Emergency Lighting Products Limited
|
|
- Lester Greene
- 5 years ago
- Views:
Transcription
1 Modern businesses are under pressure to maximise the (sales) revenue per square metre of floor space. The CEN-Power 'Compact' series of static inverters has been designed to significantly reduce the amount of floor area required without increasing the height. By careful design and selection, all components, including the batteries, can be accessed from the front. This means there is no need to leave space to the rear or sides of the cabinets for ventilation and maintenance, freeing up more floor area for other, more profitable purposes. A maximum cubicle depth of 620mm enables the equipment to comfortably fit through a standard doorway. The cubicle plinth allows for good manoeuvrability via forklift or pallet truck during installation. Systems comply with the latest British and European Standards. CEN-Power Compact series inverters are particularly useful when aesthetic or installation considerations preclude the use of conversions, slave luminaires, bulkheads, etc. This is because they are able to supply suitable standard mains luminaires without modification. They are also invaluable where high emergency lighting illuminance levels are required, such as standby lighting or high risk task areas. On medium to large installations, static inverters are a very cost-effective solution, particularly when taking into account their 10-year battery design life, which compares very favourably to the 3 to 4-year design life of self-contained nickel cadmium batteries. s
2 System Operation 2 Mains Available: The normal 230V mains supplies the battery charger (power factor corrected) which converts the AC into DC and charges the battery. The mains also supplies power to the load via the Changeover Contactor. This is the reserve or bypass path and is used with maintained systems. On systems with three phase input, the maintained circuit is supplied by only one of the three input phases (usually L3). The inverter is normally off when mains is available (passive standby). The maintained power can be remotely controlled via an external switched input. Mains Fail: The Inverter starts instantaneously and converts the DC from the battery to AC for the load. Once the inverter is on, the Changeover Contactor is switched automatically to enable the inverter to power the load. The inverter will supply 230V, 50Hz AC to the load until the mains is restored or until the end of rated duration in the case of extended mains failure. Should the battery become fully discharged the inverter will turn off automatically to protect the batteries from being overdischarged. System Features Battery Charger Power Factor Corrected, microprocessor controlled battery charger. This means that during battery recharge the current drawn from the mains is in phase with the voltage (0.99PF during recharge). In commercial terms it means lower electric bills to achieve the same result as a non-power factor corrected charger. It also means less distortion of your mains supply and low AC ripple into the battery which improves battery life. Single and three phase input available 80% capacity within 12 hours and full recharge within 24 hours, in compliance with BS EN 50171:2001. Temperature compensation battery charge voltage adjusted (+-3mV/degree C/cell) in accordance with battery manufacturers specification in order to optimise battery life. Constant voltage, current limited (C/10). Battery disconnect sensing the microprocessor tests the connection between battery and charger/inverter by monitoring the battery charge current. This proves that the battery fuse and cable are intact. Protection against battery over-voltage, input mains low and mains surges e.g. Surges caused by lightning. Battery Valve Regulated Lead Acid (VRLA) 10- year Design Life Compliant with BS EN s
3 3 Manual Battery Test A ten minute test and a deep (full duration) test are accessible via the display, the system will simulate a mains failure and discharge the battery for the predetermined time, and once the test is complete the system will reset and display an alarm if the battery is faulty. Low Voltage Battery Disconnect Disconnects the load from the battery in the event of an extended mains failure to help protect it from the damaging affects of deep discharge Resets automatically when the mains is restored Automatic Battery Test A weekly or monthly ten minute battery test can be selected. During setup, a convenient time and day for the test can be set. The battery capacity is tested, and once the test is complete the system will reset and display an alarm if the battery is faulty. Inverter High Frequency microprocessor controlled pulse width modulation (PWM) IGBT inverter. High quality sinewave output. Galvanic isolation with grounded neutral. High efficiency. Reliable, proven design Changeover Contactor Four pole (2 normally open and two normally closed) configured as a two-pole changeover to ensure that both the live and neutral are switched. Complies with relevant standards of BS Load Circuit Single output load circuit fitted as standard and is selectable maintained or non-maintained by changing a jumper bar on input terminals (default set-up is maintained) Multiple output fuse or MCB distribution option available (details on request) Remote Monitoring Facility Remote indication of a common fault is available via a changeover volt-free contact. Datalogger 200 Alarm records and 200 Battery records can be accessed via the display. An optional printer is available for hardcopy printout. Display Consists of a 4 x 20 character LCD dot-matrix display plus fourteen LED indicators, ten scrolling / command buttons and an audible alarm which sounds whenever there is a problem. LCD digital meter readings are provided, as follows (top two lines): o Inverter: o Reserve: o Charger: o Battery / DC: o Environment: o General: Volts AC / Amps / KVA / % Load / Frequency Volts AC / Amps / KVA / % Load / Frequency Volts AC / Frequency Volts DC / Battery Charge - Discharge Amps Ambient Temperature / Battery Temperature Time / Date / Auto-Test time and date of test s
4 LCD scrolling alarms / status text (lower two lines) o Charger / Reserve input mains fail o Boost Charge (vented batteries only) o Battery Disconnected o Battery / DC Over-voltage o Battery Test 10-minute + Deep Discharge Test o Battery Fault Failed Battery test o DC Earth Leakage (optional) o Auto Test (Automatic Battery Test) o Overload o Short-circuit o Over-temperature o Inverter Under-voltage o Inverter IGBT Saturation Fault o Inverter Peak Current Fault o Load On Inverter o Load on Reserve (Maintained Lights On) o Battery Low o Battery Under-voltage o Power Supply Fault LED Indicators 4 11: 12: 1: Mains On/Off 2: Battery Low 3: Battery Undervolts 4:Over Temperature 5: Inverter Off 6: Load on Inverter 7: Short Circuit (Load) 8: Overload 9: Load on Mains (Maintained Lights On) 10: No Synch. (not active) Enclosure Charger Off 13: DC Earth Leakage (optional extra) 14: Manual Bypass (optional extra) Pushbuttons High quality steel enclosure finished in RAL7032 light grey textured epoxy/polyester powder coating Front access enclosure all parts including batteries can be replaced or measured via the front door so there is no need to leave space at the back or sides of the unit for ventilation or maintenance Top cable entry with removable gland plate for easier installation IP rating for standard enclosures is IP23 (ratings up to IP55 are available, details on request) Plinth allows for good manoeuvrability via forklift or pallet truck during installation. Cabinets are only 620/400mm deep enabling them to fit through standard doors. Plinth colour is RAL7011. Single key locked front door. For added security, the option of double key locks (SD enclosures only) is available. 1: Enable & Off (Red) 2: Inverter On (Green) 3: Charger Boost (vented cells only) 4: Audible Alarm Mute/Reset 5: Indication Reset 6: Scroll Meters Left 7: Left Function Button 8: Right Function Button 9: Scroll Meters Right s
5 Type H W D SB(IP23) SD(IP23) Sizes subject to change without notice Factory Fitted Options 5 SB Enclosure SD Enclosure Integral Distribution: Single or double pole output circuit breakers can be fitted internally to eliminate the need for an external distribution board. Maximum number of outlets is 10 for single pole and 5 for double pole. Printer: An impact printer is available for hardcopy printout of Data-logger and battery test data. RS232 Port: For remote monitoring Software via RS232. SNMP Adapter: For remote monitoring of static inverter system via LAN. Battery Earth Leakage: Detects leakage current between either pole of the battery and earth and displays milliamp reading and alarm if leakage current is too high. AC output Earth Leakage protection: Can be set to 30/100/300mA depending on application. Three phase monitoring: Detects a phase failure causing inverter to start (non-maintained operation only). Charger input display: Amps / KVA / % Load Fire Alarm Interface / Test input: Requires presence of a 24V DC signal either from remote fire alarm panel or remote test facility. When 24V healthy system operates as normal. When 24V signal is lost then inverter starts up and supplies the load (non-maintained systems only). High IP rating: Up to IP55 maximum. s
6 MAINS INPUT Remote Mounted Options 6 RAU: Remote alarm unit, which can be connected up to 100 meters away by 4-core cable for remote monitoring of system. Consists of LED display with audible alarm and silence button. SIM240: In installations where the normal mains luminaire is to be energised from the static inverter under mains fail/emergency conditions then it is necessary to introduce a changeover relay/contactor for the two incoming supplies (mains and static inverter supply). Mains luminaires can be converted integrally or, if insufficient room internally, a remote version is available. Alternatively, a power relay/contactor can be installed to switch several luminaires together. LIVE EARTH Static Inverter Changeover Relay, SIM V, 50Hz AC INPUT FROM STATIC INVERTER NEUTRAL LIGHT SWITCH L E N SW. L UNSW. L E N RELAYS & ELECTRONIC CONTROL CIRCUIT SIM240 (Circuit shown in 'Mains Input Healthy' mode) Typical Schematic of Remote Power Relay / Contactor for switching of multiple luminaires External Light Switch (Supplied & Fitted by Others) 8 L1A 3 L4A Fuse 9 K1 / 1 UNSWITCHED SUPPLY FROM LOCAL DISTRIBUTION BOARD MAINS / EMERGENCY LUMINAIRES CIRCUIT K1 CONTACTS CIRCUIT SHOWN IN N4A 1 SUPPLY FROM STATIC INVERTER CIRCUIT 2 7 Remove Link For Double Pole Switching E N1A L2A N2A DE-ENERGISED STATE IMPORTANT NOTE: Contacts must be rated to 440V RMS minimum to cater for worst case scenario of mains and static inverter supplies in anti-phase. K1 / 2 L3A N3A L E N Mains Only Luminaires 230V, 50Hz AC OUTPUT TO EMERGENCY LUMINAIRES DIMMING CONTROL s
7 7 Sub Circuit Monitor - Monitors mains lighting circuits and provides a signal to the static inverter unit in the event of a mains lighting circuit failure. Normally for non-maintained systems or on the non-maintained circuit of dual output systems, but can also be used for maintained systems that operate in the nonmaintained mode by controlling the maintained circuit. Non load switching. Units are available to monitor single, 4, 8 or 12 sub circuits. A keyswitch can be fitted if required to enable simple testing by an authorised user. Hold Off Relay Monitors Monitors mains lighting circuits and are used to hold off the maintained output from the static inverter unit, providing non-maintained luminaire operation. In the event of a mains lighting circuit failure the contactor drops out, allowing the maintained supply to energise the emergency luminaires. Units are available to monitor single, 4, 8 or 12 sub circuits. A keyswitch can be fitted if required to enable simple testing by an authorised user. These are load switching devices. System Selection Table 1-Hour Systems System Type KVA Rating KW Rating Enclosure Compact SI 2.6KVA 1-Hour SB N/A COMPACT SI 5.6KVA 1-Hour SB N/A COMPACT SI 8.0K 1-Hour SD N/A COMPACT SI 10.0K -Hour SD SD COMPACT SI 12.0K 1-Hour SD SD COMPACT SI 16.0K 1-Hour SD SD COMPACT SI 20.0K 1-Hour SD SD COMPACT SI 24.0K 1-Hour SD SD Additional Batteries Enclosure COMPACT SI 32.0K 1-Hour (3 Phase input only) SD 2 x SD 3-Hour Systems COMPACT SI 1.0K 3-Hour SB N/A COMPACT SI 2.0K 3-Hour SB N/A COMPACT SI 3.2K 3-Hour SD N/A COMPACT SI 4.8K 3-Hour SD N/A COMPACT SI 5.6K 3-Hour SD N/A COMPACT SI 8.0K 3-Hour SD N/A COMPACT SI 10.0K 3-Hour SD SD COMPACT SI 12.0K 3-Hour SD 2 x SD COMPACT SI 16.0K 3-Hour SD 2 x SD COMPACT SI 20.0K 3-Hour SD 2 x SD COMPACT SI 24.0K 3-Hour SD 3 x SD COMPACT SI 32.0K 3-Hour (3 Phase input only) SD 4 X SD Notes: 20% Overcapacity included in above table in compliance with BS EN Load Power Factor no better than 0.85 is assumed Sizes subject to change without notice s
8 8 Systems have been designed and sized to make maximum use of the batteries. Single or three phase input must be specified when ordering. NB: On systems with three phase input, the maintained circuit is supplied by only one of the three input phases (usually L3/Blue Phase), however, the charger is true three-phase. System & Installation Considerations Room Ventilation Negligible amounts of hydrogen are generated under normal operating conditions, however, adequate ventilation should be provided to prevent potentially explosive levels of gases from building up. The system will generate a small amount of heat during (passive) standby operation, but during battery discharge and recharge a greater amount of heat will be generated. It is therefore necessary to provide adequate ventilation in order to keep the room cool and to ensure that the battery temperature does not rise significantly. Optimum battery operating life and performance is achieved at an ambient temperature of 20C ±5C, i.e. a temperature range of 15 to 25C. Ventilation should be designed to draw fresh, cool air in at low level and exhaust at high level. Warning Notices These should be displayed on entry doors to static inverter/battery rooms, e.g. BATTERY ROOM. EXTINGUISH ALL NAKED LIGHTS BEFORE ENTERING. NO SMOKING. Environment The room must be kept dry and free from dirt and dust at all times. Rating of System When calculating the VA and Watts rating of the static inverter it is important to ensure that the actual power consumption of each luminaire is used and not the lamp rating, i.e. the efficiency of the luminaire is taken into account. When a total load figure is achieved then spare capacity should be added in order to cater for future expansion and/or on-site amendments to the lighting design. In order to maximise the quantity of luminaires that can be connected to the static inverter their power factor should be 0.85 or higher. Modern fluorescent luminaires utilising high frequency control gear are ideally suited as they generally have power factors approaching unity. Types of Lighting Static inverter systems operating in passive standby mode are suitable for most forms of fluorescent and incandescent lighting. However, they are not suitable for discharge lighting (SON, metal halide, etc) due to the fact that when the mains supply is interrupted for only a very short period of time (typically this can be as short as 5 or 10 milliseconds) they usually have to cool down before they are able to re-strike. The changeover time of a passive standby inverter is generally too long to support this form of lighting. Also, discharge lamps normally have a warm-up period before achieving full brightness. For these reasons discharge lighting is not recommended for use as emergency lighting, however, they can be used as long as they are supplementary to a normal emergency lighting installation. We are able to supply ON-LINE or NO-BREAK static inverter systems to support combined fluorescent, incandescent and discharge lighting schemes. Glow Starters Important Note: BSEN prohibits the use of glow starters in fluorescent luminaires used for emergency lighting. Multiple Use of Systems Important Note: Systems specified for emergency lighting use should not have other services connected to them. TECHNICAL SPECIFICATION Charger Mains Supply: 230/400V ±10% Single or Three Phase, 50 or 60Hz ±5% Power Factor: 0.99 during recharge. Input Protection: MCB to BS EN Fusegear: gr to IEC and -4, DIN VDE Charge Regime: Temp. Compensation: Protection: Technology: Constant voltage, current limited. Battery float voltage controlled to ±1% with mains fluctuations as stated above. Battery recharged to achieve 80% autonomy after 12-hours and full autonomy within 24-hours. ±3mV/C/Cell. Battery over-voltage, mains input low & input surge. Full wave controlled thyristor/diode bridge with IGBT power factor correction. Micro-processor controlled. s
9 9 Inverter Voltage: 220/230/240V AC (default setting at 230V) single-phase. Other voltages available on request. Voltage Regulation: Voltage Waveform: ±1% Static, ±6% Dynamic. Sinusoidal. Frequency: 50 or 60Hz ±0.1% Distortion (THD): Load Power Factor: Overload: Efficiency: Synchronising: Protection: Technology: <3% into linear load. 0.3 lag to 0.3 lead. 120% continuous, 121% for 2-minutes, 160% for 5-seconds without reduction in output voltage. Once these levels are exceeded the output voltage will be reduced to maintain constant power until inverter under-voltage level is reached. 80 to 93% depending on inverter rating and load applied. Inverter synchronises with mains before contactor changeover. Electronic overload, short-circuit, over-temperature, inverter over/under-voltage, DC input reverse polarity & battery low voltage shutdown (battery deep discharge protection). High frequency, pulse width modulated IGBT with isolation transformer. Battery Type: 10-year design life valve regulated lead acid (VRLA). Changeover Contactor Fusegear: Double pole gr to IEC and -4, DIN VDE Standard: To the relevant requirements of BS Enclosure Type: Floor standing on raised plinth. Degree of Protection: Finish: Cable Entry: Cable Termination: IP23 (up to IP55 maximum details on request). Textured epoxy/polyester powder coat, colour light grey RAL 7032 Top DIN rail mounted, screw clamp type. General Noise Level: 1-metre distance and height. Max Relative Air Humidity: Maximum Altitude: Operating Temperature Range: Recommended Operating Temperature Range: 90%, non-condensing metres ASL before de-rating. 0 to 40C Standards System Complies With: BS EN 50171: C ±5C for optimum battery performance and life. BS EN (Safety) BS EN (EMC) BS EN (Harmonics) s
Central Battery Systems Loadstar AC/DC Systems
The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources of emergency power for escape
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationTECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)
TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power
More informationTechnical Data Sheets
GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series / 10 20 30 kva 400 VAC CE Series 4 SGT4000_010-020-030 GE_01 Manufactured by: GE
More informationPOWER kva
+44 (0)20 8868 3732 TECHNICAL DATA SHEET B9600 400-800kVA GENERAL INFORMATION UPS Type ON LINE - Doppia Conversione Nominal output power (Cos φ0,8) kva 400 500 600 800 Nominal output power (Cos φ1,0) kw
More informationTechnical data sheets
GE Consumer & Industrial Power Protection Technical data sheets Digital Energy Uninterruptible Power Supply LP 11 Series / 3 5 6 8 10 kva A product by: GE Consumer & Industrial SA General Electric Company
More informationPOWER kva
TECHNICAL DATA SHEET B9000 FXS 60-80-100-125-160kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos φ 0,8) kva 60 80 100 125 160 Nominal output power
More informationPOWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)
TECHNICAL DATA SHEET B9000 FXS 200-250 - 300kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE - Double Conversion Nominal output power (Cos φ0,8) kva 200 250 300 Nominal output power (Cos φ1,0)
More informationTechnical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality
GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino
More informationTechnical Data Sheets
GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series 10 20 30 40 kva 400 Vac CE Series 5 GE Consumer & Industrial SA General Electric Company CH
More informationIlluminator Series CR NEMA 3R
Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the
More informationTECHNICAL DATA SHEET KVA UPS Systemss
Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800
More informationEMEX Power. EMEX Power. Modular AC/AC Central Battery System. EMEX Power
EMEX Power EMEX Power Modular AC/AC Central Battery System EMEX Power EMEX Power Modular AC/AC Central Battery System System design The EMEX Power inverter and charger modules utilise solid state electronics
More informationThree Phase UPS Systems Range: 10 to 500kVA
Three Phase UPS Systems Range: 10 to 500kVA Three Phase UPS Systems Hitachi Hi-Rel Power Electronics Pvt. Ltd. is in the business of Industrial UPS Systems since 1987 and has rich experience in supplying
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91
More informationTOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS
INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...
More informationDefender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications
Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TLES_040-120_S1_UPS_GE_Floor_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41
More informationTechnical Data Sheets
Digit al Energy T M L P Seri es Di gi ta l Energy TM LP Series Digita l Energ y T M L P Se rie s GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply
More informationPower Lynx 3 Uninterruptible Power System (UPS) Technical Specifications
Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible
More informationTechnical Data Sheets
GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33U Series / 10 20 30 40 50 60 kva 208 VAC UL Series 1 Date of issue: 11/05/2008 LPS33U_030-040_S1 GE_01
More informationIlluminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System
Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical
More informationgimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy
GE Digital Energy Technical data sheet Uninterruptible Power Supply LP11 924 Series 6 & 10 kva gimagination at work GE T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www..com General data Topology VFI,
More informationPhoenix Inverter
Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC
More informationTechnical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work
Digital Energy Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91
More informationTechnical Data Sheets
GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 60 80 100 120 kva PurePulse 400 Vac CE Series 1 SG-CE Series 100-120 kva PurePulse SG-CE Series
More informationFortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state
More informationAurora Single Phase Emergency Lighting Inverters
Aurora Single Phase Emergency Lighting Inverters True Sine Wave On-Line Single Phase Emergency Lighting Inverters AURORA Series Emergency Lighting AC Inverters are among the most reliable systems available
More informationTELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)
Local Area Networks (LAN) ServerS DATA CENTRES CASH REGISTERS TELECOM- MUNICATIONS DEVICES e-business (Servers Farms, ISP/ASP/POP) INDUSTRIAL PLCs ELECTRO- MEDICAL DEVICES EMERGENCY DEVICES (Lights/Alarms)
More informationMaster Plus kva
Local Area Networks (LAN) ServerS Data Centers Telecommunication devices e-business (Servers Farms, ISP/ASP/POP) Industrial Processes Industrial PLCs Electromedical Devices Emergency Devices (lights/alarms)
More informationCobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications
Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TM SG Series 200-250 - 300 PurePulse CE S3 TM SG Series 160 PurePulse CE S3 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno)
More informationTELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)
LOCAL Area Networks (LAN) ServerS DATA CENTRES CASH REGISTERS TELECOM- MUNICATIONS DEVICES e-business (Servers Farms, ISP/ASP/POP) INDUSTRIAL PLCs ELECTRO- MEDICAL DEVICES EMERGENCY DEVICES (Lights/Alarms)
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply SGSE_010-040_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91
More informationTECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)
TECHNICAL DATA SHEET B8031 FXS 10 15 20 kva 3Ph(In) 1Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos 0.9) kva 10 15 20 Nominal output power (Cos 1.0) kw 9 13.5
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TM SG Series 100 &120 PurePulse TM SG Series 60 & 80 PurePulse SGSE_060-120_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino
More informationPowerPro three phase UPS technical data
PowerPro three phase UPS technical data General Specification Model RM/RT10 RM/RT15 RM/RT20 RT30 RT40 RT60 RT80 RT100 RT120 RT160 UPS type Power rating kva 10 15 20 30 40 60 80 100 120 160 kw 8 12 16 24
More informationPowerValue 11/31 T kva
Technical Datasheet PowerValue 11/31 T 10-20 kva Classification IEC/EN 62040-3 VFI-SS-111 Working mode on-line double conversion Power rating 10-20 kva Paralleling up to 4 units (up to 80 kva) Output power
More informationTECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)
TECHNICAL DATA SHEET B8033FXS 10 15 20 kva 3Ph(In) 3Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cosϕ 0.9) kva 10 15 20 Nominal output power (Cosϕ 1.0) kw 9 13.5
More informationLiebert. FP 50Z kva
Liebert FP 50Z 5 250 kva Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online faster and at a lower cost when search and social
More informationFortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting
More informationMaster Plus kva
LOCAL AREA NETWORKS SERVERS DATA CENTERS TELECOM MUNICATION DEVICES (Servers Farms, ISP/ASP/POP INDUSTRIAL PROCESSES INDUSTRIAL PLCS MEDICAL DEVICES EMERGENCY DEVICES ights/alarms Master Plus 100- kva
More informationMaster DIALOG INDUSTRY RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs Emergency devices (lights/alarms) Electro-medical devices Telecommunication devices Industrial applications
More informationLiebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL
GXT4 5000 & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY This specification shall define the electrical and mechanical characteristics and requirements for a continuousduty,
More informationPOWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting
POWER+ PREMIUM CBS CENTRALIZED Battery System BS-EN-50171 Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS 10KVA-40KVA The systems running
More informationEFFEKTA Power Supplies
EFFEKTA GENERAL INFORMATION UPS topology ON LINE - Double Conversion Classification VFI-SS-111 in accordance with IEC 62040-3 Nominal output power (Cos Ø 0,9) - kva 10 15 20 30 40 Nominal output power
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company imagination at work QUITO: Elia Liut N45-26 y Edmundo Chiriboga Telf:
More informationCentral Battery Systems
Central battery system based emergency lighting is ideal for medium to large installations. For projects where central control and testing is desirable, a central battery system is a viable and cost effective
More informationLiebert GXT VA RT230 Rack-Tower model GUIDE SPECIFICATIONS 1.0 GENERAL
1.1 SUMMARY Liebert GXT3 10000VA RT230 Rack-Tower model GUIDE SPECIFICATIONS 1.0 GENERAL This specification shall define the electrical and mechanical characteristics and requirements for a continuousduty,
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationPSU EN54-4 Power Supplies
PSU EN54-4 Power Supplies Ordering: Models, Sales Order Parts: PSU MXP-549 : 1.5A PSE in 7Ah enclosure MXP-550 : 3.0A PSE in 17/18Ah enclosure MXP-550D : 3.0A PSE in 25Ah enclosure MXP-551 : 5.0A PSE in
More informationTechnical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER
Technical Specifications Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Sentinel PRO CONTENTS 1. GENERAL DESCRIPTION... 2 1.1. Main features of the UPS unit... 3 1.2. Standard Versions...
More informationTLE Series UPS 400/500 kw With eboost Technology
TLE Series UPS 400/500 kw With eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical power
More informationINDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL
Local Area NETWORKS (LAN) ServerS DATA CENTRES TELECOM- MUNICATIONS DEVICES e-business (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCs ELECTRO- MEDICAL DEVICES EMERGENCY DEVICES (Lights/Alarms)
More informationLumencia. LLMPS SERIES Micro Power Systems. Multi-Unit Residential Lighting. Job Name: Type:
APPLICATIONS LLMPS Series inverter systems are designed to provide sinusoidal AC emergency power to incandescent, flourescent, or LED fixtures of between 20 and 55 watts. Surface, recessed or ceiling T-Grid
More informationDycon D2430 EN54-4 Fire Alarm Power Supply Series
Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product
More informationCentral Battery Systems
Central battery system based emergency lighting is ideal for medium to large installations. For projects where central control and testing is desirable, a central battery system is a viable and cost effective
More informationPOWERTRONIX QUASAR 5-40 KVA
POWERTRONIX QUASAR 5-40 KVA DT 0251 E00 TECHNICAL DATA Rev. Description Date Checked Released Date Type of doc. Page n Pag. Tot. ISSUED 07.03.2000 E.Borsa 07.03.2000 Approved A.Gorlani Pag.1/6 Cod. DT251
More informationEaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC
Manufacturer s declaration in accordance with 8- Frame Model catalogue reference 93PS-XX(20)-YY- 93PS-XX(40)-YY- Number of power modules (UPM) 1 1 or 2 Number of internal batteries 0 to 2 x 32 blocks 0
More informationEMERGENCY ELECTRO- MEDICAL INDUSTRIAL PLCS DEVICES. (Lights/Alarms)
LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES BM Plus Series BMLM 10-20 kva Single-phase BMLT 10-120 kva Three-phase CASH REGISTERS TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP)
More informationSola 3000 Guide Specifications
Sola 3000 Guide Specifications CSI 16610 - Static Uninterruptible Power Supply Systems - Sola 3000 Guide Specifications for a 700 to 2200 VA Single - Phase Uninterruptible Power Supply System 1.0 GENERAL
More informationProduct Specifications
Product Specifications Guide Specification for FirstLine 10Kva, 15Kva, and 20Kva Three-Phase, On-Line Uninterruptible Power Supply 4-15-10 301 Gaddis blvd, Dayton, OH 45403, USA Telephone: (866) 261-2257,
More informationIndustrial Chargers and
Industrial Chargers and DC Systems SPR - Single Phase Rectifier TPR - Three Phase Rectifier 12V 250V 5A 1000A Designed for all Industrial applications Oil & Gas, Petrochemicals Offshore, Onshore, Pipelines
More informationConceptpowerTM Modular kVA
TECHNICAL SPECIFICATIONS ConceptpowerTM Modular 10-15-20-30-40kVA Uninterruptible Supply (UPS) Modular, n+1 redundant, three-phase On-line, Double-Conversion, VFI Classic-Line 10-40kVA Gemini-Line 10-30kVA
More informationTLE Series UPS 160/200/225/250 kw with eboost Technology
TLE Series UPS 160/200/225/250 kw with eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical
More informationLiebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL
1.1 SUMMARY Liebert GXT3 8000 & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL This specification shall define the electrical and mechanical characteristics and requirements
More informationEMEX Power Modular AC/AC central power supply system
90 EMERGI-LITE EMERGENCY LIGHTING & CENTRAL POWER SUPPLY SYSTEMS Modular AC/AC central power supply system The inverter and charger modules utilise solid state electronics of the highest reliability to
More informationINTRODUCING THE NEW MINI INVERTERS BY READY-LITE
INTRODUCING THE NEW MINI INVERTERS BY READY-LITE RELIABILITY THROUGH TECHNOLOGY FOR ECONOMICAL, RELIABLE POWER IN AN EMERGENCY, DEPEND ON MINI INVERTERS LED technology in emergency lighting systems has
More informationTower Electronic Systems
3300 UPS Instruction Manual AUGUST 2005 CONTENTS 1.0 INTRODUCTION 1.1 General description 3 1.2 UPS building blocks 3 1.2.1 Boost converter 3 1.2.2 Inverter 3 1.2.3 Static transfer switch 3 1.2.4 Battery
More informationAPC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply
APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous
More informationTechnical Specification SENTINEL PRO
Technical Specification SENTINEL PRO Contents 1 GENERAL DESCRIPTION... 3 1.1 Main features of the UPS unit... 4 1.2 Standard Versions... 4 1.3 ER Versions for extended autonomy... 4 2 SENTINEL PRO SERIES
More informationMarketing Management Team of Europe
Emerson Network Power Liebert NXe UPS GUIDE SPECIFICATIONS For a 10 to 20 kva (50 or 60Hz) Parallelable Digital Uninterruptible Power Supply (UPS) System - 1 - Contents 1.1 SUMMARY... 3 1.2 STANDARDS...
More information3. MAJOR SYSTEM COMPONENTS Emergency Lighting Power System shall consist of the following major subsystems:
TECHNICAL GUIDE SPECIFICATIONS Power-Lite Single Phase, (200 to 490 Watts) UL924 Central Lighting Inverter 1. SCOPE The Emergency Lighting Power System shall be a solid-state single phase unit designed
More informationDELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw
DELPHYS GP Green Power 2.0 range 160 to 1000 kva/kw OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application.
More informationIndustrial PFC UPS System
Based on Statron s leading A.T.I.S. (Advanced Technology Industrial System) platform, the S3000 range is a true-industrial UPS system using the latest Power Factor Corrected (PFC) IGBT rectifier technology.
More informationTECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III
TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III 1. SCOPE A. The Central Lighting Inverter shall be a solid-state three phase system designed to provide
More informationDistinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation
SUN MAGIC + SUN MAGIC + is a state of art PCU product from ENERTECH product basket with Global standards. This unit will give operational flexibility to its customers to enjoy the benefits of advanced
More informationTECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT
TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters
More informationUPS Multi Sentry 10-20kVA
The Multi Sentry series is ideal for protecting data centres and telecommunications systems, IT networks and critical systems in general, where the risks connected with poor energy supply can compromise
More informationLiebert PowerSure PSI UPS
Liebert UPS GUIDE SPECIFICATIONS 1000VA to 3000VA Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical and mechanical characteristics and
More informationPower Safety. Protect 8. Industrial UPS. Protect 8.31 Single Phase output 10 kva 120 kva. Protect 8.33 Three Phase output 10 kva 120 kva
Power Safety Protect 8. Industrial UPS Protect 8.31 Single Phase output 10 kva 120 kva Protect 8.33 Three Phase output 10 kva 120 kva 400 V AC input 220 V DC The Building Block UPS Engineering is our Business
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationTLE Series UPS 750/1000 kw With eboost Technology
TLE Series UPS 750/1000 kw With eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical
More informationTECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS
Tender Paper TECHNICAL SPECIFICATIONS FOR 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS Contents 1. General 2. Tender submission requirements 3. Environmental
More informationLiebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS
1.1 SUMMARY Liebert GXT4 8000 & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL This specification shall define the electrical and mechanical characteristics and requirements
More informationMaster MPS kva kva 3:1 3:3 VFI TYPE
DATACENTER E-MEDICAL INDUSTRY TRANSPORT EMERGENCY VFI TYPE ONLINE Master MPS 3:1 3:3 10-100 kva 10- kva 4 SmartGrid ready f lywheel compatible Supercaps UPS Service 1st start HIGHLIGHTS Efficiency Control
More informationK25000 & KD25000 Series
K25000 & KD25000 Series Fire Alarm Power Supplies Installation, Commissioning and Operating Manual Man-1128 Issue 14 January 2016 Man-1128_K25400_series_Power_Supply_Manual_14 Page 1 of 20 Section Page
More informationILLUMINATOR LV. Emergency Lighting Inverter System 175VA through 750VA. Illuminator Series LV Single Phase
ILLUMINATOR LV Emergency Lighting Inverter System 175VA through 750VA Illuminator Series LV Single Phase ILLUMINATOR SERIES LV The Illuminator Series LV is a 175VA-750VA fast transfer Emergency Lighting
More informationDistinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation
SUN MAGIC SUN MAGIC is a state of art PCU product from ENERTECH product basket with Global standards. This unit will give operational flexibility to its customers to enjoy the benefits of advanced monitoring
More informationMERU Solar Off-Grid Inverters
1 kva / 2 kva Off-Grid Solar Inverters with LCD and LED displays 24 / 48 VDC battery versions for 1 kva and 48 VDC for 2 kva Pure sine wave with highest efficiency Fully configurable (PV / Grid priority
More informationPowerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)
A Complete solution for small battery-backed dc instrument power systems. DATASHEET Supply 12Vdc 8A or 24Vdc 6A loads Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where
More informationModel ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase
Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible
More informationSmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option
SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation
More informationtel: Enhanced Power Services Limited Industrial PLCs Electro Medical Devices
Enhanced Power Services Limited Local Area Networks (LAN) Servers Data Centres Cash Registers Telecomunication Devices e-business (Server Farms, ISP/ASP/POP) Industrial PLCs Electro Medical Devices Emergency
More informationRental Power QSB7 series engine
Specification sheet Rental Power QSB7 series engine 150 kva 200 kva 50 Hz 135 kw 180 kw 60 Hz Description This Cummins commercial generator set is a fully integrated power generation system, providing
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS 40, 60, 80 kva (three phase input and output) GENERAL DATA Output Rated Power kva 40 60 80 Output Power Factor 0.8 Topology Technology Construction Parallel Configuration Redundant
More informationMKN-DSP SERIES - THREE PHASE
Output Power Factor 0.9 MKN-DSP SERIES - THREE PHASE Double conversion True On-Line UPS 3 Phase Input - 3 Phase Output 10 KVA 15 KVA 20 KVA 30 KVA 40 KVA 50 KVA 60 KVA Model for: 208/120 V 220/127 V /
More informationMASTERYS IP+ 10 to 80 kva
MASTERYS IP+ 10 to 80 kva OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application. the information
More information