrial Applications 2004 Lloyd's

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS PLC DSE704 AUTOSTART CONTROL MODULE OPERATING MANUAL 057-042 704 Operating Instructions Issue 2.1 18/06/2007 11:27:00 JR - 1 - Deep Sea Electronics Plc

More information

Number 22 of 2001 MOTOR VEHICLE (DUTIES AND LICENCES) ACT, ARRANGEMENT OF SECTIONS. Section 1. Interpretation.

Number 22 of 2001 MOTOR VEHICLE (DUTIES AND LICENCES) ACT, ARRANGEMENT OF SECTIONS. Section 1. Interpretation. Number 22 of 2001 MOTOR VEHICLE (DUTIES AND LICENCES) ACT, 2001. Section 1. Interpretation. ARRANGEMENT OF SECTIONS 2. Application of certain sections. 3. Amendment of Act of 1952. 4. Amendment of Act

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors Type range: UN813.3ANI UN813.4ANI UN813.3ANDCB UN813.4ANDCB UN813.5ANI Fig. 1: UN813.3ANI Fig. 2: UN813.4ANI You have selected

More information

TRIMOD HE UPS. MODULAR THREE-PHASE UPS from 10 to 80 kw THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

TRIMOD HE UPS. MODULAR THREE-PHASE UPS from 10 to 80 kw THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES TRIMOD HE UPS MODULAR THREE-PHASE UPS from 10 to 80 kw THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES TRIMOD HE HIGH performance HIGH efficiency LOW environmental impact DEVELOPMENTS

More information

Guideline No.: E-04(201610) E-04 GENERATORS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-04(201610) E-04 GENERATORS. Issued date: October 28,2016. China Classification Society Guideline No.: E-04(201610) E-04 GENERATORS Issued date: October 28,2016 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements, inspection

More information

Draft Indian Standard SAFES Part 1 Specification (Fifth Revision)

Draft Indian Standard SAFES Part 1 Specification (Fifth Revision) Draft for Comments Only Draft Indian Standard SAFES Part 1 Specification (Fifth Revision) Not to be reproduced without the permission of Last date for receipt of BIS or used as a STANDARD comments is 31-01-2014

More information

REQUISITION: MAY 2018 SCOPE OF WORK AND SPECIFICATION

REQUISITION: MAY 2018 SCOPE OF WORK AND SPECIFICATION REQUISITION: 11094449 MAY 2018 SCOPE OF WORK AND SPECIFICATION PROVISION AND SUPPLY OF INDUSTRIAL TYRE MAINTENANCE SERVICES, TYRE MANAGEMENT SERVICES AND TYRE SCRAPPING SERVICES FOR TRANSNET SOC LTD (REG.NO

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

SMSIL-4THGU-E ISSUE: 12/12 SIL-SAFETY MANUAL. Upgrade Series Actuators

SMSIL-4THGU-E ISSUE: 12/12 SIL-SAFETY MANUAL. Upgrade Series Actuators SMSIL-4THGU-E ISSUE: 12/12 GB SIL-SAFETY MANUAL FOR AIR TORQUE 4 th Generation Upgrade Series Actuators GB SMSIL-4THGU-E 1) INTRODUCTION 1.1) Scope This manual contains information, safety-related characteristics

More information

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February

More information

This is a new permit condition titled, "2D.1111 Subpart ZZZZ, Part 63 (Existing Non-Emergency nonblack start CI > 500 brake HP)"

This is a new permit condition titled, 2D.1111 Subpart ZZZZ, Part 63 (Existing Non-Emergency nonblack start CI > 500 brake HP) This is a new permit condition titled, "2D.1111 Subpart ZZZZ, Part 63 (Existing Non-Emergency nonblack start CI > 500 brake HP)" Note to Permit Writer: This condition is for existing engines (commenced

More information

Rule No. 1. Scope Definitions Periodicity of technical inspections Technical inspection Inspection requirements...

Rule No. 1. Scope Definitions Periodicity of technical inspections Technical inspection Inspection requirements... Submitted by the Co-Chairs of the IWG on PTI Informal document WP.29-171-21 171 st WP.29, 14-17 March 2017, Agenda item 7.3) PROPOSALS FOR NEW RULE ON PERIODICAL TECHNICAL INSPECTIONS OF MOTOR VEHICLES

More information

GUWAHATI MUNICIPAL CORPORATION WATER WORKS :: PANBAZAR GUWAHATI

GUWAHATI MUNICIPAL CORPORATION WATER WORKS :: PANBAZAR GUWAHATI GUWAHATI MUNICIPAL CORPORATION WATER WORKS :: PANBAZAR GUWAHATI-781001 DETAILED QUOTATION NOTICE & DOCUMENTS NAME OF WORK:- Annual quotation for supply of spare parts for machineries for the year 2017-2018.

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.29/2017/10 Distr.: General 22 December 201 Original: English Economic Commission for Europe Inland Transport Committee World Forum for Harmonization

More information

OPERATOR'S MANUAL COMPONENT OF CRUSHING AND SCREENING PLANT: DIESEL AND ELECTRIC DRIVEN, WHEEL MOUNTED, 75 TON PER HOUR

OPERATOR'S MANUAL COMPONENT OF CRUSHING AND SCREENING PLANT: DIESEL AND ELECTRIC DRIVEN, WHEEL MOUNTED, 75 TON PER HOUR OPERATOR'S MANUAL FOR CRUSHER, ROLL: DIESEL AND ELECTRIC DRIVEN, WHEEL MOUNTED, PNEUMATIC TIRES, 75 TON PER HOUR EAGLE CRUSHER MODEL 5230B AND 5230C (NSN 3820-00-788-5999) EAGLE CRUSHER MODEL 5230D (NSN

More information

COMMISSION REGULATION (EU) / of XXX

COMMISSION REGULATION (EU) / of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2017) XXX draft COMMISSION REGULATION (EU) / of XXX implementing Regulation (EU) No 595/2009 of the European Parliament and of the Council as regards the determination

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

Code of Practice for Vessel Bunkering Operations & Transfer of Waste Liquids by Road Tanker within Jersey Harbours

Code of Practice for Vessel Bunkering Operations & Transfer of Waste Liquids by Road Tanker within Jersey Harbours Code of Practice for Vessel Bunkering Operations & Transfer of Waste Liquids by Road Tanker within Jersey Harbours This Code covers the use of Road Tankers to conduct vessel bunkering operations (including

More information

ECE/RCTE/CONF/4/Add.1/Rev.2

ECE/RCTE/CONF/4/Add.1/Rev.2 ECE/RCTE/CONF/4/Add.1/Rev.2 8 May 2018 Agreement Concerning the adoption of uniform conditions for periodical technical inspections of wheeled vehicles and the reciprocal recognition of such inspections

More information

EDDY CURRENT VARIABLE SPEED DRIVE CONTROLLER - TYPE PM-07

EDDY CURRENT VARIABLE SPEED DRIVE CONTROLLER - TYPE PM-07 EDDY CURRENT VARIABLE SPEED DRIVE CONTROLLER - TYPE PM-07 When properly installed, operated and maintained, this equipment will provide a lifetime of optimum operation. It is mandatory that the person

More information

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS.

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. DRAFT SPECIFICATION NO : RDSO/PE/SPEC/D/PS/0010-99 (REV. 0 ) SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. 0. FOREWORD 0.1 This specification covers manufacturing and

More information

COMMISSION REGULATION (EU) / of XXX

COMMISSION REGULATION (EU) / of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2018) XXX draft COMMISSION REGULATION (EU) / of XXX amending Regulation (EU) 2017/2400 and Directive 2007/46/EC of the European Parliament and of the Council as regards

More information

DART Charger Product Description, Information and Specification

DART Charger Product Description, Information and Specification g Digital Energy DART Charger Product Description, Information and Specification Document Number : PRPI-029 Version : 1.00 Revision : 2 Date : 03.02.11 Classification: NOTICE OF COPYRIGHT & PROPRIETARY

More information

Page 1 of 10. Motor Pool Policies & Procedures

Page 1 of 10. Motor Pool Policies & Procedures Page 1 of 10 Motor Pool Policies & Procedures Page 2 of 10 I. Request Vehicle from Motor Pool A. Call Motor Pool to check availability of desired vehicle and make reservation. B. Complete and submit Motor

More information

1.0 Scope. 2.0 Codes and Standards

1.0 Scope. 2.0 Codes and Standards Table of Contents 1.0 Scope... 2 2.0 Codes and Standards... 2 3.0 Site Conditions... 3 4.0 General Requirements... 3 5.0 Technical Requirements... 5 6.0 Protection, Alarm, Control, Indication and Metering

More information

CENTRAL MARKS DEPARTMENT II (Legal) Our Ref: CMD-II(L)/16:

CENTRAL MARKS DEPARTMENT II (Legal) Our Ref: CMD-II(L)/16: CENTRAL MARKS DEPARTMENT II (Legal) Our Ref: CMD-II(L)/16: 15633 22 04 5 Subject: Coents on Draft Aendent 4 April 5 to IS 15633:2005 Specification for Autootive Vehicles Pneuatic Tyres for Passenger Car

More information

Tender for procurement of Passive Components of LAN & Wi-Fi and their installation. Corrigenda. Annexure/Clause For Read

Tender for procurement of Passive Components of LAN & Wi-Fi and their installation. Corrigenda. Annexure/Clause For Read Tender for procurement of Passive Components of LAN & Wi-Fi and their installation Corrigenda Sl. No. Annexure/Clause For Read Item Specifications Item Specifications 1. Annexure-I, Point No. 1.3 24 Port

More information

Implementation procedure for certification and continued airworthiness of Beriev Be-200E and Be-200ES-E

Implementation procedure for certification and continued airworthiness of Beriev Be-200E and Be-200ES-E 1. Scope 1.1 The general process is described in the implementation procedure for design approvals of aircraft, engine and propeller from CIS and in the implementation procedure for design approvals of

More information

Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification:

Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification: Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification: 1 Capacity 5 ky A UPS system with APFC system 2 Input supply Suitable for400±15% Y, 3 phase, 50

More information

659 December 3, 2018 PROVINCE OF BRITISH COLUMBIA ORDER OF THE LIEUTENANT GOVERNOR IN COUNCIL

659 December 3, 2018 PROVINCE OF BRITISH COLUMBIA ORDER OF THE LIEUTENANT GOVERNOR IN COUNCIL PROVINCE OF BRITISH COLUMBIA ORDER OF THE LIEUTENANT GOVERNOR IN COUNCIL page l of6 Rl0269018 Other: OIC 1004/58 Act and section: Motor Vehicle Amendment Act, 2018, S.B.C. 2018, c. 18, s. 29; Motor Vehicle

More information

State of California AIR RESOURCES BOARD. EXECUTIVE ORDER D Relating to Exemptions Under Section of the Vehicle Code

State of California AIR RESOURCES BOARD. EXECUTIVE ORDER D Relating to Exemptions Under Section of the Vehicle Code (Page 1 of 2) State of California AIR RESOURCES BOARD EXECUTIVE ORDER D 176 11 Relating to Exemptions Under Section 27156 of the Vehicle Code DINAN ENGINEERING, INC. HIGH FLOW COLD AIR INTAKE SYSTEM Pursuant

More information

European Union, Trade in goods with Israel

European Union, Trade in goods with Israel Union, Trade in goods with Israel Table of Contents pg Union, Trade with Israel - Key Figures 2 - / 2017 2 - - AMA/NAMA product Groups 2 - - SITC product Groups 2 - - Top 5 - HS sections 2 - - Top 5 -

More information

OPERATOR'S MANUAL FOR

OPERATOR'S MANUAL FOR OPERATOR'S MANUAL FOR CRUSHER, JAW: DIESEL AND ELECTRIC DRIVEN, WHEEL MOUNTED, PNEUMATIC TIRES, 75 TON PER HOUR EAGLE CRUSHER MODEL 5157 AND 5157A (NSN 3820-00-783-7311) EAGLE CRUSHER MODEL 5157B (NSN

More information

भ रत य रज़वर ब क RESERVE BANK OF INDIA. RBI/ /103 DPSS.CO.PD No.1463/ / January 08, 2019

भ रत य रज़वर ब क RESERVE BANK OF INDIA.   RBI/ /103 DPSS.CO.PD No.1463/ / January 08, 2019 भ रत य रज़वर ब क RESERVE BANK OF INDIA www.rbi.org.in RBI/2018-19/103 DPSS.CO.PD No.1463/02.14.003/2018-19 January 08, 2019 The Chief Executive Officer / President All authorised card payment networks Madam

More information

Emotron FDU and VFX 2.0

Emotron FDU and VFX 2.0 Emotron FDU and VFX 2.0 AC drives with protection class IP20 and IP21 7.5-132 kw Addendum to instruction manual English Software version 4.3X Addendum valid for Emotron FDU and Emotron VFX AC drives This

More information

European Union, Trade in goods with Brazil

European Union, Trade in goods with Brazil European Union, Trade in goods with Brazil Table of Contents pg - Key Figures 2 - / 2017 2 - - AMA/NAMA product Groups 2 - - SITC product Groups 2 - - Top 5 - HS sections 2 - - Top 5 - SITC sections 2

More information

E/ECE/324/Rev.2/Add.140 E/ECE/TRANS/505/Rev.2/Add.140

E/ECE/324/Rev.2/Add.140 E/ECE/TRANS/505/Rev.2/Add.140 30 January 2017 Agreement Concerning the Adoption of Uniform Technical Prescriptions for Wheeled Vehicles, Equipment and Parts which can be Fitted and/or be Used on Wheeled Vehicles and the Conditions

More information

Draft Indian Standard SYN GAS/ AMMONIA TURBO COMPRESSOR LUBRICATING OILS SPECIFICATION

Draft Indian Standard SYN GAS/ AMMONIA TURBO COMPRESSOR LUBRICATING OILS SPECIFICATION Comments Only BUREAU OF INDIAN STANDARDS Draft Indian Standard Doc:PCD 3(2537)C September 2012 SYN GAS/ AMMONIA TURBO COMPRESSOR LUBRICATING OILS SPECIFICATION Not to be reproduced without the permission

More information