1 User Manual ZSP100 Document No Page 1/6 MERAWEX Sp. z o.o. Toruńska Gliwice Poland tel fax merawex@merawex.com.pl USER MANUAL Power supplies for fire indication, heat and smoke control systems, fire protection and fire automation devices according to EN 54-4 and EN ZSP A-07, ZSP A-18 ZSP A-07, ZSP A-18 ZSP A-07, ZSP A-18, ZSP A-40 ZSP A-07, ZSP A-18, ZSP A January 2018 Certification of constancy of performance CNBOP No CPR-0454 Certificate of admittance CNBOP No. 2582/2016 Warnings Please read all these tips and regulations. Mistakes in their observance may cause damage, electric shock, fire or serious injury. It is forbidden to carry and transport the device with mounted and connected batteries. This can cause severe internal faults and can lead to the loss of operation safety. Installation and connections can be made only when batteries removed. When connecting batteries, please pay particular attention if their polarity matches the description on the connector. Do not block ventilation openings. Provide a free space of at least 10 cm at the sides of the device, enabling its proper ventilation. Otherwise, it can lead to damage of the device or early battery deterioration. Please, install the device in a place where it is not exposed to direct sunlight. The device must be powered from the mains with a protective earthing terminal. Before starting the device, please, check the quality of all connections. The device may interfere with operation of sensible radio and television equipment located nearby. The device must be serviced by servicemen of the manufacturer or specialized service companies authorized by the manufacturer.
2 User Manual ZSP100 Document No Page 2/6 Technical description The power supplies are designed to supply uninterruptible power to 24V fire protection devices, meeting the requirements of the EN 54-4+A1+A2 and EN The source of backup power is two 12V lead-acid VRLA type batteries. The power supplies are designed for wall mounting. All ten versions made in three types of cabinets are described in the table below. Table 1. Versions of ZSP100 Power supply in cabinet Power supply block Charging current Imax b Data plate Imax a Batteries Cabinet ZSP A-07 ZSPM A 1.5A 1.1A 7 9Ah 7 ZSP A-18 ZSPM A 1.5A 0.7A 7 20Ah 18 ZSP A-07 ZSPM A 2.5A 2.1A 7 9Ah 7 ZSP A-18 ZSPM A 2.5A 1.7A 7 20Ah 18 ZSP A-07 ZSPM A 4.0A 3.6A 7 9Ah 7 ZSP A-18 ZSPM A 4.0A 3.2A 7 20Ah 18 ZSP A-40 ZSPM A 4.0A 2.3A 17 45Ah 40 ZSP A-07 ZSPM A 5.5A 5.1A 7 9Ah 7 ZSP A-18 ZSPM A 5.5A 4.7A 7 20Ah 18 ZSP A-40 ZSPM A 5.5A 3.8A 17 45Ah 40 Completion of power supply: - power supply cabinet with power supply block inside - glands: DW16-RM 1 pc. DW20-RM 3 pcs. Optional equipment: - 4 cabinet mounting brackets with wall distance shoulder - module of 6 auxiliary outputs type ZSP100-OUT6 - tamper switch with cables - additional glands Fig. 1. Exemplary view of power supply in cabinet 18. Cabinets, in the upper part and on the left side, include ready, but still closed holes for the glands and also have a rectangular cut-out from the wall side, to pass electrical wires. Before installing the cabinets, please choose cable routing, remove the appropriate hole covers by breaking them out and mount the required amount of glands in right places. Table 2. Overall dimensions and mounting Cabinet Overall dimensions (W x H x D) [mm] 340 x 250 x x 356 x x 356 x 187 Mounting - inside cabinet (W x H) [mm] 276 x x x when using clips (W x H) [mm] 276 x x x 370 Weight without battery bank max. 3.1kg 4.2kg 6.9kg Weight with battery bank max. 8.4kg 16.2kg 35.9kg Holes for glands - in upper side 6x DW20-RM, 1xDW16-RM - in left side 3x DW20-RM, 6x DW20-RM, 6x DW20-RM, 1xDW16-RM 1xDW16-RM 1xDW16-RM
3 User Manual ZSP100 Document No Page 3/ Fig. 2. Exemplary layout of mounting holes of power supply in cabinet 18 The cabinet must be mounted to the wall with 4 steel screws. Please do not use plastic raw plugs. Prior to installation, it is advisable to remove the power supply block by unscrewing two bolts at the bottom, light deflection and sliding the whole block down. After mounting the cabinet, please mount the block of the power supply again. Table 3. Basic electrical and environmental parameters Nominal voltage *1) 110 / 230V +10% -15% Nominal output voltage *2) 27.1V Output voltage regulation *3) V Quiescent current consumption from battery max. 17 ma Power consumption from mains when battery is charged ~ 1.7W Efficiency at nominal load and when battery charged 89% Max. resistance of battery circuit *4) 250mΩ Number of batteries supervised 2 Number of outputs protected with separate fuses 2 Operation temperature C Ingress protection EN 60529:2003 IP 42 Functional class EN :2007 A Environmental class EN : Protection class EN : A1:2011 I *1) To use mains voltage 110V in ZSP100 power supplies consisting of power module ZSM-150, the mains voltage switch should be switched to 115V; it is not needed for ZSP100 versions including ZSPM-75 *2) It concerns floating operation mode at 25 C *3) The range includes a voltage between the voltage discharge of the battery (the end of the battery cycle) to the voltage of bulk charging. *4) A resistance value of the battery circuit at which the fault indication is activated. Installation and connection The power supply must be connected to a fixed installation with the use of protective cable and taking into account the markings L and N. It is recommended to include a surge protection system in the installation. The mains voltage should not be switched off by means of the main fire protection power switch. It is required to mount in the power circuits, outside the power supply, an installation breaker of the nominal current of at least 3A. The power area and the switch itself should be marked with red and a number of the power supply. One circuit breaker should protect only one power supply. Batteries should be connected after making all the other connections (output voltage of 24V and indication circuits) and connecting a LED harness on the housing plus possibly the tamper switch. After placing the batteries on the bottom of the cabinet, please place the temperature probe between them in such way, that it is in contact with walls of both batteries and then connect the cables to the appropriate poles: red cable to the pole (+) of one battery and the black cable to the pole (-) of the other. As a last, please make the connection between two batteries.
4 User Manual ZSP100 Document No Page 4/6 Fig. 3. View and components location of power supply module ZSPM-75 Table 4. Description of chosen components on ZSPM module (designations of fig. 3) Nr Description Marking Recommended type and cable diameter 1 3 solid core flame retardant halogen free Mains power connector L, N, cable *) mm 2 2 Cables for connecting batteries 3 Temperature probe 4 Load 1 connector OUT 1 twin solid core flame retardant halogen 5 Load 2 connector OUT 2 6 Output of general fault signal GEN FLT 7 Output of mains fault signal MAINS FLT 8 Input of external fault signal EXT FLT 9 LED of internal indication - green MAINS 10 LED of internal indication - yellow BAT 11 Connector for indication diodes Z201 free cable *) 1 or 2.5mm 2 twin solid core telecom flame retardant cable *) 1x2x0.8mm 2 12 Connector for tamper switch Z204 Factory installed jumper 13 Input for indication from packet of additional J201 outputs *) Selection of wires in power and control systems of fire protection equipment can be subject of different law and regulations, e.g. civil engineering code and derived ordinances. Notes There are 3 relay contacts available for each of the fault indication outputs. The figure describing the connector of the relays shows an arrangement of terminals when the mains is off (relay de-energized). The input of an external fault is connected with its terminal (-) to the negative pole of the battery (B-). Detection of the voltage 0V (short circuit) will generate fault indication. In this state, the current of approx. 0.25mA flows between the terminals (+) and (-) of the input. If the power supply cabinet is to be equipped with the tamper switch, please connect the plug of the sensor harness in a place of the factory set jumper on the connector Z204. The only components that can be exchanged by a user are fuses described in the table below. It is permissible to replace the fuses only with the ones of the same value and speed. Table 5. Fuses ratings ZSPM-75 ZSPM-150 B201 Mains circuit (slow-blow T) 2 AT 4 AT B101, B102 Output circuits (fast-blow F) 3.15 AF 6.3 AF B103 Battery circuit (fast-blow F) 6.3 AF 8 AF
5 User Manual ZSP100 Document No Page 5/6 First start If all the connections are made correctly, then after turning on the power supply, the status indication should be in accordance with the one mentioned in the table below in the column Correct start. Another signal indicates the occurrence of one of the errors described in the Appendix to the User Manual. Before using the power supply, please, perform additional two tests. Test of power backup. Please, disconnect the mains with the installation breaker. The power supply should switch into the battery operation mode, retaining voltage on its both outputs. The test can be performed by any probe, e.g. by using a voltmeter or a suitable bulb. If disconnection of power was done by removing the fuse B201, the condition can be detected only after 10 minutes. The GEN FLT relay will react with a delay of 5 seconds. Test of battery presence. When the power supply is powered with the mains, please break the circuit of the battery by disconnecting one of the cables. This condition will be detected at the next test, which can take up to 10 minutes. Table 6. Indication during tests Correct start Test of power backup LED indication on cabinet s door Test of battery presence 230VAC green LED on blinking on ALARM yellow LED off on on LED indication on PCB of ZSPM power supply MAINS green LED on off on BAT yellow LED off off blinking *) Relay indication MAINS FLT Mains fault energized de-energized energized GEN FLT General fault energized de-energized de-energized *) If the battery is disconnected for more than 12 min., the diode BAT will be permanently on. Please check during the tests whether the fault indication GEN FLT is successfully transmitted to the fire alarm control panel. Notes on operation and maintenance of power supply The power supplies after installation only require ongoing supervision in the case of possible faults that may occur during operation. Output voltages as well as indication levels are factory preset. Please, do not connect to each other the negative pole of the battery (B-) to the negative pole OUT1 and OUT2 (-) The battery bank is connected by the power supply only when the mains power is present and only when the battery voltage is higher than 21.6V. The battery will not be detected by the power supply if the battery is faulty (voltage below 10V). Warning indication (short flashes of LED ALARM) is activated for intermediate voltages, but the battery itself still will not be connected. In the battery operation mode, when the mains power is out and when the battery is discharged down to 21V, the LVDD (Low Voltage Disconnect Device) disconnects the battery. The battery should not be left in such the state for a long time as power supply still takes some minimal current for own needs, so it can lead to its further discharge and it might not be reconnected by the power supply after the mains power is back. If it is foreseen to leave power supply for a long time without mains power, then power supply battery must be disconnected, otherwise it will lead to its deep discharge, which decreases its lifetime. Battery life drops significantly with temperature increase. The temperature increase of every 8 10 C shortens the life by half. According to the recommendations of the CNBOP and VdS authorities, batteries should be exchanged regardless of their state after 4 years of operation. The power supplies should be inspected once a year by performing the tests described in the part First Start.
6 User Manual ZSP100 Document No Page 6/6 Appendix Table 7. LED indication, on the outside of power supply (cabinet s door) 230VAC green LED 0 - no mains power, battery disconnected (no-voltage state) 1 - mains present, power supply/charger operational 0/1 blinking - battery operation: no mains or faulty power supply/charger *1) ALARM yellow LED 0 - no faults 1 - battery operation: no mains or faulty power supply/charger *1) - no battery, or voltage of connected battery is lower than 10V - LVDD is turned off - too high resistance of battery circuit or battery fuse blown (>250mΩ) - output fuse blown - blown fuse in module of additional fuses (if connected) - battery voltage below 22V when mains power present *2) 0/1 blinking - external alarm or internal alarm (tamper) 0/1 flashing - battery recognized (U>10V) but its voltage is too low (U<21.6V) - LVDD remains disconnected *1) Power supply/charger failure is recognized at the latest after 10 minutes of the occurrence of the event (the check is performed simultaneously with the measurement of the resistance of the battery circuit). *2) The state can occur after the mains power is back and when battery charging just started. Table 8. LED indication on PCB of power supply ZSPM (PCB) MAINS green colour BAT yellow colour 0 no mains power 1 mains power present, power supply/charger operational 0/1 flashes mains power present, power supply/charger faulty *1) 0 battery correct 1 or 0/1 blinking resistance of battery circuit >250mΩ (including lack of battery or blown battery fuse *2) *1) Power supply/charger failure is recognized at the latest after 10 minutes of the occurrence of the event (the check is performed simultaneously with the measurement of the resistance of the battery circuit). *2) Resistance measurements of the battery circuit, including the battery disconnection and battery fuse blow, is performed every 10 minutes. After detecting the excess three times, one after another, the BAT LED is on with the steady light and, in the same time, the relay indication of the general fault GEN FLT is triggered. This behavior allows checking the system (e.g.: for maintenance purposes) by temporarily disconnecting the battery without generating a fault indication if restored to the correct state within 2 minutes. Table 9. Relay indication (0 - relay de-energized, 1 - relay energized) MAINS FLT Mains fault 0 - no mains power (mains only, not reacting to power supply/charger s fault) 1 - mains power present, power supply/charger operational GEN FLT General fault 0 *1), *2) - always, when LED ALARM is on, blinking or flashing 1 - no faults *1) Power supply/charger fault is recognized at the latest after 10 minutes of the occurrence of the event (the check is performed simultaneously with the measurement of the resistance of the battery circuit). *2) After the mains failure and after its recovery, the indication is activated with 5s delay. Handling packaging, used products and batteries Product packaging is made of non-hazardous materials (wood, paper, cardboard, plastics), which can be recycled. Packages which are no longer needed should be passed on to a waste collection station, after they had been sorted. This marking on the product indicates that the product after that time should not be disposed with household waste, but should be sent to a collection point for electronic waste. Used batteries are a hazardous waste and must be disposed of. This will help to avoid adverse effects on human health and the environment from uncontrolled waste disposal.
AWZ 110. AWZ 13,8V/1A/7Ah/LM
AWZ 110 v.1.3 AWZ 13,8V/1A/7Ah/LM Linear buffer power supply unit Grade 2. EN* Edition: 9 from 02.11.2017 Supercedes the edition: 8 from 23.01.2017 GREY POWER plus Features: EN50131-6 compliance, 1 2 grades
More informationPSBSH 2012B. PSBSH 13,8V/2A/7Ah/HERMETIC
PSBSH 2012B v.1.2 PSBSH 13,8V/2A/7Ah/HERMETIC Buffer switch mode power supply unit, EN** Edition: 7 from 02.11.2017 Supercedes the edition: 6 from 08.06.2017 Features: DC 13,8V/2A uninterruptible power
More informationPower supply for fire detection and fire alarm systems, smoke and heat control systems, and other fire protection systems, series ZSP135-DR
Power supply for fire detection and fire alarm systems, smoke and heat control systems, and other fire protection systems, series ZSP135-DR The power supply is a guaranteed source of 24V voltage. The wall
More informationFIREMAN'S MICROPHONE POWER SUPPLY FOR THE VOICE ALARM SYSTEMS 24V
DSOS24V v.1.0 FIREMAN'S MICROPHONE POWER SUPPLY FOR THE VOICE ALARM SYSTEMS 24V EN* Edition: 2 from 30.08.2017 Supercedes edition: 1 from 24.05.2016 PSU features. Compliant with the requirements of the
More informationPREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.
EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL GLT.MAN-138 CONTENTS Introduction to the Premier Power Pack PSU... 2 Changes to EN54-4 (The Fire Alarm Equipment Power Supply Standard)... 3 Indications... 4
More informationPSDCB161220E. v.1.0. PSDCB 13,8V/20A/16x1A/65Ah. Buffer power supply for up to 16 HD cameras. EN** Edition: 3 from
PSDCB161220E v.1.0 PSDCB 13,8V/20A/16x1A/65Ah Buffer power supply for up to 16 HD cameras. EN** Edition: 3 from 15.11.2017 Supercedes the edition: 2 from 24.04.2017 GREEN POWER CCTV Features: DC 13,8V/20A
More information27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2
1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:
More informationYour new LM controller is a state-of-the art device which was developed in accordance with the latest
CAP LM-series Solar charge controller User Manual Thank you very much for buying this CAP product. Please read the instructions carefully and thoroughly before using the products. Your new LM controller
More informationPSU EN54-4 Power Supplies
PSU EN54-4 Power Supplies Ordering: Models, Sales Order Parts: PSU MXP-549 : 1.5A PSE in 7Ah enclosure MXP-550 : 3.0A PSE in 17/18Ah enclosure MXP-550D : 3.0A PSE in 25Ah enclosure MXP-551 : 5.0A PSE in
More informationPSUPS10A12C. PSUPS 13,8V/12V/10A/17Ah. Buffer power supply for 8 HD cameras and recorder. v.1.0. Supercedes the edition: 1 from
v.1.0 PSUPS 13,8V/12V/10A/17Ah Buffer power supply for 8 HD cameras and recorder EN Edition: 2 from 15.11.2017 Supercedes the edition: 1 from 23.05.2017 GREEN POWER CCTV Features: DC 13,8V uninterruptible
More informationPOWER SUPPLY aps-412_en 06/16
APS-412 POWER SUPPLY aps-412_en 06/16 The APS-412 switching power supply has been designed for use with 12 V DC electrical devices. It comes with a dedicated connector allowing for integration with Satel's
More informationSBC V In-Car Charger Dual Input (Solar MPPT & DC)
SBC-5926 12V In-Car Charger Dual Input (Solar MPPT & DC) Operation manual Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation instructions
More informationElmdene International Ltd
1 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44(0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk 13.8Vdc Switch Mode Power Supply GEN3-08-y
More informationPhocos CML-V2. Solar charge controller. User Manual (English) Dear customer,
Phocos CML-V2 Solar charge controller User Manual (English) Dear customer, Thank you very much for buying this Phocos product. Please read the instructions carefully and thoroughly before using the product.
More informationABB i-bus EIB EIB Power Supply Units SV/S SV/S SU/S
Product Manual ABB i-bus EIB EIB Power Supply Units SV/S 30.320.5 SV/S 30.640.5 SU/S 30.640. Intelligent Installation Systems Contents Page EIB Power Supply Units. Introduction.........................................
More information24V 3A EN54 Ancillary Power Supply
24V 3A EN54 Ancillary Power Supply Normal supply - green light on Fault condition - call Engineer Control relay - activated 3A Power Supply C-TEC Manufactured in England by C-Tec EN 54-4 : 1997 INSTALLATION
More informationBNC08128C. BNC 13,8V/8x1A/17Ah. Switch mode buffer power supply unit for CCTV. v.1.0 EN** Edition: 1 from Supersedes the edition:
BNC08128C v.1.0 BNC 13,8V/8x1A/17Ah Switch mode buffer power supply unit for CCTV. EN** Edition: 1 from 26.11.2013 Supersedes the edition: ------ GREEN POWER CCTV BNC PSU features: DC 13,8V/8x1A uninterruptible
More informationInstallation Instructions
AQU244 & AQU128 Series Installation Instructions Installation Instructions AQU244 24vdc 5A Supervised Power Supply/Charger module AQU128 12vdc 10A Supervised Power Supply/Charger module Both Mounted in
More informationInstallation and Operating Instructions. MPPT Solar System Controller ISC3040
Installation and Operating Instructions MPPT Solar System Controller ISC3040 ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s
More informationAWZ 200. AWZ 13,8V/2A/7Ah/L
GREY POWER AWZ 200 v.2.4 AWZ 13,8V/2A/7Ah/L Linear, Buffer Power Supply Unit EN** Edition: 7 from 15.05.2014 Supercedes the edition: 6 from 13.02.2014 Features: 13,8VDC/2A uninterruptible supply fitting
More informationc-go 12V/10A 12V/20A Power supply and battery charger Instruction manual
c-go 12V/10A 12V/20A Power supply and battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Mounting and installation... 4 4. Operation... 5 5. Problem solving...
More informationInstallation and Operating Instructions. Solar System Controller ISC3020
Installation and Operating Instructions Solar System Controller ISC3020 ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s of
More informationMODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM
MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...
More informationLEAD ACID BATTERY CHARGER
LEAD ACID BATTERY CHARGER MODEL NO: LA4 & LA6 OPERATION & MAINTENANCE INSTRUCTIONS LS1214 INTRODUCTION Thank you for purchasing this CLARKE Battery Charger. Please read this manual thoroughly, before attempting
More informationUSER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG SKYLLA 24/100 3-PHASE CE
USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG SKYLLA 24/100 3-PHASE CE SECTIONS: ENGLISH 2 NEDERLANDS 17 DEUTSCH 37 Victron Energy BV De Paal 35 1351 JG Almere-Haven The Netherlands Article number
More informationDycon D2430 EN54-4 Fire Alarm Power Supply Series
Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product
More informationThe 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.
1 Elmdene International Ltd Tel: +44 (0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk STANDBY 220V AC POWER SYSTEM IDEAL
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationInstallation and Operating Instructions. Solar System Controller ISC3030
Installation and Operating Instructions Solar System Controller ISC3030 ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s of the
More informationAL600ULX Series. Power Supply/Charger Installation Guide
AL600ULX Series Power Supply/Charger Installation Guide Models Include: AL600ULX - Single Output AL600ULPD4 AL600ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL600ULPD8 AL600ULPD8CB - Eight
More information8 Step Fully Automatic Intelligent BATTERY CHARGER 12V 5A USER S MANUAL. Charges & Maintains. Flooded (WET), MF, VRLA, AGM, GEL & Calcium batteries
8 Step Fully Automatic Intelligent BATTERY CHARGER 12V 5A Charges & Maintains Flooded (WET), MF, VRLA, AGM, GEL & Calcium batteries USER S MANUAL 5 User s Manual And Guide To Professional Battery Charging
More informationPOE1824B. PoE 27,6V/4x0,4A/2x7Ah/PoE
v.1.0 PoE 27,6V/4x0,4A/2x7Ah/PoE Buffer switch mode power supply unit EN* Edition: 2 from 16.09.2013 Supercedes the edition: 1 from 06.02.2012 Features: DC 27,6 V/4x0,4A uninterruptible power supply fitting
More informationDC POWER SUPPLY SYSTEMS
DC POWER SUPPLY SYSTEMS double branch Rectifier - SCR type TITANIUM 2R-SCR PLUS SERIES TITANIUM 2R-SCR rectifier series belongs to the Double Branch category thus provided with two independent AC / DC
More informationc-go 24V/6A 24V/8A 24V/12A
c-go 24V/6A 24V/8A 24V/12A Battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Quick start guide... 4 4. Operation... 4 5. Problem solving... 6 6. Specifications...
More informationPowerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)
A Complete solution for small battery-backed dc instrument power systems. DATASHEET Supply 12Vdc 8A or 24Vdc 6A loads Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where
More informationInstallation Instructions
Installation Instructions AQU243-8C1R -8F8R -8C8R 24VDC/3.3Amp Supervised (AC & Battery) Power Supply/Charger Module, 85-264vac, 14 x 9 x 3.5" Enclosure, UL294, UL603 & UL1481 Listed AQU243 with one PDB-8C1R
More informationSCC-MPPT Solar Charge Controller
Table 4: Alarm point for low battery voltage table Model Alarm point SCC-MPPT-300 10.5 V SCC-MPPT-600 21.0 V Table 5: Charging hour table for reference Battery Capacity To 90% capacity @ 25A charging current
More informationRECHARGEABLE SPOTLIGHT
RECHARGEABLE SPOTLIGHT MODEL: RWL10 Part No: 4002822 INSTRUCTION MANUAL LS0609 INTRODUCTION Thank you for purchasing this CLARKE product Before attempting to use the product, it is essential that you read
More informationNON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT
Model No. PEL00581 NON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT 1 Please read these instructions carefully before starting installation and retain for future reference. The centre page
More informationAll In one uninterruptible power supply solutions
All In one uninterruptible power supply solutions For the life of your systems with Battery Care concept Integrated Electronic Solution Yet another strong proposition from Adelsystem, result of the continuing
More informationPSU-S-12V/L-1A/5/FTA/PTC-TR-MC AWZ v.1.0
PSU-S-12V/L-1A/5/FTA/PTC-TR-MC AWZ 05121 v.1.0 Linear, stabilized power supply unit. Edition: 1 from the 2 nd February 2011 Supercedes edition: Features of the power supply unit: five outputs protected
More information10A / 15A / 20A Solar Charge Controller. PU1024 / PU1524 / PU2024 series INSTRUCTION MANUAL
10A / 15A / 20A Solar Charge Controller PU1024 / PU1524 / PU2024 series INSTRUCTION MANUAL Dear Customer, Thank you very much for choosing our product. This manual contains important information about
More informationSCCP PWM Charge Controller/Load Manager Owner s Manual
SCCP05-050 PWM Charge Controller/Load Manager Owner s Manual NOTE: Follow instructions in order. Charge batteries at least once a week. Use reducers to connect larger wires disconnect to terminals. battery
More informationIndustrial Chargers and
Industrial Chargers and DC Systems SPR - Single Phase Rectifier TPR - Three Phase Rectifier 12V 250V 5A 1000A Designed for all Industrial applications Oil & Gas, Petrochemicals Offshore, Onshore, Pipelines
More informationOperating Manual
Operating Manual 15-24-1000 15-36-1000 1. Safety 2 1.1 Warnings, Cautions and Notes 2 1.2 General Warning 2 1.3 Fire Risk 2 1.4 Electric Shock Risk 2 1.5 Chemical Risk 3 1.6 Do s 3 1.7 Do Not s 3 1.8 DC
More informationGeneral Description. BADICHEQ 3000 (Battery Diagnostic & Charge Equalizing) The compact solution for perfect battery management
General Description BADICHEQ 3000 1 Chapter1: Introduction I: The problem General Description BADICHEQ 3000 (Battery Diagnostic & Charge Equalizing) The compact solution for perfect battery management
More informationInnovative Circuit Technology Ltd.
Innovative Circuit Technology Ltd. IntelliCharge Battery Charger Series INSTRUCTION MANUAL 855-342-000 Models: ICT24012-30BC2, ICT24012-30BC2M ICT24012-15BC2, ICT24012-15BC2M ICT24024-15BC2, ICT24024-15BC2M
More informationThe Traveler Series: Wanderer
The Traveler Series: Wanderer RENOGY 30A PWM Charge Controller Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version: 2.3 Important Safety Instructions Please save these instructions.
More informationwith lcd display 12-42v
instructions for: AUTO PROBE with lcd display 12-42v MODEL No: PP7 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these instructions
More informationK25000 & KD25000 Series
K25000 & KD25000 Series Fire Alarm Power Supplies Installation, Commissioning and Operating Manual Man-1128 Issue 14 January 2016 Man-1128_K25400_series_Power_Supply_Manual_14 Page 1 of 20 Section Page
More informationOPERATION & MAINTENANCE INSTRUCTIONS
AUTOMATIC BATTERY CHARGER / MAINTAINER MODEL NO: CBO9-12 PART NO: 6267025 OPERATION & MAINTENANCE INSTRUCTIONS LS0315 INTRODUCTION Thank you for purchasing this CLARKE product. Before attempting to use
More informationElectronic Ballast EVG 2000-T
Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications
More information12 amp RMS Battery Charger
12 amp RMS Battery Charger 83-5000-12 If faults cannot be remedied, contact the Helpline on 020 8391 6767 helpline@hilka.co.uk Manufactured under license by Hilka Pro Imports GUARANTEE This product is
More informationInstallation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z
Installation and operating instructions Solar charge controller MPPT 10 A / 20 A EN 1 Contents 1. About these instructions... 3 1.1 Applicability... 3 1.2 Users... 3 1.3 Description of symbols... 3 2.
More informationCaution Wear protective glasses and turn your face away when connecting or disconnecting from the battery.
SmartCharge User Manual Item Code: 979997 4A SmartCharge Up to.0l Engines Item Code: 97996 5A SmartCharge Up to.5l Engines Caution Wear protective glasses and turn your face away when connecting or disconnecting
More informationINSTRUCTION MANUAL A141 High Level Audible Warning System / Battery backup
Control Panel Unit Type No. A141AC230GB Input Voltage: 115 or 230VAC (90V to 264V AC range) Operating Temp: -20 to +55 C IP Rating: IP65 Marking: Control Unit weight : 23kg 3) Installation Requirements
More informationHPSB 2512B v.1.0 HPSB 13,8V/2A/7Ah Buffer, switch mode power supply unit.
HPSB 2512B v.1.0 HPSB 13,8V/2A/7Ah Buffer, switch mode power supply unit. EN* Edition: 5 from 05.06.2014 Supercedes the edition: 4 from 10.02.2014 Features: DC 13,8V/2A uninterruptible power supply* fitting
More informationOPERATION & MAINTENANCE INSTRUCTIONS
AUTOMATIC BATTERY CHARGER / MAINTAINER MODEL NO: CBO9-6/12 PART NO: 6267020 OPERATION & MAINTENANCE INSTRUCTIONS LS0615 INTRODUCTION Thank you for purchasing this CLARKE product. Before attempting to use
More informationSCC-MPPT Solar Charge Controller
Table 3: Charging voltage for 4 types of battery Battery Battery 12V battery system 24V battery system Type Type Code Bulk Floating Bulk Floating Vented 01 14.3 V 13.2 V 28.6 V 26.4 V Sealed 02 14.3 V
More informationBATTERY BOOSTER/CHARGER MODEL NO: DIGICAR 600
BATTERY BOOSTER/CHARGER MODEL NO: DIGICAR 600 PART NO: 6261200 OPERATION & MAINTENANCE INSTRUCTIONS LS0815 INTRODUCTION Thank you for purchasing this CLARKE Battery booster / charger which is suitable
More informationSolar Charge Controller
Table 3: Charging voltage for 4 types of battery Battery Type Battery Type Code SC-600W MPPT Bulk Voltage Floating Voltage Vented 01 28.6 V 26.4 V Sealed 02 28.6 V 26.8 V Gel 03 28.6 V 27.4 V NiCd 04 28.6
More informationPure Sine Wave Inverter Charger
Pure Sine Wave Inverter Charger Renogy 1000W 2000W Pure Sine Wave Inverter Charger Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.6 1 Important Safety Instructions Please save
More informationSC-10 MPPT User Manual
SC-10 MPPT User Manual ELECTRICAL SPECIFICATIONS Efficiency Typical 96% Input Voltage 16V to 55V Output Voltage (Float) 13.5V / 27V Output Voltage (Bulk) Flooded 14.5V / 29V Sealed 14.2V / 28.4V Peak 250W
More informationFlex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No
Flex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No. 20 751 167 Distributor: Producer: METREL d.d. Ljubljanska 77 SI-1354 Horjul Tel.: +386 1 75 58 200 Fax: +386 1 75 49 226 E-mail:
More informationSCC-MPPT Solar Charge Controller
Solar Charge Controller Quick Guide 200W 300W 400W 600W 850W V. 2.2 1. Introduction solar charge controller uses PWM-based DSP controller to keep the batteries regulated and prevent batteries from overcharging
More informationPower Supply EL
General information: EL630-1203-7 has been specifically developed to meet the DC powering requirements for telecommunications, industrial and marine applications. The output is current limited, with short
More informationArt. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2
SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...
More informationHome Solar 400 (HS 400) Home Solar 800 (HS 800) Home Backup 400 (HB 400) Home Backup 800 (HB 800) Owner s Manual
Home Solar 400 (HS 400) Home Solar 800 (HS 800) Home Backup 400 (HB 400) Home Backup 800 (HB 800) Owner s Manual For safe and optimum performance, the Home Solar or Home Backup unit must be used properly.
More informationOPERATION & MAINTENANCE INSTRUCTIONS
AUTOMATIC BATTERY CHARGER / MAINTAINER MODEL NO: CBO9-12 PART NO: 6267025 OPERATION & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS LS0118 - ISS 3 INTRODUCTION Thank you for purchasing this CLARKE product.
More informationFUM-24xxCBP Series 3 Stage Battery Charger User Manual
FUM-24xxCBP Series 3 Stage Battery Charger User Manual Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation instructions for correct use
More informationFC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE
FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101037 Document revision: A Engineering change number: 105073 Date: 1/13/2006 1840 Industrial Circle
More informationBATTERY BOOSTER/CHARGER MODEL NO: DIGICAR 900
BATTERY BOOSTER/CHARGER MODEL NO: DIGICAR 900 PART NO: 6261205 OPERATION & MAINTENANCE INSTRUCTIONS LS0715 INTRODUCTION Thank you for purchasing this CLARKE Battery booster / charger which is suitable
More informationACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery
More informationOPERATING MANUAL PHASE SEQUENCE AND MOTOR ROTATION DIRECTION TESTER TKF-13
OPERATING MANUAL PHASE SEQUENCE AND MOTOR ROTATION DIRECTION TESTER TKF-13 v1.5 07.07.2011 Table of contents 1. Safety measures... 2 2. Phase spin direction test... 3 3. Motor shaft spin direction (using
More informationMODEL ELC-12/40-CVM-D BATTERY CHARGER
NATIONAL RAILWAY SUPPLY MODEL ELC-12/40-CVM-D BATTERY CHARGER Installing, Operating and Service Instructions for the ELC-12/40-CVM-D Solid State Charger PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING
More informationUninterruptible Power System
USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency UPS 1 st Edition Uninterruptible
More informationPURE SINE WAVE DC TO AC POWER INVERTER
PURE SINE WAVE DC TO AC POWER INVERTER 60S-12A / 60S-24A 60S-12E / 60S-24E 100S-12A / 100S-24A 100S-12E / 100S-24E 150S-12A / 150S-24A 150S-12E / 150S-24E Instruction manual SINE WAVE INVERTER Please read
More informationLanguage specific user manuals are available on
User Manual WEB Charger for Lead Acid Batteries EN User Manual Language specific user manuals are available on www.mascot.no/downloads/usermanuals Bruksanvisning Käyttöohjeet Bedienungsanleitung Mode d
More informationECONOMISER SERIES E2T USER MANUAL
TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014
More informationSentry Battery Charger. Installation and Operations Manual Section 75
Sentry Battery Charger Installation and Operations Manual 00-02-0616 03-03-08 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to change our
More informationPSU-S-12V/L-3A/9/FTA/PTC-TR-MC AWZ v.1.0
PSU-S-12V/L-3A/9/FTA/PTC-TR-MC AWZ 09123 v.1.0 Linear, stabilized power supply unit. EN Edition: 1 from the 30 th January 2011 Supercedes edition: Features of the power supply unit: 3 groups (A, B, C)
More informationCBI All in One DC UPS Power Solutions
CBI All in One Power Solutions Everything and more! More efficiency of the battery thanks to continuous control over time. More monitoring in main connection nodes: input, output load, battery. Event logging:
More informationMANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel
MANUAL CONGRATULATIONS on the purchase of your new CTEK professional battery management unit. This unit is part of a range of professional battery chargers from CTEK SWEDEN AB. It represents the latest
More informationGENERALITIES TECHNICAL FEATURES
GENERALITIES This device is a traditional three-phases battery charger, with a power supply of 230Vac or 400Vac. The battery charger is a WA charge cycle type, which ensures a decrease of the current and
More informationUser Manual. Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5
More informationHD UNIT INSTALLATION & SERVICE BOOKLET 3-7
HD UNIT INSTALLATION & SERVICE BOOKLET 3-7 2 Heat exchanger Fan Mounting hole Speed control Air flow hole Technical information plate Power cable 230V Glycol inlet/outlet WARNING During the installation
More informationOPERATOR'S MANUAL IMPORTANT SAFETY INSTRUCTIONS
ASSOCIATED OPERATOR'S MANUAL IMPORTANT SAFETY INSTRUCTIONS MODEL 6366 12 VOLT, 0-20 AMP 4 X 20 BATTERY CHARGER 1. SAVE THESE INSTRUCTIONS. This manual contains important safety and operating instructions
More informationMB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR
MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside
More informationIlluminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System
Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical
More informationIMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS
THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. IMPORTANT SAFEGUARDS INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL When using
More informationSENS DC PowerCab 120 Installation, Operation, & Maintenance Manual
Installation, Operation, & Maintenance Manual Stored Energy Systems Packaged By: 1840 Industrial Circle C&C Power, Inc. Longmont, Co 80501 395 Mission Street www.sens-usa.com Carol Stream, IL 60188 Technical
More informationDIN-Rail DC UPS. Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications
DIN-Rail DC UPS Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications Combines all system power functions: power supply, battery charger, UPS circuitry
More informationHIGH FREQUENCY AUTOMATIC BATTERY CHARGER
HIGH FREQUENCY AUTOMATIC BATTERY CHARGER MODEL NO: HFBC12 PART NO: 6267000 OPERATION & MAINTENANCE INSTRUCTIONS LS0814 INTRODUCTION Thank you for purchasing this CLARKE High Frequency Automatic Battery
More informationThe Traveler Series: Wanderer
The Traveler Series: Wanderer RENOGY 30A Charge Controller Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version: 2.0 Important Safety Instructions Please save these instructions. This
More informationDIAGNOSTIC POWER SUPPLY WSC 720. user guide. 12 V/24 V lead acid batteries ah
DIAGNOSTIC POWER SUPPLY WSC 720 user guide 12 V/24 V lead acid batteries 40-500 ah gb 1 Thank you for choosing this charger from Exide Technologies Your WSC720 is a quality product from Exide Technologies.
More informationTABLE OF CONTENTS. 300 W Mobile Power Outlet SAVE THESE INSTRUCTIONS!
300 W Mobile Power Outlet 011-1870-6 TECHNICAL SPECIFICATIONS... 3 Safety Information... 4 KEY PARTS diagram... 7 INTENDED USE... 9 Options for connecting devices to the power inverter... 9 Operation...
More informationACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER
ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER SPECIFICATIONS: *Photo for reference only* Part number 8890439 Mode Select: Selects Battery Type Refer to Section 6. IMPORTANT: READ
More informationInstruction of Solar Charge Controller. User s Manual
Instruction of Solar Charge Controller User s Manual 12V/24V 10A/20A Dear Users: Thank you for selecting our product. Please read this manual carefully before you use this product. 0 The controller is
More informationInstruction of Solar Charge Controller. User s Manual
Instruction of Solar Charge Controller User s Manual 12V/24V 30A Dear Users: Thank you for selecting our product. Please read this manual carefully before you use this product. The controller is for off-grid
More informationPANcharge1k Battery Charger User's Manual
PANcharge1k Battery Charger User's Manual Ver.1.00E Table of Contents 1. Important Safety Instructions... 3 1-1 General Safety Precautions... 3 1-2 Battery Precautions... 3 1-3 Electromagnetic Disturbance...
More information