Beginner's Guide to Marinas, RV Parks, and NEC Requirements for Both

Size: px
Start display at page:

Download "Beginner's Guide to Marinas, RV Parks, and NEC Requirements for Both"

Transcription

1 Eaton's Beginner's Guide to Marinas, RV Parks, and NEC Requirements for Both Beginner's Guide to Marinas, RV Parks, and NEC Requirements for Both Introduction This guide is intended to give you quick, base knowledge on standard industry terms, systems, and NEC guidelines driving safety and reliability. Use this guide as a quick reference, and get up to speed at your own pace. There are two main sections: - Marinas - RV Parks and within them are subsections: - Terminology - Components within Electrical System - NEC Requirements If you have any questions, please do not hesitate to call and ask for Technical Assistance at One of our industry experts will be happy to help walk you through any questions you may have.

2 Marinas Terminology: o Docks: a structure extending alongshore or out from the shore into a body of water, to which boats may be moored. o Slips: a boat slip is the portion of a pier, main pier, finger pier, or float where a boat is berthed or moored, or used for embarking or disembarking. o Power Pedestal: a secure, weatherproof, electrical enclosure for safe utility connection between the Marina and the vessel. Can offer electricity, water, internet, cable, phone, with additional features like ground fault protection, as well. o Distribution Equipment: Refers to any electrical enclosure that safely routes electricity to circuits. Usually involves circuit breakers, but can utilize safety switches or fuses. Panelboards, Substations, or Enclosed Circuit Breakers are all examples of Distribution Equipment. o Direct feeding vs. Loop feeding: electrically having multiple pedestals on the same circuit saves on wiring costs, and can assist in capturing and protecting against leakage grouping (see NEC section below on Leakage grouping) o Demand factor: See NEC section, below o Datum plane: See NEC section, below o Upstream (electrical): refers to all electrical devices and wiring that feed power to the point of reference o Downstream (electrical): refers to all electrical devices and wiring that the point of reference supplies power to o Shore power: electrical provision for power to a vessel while its main and auxiliary engines are shut down

3 Components within Standard Marina Electrical System: Transformer o Electricity provided by utility usually arrives at voltage of 480V or 600V to enter Marina to distribute to docks o Transformer will drop voltage to a more usable voltage such as 120V, 120/240V, or 120/208V. o Transformer can be located within a Substation, which will also divide the electrical power to feed multiple subsidiary circuits Some facilities may not want to drop voltage, and choose to use 480V or 600V. These are usually facilities with very large vessels that can accept that voltage. Substation o A weatherproof enclosure that houses a transformer to step down voltage, and also divides electrical power to feed multiple subsidiary circuits. o Can route circuits directly to the pedestals, or to other Panelboards Panelboards o A weatherproof enclosure that divides electrical power to feed multiple subsidiary circuits o Can route circuits directly to pedestals, or to other Panelboards, or other Substations Pedestals o a secure, weatherproof, electrical enclosure for safe utility connection between the Marina and the vessel. Can offer electricity, water, internet, cable, phone, with additional features like ground fault protection, as well. Can be loop fed to have multiple pedestals on the same circuit from a panelboard or substation. Copper vs aluminum o Marine distribution equipment and pedestals generally use all copper conductors and connectors. This is due to the humid and (depending on location) salty atmosphere that marine environments tend to experience. Aluminum conductors can oxidize and slowly disintegrate over a few years, leading to necessary replacement. Copper conductors and components much longer, and do not suffer the same drawbacks as aluminum.

4 Stainless steel (316L vs 430) vs galvanized steel o Marine distribution equipment and pedestals generally use stainless steel instead of galvanized steel for their structural housings. This is due to the humid and((depending on location))salty atmosphere that marine environments tend to experience. Galvanized steel can rust and disintegrate, leading to an enclosure that is no longer weatherproof or structurally sound. This is why stainless steel is the default for the marina industry, as it does not suffer these same drawbacks. An example of a marina electrical layout

5 NEC 2017, Section 555: Marinas, Boatyard, and Commercial and Noncommercial Docking Facilities Be familiar with the entirety of NEC 2017, section 555 Datum plane: All electrical devices must be mounted higher than the datum plane: Land Area Subject to Tidal Fluctuation. Horizontal plane 2 ft above highest tide level under normal circumstances Land Areas Not Subject to Tidal Fluctuation. Horizontal plane 2 ft above highest water level under normal circumstances Floating Piers. The horizontal plane 30 in. above the water level at the floating pier and a minimum of 12 in. above the level of the deck. NEC 2017, Section for ground fault protection o New to the 2017 National Electrical Code: The overcurrent protective devices that supply the marina, boatyards, and commercial and noncommercial docking facilities shall have ground-fault protection not exceeding 30mA o Electric Shock Drowning (the reason behind 555.3) Electric Shock Drowning occurs when faulty wiring on a boat or in a marina causes underwater metals to become energized. Examples of underwater metals that could become energized: Boat Props, Dock Frames, Ladders This creates an electrical field in the water. The magnitude and intensity of the electrical field is determined by how much current is being leaked into the water. A swimmer enters the electrical field and completes the electrical circuit to ground. The swimmer becomes a target for the electrical current leakage because the human body is a better conductor of electricity than fresh water. Fresh water is close to 70 times more resistive than salt water. This makes electric current leakage in fresh water marinas a major concern. Depending on the amount of current in the water and a swimmers location relative to the electrical field, a person may experience effects ranging from a slight tingle, to complete loss of muscle control, causing drowning. Even more electricity leads to ventricular fibrillation. As little as 10mA can start to cause significant issues.

6 o o Leakage Grouping Occurs when multiple vessels are producing stray current on the same piece of ground fault protection or ground fault monitoring device. The leakage produced by a single vessel may not be high enough to trigger a circuit breaker or alarm, but the collective leakage produced by multiple vessels can be extremely dangerous for anyone in the water. This is why it s important to think of an entire zone in the water and not just individual vessels or pedestals. Two vessels might only leak 20mA each, but that s potentially 40mA at the peak location between the vessels! Eaton Solutions to combat ESD: 1. Distribution equipment with ground fault protection Eaton s distribution equipment combines space-saving designs with modular construction and increased systems ratings to provide economical and dependable electrical system distribution and protection. Combined with powerful ground fault technology, the distribution equipment can protect downstream pedestals from ground leakage and prevent ESD. Ground fault monitors with shunt trip circuit breakers help evaluate the level of electrical leakage being released from specific power sources and then intervene to interrupt the circuit. The ground fault monitoring system operates 24 hours a day and provides a visual status. A variety of options are available but standard features include: an adjustable trip level of 10mA to 10A; visual alarms; controls for up to 13 circuits; and a heavy 316L stainless steel housing that is powder-coated with a polyester resin to minimize corrosion.

7 2. Ground fault pedestals Eaton MP&L was the first to introduce ground fault protection with notification at each and every slip with its industry-leading ground fault pedestal solution. The newest power pedestal features integrated ground fault breakers and visual trip fault notification. A flashing red light immediately lets marina staff know that power has been disconnected, potentially avoiding a dangerous situation. Eaton s most popular, practical and durable pedestal styles include the Lighthouse and Lighthouse SS. The pedestals have lockable weatherproof doors to protect the breakers and receptacle while in use, and a heavy resin housing with a two-part UV resistant polyurethane finish to guard against weathering from the elements. The NEMA 3R rating pedestals offer circuit breaker protection for all receptacles and feature copper bus bars with ratings from 250 to 500A. A 'hingeless base provides easy access for both installation and maintenance. The user-friendly pedestals include a photocell-controlled LED light with amber lens that gives 360 lighting, and a backlit universal faceplate is included for easy receptacle plug-in at night. Optional features include high-speed internet connections and single or dual phone and/or cable TV connections, surge protection, and wireless remote metering for electricity and water.

8 3. Ground fault monitor, integrated into safety disconnect Eaton manufactures state-of-the art D64 ground fault monitors, which - when integrated into a safety disconnect -do not require the marina to retrofit pedestals or distribution equipment. This device, combined with a standalone safety switch disconnect, can be installed anywhere in a circuit to protect it. The downside to this solution is, although easy to install, it can be difficult to pinpoint where the ground fault originates Demand factor o There is a demand factor to allow a discount on electrical calculations. Refer to to identify the demand factor for your particular situation. For example, five shore power receptacles can assume a 90% rating factor. o For situations where two receptacles are provided to accommodate one slip, and these receptacles have different voltages (for example, one 30A, 125V, and one 50A, 125/250V), only the receptacle with the larger kilowatt demand shall be required to be calculated. Map of the US and NEC level adopted, by state. Handy link Sign up for our Listserv to hear in advance about Eaton s new products and trainings we offer, once a quarter.

9 RV Parks Terminology: o Sites: a location rented out or owned, where one can park a Recreational Vehicle, usually with provided amenities such as electricity, cable/internet/ phone, and sewage. o Power Pedestal: a secure, weatherproof, electrical enclosure for safe utility connection between the Marina and the vessel. Can offer electricity, water, internet, cable, phone, with additional features like ground fault protection, as well. o Distribution Equipment: Refers to any electrical enclosure that safely routes electricity to circuits. Usually involves circuit breakers, but can utilize safety switches or fuses. Panelboards, Substations, or Enclosed Circuit Breakers are all examples of Distribution Equipment. o Loop feeding: electrically having multiple pedestals on the same circuit saves on wiring costs, and can assist in capturing and protecting against leakage grouping (see NEC section below on Leakage grouping) o Demand factor: See NEC section, below o Upstream (electrical): refers to all electrical devices and wiring that feed power to the point of reference o Downstream (electrical): refers to all electrical devices and wiring that the point of reference supplies power to

10 Components within Standard RV Park Electrical System: o Utility Electricity provided by utility usually arrives at voltage of 480V or 600V to enter Marina to distribute to docks o Transformer Transformer will drop voltage to a more usable voltage such as 120V, 120/240V, or 120/208V. Transformer can be located within a Substation, which will also divide the electrical power to feed multiple subsidiary circuits Some facilities may not want to drop voltage, and choose to use 480V or 600V. These are usually facilities with very large vessels that can accept that voltage. o Substation A weatherproof enclosure that houses a transformer to step down voltage, and also divides electrical power to feed multiple subsidiary circuits. Can route circuits directly to the pedestals, or to other Panelboards Panelboards o A weatherproof enclosure that divides electrical power to feed multiple o subsidiary circuits Can route circuits directly to pedestals, or to other Panelboards, or other Substations Pedestals o a secure, weatherproof, electrical enclosure for safe utility connection between the Marina and the vessel. Can offer electricity, water, internet, cable, phone, with additional features like ground fault protection, as well. Can be loop fed to have multiple pedestals on the same circuit from a panelboard or substation.

11 NEC 2017, Section 551: Recreational Vehicles and Recreational Vehicle Parks Be familiar with the entirety of NEC 2017, section 551 Key takeaways: o Each RV site shall supply at least one 20A, 125-volt receptacle o A minimum of 70% of all RV sites shall supply a 30A receptacle o A minimum of 20% of existing and 40% of new RV sites shall supply a 50A receptacle o There is a demand factor to allow a discount on electrical calculations. Refer to to identify the demand factor for your particular situation. For example, 5 RV sites can assume a 65% demand factor. Map of the US and NEC level adopted, by state. Handy link Sign up for our Listserv to hear in advance about Eaton s new products and trainings we offer, once a quarter. For more information, please us at MarinaSales@eaton.com or call Eaton is a registered trademark.all other trademarks are property of their respective owners Eaton Corporation All Rights Reserved Printed in USA October 2018 Eaton Corporation Marina Power and Lighting 149 Warwick Court Williamsburg, VA United States

Lighthouse Power Pedestals,

Lighthouse Power Pedestals, Lighthouse Power Pedestal One of our most popular units, the all-purpose Lighthouse pedestal has a wide range of features. With units in service around the world, this stylish power pedestal is recognized

More information

RV Park Equipment Product Focus. Power Pedestals Distribution Equipment

RV Park Equipment Product Focus. Power Pedestals Distribution Equipment RV Park Equipment Product Focus s Distribution Equipment Eaton Corporation RV Park Hookups Product Eaton offers a complete portfolio of electrical products for your RV project including pedestals, distribution

More information

Marina Power and Lighting Product Focus. Power Pedestals Distribution Equipment

Marina Power and Lighting Product Focus. Power Pedestals Distribution Equipment Marina Power and Lighting Product Focus Power Pedestals Distribution Equipment Eaton Corporation Marina Power and Lighting A Powerful Solution for the Marina Industry The Most Complete, Highest Quality,

More information

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse Power Pedestal

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse Power Pedestal DRILL \ PUNCH OUT TO SIZE REQUIRED DRILL \ PUNCH OUT TO SIZE REQUIRED Lighthouse Power Pedestal - Specifications Lighthouse Power Pedestal Dimensions Height: 44.00" (1117.60 mm) Width: 13.67" (347.22 mm)

More information

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Newport Harbor Mate Utility Center

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Newport Harbor Mate Utility Center Newport Harbor Mate Dimensions Height: 14.50" (368.30 mm) Width: 10.50" (266.70 mm) Depth: 10.40" (264.16 mm) Newport Harbor Mate Utility Center Diagram 2.77" Approximate Weight: 11 lbs. (5.0 kg) 10.31"

More information

Harbor Light Model HL General Specifications

Harbor Light Model HL General Specifications Harbor Light Model HL30100 General Specifications Rev.5 02-02-17 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988 ALL HARBOR LIGHT

More information

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse-SS Power Pedestals

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse-SS Power Pedestals Lighthouse-SS Power Pedestal Dimensions Height: 44.00" (1117.60 mm) Width: 9.565" (242.95 mm) Depth: 9.875" (250.83 mm) Lighthouse-SS Base Diagram Ø0.50" MOUNTING HOLE (TYP.) 9.5625" 8.0625" 7.3125" C:\Documents

More information

Bayside Model BU2050 Installation, Maintenance, and Operation Manual

Bayside Model BU2050 Installation, Maintenance, and Operation Manual Bayside Model BU2050 Installation, Maintenance, and Operation Manual 000000 000000 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988

More information

Installation Instructions for Lighthouse SS Power Pedestal Rev. 3 5/20/14

Installation Instructions for Lighthouse SS Power Pedestal Rev. 3 5/20/14 Installation Instructions for Lighthouse SS Power Pedestal Rev. 3 5/20/14 Hazardous voltage. Can cause severe injury or death. Turn off main power before opening panel. Eaton Electrical Inc. strongly recommends

More information

Anchorage SS Center Model AN3050. Installation, Maintenance, and Operation Manual

Anchorage SS Center Model AN3050. Installation, Maintenance, and Operation Manual Anchorage SS Center Model AN3050 Installation, Maintenance, and Operation Manual Rev.3 06-29-16 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax:

More information

General Specifications for Lighthouse Power Pedestal

General Specifications for Lighthouse Power Pedestal Dimensions Height: 44.00 11 (1117.60 mm) Width: 13.67" (347.22 mm) Depth: 13.75" (349.25 mm) Lighthou98 Base Diagram ---13,75 1 --- Approximate Weight: 30 lbs. (13.6 kg) Multiply base dimensions by 25.4

More information

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Hatteras Light Pedestals

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Hatteras Light Pedestals Hatteras Light Power Pedestal Dimensions Height: 31.00" (787.40 mm) Width: (190.50 mm) Depth: (190.50 mm) Hatteras Light Base Diagram Approximate Weight: 14 lbs. (6.4 kg) 1.73" UL FILE # E133781 Ø0.41

More information

Marina Power & Lighting Capabilities Brochure

Marina Power & Lighting Capabilities Brochure Marina Power & Lighting Capabilities Brochure Marina RV EVSE Temporary Power Stainless Steel The world s largest and most trusted supplier of marina power equipment About Eaton: Known as the leader in

More information

Marina Power and Lighting Equipment. Product Focus. Power Pedestals Distribution Equipment. High-Quality, Weatherproof Electrical Equipment

Marina Power and Lighting Equipment. Product Focus. Power Pedestals Distribution Equipment. High-Quality, Weatherproof Electrical Equipment Marina Power and Lighting Equipment Product Focus Power Pedestals Distribution Equipment High-Quality, Weatherproof Electrical Equipment Eaton Corporation Marina Power and Lighting A Powerful Solution

More information

Installation Instructions for Admiral Power Pedestal (# )

Installation Instructions for Admiral Power Pedestal (# ) Installation Instructions for Admiral Power Pedestal (#70-8643) Hazardous voltage. Can cause severe injury or death. Turn off main power before opening panel. Eaton Electrical Inc. strongly recommends

More information

Marina Power and Lighting, Inc. General Specifications for the Newport Harbor Mate

Marina Power and Lighting, Inc. General Specifications for the Newport Harbor Mate Marina Power and Lighting, Inc. General Specifications for the Newport Harbor Mate All Power Pedestals Must Meet the Following: Part I. General: 1.1 General Requirements- A.) Shall be tested and certified

More information

Installation Instructions for the Powerslide RV Pedestal #

Installation Instructions for the Powerslide RV Pedestal # Installation Instructions for the Powerslide RV Pedestal #70-8760 Rev: 11/20/2017 Hazardous voltage. Can cause severe injury or death. Eaton Electrical Inc. strongly recommends that these products be installed

More information

Fire Station Hose Rack Model FSHR Installation, Maintenance, and Operation Manual

Fire Station Hose Rack Model FSHR Installation, Maintenance, and Operation Manual Fire Station Hose Rack Model FSHR Installation, Maintenance, and Operation Manual Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988

More information

Marina Mate SS Model MMSS2050 Installation, Maintenance, and Operation Manual

Marina Mate SS Model MMSS2050 Installation, Maintenance, and Operation Manual Marina Mate SS Model MMSS2050 Installation, Maintenance, and Operation Manual Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988 Marina

More information

Power Pedestals. 6.1 Introduction Product Description... 2 Application Description... 2 Optional Features... 2

Power Pedestals. 6.1 Introduction Product Description... 2 Application Description... 2 Optional Features... 2 Construction Site and RV Parks Marina Power and Lighting Mobile Home Panels. Introduction Product Description............................................. Application Description...........................................

More information

Power Pedestals. 5.1 Introduction Product Description... Application Description... Optional Features...

Power Pedestals. 5.1 Introduction Product Description... Application Description... Optional Features... Construction Site and RV Parks Marina Power and Lighting Mobile Home Panels. Introduction Product Description....................................... Application Description.....................................

More information

6.1 Introduction Product Description... Application Description... Optional Features...

6.1 Introduction Product Description... Application Description... Optional Features... Construction Site and RV Parks Marina Power and Lighting Mobile Home Panels. Introduction Product Description....................................... Application Description....................................

More information

Harbor Light SS Model HLSS Installation, Maintenance, and Operation Manual

Harbor Light SS Model HLSS Installation, Maintenance, and Operation Manual Harbor Light SS Model HLSS30100 Installation, Maintenance, and Operation Manual Rev.5 07-05-16 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax:

More information

Ten Deadly Conditions to Check for in Your Boat's Electrical System - Part 2

Ten Deadly Conditions to Check for in Your Boat's Electrical System - Part 2 Ten Deadly Conditions to Check for in Your Boat's Electrical System - Part 2 In the September newsletter, 1 through 5 of the ten deadly conditions were presented (link to previous article). Deadly conditions

More information

Marina Mate SS Model MMSS2050. Installation, Maintenance, and Operation Manual

Marina Mate SS Model MMSS2050. Installation, Maintenance, and Operation Manual Marina Mate SS Model MMSS2050 Installation, Maintenance, and Operation Manual Rev.6 07-05-16 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988

More information

Installation, Maintenance, and Operation Manual

Installation, Maintenance, and Operation Manual GTX TM UNIT SUBSTATION Installation, Maintenance, and Operation Manual Rev.3 03-10-15 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

Volume 1 Residential and Light Commercial CA E December

Volume 1 Residential and Light Commercial CA E December Power Pedestals Power Pedestals Construction Site and RV Parks Marina Power and Lighting Mobile Home Panels.1 Introduction Product Description............................................. 28 Application

More information

Every accessory for today s dock......except the boat. Version 08

Every accessory for today s dock......except the boat. Version 08 Every accessory for today s dock......except the boat. Version 08 ABOUT US... International Dock Products, Inc. was established in 1995 as a result of a merger between S. King Fulton, Inc. and Flexmaster,

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

Design Standards NEMA

Design Standards NEMA Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL,

More information

Hubbell Marine Isolation Transformers 15 kva and 25 kva Models

Hubbell Marine Isolation Transformers 15 kva and 25 kva Models Shore Power System 15 kva and 25 kva Models Protects Sensitive Equipment on Board Virtually Eliminates Potential for In-Water Stray Current Can be wired per ABYC E-11 for either a Polarization or Isolation

More information

GTX UNIT SUBSTATION Installation, Maintenance & Operation Manual

GTX UNIT SUBSTATION Installation, Maintenance & Operation Manual GTX UNIT SUBSTATION Installation, Maintenance & Operation Manual Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 REV.1 April 18, 2014 CAUTION Toll Free: 1-855-258-3939 Fax: 1-757-258-3988

More information

Transmission & Distribution Glossary of Electrical Terms

Transmission & Distribution Glossary of Electrical Terms Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Contents. Power Outlet. Don t Give Up! If you don t find the product you want in this catalog, try the Flex Center at

Contents. Power Outlet. Don t Give Up! If you don t find the product you want in this catalog, try the Flex Center at -1 Power Outlet Panels Contents Description Page Surface Units................................................... -3 Pedestal Units.................................................. -3...............................................

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

6.2. Power Pedestals. Contents

6.2. Power Pedestals. Contents Power Pedestals.2 Power Outlet Panels Contents Description Page Product Overview................................. 287 Application Description.......................... 288 Features and Benefits...........................

More information

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements 1. PURPOSE sponsored by ABYC, BMF, ICOMIA, IMCI, and NMMA Author: Wieger de Wit Guideline Number 3 Electrical

More information

! WARNING! WARNING. Dock Boxes Unlimited, Inc. strongly recommends that these products be installed by a qualified electrician.

! WARNING! WARNING. Dock Boxes Unlimited, Inc. strongly recommends that these products be installed by a qualified electrician. Coming together is a beginning. Keeping together is progress. Working together is success. Installation Instructions for the Hatteras Light Power Pedestal (#70-8631)! DANGER! WARNING! WARNING Hazardous

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

Learning Module 10: Loadcenters. 101 Basic Series

Learning Module 10: Loadcenters. 101 Basic Series Learning Module 10: Loadcenters 101 Basic Series What You Will Learn We ll step through each of these topics in detail: What Does a Loadcenter Do? 4 Applications 4 Basic Circuitry and Wiring 5 Residential

More information

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrical Safety Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock

More information

Tradition. Technology. Innovation.

Tradition. Technology. Innovation. Tradition. Technology. Innovation. 2 Tradition. Technology. Innovation. 50433 IEM CorpBror1.indd 2 4/3/15 2:41 PM Today, IEM has expanded beyond Silicon Valley to supply specialized electrical equipment

More information

Recreational Vehicle Park Electrical Products & Accessories

Recreational Vehicle Park Electrical Products & Accessories Recreational Vehicle Park Electrical Products & Accessories 2 MILBANK OVERVIEW Milbank Overview Energy At Work since 1927 Milbank designs and manufactures electrical solutions that move and manage power

More information

FACT SHEET Standard: Electrical Safety

FACT SHEET Standard: Electrical Safety What is a Ground Fault Circuit Interrupter? FACT SHEET The ground-fault circuit interrupter, or GFCI, is a fast-acting circuit breaker designed to shut off electric power in the event of a ground-fault

More information

Busway. Siemens STEP 2000 Course. STEP 2000 Courses distributed by

Busway. Siemens STEP 2000 Course. STEP 2000 Courses distributed by Siemens STEP 2000 Course Busway It's easy to get in STEP! Download any course. Hint: Make sure you download all parts for each course and the test answer form. Complete each chapter and its review section

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

ASCO Low Voltage Automatic Transfer Switch Systems

ASCO Low Voltage Automatic Transfer Switch Systems ASCO Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications ASCO s experience and commitment to excellence in designing and building Emergency Power

More information

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1 Webinar 1 Electrical 2 1 Webinar Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock)

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication serves as a guide that represents the consensus of NEMA member companies and is not intended to override the recommendations

More information

5.2. Power Pedestals. Contents Description

5.2. Power Pedestals. Contents Description .2 Power Outlet Panels Contents Description Product Overview......................... Application Description.................. Features and Benefits................... Standards and Certifications..............

More information

Fused Coordination Panelboard

Fused Coordination Panelboard Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined

More information

G E N E S I S S T O R M SPECIALIZED TOP OFF AND REPLENISHMENT MODULE

G E N E S I S S T O R M SPECIALIZED TOP OFF AND REPLENISHMENT MODULE G E N E S I S S T O R M SPECIALIZED TOP OFF AND REPLENISHMENT MODULE INSTALLATION AND USE Congratulations on your purchase of the GENESIS STORM Specialized Top Off and Replenishment Module! Please take

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are

More information

Low Voltage Automatic Transfer Switch Systems

Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

Electrical Safety and Overcurrent Protection

Electrical Safety and Overcurrent Protection Electrical Safety and Overcurrent Protection Dave Vallier DSE Bussmann division Contact info: Phone: 586-201-1348 Email: Davemvallier@eaton.com Agenda 1. Electrical hazards overview 2. The role of the

More information

Installation and Construction Notes for EVSE4

Installation and Construction Notes for EVSE4 Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process

More information

AIR CORE REACTORS. Phoenix Electric Corporation

AIR CORE REACTORS. Phoenix Electric Corporation AIR CORE REACTORS Phoenix Electric Corporation PHOENIX ELECTRIC CORPORATION designs and manufactures Dry Type Air Core Reactors for operation on systems rated through 800 kv. All reactors are custom designed

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information

PowerPact B. Molded case circuit breakers and switches from A

PowerPact B. Molded case circuit breakers and switches from A PowerPact B Molded case circuit breakers and switches from 15-125 A 2 schneider-electric.us Efficiency that clicks. PowerPact B molded case circuit breakers Schneider Electric introduces a new family member

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD BRANCH CIRCUIT PROTECTION FUSED COORDINATION BOARD MERSEN S FUSED COORDINATION BOARD Selective Coordination is required in several locations as defined in the National Electrical Code (NEC). Mersen s Fused

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Fused Coordination Panelboard

Fused Coordination Panelboard Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined

More information

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission

More information

Electrical Equipment and Terminology

Electrical Equipment and Terminology Youth Explore Trades Skills Description Understanding the language of the electrical trade and knowing what electrical equipment is named and its purpose are very important. Anyone who is exposed to a

More information

These devices meet the requirements of OSHA 29 CFR (b)(1)(ii) and OSHA 29 CFR (a) (2)(ii)(G). Airpax LEL series

These devices meet the requirements of OSHA 29 CFR (b)(1)(ii) and OSHA 29 CFR (a) (2)(ii)(G). Airpax LEL series PGFM Series GFCI Ground Fault Protection Sensing Module INTRODUCTION The LineGard PGFM GFCI Sensing Module is a ground fault or equipment leakage sensing device designed and manufactured by North Shore

More information

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Robert P. Hansen, P.E., PhD GE Specification Engineer Introduction Switchboards are a widely used type of equipment

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution

Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution Electrical Safety Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: What it is made of. Its size. Its temperature. Substances with very little resistance

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

Installation Guide Galvanic Isolator Gi50/32/S/SA - 120a Surge Current

Installation Guide Galvanic Isolator Gi50/32/S/SA - 120a Surge Current Installation Guide Galvanic Isolator Gi50/32/S/SA - 120a Surge Current The Gi50/32/SA withstands fault surges of up to 120a, and is designed for installations connected to shore supplies protected by an

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

4400JF (120V) Aerating Fountain Specifications

4400JF (120V) Aerating Fountain Specifications 4400JF (120V) Aerating Fountain Specifications This specification is written and intended to provide bidders the necessary information pertaining to the floating aerating fountain(s) or surface aerator

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC 2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC

More information

The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730

The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730 The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730 In this article, Geoff Cronshaw looks at the impact that some of the proposed changes in the DPC (draft for public comment)

More information

8400JF (240V Single Phase) Aerating Fountain Specifications

8400JF (240V Single Phase) Aerating Fountain Specifications 8400JF (240V Single Phase) Aerating Fountain Specifications This specification is written and intended to provide bidders the necessary information pertaining to the floating aerating fountain(s) or surface

More information

GE Energy Industrial Solutions. EV Charging Station. Application Guide. imagination at work

GE Energy Industrial Solutions. EV Charging Station. Application Guide. imagination at work GE Energy Industrial Solutions EV Charging Station Application Guide imagination at work EV Charging Station Introduction The GE EV Charging Station offers Level II charging capable of reducing charge

More information

Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray

Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray Product LINE Guide Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray Voltage Isolation Power Factor Correction

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Electric Motor Controls BOMA Pre-Quiz

Electric Motor Controls BOMA Pre-Quiz Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,

More information

Small Motor Control (1/4 HP HP)

Small Motor Control (1/4 HP HP) PDHonline Course E110 (2 PDH) Small Motor Control (1/4 HP - 200 HP) Instructor: Thomas Mason, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

ELECTRICAL. 60 Minutes

ELECTRICAL. 60 Minutes ELECTRICAL 60 Minutes AGENDA Electrical definitions Electrical shocks, burns and secondary injuries Electrical hazards in the workplace Safety devices and prevention steps Do s and Don ts INTRODUCTORY

More information

Design considerations for generator set mounted paralleling breakers

Design considerations for generator set mounted paralleling breakers Our energy working for you. Design considerations for generator set mounted paralleling breakers White Paper Hassan Obeid, Application Group Cummins Power Generation Cummins Power Systems has been delivering

More information

Modular medium-voltage switchgear. NorMax

Modular medium-voltage switchgear. NorMax Modular medium-voltage switchgear NorMax NorMax MODULAR MEDIUM-VOLTAGE SWITCHGEAR 2 NorMax Modular medium-voltage switchgear Contents Subject Page Table of contents 2 Introduction and main features 2 Technical

More information

Ranger Tugs and Cutwater Boats Orientation Checklist

Ranger Tugs and Cutwater Boats Orientation Checklist Ranger Tugs and Cutwater Boats Orientation Checklist Boat Model: Owner's name: Delivery Captain: Date: DAY 1 Main Cabin: Main cabin components and functions Raising & Lowering the dinette table and bed

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information