1 Revision A
2 Table of Contents Revision History...2 Overview...3 Soft Start not complete fault...3 Under voltage fault...4 Under voltage warning limit...5 Over voltage maximum limit...5 Over voltage warning limit...7 Managing excessive +48 V internal propulsion bus voltages within the QS 100 stator...7 Coil/block level power management (software enabled)...7 Hardware power management (in hardware)...10 List of Figures Figure 1: High level detail of soft start circuit within the QS Figure 2: Soft start not complete messaging behavior... 4 Figure 3: Under voltage messaging behavior... 5 Figure 4: Inverter status and OV fault behavior... 6 Figure 5: Coil/individual block current vs. +48 V internal propulsion bus voltage (10 msec filter applied)... 8 Figure 6: Coil/individual block current vs. +48 V internal propulsion bus voltage with Slave code version or higher (1 msec filter applied)... 9 Figure 7: Power dissipation per block vs. +48 V internal propulsion bus voltage... 9 Figure 8: Power dissipation per block vs. +48 V internal propulsion bus voltage for slave code version greater than Figure 9: 10 Ohm resistor power dissipation vs. +48 V internal propulsion bus voltage Revision History Rev. Date Author Description A 3/2/2015 E. Wildi Initial release 2015 MagneMotion, Inc. Page 2 of 11
3 Overview The QS 100 platform is designed to operate at a nominal 48 VDC +/-5% bias. However voltage drops in the power distribution system when delivering power to the stator(s) and voltage increases during regeneration events will lead to fluctuations in the voltages seen at the QS stator terminals. How voltage conditions at the QS are managed and communicated is the object of this document. Soft Start not complete fault The QS inverters are enabled when the filtered QS V internal propulsion bus (after the soft start circuitry, see Figure 1) rises above 43 V. Until this voltage is reached, the QS motor status through the HLC will report a soft-start not complete and the system will not allow vehicle motion to occur. Once this internal voltage is reached, the system will support vehicle motion and operate as intended (soft start switch closed). If the internal bus voltage drops below 41 V during operation, the soft-start switch will open and the motor status through the HLC will report a soft start not complete message to the host (refer to either the Host Controller TCP/IP Communication Protocol User s Manual, the Host Controller EtherNet/IP Communication Protocol User s Manual, or the Mitsubishi PLC TCP/IP Library User s Manual). All inverters within this QS 100 stator will be disabled and any vehicles in motion over this stator will no longer be under active control and as such their motion will be undefined. Soft Start QS V propulsion Soft start resistor +48 V internal propulsion bus Switch 10 Ohm +48 V return Figure 1: High level detail of soft start circuit within the QS 100 Normal operation will resume (soft start switch closed) once the internal propulsion bus gets back up to 43 V; the motor status for the soft start error message will automatically self-clear at that time. This messaging behavior is illustrated in Figure 2. Not shown, is the additional constraint that the voltage across the soft start resistor shown in Figure 1 must be < 2 V to allow the switch to close and thereby prevent a soft start not complete error message to appear MagneMotion, Inc. Page 3 of 11
4 A soft start fault may be due to an internal failure within the QS 100 or more likely, a result of the voltage applied to the QS V propulsion bus being too low. 41 V 43 V +48 V internal propulsion bus voltage (filtered) Under voltage fault Figure 2: Soft start not complete messaging behavior An under voltage fault will be declared and reported to the host (refer to either the Host Controller TCP/IP Communication Protocol User s Manual, the Host Controller EtherNet/IP Communication Protocol User s Manual, or the Mitsubishi PLC TCP/IP Library User s Manual), when the +48 V propulsion filtered voltage measured at the QS 100 is below +43 V upon initial power up. Once this fault clears, it will only re-appear if the filtered +48 V propulsion voltage drops below +41 V. The QS motor status through the HLC will reports this under voltage fault. This fault self-clears when the filtered +48 V propulsion input voltages rises back to >43 V. The behavior of this fault messaging is illustrated in Figure 3. This fault is likely due to excessive +48 V propulsion / +48 V return cable resistance from the 48 V power source to the QS or to an internal failure within the QS 100 that is significant enough to collapse the +48 V propulsion voltage at the QS 100 proper. This fault message is only available on systems that run the following software. It is not active on prior software version: NC version or higher Master version or higher Soft start not complete error will be reported No soft start not complete error will be reported 2015 MagneMotion, Inc. Page 4 of 11
5 41 V 43 V +48 V propulsion voltage (filtered) Under voltage warning limit Figure 3: Under voltage messaging behavior When the QS V propulsion bus drops below 42.5 V, an under voltage warning will be logged by the HLC when the Log Level for Faults is set to the Warning level (refer to the Node Controller Web Interface User s Manual). This warning is not pushed to the host. When the voltage rises back up to 43 V this fault will self-clear. There is no voltage filtering associated with this warning since the intent is to capture maximum voltage excursions. Upon initial system power up, this fault will be present and persist until the propulsion bus reaches 43 V. The intent of this feature is to verify proper cabling and power distribution for new systems and may be used to do periodic assessment of the system to make sure no degradation has occurred. A properly designed system should never exhibit this alarm following system power up. This feature is available only on systems running the following code base or higher: NC version or higher Master version or higher Under voltage error will be reported Over voltage maximum limit No under voltage error will be reported Based on the specific system wiring and vehicle activity, it is possible for regenerated power resulting from vehicle decelerations to cause the QS +48 V propulsion bus voltage to rise to excessive levels and MMI has implemented protective features to guard against operating conditions that could damage the motor. Since the source of such a condition is due to regeneration effects associated with active braking or deceleration of a vehicle (loaded or unloaded) over the stator, a means (among others) of eliminating such regenerated power is to shut down the QS inverters MagneMotion, Inc. Page 5 of 11
6 When the QS V propulsion bus reaches 59 V, the QS 100 inverters are shut down thereby eliminating any regeneration effects within this stator (assuming this stator contributes to regeneration). Vehicle arrays over this stator will no longer be under active control and therefore will no longer decelerate as intended. An over voltage fault will be reported to the host when this condition is detected (refer to either the Host Controller TCP/IP Communication Protocol User s Manual, the Host Controller EtherNet/IP Communication Protocol User s Manual, or the Mitsubishi PLC TCP/IP Library User s Manual). To avoid issuing an over voltage fault to the host due to spurious noise, the +48 V propulsion voltage used to trigger this event is filtered. This error message and the associated fault will persist until the filtered voltage at the QS V propulsion bus drops below 57 V. At this time the system will attempt to resume active control of the vehicle. This inverter status behavior is shown in Figure 4. There are several possible solutions available to eliminate a fault of this type. Specifically: 1. Reduce cable resistance between stators that share a common +48 V propulsion supply if voltage drops in these cables leads to excessive voltages on stator(s) undergoing regeneration. 2. Reduce maximum speed and/or maximum accelerations to reduce the amount of regenerated power flowing back into the system. 3. Increase spacing between vehicles on stators sharing a common +48 V propulsion supply to increase the number of blocks available to absorb power during regeneration. 4. Connect more QS 100 stators to a common +48 V propulsion supply to increase the number of blocks available to absorb regenerated power. 5. If all of the above resolution paths have been explored and the problem still persists, the only solution is to add an active voltage clamp across the +48 V propulsion supply local to the power supply or to the QS 100 stator(s) that are exhibiting this issue. The clamping voltage should be above 51 V but kept as low as possible. 57 V 59 V +48 V propulsion voltage (filtered) Inverter operational and no OV fault declared Inverter disabled and OV fault reported Figure 4: Inverter status and OV fault behavior 2015 MagneMotion, Inc. Page 6 of 11
7 Over voltage warning limit When the QS 100 master board detects instantaneous voltages in excess of 57 V on its +48 V propulsion bus, an over voltage warning will be issued to the HLC when the Log Level for Faults is set to the Warning level (refer to the Node Controller Web Interface User s Manual). This warning fault is not pushed to the host and will self-clear once the +48 V propulsion bus voltage drops below 56.5 V. The intent of this feature is to verify proper cabling and power distribution for new systems and to support periodic assessments of the system to make sure no degradation has occurred. Any warnings observed as part of system commissioning need to be addressed and resolved using one or several of the resolution methods described above under over voltage faults. The warning feature is only available on systems operating with the following code base: NC version or higher Master version or higher Managing excessive +48 V internal propulsion bus voltages within the QS 100 stator To supplement any external power management schemes applied to a QS 100 system, a means of internally consuming regenerated power within a QS 100 stator is incorporated as a product feature. Coil/block level power management (software enabled) When the filtered +48 V internal propulsion bus reaches 53 V, current will begin to ramp in coils/blocks that are available to effectively allow the QS stator to absorb/ dissipate power due to regeneration within itself or coming from other QS 100 stators connected on a commonly shared +48 V power supply. The current in these available blocks ramps linearly to 5 A over a 2 volt range from 53 V to 55 V in this case. The coil current remains constant at 5 A for voltages above 55 V and drops to zero for voltages above 59 V (since all inverters are turned off as outlined above). This behavior is shown in Figure MagneMotion, Inc. Page 7 of 11
8 Figure 5: Coil/individual block current vs. +48 V internal propulsion bus voltage (10 msec filter applied) For slave software version or higher, the voltage at which coil current initiates has been reduced to 51.5 V. The linear ramp from 0 to 5 A occurs between 51.5 V and 53.5 V and is maintained at 5 A above this level until voltages reach 59 V. This behavior is shown in Figure 6. The voltage filtering is also less aggressive (1 msec) in this code version. For slave software version or higher, the number of coils available to absorb power has been increased. In prior slave code versions, coils that were under the vehicle as configured (typically longer than the vehicle magnet array length) and coils allocated ahead of a vehicle in motion (associated with brick wall headway) were not used to absorb power. For vehicles that are appreciably longer than the magnet array and/or for vehicles that are travelling at their maximum velocity in a convoy, this represents an appreciable number of blocks. The new slave code maximizes the number of blocks available to absorb power. Specifically, a coil block is available and will be used to dissipate power within a QS 100 stator if its neighboring block (upstream and downstream) does not have a magnet array spanning it. Note that a neighboring block may be within a different QS 100 stator as would be the case for the first and last blocks within a given QS 100 stator MagneMotion, Inc. Page 8 of 11
9 Figure 6: Coil/individual block current vs. +48 V internal propulsion bus voltage with Slave code version or higher (1 msec filter applied) For a nominal coil/block resistance of 1.9 Ohm, the dissipated power will be 47.5 W per block when the 5 A current level is reached and will remain at this level up to 59 V. The dissipated power vs V internal propulsion bus voltage for both slave code base versions is shown in Figure 7 and Figure 8. Figure 7: Power dissipation per block vs. +48 V internal propulsion bus voltage 2015 MagneMotion, Inc. Page 9 of 11
10 For the legacy slave code base, when the +48 V internal propulsion bus is between 53 V and 55 V, the power dissipated per block can be expressed as: * (+48 V internal propulsion bus - 53) 2 Watts. For the slave code base or higher, when the +48 V internal propulsion bus is between 51.5 V and 53.5 V, the power dissipated per block is: * (+48 V internal propulsion bus 51.5) 2 Watts Figure 8: Power dissipation per block vs. +48 V internal propulsion bus voltage for slave code version greater than The QS m stator has 10 blocks and the QS 100 ½ m has 5 blocks. Therefore, the maximum power each stator can absorb is 475 W and W respectively. Hardware power management (in hardware) When the + 48 V internal propulsion voltage rises above 58.9 V, a 10 Ohm resistor within the QS 100 is switched across +48 V propulsion and +48 V return as shown in Figure 1. This internal load will remain active for voltages higher than this voltage and will be removed when the voltage goes below 56.9 V. The power dissipated by this load, shown in Figure 9, is additive to any power dissipated by the coils/blocks as outlined above MagneMotion, Inc. Page 10 of 11
11 Figure 9: 10 Ohm resistor power dissipation vs. +48 V internal propulsion bus voltage The power dissipation through this 10 Ohm resistor can be expressed as: (+V propulsion) 2 /10 Watts At 58.9 V this translates to 347 W and at 56.9 V it would be 324 W. Under normal use conditions, this resistor should never be activated or be relied upon to absorb regeneration power. This resistor is meant to handle anomalous high voltage transients that might otherwise lead to a catastrophic voltage induced stator failure MagneMotion, Inc. Page 11 of 11
APPLICATION NOTE QuickStick 100 Power Cable Sizing and Selection
APPLICATION NOTE QuickStick 100 Power Cable Sizing and Selection Purpose This document will provide an introduction to power supply cables and selecting a power cabling architecture for a QuickStick 100
More informationKelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.
Kelly HSR Opto-Isolated Series Motor Controller with Regen User s Manual HSR72601 HSR72801 HSR12401 HSR12601 HSR12901 HSR14301 HSR14501 HSR14701 Rev.3.3 Dec. 2011 Contents Chapter 1 Introduction... 2 1.1
More informationAPPLICATION NOTE AN-ODP March 2009
Application Note Title AN-ODP-37 Braking Resistor Selection and Usage Revision History Version Comments Author Date 2.21 Previous version NX 15/6/07 3.00 Revised to new format, additional information added
More informationSTR3. Step Motor Drive. User Manual
STR3 Step Motor Drive User Manual Contents 1 Introduction... 3 1.1 Overview... 3 1.2 Features... 3 1.3 Block Diagram... 4 1.4 Safety Instructions... 5 2 Getting Started... 6 2.1 Mounting Hardware... 6
More informationKelly KDC Series/PM Motor Controller User s Manual
Kelly KDC Series/PM Motor Controller User s Manual KDC48600 KDC48601 KDC48602 KDC48603 KDC72600 KDC72601 KDC72602 KDC72603 KDC72800 KDC72801 KDC72802 KDC72803 KDC12602 KDC12603 Rev.3.3 May 2011 Contents
More informationWelcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.
Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the
More informationKelly KDHA High Voltage Series/PM Motor Controller User s Manual
Kelly KDHA High Voltage Series/PM Motor Controller User s Manual KDH07500A KDH07501A KDH07700A KDH07701A KDH09400A KDH09401A KDH09500A KDH09501A KDH12400A KDH12401A KDH12500A KDH12501A KDH14300A KDH14301A
More informationFeatures IN THIS CHAPTER
CHAPTER THREE 3Special Features IN THIS CHAPTER Motor Braking Regeneration Solutions Sharing the Power Bus: V Bus+ and V Bus- Current Foldback (I T Limit) Front Panel Test Points Resolver Alignment ➂ Special
More informationUnderstanding Part Numbers
Understanding Part Numbers NEMA 17 FRAME SM1725D NEMA 23 FRAME SM23165D SM23165DT SM23375D SM23375DT SM2315D SM2325D SM2335D SM2345D Animatics Class 5 SmartMotor Part Numbering Guidelines Frame Size Motor
More informationBrushed. Brushed. Brushed Motor
Kelly Kelly Kelly Kelly KD KD KD KD Series Series Series Series DC DC DC DC Motor Motor Motor Motor Controller Controller Controller Controller User User User User s Manual Manual Manual Manual V 2.5 2.5
More informationPowerOhm Installation Manual for BM R Series Braking Modules
PowerOhm Installation Manual for BM R Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal
More informationBG45 BG65S BG75 Axial Parallel Axial Parallel Axial Parallel CASM-32 (LS/BS/BN) X X CASM-40 (LS/BS/BN) X X X X CASM-63 (LS/BN/BF) X X
1 System Overview CASM electric cylinders powered by brushless DC motors are ideally suited for fast and powerful movements. Replacement of pneumatic cylinders has never been easier. Just parameterize
More informationAPPLICATION NOTE. Labeling Machine
Labeling Machine 1 3.3 Application to Labeling Machine 1 Description... 3 2 System plan... 3 2.1 Master axis Axis of conveyor... 4 2.2 Camshaft axis Label feeding axis... 4 2.3 Label positioning sensor...
More informationQuickStick Repeatability Analysis
QuickStick Repeatability Analysis Purpose This application note presents the variables that can affect the repeatability of positioning using a QuickStick system. Introduction Repeatability and accuracy
More informationVASCO. Variable Speed Controller ENGLISH
VASCO Variable Speed Controller ENGLISH Variable Speed Controller VASCO is a purpose-built family of variable frequency drives, designed to control and protect pumping systems based on changing pump speed.
More informationIntroduction to hmtechnology
Introduction to hmtechnology Today's motion applications are requiring more precise control of both speed and position. The requirement for more complex move profiles is leading to a change from pneumatic
More informationAdaptive Cruise Control System Overview
5th Meeting of the U.S. Software System Safety Working Group April 12th-14th 2005 @ Anaheim, California USA 1 Introduction Adaptive Cruise System Overview Adaptive Cruise () is an automotive feature that
More informationPowerOhm Installation Manual for LG ATV Series Braking Modules
PowerOhm Installation Manual for LG ATV Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal
More informationTachometer (RPM Feedback) General
Tachometer (RPM Feedback) General The force of magnetic fields interacting drives all electric motors. How the magnetic field is created on the moving rotor determines the type of control required on the
More informationProduct Guide: Series III Pump Control Board Set (RoHS)
revised 04/08/10 Description: The Series III Pump Control Board Set provides motor drive and pump control for a wide assortment of pumps from Scientific Systems, Inc. The assembly consists of two circuit
More informationADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED
ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL Dual Rating NRTL/C CERTIFIED Technologies Inc. mgitech.com Sensor/Sensorless Vector Control Dual current rated for constant and variable torque Auto
More informationSR3-mini. Step Motor Drive User Manual. AMP & MOONS Automation
SR3-mini Step Motor Drive User Manual AMP & MOONS Automation Contents 1 Introduction... 3 1.1 Overview...3 1.2 Features...3 1.3 Block Diagram...4 1.4 Safety Instructions...5 2 Getting Started... 6 2.1
More information5.1 Errors (Alarms) Error (alarm) definitions PROTECTIVE FUNCTIONS. (1) Major faults
.1 Errors (Alarms) If any fault has occurred in the inverter, the corresponding protective function is activated and the error (alarm) indication appears automatically on the PU display. When the protective
More informationSDC,Inc. SCR-Regenerative Ac Drive
SDC,Inc WWW.STEVENSDRIVES.COM APPLICATION NOTE #: AN_REG_GEN000 EFFECTIVE DATE: 12 MAR 02 SUPERSEDES DATE: Original NO. OF PAGES: 10 SCR-Regenerative Ac Drive Using a regeneration controller with adjustable-frequency
More informationENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER
ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST
More informationSMD10 SMD11 SMD15 SMD30
SMD10 SMD11 SMD15 SMD30 Step Motor Drivers User Manual JVL Industri Elektronik A/S - January 1992 LB0009-02GB Revision 11th Feb 98 Contents 1.1 Introduction 2 1.2 Overview of Driver Models 3 1.3 Front
More informationHIGH POWER SOLENOID DRIVER 1
Elactis SA Switzerland Phone : Fax : E-mail : Web : +41 22 364 65 85 +41 22 364 65 87 info@elactis.com http://www.elactis.com HIGH POWER SOLENOID DRIVER 1 ADRV1012K 1 This datasheet is a preliminary description.
More informationATOTH-G Series BLDC Motor Controller. User s Manual
ATOTH-G Series BLDC Motor Controller User s Manual Contents Chapter One Summary...1 Chapter Two Main Features and Specifications.2 2.1 Basic Functions...2 2.2 Features... 5 2.3 Specifications...6 Chapter
More informationQuick Reference Guide. For NFX9000 Adjustable Frequency Drives. February 2006 NQ00. MN E February 2006
Quick Reference Guide For NFX9000 Adjustable Frequency Drives February 2006 5011640900 NQ00 MN04001003E February 2006 Hazardous High Voltage WARNING Motor control equipment and electronic controllers are
More informationMotor Protection With The MonitorPro
Motor Protection With The MonitorPro This application note can show you the easy way to protect your motors and your pump stations. The MultiTrode MonitorPro can protect your motors from a wide range of
More informationSeries 905-IV16(E) CAN/CANopen Input Modules Installation and Operating Manual
Series 905-IV16(E) CAN/CANopen Input Modules Installation and Operating Manual Model 905 IV16 DC Input Module. Page 2 Operations Manual Table of Contents Table of Contents...2 Module Installation Procedure...3
More informationDRV-1. Step Motor Drive. User Manual Mentor Avenue Cincinnati, Ohio Tel (513)
DRV-1 Step Motor Drive User Manual 1776 Mentor Avenue Cincinnati, Ohio 45212 Tel (513) 318-4600 www.resolutionair.com 2 Contents 1 Introduction... 3 1.1 Overview... 3 1.2 Features... 3 1.3 Block Diagram...
More informationFull Bridge Permanent Magnet DC Motor Controller User's Manual
www.igreatway.com Email:info@igreatway.com V 3.3 Full Bridge Permanent Magnet DC Motor Controller User's Manual PM24101 PM24201 PM24301 PM36101 PM36201 PM48101 PM48201 PM48301 PM48401B PM48501B PM72101
More informationArtisan Technology Group is your source for quality new and certified-used/pre-owned equipment
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED
More information8 Troubleshooting and Maintenance
8 Troubleshooting and Maintenance 8.1 Troubleshooting 8.1.1 Troubleshooting of LED Indicators See Tab. 7-4 State Descriptions of LED Indicators for the definition. Fault Type LED indicators and LCD screen
More informationContinental Hydraulics Installation Manual CEM-AA-A
Continental Hydraulics Installation Manual CEM-AA-A Description: This power amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to proportional
More informationAC Drives Regenerative Energy Solutions. Product Summary
AC Drives Regenerative Energy Solutions Product Summary #% &TKXGU Regenerative Energy Solutions Snubber Resistor Braking Kits Line Regeneration Controls Synchronous Rectifier Controls AC Drives and Regenerative
More informationDevices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB
Kelly KEB Brushless Motor Controller User s Manual Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 KEB EB72 72331 KEB72450 KEB EB72 72451 KEB72600 KEB
More informationAPC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply
APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous
More informationELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243
ELECTRIC SCHEMATICS NOTES: (Unless otherwise specified). Switch S BASE/PLATFORM makes contact from the CENTER to the LEFT position when placed in BASE.. Switch S UP/DOWN makes contact from the CENTER to
More informationApplication Note CTAN #127
Application Note CTAN #127 Guidelines and Considerations for Common Bus Connection of AC Drives An important advantage of AC drives with a fixed DC is the ability to connect the es together so that energy
More informationDMX-A2-DRV Integrated Advanced Step Motor Driver
DMX-A2-DRV Integrated Advanced Step Motor Driver DMX-A2-DRV Manual page 1 rev 3.10 COPYRIGHT 2008 ARCUS, ALL RIGHTS RESERVED First edition, May 2008 ARCUS TECHNOLOGY copyrights this document. You may not
More informationCompatibility of STPA with GM System Safety Engineering Process. Padma Sundaram Dave Hartfelder
Compatibility of STPA with GM System Safety Engineering Process Padma Sundaram Dave Hartfelder Table of Contents Introduction GM System Safety Engineering Process Overview Experience with STPA Evaluation
More information10+ YEARS SPECIFIED BATTERY LIFE. Case study: Strips by. Optimizing power usage in IoT devices
Case study: Strips by Published: September 2017 10+ YEARS SPECIFIED BATTERY LIFE Optimizing power usage in IoT devices In many modern battery operated systems, the expected battery life is dependent on
More informationDESCRIPTION. Chrysler NCV3 Service Info Section 08 > Electronic Modules > MODULE, Transmission Control Information
DESCRIPTION The transmission control module (TCM) receives, processes and sends various digital and analog signals related to the automatic transmission. In addition, it processes information received
More informationFuel Cell Lab Manual. Non Conventional Energy Systems Facility. Non Conventional Energy Systems Facility. Boiler House
Fuel Cell Lab Manual Non Conventional Energy Systems Facility Boiler House Department of Mechanical Engineering IIT Kanpur System Description The Nexa system provides up to 1200 watts of unregulated DC
More informationPowerOhm Installation Manual for BM R Series Braking Modules
PowerOhm Installation Manual for BM R Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal
More informationTG350 User Manual. Manual Revision: Min. FW Revision: Date Released: 09/01/ DYNAGEN Technologies Inc
TG350 User Manual Manual Revision: 1.4.0 Min. FW Revision: 1.42.01 Date Released: 09/01/2014 Table of Contents 1 Introduction 1.1 Specifications... 3 2 Installation 2.1 Terminal s... 6 2.2 Typical Wiring...
More informationRT2DB Excitation and voltage regulation system for synchronous generators
s RT2DB Excitation and voltage regulation system for synchronous generators Fully digital. Parameter settings done by software. Self monitoring routines. Maintenance free. High reliability. Excellent dynamic
More informationTECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER
I. REFERENCE: 1 30 [1] Snow Engineering Co. Drawing 80504 Sheet 21, Hydraulic Schematic [2] Snow Engineering Co. Drawing 60445, Sheet 21 Control Logic Flow Chart [3] Snow Engineering Co. Drawing 80577,
More informationMANTECH ELECTRONICS. Stepper Motors. Basics on Stepper Motors I. STEPPER MOTOR SYSTEMS OVERVIEW 2. STEPPING MOTORS
MANTECH ELECTRONICS Stepper Motors Basics on Stepper Motors I. STEPPER MOTOR SYSTEMS OVERVIEW 2. STEPPING MOTORS TYPES OF STEPPING MOTORS 1. VARIABLE RELUCTANCE 2. PERMANENT MAGNET 3. HYBRID MOTOR WINDINGS
More informationRM B. Features. Drive Model Number Scheme. A RM6 Product Series
Features RM6 series are suitable for constant and variable torque loads (mixer, conveyor, fan, pump, etc.) Overload capacity with 150% drive s rated output current for 1 min can sustain heavy load conditions
More informationOvervoltage protection and voltage stabilization for Motion Control terminals
Keywords Buffer capacitor Brake chopper Fieldbus Drive Stepper DC motor Output stage DC link Overload Recovery EtherCAT K-Bus Bus Terminal PLC Overvoltage protection and voltage stabilization for Control
More informationKelly HPM High Power Full Bridge Permanent Magnet DC Motor Controller User s Manual
Kelly HPM High Power Full Bridge Permanent Magnet DC Motor Controller User s Manual HPM72601 HPM72801 HPM12401 HPM12601 HPM12801 HPM14301 HPM14501 HPM14701 Rev.3.4 Dec. 2016 Contents Chapter1 Introduction...
More informationRVS-DN Digital Reduced Voltage Motor Starter
RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationProduct Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement
Product Manual 36060 (Revision A, 8/2015) Original Instructions ProAct II Digital Speed Control System Technical Supplement DEFINITIONS This is the safety alert symbol. It is used to alert you to potential
More information2232 S 024 BX4 CSD/CCD 24 12,4 6,4 67,7 2 / 17 4,1 / ball bearings, preloaded 0,015. stainless steel 77 electronically reversible
NEW Brushless DC-Servomotor with integrated Motion Controller and or CN interface 18 mnm For combination with Gearheads: 22F, 22/7, 26 2232... BX4 CSD/CCD 1 2 3 4 Nominal voltage Terminal resistance, phase-phase
More informationApplication Note CTAN #234
Application Note CTAN #234 The Application Note is pertinent to the Unidrive SP Family A Guide to Tuning the Unidrive SP Introduction: The Unidrive SP provides a number of features that greatly assist
More information3242 G 024 BX4 CS/CC 24 3,6 18,2 77,3 1,6 / 12,4 9 / ball bearings, preloaded 0,015. stainless steel 370 electronically reversible
Brushless DC-Servomotor with integrated Motion Controller and or CN interface 6 mnm For combination with Gearheads: 3/1, 32, 32/3, 32/3 S, 38/1, 38/1 S, 38/2, 38/2 S 3242... BX4 CS/CC 1 2 3 4 Nominal voltage
More informationModel DE-3 Air Release Heads Parts List
Issue/Rev. 0.0 (1/14) Smith Meter Air Eliminator Model DE-3 Air Release Heads Parts List Bulletin MN03021 Contents Section 1 Introduction... Page 2 Principle of Operation... Page 2 Section 2 Installation...
More informationDelphi D12S Non-Isolated Point of Load
FEATURES High Efficiency: 93.4% @ 12Vin, V/A out Size: 3.x1.x12.mm (1. x.61 x.46 ) Wide input range: 4.V~13.2V Output voltage programmable from.9vdc to.vdc via external resistors No minimum load required
More informationSmall Full Bridge Permanent Magnet Motor DC Controller User Manual
Small Full Bridge Permanent Magnet Motor DC Controller User Manual SPM24051X SPM24101X SPM24121X SPM48051X SPM48101X SPM48121X SPM72051X SPM72101X SPM72121X SPM48151E SPM48181E SPM48221E SPM72151E SPM72181E
More informationDesign considerations for generator set mounted paralleling breakers
Our energy working for you. Design considerations for generator set mounted paralleling breakers White Paper Hassan Obeid, Application Group Cummins Power Generation Cummins Power Systems has been delivering
More informationProducts Tde Macno. User s Manual BRAKING UNIT. Cod. MP00401E00 V_1.0
Products Tde Macno User s Manual BRAKING UNIT Cod. MP00401E00 V_1.0 SUMMARY 1 GENERAL DESCRIPTION... 2 2 USE LIMITATIONS... 2 2.1 Climatic Class... 2 2.2 Resistance To Chemically Active Substances...
More informationUser s Manual. For. BH-MSD-2A Micro Stepping Driver
User s Manual For BH-MSD-2A Micro Stepping Driver Product Number Code For Micro step drive Website:-www.bholanath.in Page 2 BH MSD 2A BHOLANATH MICRO STEP DRIVE 2 Amp 1:DC power input :12V~36VDC 2.Output
More informationXP600/1100/2000 INSTALLATION AND OPERATION MANUAL
7317 Jack Newell Blvd North Fort Worth, Texas 76118-71 817-595-4969 voice, 817-595-129 fax 8-886-4683 toll free website wwwexeltechcom Manufacturer of UL Listed Products Copyright 21 Exeltech Inc All rights
More informationTECHNICAL DATA SHEET KVA UPS Systemss
Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800
More informationDIGITAL FLOWMETER AND PRESSURE INDICATOR MODEL FPA400
Document Number: XE-FPA4PM-R0A FPA400 Rev160601 DIGITAL FLOWMETER AND PRESSURE INDICATOR MODEL FPA400 OPTIONAL BACKLIGHTING FIRE RESEARCH CORPORATION www.fireresearch.com 26 Southern Blvd., Nesconset,
More informationUser s Manual. For DM542T. Full Digital Stepper Drive
User s Manual For DM542T Full Digital Stepper Drive Designed by StepperOnline Manufactured by Leadshine 2017 All Rights ReservedAttention: Please read this manual carefully before using the drive! #7 Zhongke
More informationKinetics Industries, Inc. 140 Stokes Ave. Trenton, NJ 08638 Tel: 609-883-9700 sales ext 122, Fax: 609-883-0025 e-mail: info@kinetics-industries.com www.kinetics-industries.com Kinetics manufacturer of:
More informationMDC V, 30A Brushless Controller. User s Guide L East Orangefair Lane, Anaheim, CA
MDC150-012301 12V, 30A Brushless Controller User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714) 992-0471
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationMPPT75HV MAXIMUM POWER POINT TRACKING SOLAR BATTERY CHARGE CONTROLLER
MPPT75HV MAXIMUM POWER POINT TRACKING SOLAR BATTERY CHARGE CONTROLLER The Intronics Power Inc. MPPT75HV Solar Charge Controller continually tracks the maximum power point of the solar panel array, adjusting
More informationSuper Calendar. Heated rolls
Application Assistant Surface Winders are used to roll up material such as wire, paper, film, metals and textiles. The surface winding method applies the driving power to a fixed diameter roll or rolls,
More informationQuickStick 100 User s Manual
QuickStick 100 User s Manual 990000460 Rev. D Although every effort is made to ensure the accuracy of this document, assumes no responsibility for any errors, omissions, or inaccuracies. Information provided
More informationCENTROIDTM. AC Brushless Drive. Product Spec Sheet
4 Axis, up to 2 KW motors Brake Output for each axis Overtemp and Overcurrent Protection All-software Configuration Self-cooled Fiber Optic Control CENTROIDTM AC Brushless Drive Product Spec Sheet AC Brushless
More informationSuper Calendar. Heated rolls
Application Report Surface Winders are used to roll up material such as wire, paper, film, metals and textiles. The surface winding method applies the driving power to a fixed diameter roll or rolls, on
More informationAdvanced User Manual
Advanced User Manual Banks SpeedBrake For use with Palm Tungsten E2 2004-2005 Chevy/GMC 6.6L (LLY) Turbo-Diesel Pickup THIS MANUAL IS FOR USE WITH KITS 55419 & 55421 Gale Banks Engineering 546 Duggan Avenue
More informationApplication Software Dual Path Control DPC
Industrial Hydraulics lectric Drives and Controls Linear Motion and Assembly Technologies Pneumatics Service Automation Mobile Hydraulics Application Software Dual Path Control DPC R 95 325/03.04 Version
More informationTECH XP600/1100 INSTALLATION AND OPERATION MANUAL. Manufacturer of UL Listed Products.
http://wwwwholesalesolarcom/invertershtml TECH 7317 Jack Newell Blvd North Fort Worth, Texas 76118-71 8175954969 voice, 817595129 fax 88864683 toll free website wwwexeltechcom R Manufacturer of UL Listed
More informationRVS-DX Digital Reduced Voltage Motor Starter
RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationInstallation Inspection Guide Retractable Grounding Assembly (RGA) Rev A, 10/3/13
Installation Inspection Guide Retractable Grounding Assembly (RGA) Rev A, 10/3/13 II 2 G T4 Manufactured for Lightning Eliminators & Consultants, Inc. by Conductix, Inc. 10102 F St Omaha, NE 68127. 1.0
More informationExample application for an supply air control with recirculated air addition. HVAC Application Note 3
Example application for an supply air control with recirculated air addition HVAC Application Note 3 Version 14.03.2007 2 General Copyright 2007 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved.
More informationRVS-DN Digital Soft Starter A, V Instruction Manual
RVS-DN Digital Soft Starter 8-2700A, 220-1000V Instruction Manual Ver. 171001 Table of Contents Page Subject Appendix Page Subject 2 Starter Selection 41 Table of content 3 Installation 42 UL and cul instructions,
More informationTECH XP600/1100 INSTALLATION AND OPERATION MANUAL
TECH 7317 Jack Newell Blvd North Fort Worth, Texas 76118-71 8175954969 voice, 817595129 fax 88864683 toll free e-mail address info@exeltechcom e-mail address sales@exeltechcom website wwwexeltechcom Copyright
More informationTechnical Explanation for Inverters
CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor
More informationThe function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:
1.0 Introduction: This probe is designed to provide an additional help to automotive technicians in trouble shooting of electrical circuits problems in the car. Apart from using the normal multi tester,
More informationOPERATOR TROUBLESHOOTING GUIDE
OPERATOR TROUBLESHOOTING GUIDE ABOUT THE TROUBLESHOOTING GUIDE This document is provided for the use of qualified operator installers. The installer should familiarize themselves with this guide Options
More informationPF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016
PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication
More informationMANUAL 1207& 1207A CURTIS PMC. MultiMode MOTOR CONTROLLERS
MANUAL 1207& 1207A MultiMode MOTOR CONTROLLERS 1999 CURTIS INSTRUMENTS, INC. DESIGN OF CURTIS PMC 1200 SERIES CONTROLLERS PROTECTED BY U.S. PATENT NO. 4626750. CURTIS PMC 235 East Airway Boulevard Livermore,
More informationMondoStep 7.8. High Performance Microstepping Driver. User s Manual. Version PROBOTIX All Rights Reserved
MondoStep 7.8 High Performance Microstepping Driver User s Manual Version 1.0 2010 PROBOTIX All Rights Reserved Attention: Please read this manual carefully before using the driver! Table of Contents 1.
More informationApplication Note. Common Bussing AC Drives. For 650 and 690+ series drives APP-AC-03
Application Common Bussing AC Drives APP-AC-03 For 650 and 690+ series drives APP-AC-03 2004 SSD Drives inc. 9225 Forsyth Park Drive, Charlotte, NC 28273 Page of 5 Introduction On occasion, one or more
More information1.Safety Summary The following safety precautions should be taken to avoid injury and prevent damage to this and other associated products. To avoid d
Category Dear Customer: Thank you very much for purchasing our products! This manual will provide some important information and recommendations including: installation, operation and troubleshooting.
More informationA problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.
10 Troubleshooting When a protection condition is detected, the VLT Soft Starter MCD 500 writes this condition to the event log and may also trip or issue a warning. The soft starter response depends on
More informationPrepared By: Ahmad Firdaus Bin Ahmad Zaidi
Prepared By: Ahmad Firdaus Bin Ahmad Zaidi A stepper motor is an electromechanical device which converts electrical pulses into discrete mechanical rotational movements. Stepper motor mainly used when
More informationDIGITAL PRESSURE AND FLOW INDICATOR MODEL FPA500
Document Number: XE-FPA5PM-R0A FPA500 Rev150728 DIGITAL PRESSURE AND FLOW INDICATOR MODEL FPA500 FIRE RESEARCH CORPORATION www.fireresearch.com 26 Southern Blvd., Nesconset, NY 11767 TEL 631.724.8888 FAX
More informationSeparately Excited Electronic Motor Speed Controller Model 1243 SepEx
Motor Controllers Separately Excited Electronic Motor Speed Controller Model 1243 SepEx www.curtisinstruments.com 1 Curtis PMC Model 1243 SepEx programmable controllers provide smooth and seamless regenerative
More informationTECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)
TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power
More informationMODS Mask Select Data Sheet General Description
MODS Mask Select Data Sheet General Description The MODS Mask Select mechanism translates the 24 position mask storage magazine to align the requested mask with the Mask Insert rails. This places the requested
More informationExplanation 1 Input External Switch 2 Input Hipot Safety Switch
on the 1100H+ The 1100H+ has capability, which allows you to set up the tester to control external devices with tester functions. You can also use an input on the tester to start a test. For example, the
More information