1 H September, 2015 INSTALLATION/SETUP INSTRUCTIONS Electronic Mild Temperature Thermostat gas-fired duct furnace/make-up air units Model Series: D, H, I, & O Application The Electronic Mild Temperature Thermostat option is used to automatically disable the gas controls when the inlet air temperature reaches the desired setpoint to prevent the furnace from excessively cycling at mild outside air temperature conditions. The option uses a Johnson Controls System 350 on/off electronic temperature control with single-pole, double-throw relay output and LED indication. Figure 1.1 Mild Temperature Thermostat WARNING 1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage. 2. All units must be wired strictly in accordance with wiring diagram furnished with the unit. Any wiring different from the wiring diagram could result in a hazard to persons and property. 3. All wiring must be done with a wiring material having a remperature rating of at least 105 C. Components For Model Sizes (Digits 4-6) : AA-1C Electronic Temperature Control Module F range, 1 to 30 F differential SET189A-600R Inlet Air Temp Sensor (factory installed on outdoor units, field installed on indoor units) For Model Sizes (Digits 4-6) : Same as above, but adds S350AA-1C Electronic Stage Module - 1 to 30 F differential The Electronic Temperature Control operates on 24VAC and supplies a SPDT relay output based on a temperature change against the setpoint. When the temperature rises above the setpoint, the relay contacts open. An LED on the front panel labeled ON illuminates to indicate when the relay is energized. There are two adjustable features on the controller, the setpoint and differential, which are covered later in these instructions. The S350 Electronic Stage Module provides SPDT relay output when the differential from the has been satisfied. An LED on the front panel labeled ON illuminates to indicate when the relay is energized. There are two adjustable features on the controller, the offset and differential, which are covered later in these instructions. Wiring This option is prewired at the factory. Additional wiring is not required. In the event that additional wiring is necessary, installation of wiring must conform with local building codes, or in the absence of local codes, of the National Electric Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code. IMPORTANT The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these units must be performed by a qualified installation and service agency. Modine manuals may contain excerpts from component supplier literature adapted for Modine products. Any accompanying component supplier literature is for general information. THIS MANUAL IS THE PROPERTY OF THE OWNER. PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.

2 INSTALLATION/SETUP Electronic Mild Temperature Thermostat Sensor Mounting (Indoor Units Only) This section applies ONLY to indoor models ( D and I model series units). Outdoor models ( H and O model series) already have the sensor mounted on the unit inlet. 1. The unit comes with the sensor prewired, with the sensor and wire coiled in the blower section for shipping purposes. Extend the sensor/wire outside the blower casing as shown in Figure 2.1. Figure 2.1 Sensor Installation on Indoor Units EXTEND SENSOR CABLE THROUGH BUSHING IN CASING Definitions Before proceeding to the Settings Adjustments section, review the following definitions and refer to Figure 2.3. Setpoint Setpoint is the temperature at which the relay will deenergize. When the temperature at the sensor rises above the setpoint (i.e. mild outside air temperature conditions), the relay will be de-energized, the contacts will open, and the gas controls will be disabled. Differential Differential is the change in sensor temperature between energization and de-energization of the relay. When the temperature falls below the setpoint by the number of degrees of differential, the relay will be energized, the contacts will close, and the gas controls will be enabled. Offset This adjustment only applies to units with the S350 Electronic Stage Module. The offset adjustment determines the amount of offset from the setpoint that the S350 s relay will de-energize. When the temperature sensed rises above the Setpoint MINUS the S350 Offset, the relay will be de-energized, the contacts will open, and the gas controls for Furnace #3 will be disabled. 2. The sensor wire included provides enough length to install the sensor bracket approximately 2 feet from the inlet end of the unit. If additional length is required, please refer to the Wiring section. 3. Drill a single 1-1/4" diameter hole in the outside air intake duct to mount the sensor bracket. 4. Before mounting the bracket, secure the sensor and sensor wire to the bracket with the cable ties provided. Refer to Figure Insert the bracket into the hole drilled in step 3 and secure to the duct with the screws provided. Figure 2.2 Sensor Installation on Indoor Units DUCTWORK BY OTHERS Note that for the Setpoint, Differential, and Offset to work properly for the Mild Temperature Thermostat application, the mode must be set to Heating. Refer to the section Settings Adjustments for instructions. Figure 2.3 Mild Temp Stat Control Descriptions (+) TEMPERATURE ( ) OFF ON OFFSET S350 OFF ON CLOSE-UP VIEW OF SENSOR/BRACKET BEFORE INSTALLED IN DUCTWORK

3 INSTALLATION/SETUP Electronic Mild Temperature Thermostat Settings Determination Before proceeding to the adjustment of settings on the and, if applicable, the S350, review the following sections to determine the suggested settings for the unit as configured. There are two ways to determine the settings: 1) Use the Table Method with Tables on this page, based on the Model Size of the unit, or 2) Use the Calculation Method on pages 4 through 6 to derive the settings for conditions not shown in Tables 3.1 through 3.4. After using either method to determine the correct settings, please proceed to the Settings Adjustment Section on page 7 for instructions. Table Method If the job conditions are different than shown in Tables 3.1 through 3.4, proceed to the Calculation Method on pages 4 through 6. Model Sizes (Digit 4-6) = 75 through 400 For Model Sizes (Digit 4-6) = 75 through 400, the discharge air temperature setpoint is required. With that information, Table 3.1 can be used to determine the suggested Setpoint on the. Example: What is the Setpoint for a 350 sized unit, 100 F air temperature rise, -25 F outside air temperature, and a discharge air setpoint of 75 F? Answer: The only relevant information is the discharge air temperature setpoint, in this case, 75 F. From Table 3.1, the suggested Setpoint on the is 70 F. Table 3.1 Setpoint for Model Sizes (Digit 4-6) = 75 to 400 Temp Rise Discharge Air Temp ( F) ( F) All Model Sizes (Digit 4-6) = 500 through 800 For Model Sizes (Digit 4-6) = 500 through 800, the discharge air temperature setpoint is required, along with the unit design air temperature rise. Table 3.2 can then be used to determine the suggested Setpoint on the. Example: What is the Setpoint for a 600 sized unit, 100 F air temperature rise, -20 F outside air temperature, and a discharge air setpoint of 80 F? Answer: The only information that is relevant is the discharge air temperature setpoint of 80 F and the air temperature rise of 100 F. From Table 3.2, the suggested Setpoint on the is 35 F. Table 3.2 Setpoint for Model Sizes = 500 to 800 Temp Rise Discharge Air Temp ( F) ( F) Model Sizes (Digit 4-6) = 840 through 960 For Model Sizes (Digit 4-6) = 840 through 960, the discharge air temperature setpoint is required, along with the unit design air temperature rise. Table 3.3 can then be used to determine the suggested Setpoint on the and Table 3.4 used to determine the Offset on the S350. Example: What is the Setpoint () and Offset (S350) for a 960 sized unit, 70 F air temperature rise, 0 F outside air temperature, and a discharge air setpoint of 70 F? Answer: The only relevant information is the discharge air temperature setpoint of 70 F and the air temperature rise of 70 F. From Table 3.3, the suggested Setpoint on the is 52 F. From Table 3.4, the S350 Offset is 24 F Table 3.3 Setpoint, Model Sizes 840 to 960 Temp Rise Discharge Temp ( F) ( F) Table 3.4 S350 Offset, Model Sizes 840 to 960 Temp Rise ( F) Offset for All Discharge Temps ( F) 120 to

4 30 F INSTALLATION/SETUP Electronic Mild Temperature Thermostat Calculation Method If the job conditions are different than shown in Tables 3.1 through 3.4, the following Calculation Method can be used to determine the setpoints. If the Table Method from page 3 was used to determine the correct settings, proceed to page 7 for instructions on adjusting the settings. Settings for Model Sizes (Digit 4-6) = 75 through 400 For these units, the Setpoint and Differential must be set on the controller. The Setpoint is typically set as follows: Setpoint = Discharge Temperature - 5F The Differential is typically set at 3 F to avoid nuisance switching. Example: What are the settings for a unit with a discharge temperature setpoint of 70 F? Setpoint = 70 F 5 F = 65 F Differential = 3 F Referring back to the Definitions, the following is the sequence of operation for the control: o o Once the outside air temperature falls to 62 F (65 F Setpoint - 3 F Differential), the gas controls will be enabled. Once the gas controls are enabled, they will remain enabled until the temperature rises above the 65 F Setpoint. Figure 4.1 Mild Temperature Thermostat Settings for Model Sizes (Digit 4-6) 75 to 400 JOHNSON AA-1C SHOWN WITH FRONT COVER REMOVED (CONTROL IS LOCATED IN THE BLOWER ELECTRICAL COMPARTMENT) JUMPER POSITION HEATING COM N.O. FURNACE #1 FACTORY WIRING

5 30 F INSTALLATION/SETUP Electronic Mild Temperature Thermostat Calculation Method (continued) Settings for Model Sizes (Digit 4-6) = 500 through 800 For these units, the Setpoint and Differential must be set on the controller. The Setpoint is typically set as follows: Setpoint = Discharge Temperature (0.5 x T) + 5 F The Differential is typically set at 3 F to avoid nuisance switching. Example: What are the settings for a unit with a discharge temperature setpoint of 70 F and temperature rise of 90 F? Setpoint = 70 F (0.5 x 90 F) + 5 F = 30 F Differential = 3 F Referring back to the Definitions, the following is the sequence of operation for the control: o o Once the outside air temperature falls to 27 F (30 F Setpoint - 3 F Differential), the gas controls will be enabled. Once the gas controls are enabled, they will remain enabled until the temperature rises above the 30 F Setpoint. Figure 5.1 Mild Temperature Thermostat Settings for Model Sizes (Digit 4-6) 500 to 800 JOHNSON AA-1C SHOWN WITH FRONT COVER REMOVED (CONTROL IS LOCATED IN THE BLOWER ELECTRICAL COMPARTMENT) JUMPER POSITION HEATING COM N.O. FURNACE #2 FURNACE #1 FACTORY WIRING

6 30 F INSTALLATION/SETUP Electronic Mild Temperature Thermostat Calculation Method (continued) Settings for Model Sizes (Digit 4-6) = 840 through 960 For these units, the Setpoint and Differential must be set on the controller and S350. The Setpoint is typically set as follows: Setpoint = Discharge Temperature (0.33 x T) + 5 F The Differential on both and S350 are typically set at 3 F to avoid nuisance switching. The Offset on the S350 is typically set as following this 3-step process: a. Calculate Desired Stage Setpoint = Discharge Temperature (0.67 x T) b. Calculated Offset = Setpoint Calculated Desired Stage Setpoint c. Actual Offset is one of the following: a. If Calculated Offset 30 F, then Offset=Calculated Offset 5 F b. If Calculated Offset>30 F, then Offset=30 F 5 F = 25 F Example #1: What are the settings for a unit with a discharge temperature setpoint of 75 F and temperature rise of 100 F? Setpoint = 75 - (0.33 x 100) + 5 F = 47 F Once the outside air temperature falls to 44 F (47 F Setpoint - 3 F Differential), the gas controls of Furnace #2 will be enabled. Differential on and S350 = 3 F Calculate Desired Stage Setpoint = 75 (0.67 x 100) = 8 F Calculated Offset = 42 F 8 F= 34 F Since 34 F > 30 F, Offset = 30 F 5 F = 25 F Once the outside air temperature falls to 19 F (47 F Setpoint 25 F Offset 3 F Differential), the gas controls of Furnace #3 will be enabled. Example #2: What are the settings for a unit with a discharge temperature setpoint of 75 F and temperature rise of 60 F? Setpoint = 75 - (0.33 x 60) + 5 F = 60 F Once the outside air temperature falls to 57 F (60 F Setpoint - 3 F Differential), the gas controls of Furnace #2 will be enabled. Differential on and S350 = 3 F Calculate Desired Stage Setpoint = 75 (0.67 x 60) = 35 F Calculated Offset = 60 F 35 F = 25 F Since 20 F 30 F, Offset = 25 F 5 F = 20 F. Once the outside air temperature falls to 37 F (60 F Setpoint 20 F Offset 3 F Differential), the gas controls of Furnace #3 will be enabled. Figure 6.1 Mild Temperature Thermostat Settings for Model Sizes (Digit 4-6) 840 to 960 JOHNSON AA-1C AND S350AA-1C SHOWN WITH FRONT COVERS REMOVED OFFSET (CONTROL IS LOCATED IN THE BLOWER ELECTRICAL COMPARTMENT) JUMPER POSITION HEATING COM N.O. S350 COM N.O. FURNACE #3 FURNACE #2 FURNACE #1 FACTORY WIRING

7 INSTALLATION/SETUP Electronic Mild Temperature Thermostat Settings Adjustments The mild temperature thermostat control must be setup and adjusted to properly lockout the gas controls as outside temperatures increase and re-enable the controls as outside temperatures fall. This is to minimize furnace cycling when heating demand is below the minimum turndown of the furnace and additional heating is not needed. Figure 7.1 and S350 (With Covers On) 1. Remove the controller cover(s) by loosening the cover screws, accessible from the front of the control. Each controller block has 4 screws. Units with Model Digits 4-6 = 75 to 800 have one (1) Johnson Controls main control block. Units with Model Digits 4-6 = 840 to 960 have one (1) Johnson Controls main control block and one (1) S350 stage adder control block. 2. To set the controller (refer to Figures 7.1 and 7.2): a. Verify that the heating/cooling jumper blocks are in the HEATING position. b. Adjust the differential potentiometer DIFF to the desired number of degrees between relay energized and de-energized. This is typically set for 3 F. c. The Setpoint will be set once the cover is secured back on the controller. 3. To set the S350 stage adder (if equipped): a. Verify that the heating/cooling jumper blocks are in the HEATING position. b. Adjust the differential potentiometer DIFF to the desired number of degrees between relay energized and de-energized. This is typically set for 3 F. c. Adjust the Offset to the value determined in the preceding section (using either the Table Method or the Calculation Method). 4. Replace the cover(s) and fasten in place with the four screws on each cover. 5. Adjust the Setpoint dial on the front of the to the desired setting. Figure 7.2 and S350 (With Covers Off) DIFF S350 OFFSET S350 DIFF

8 INSTALLATION/SETUP Electronic Mild Temperature Thermostat Modine Manufacturing Company has a continuous product improvement program, and therefore reserves the right to change design and specifications without notice. Modine Manufacturing Company 1500 DeKoven Avenue Racine, Wisconsin, USA Phone: (HEAT) Modine Manufacturing Company

System 350 P352AB Electronic Pressure Control Series

System 350 P352AB Electronic Pressure Control Series System 350 P352AB Electronic Pressure Control Series System 350 Product Guide 930 Basic Controls Section Product/Technical Bulletin P352AB Issue Date 0200 The P352AB controls are On/Off electronic pressure

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481038 Model PVF(-H) and PVG Indirect Gas-Fired Heat Modules Indirect Gas-Fired Furnaces Installation, Operation and Maintenance Manual Please read and save these instructions for future reference.

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481038 Model PVF and PVG Indirect Gas-Fired Heat Modules Indirect Gas-Fired Furnaces Installation, Operation and Maintenance Manual Please read and save these instructions for future reference.

More information

ECONOMIZERS. 5/2012 Supersedes

ECONOMIZERS. 5/2012 Supersedes Litho U.S.A. 2012 ECONOMIZERS 507031 01 5/2012 Supersedes 506747 01 K1ECON ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS AND OUTDOOR AIR HOODS USED WITH KG/KC/KH 024, 030, 036, 048, 060, 072, 090

More information

R81EAA-2 Economizer Circuit Board

R81EAA-2 Economizer Circuit Board FAN 121, 628.1 Motor Actuators Section M Technical Bulletin R81E Issue Date 0993 R81EAA-2 Economizer Circuit Board Applications Setpoint Adjustment Temp T1 T2 S2 1O S 1 8 9 Changeover Relay Refrigeration

More information

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev.

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev. Installation Guide DigiTract 4 Two Stage Heat/Cool Comfort Control System Part #DT4MAN Rev. October 2013 Zoning Systems That s all we do. TABLE OF CONTENTS...Page INTRODUCTION...1 SYSTEM DESCRIPTION...1

More information

Installation Instructions

Installation Instructions CRPWREXH068A00 CRPWREXH069A00 CRPWREXH070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 15 to 25 TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION...

More information

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT Supersedes Form145.10-IOM1 (810) Form 145.10-IOM1 (910) LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS IMPORTANT!

More information

Installation Instructions

Installation Instructions H068A00 H069A00 H070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 12.5to25TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION... 2 Power Exhaust

More information

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited. SERVICE MANUAL ELECTRIC BRAISING PANS (30 & 40 GALLON) VE30 VE40 ML-126849 ML-126850 VE40 SHOWN - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used

More information

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures A419 Issue Date February 10, 2003 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures The A419 series controls are single-stage, electronic temperature

More information

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012 COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES 506953-01 3/2014 Supersedes 8/2012 Litho U.S.A. MSAV Supply Air Blower VFD Kit INSTALLATION INSTRUCTIONS FOR MSAV (MULTI-STAGE AIR VOLUME) SUPPLY AIR BLOWER

More information

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone. INSTALLATION & OPERATION MANUAL Fan Powered Terminals VAV TERMINALS IOM FAN POWERED TERMINALS Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is

More information

ECONOMIZERS. 1/2012 Supersedes

ECONOMIZERS. 1/2012 Supersedes ECONOMIZERS Litho U.S.A. 2012 506948 01 1/2012 Supersedes 506394 01 K1ECON20C 1 ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZER AND OUTDOOR AIR (604592 03; 54W77) USED WITH KG/KC/KH 180 300S UNITS

More information

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas Installation Manual IOM-MBC-00 08-30-04 Mixing Box Control Systems Installation,, and Maintenance Manual Contents Page Introduction...1 General...1 Safety...1 Inspection...1 Mixing Box Control Systems...2

More information

System 350 S350C Temperature Slave Stage Module

System 350 S350C Temperature Slave Stage Module FANs 930, 930.5, 125, 121 Product/Technical Bulletin Issue Date April 8, 2014 System 350 Temperature Slave Stage Module The Temperature Slave Stage Module is used in conjunction with the A350 Temperature

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

Addendum. Remote Air-Cooled Condenser

Addendum. Remote Air-Cooled Condenser Addendum Remote Air-Cooled Condenser Contents Overview... 1 Save these instructions........................... 1 Safety symbols that may be used in this manual........... 1 Cross-reference symbols used

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS TEC20 TEC20H ELECTRONIC CONTROLLER BARD MANUFACTURING COMPANY Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-306D Supersedes: 2100-306C File: Volume

More information

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control SP-32, SP-32D SP-33, SP-33D SP-34, SP-34D Single Stage Temperature Control Description The SP-3x and SP-3xD series of controls are single stage, general purpose, temperature controls with wide application

More information

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev.

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev. Installation Guide DigiTract Two Stage Heat/Cool Comfort Control System Part #DTMAN Rev. February 008 Zoning Systems That s all we do. TABLE OF CONTENTS...Page INTRODUCTION... SYSTEM DESCRIPTION... COMPONENT

More information

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS SLC-811X Series TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com Single Loop Proportional Temperature Controller General Instructions APPLICATION Electronic temperature controller

More information

TC-200 Series. Application. Features. Applicable Literature. Single Bulb Thermostats General Instructions

TC-200 Series. Application. Features. Applicable Literature. Single Bulb Thermostats General Instructions T-200 Series Single ulb Thermostats General Instructions Application These units are used for on-off control of media temperature in ducts, tanks, etc. Features Mechanism enclosed in rugged die cast case

More information

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

EconoMi$er, Power Exhaust, and Sensor Installation Instructions

EconoMi$er, Power Exhaust, and Sensor Installation Instructions Small Rooftop Units Gas Heating/Electric Cooling, Electric Cooling, and Heat Pump Units 3 to.5 Tons (50/60 Hz) EconoMi$er Package for Vertical and Horizontal Duct Systems Issue Date /0/0 EconoMi$er, Power

More information

CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. OUTDOOR AIR S Litho U.S.A. 507214-01 2014 12/2014 Supersedes 9/2013 OUTDOOR AIR S INSTALLATION INSTRUCTIONS FOR OUTDOOR AIR S AND OUTDOOR AIR USED WITH 156-300S UNITS Shipping and Packing List Package

More information

Installation Instructions

Installation Instructions 08A0, 09A0, 08A00, 08A00 For Use With Horizontal EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY HORIZONTAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS

More information

Package Unit Modulating Economizer Installation Instructions

Package Unit Modulating Economizer Installation Instructions Package Unit Modulating Economizer Installation Instructions Downflow Unit Warning: Recognize this symbol as an indication of Important Safety Information! Read all instructions prior to installation.

More information

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators Installation Sheets Manual 121 Relays and Contactors Section R Technical Bulletin R81EAA Application R81 plug-in electronic

More information

Installation Instructions

Installation Instructions CRPWREXH08A0, CRPWREXH09A0, CRPWREXH08A00, CRPWREXH08A00 For Use With Horizontal EconoMi$er IV, EconoMi$er, or EconoMi$er X (W70) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... PACKAGE

More information

Package Unit Modulating Economizer Installation Instructions

Package Unit Modulating Economizer Installation Instructions Package Unit Modulating Economizer Installation Instructions Downflow Unit Warning: Recognize this symbol as an indication of Important Safety Information! Read all instructions prior to installation.

More information

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide 32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 458295 Automatic Fire Damper Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

GE Sensing & Inspection Technologies

GE Sensing & Inspection Technologies GE Sensing & Inspection Technologies Modus Model RPM-1 Room Pressure Monitor Installation and Setup Guide 1. GENERAL The RPM-1 monitors either positive or negative room pressures (see the Datasheet for

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

A25 Series Warm Air Control with Manual Reset

A25 Series Warm Air Control with Manual Reset FANs 125, 121 Product/Technical Bulletin A25 Issue Date 0316 A25 Series Warm Air Control with Manual Reset The A25 Series Warm Air Control with Manual Reset is designed to shut down fans, burners, dampers,

More information

PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR

PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR VPC-AA The VPC-AA Parking Lot Controller is an easily installed device designed for mid-sized parking lot installations. The weather proof design is ideal

More information

WATER COOLED AIR CONDITIONING UNITS MODEL CVWSEK-060 WATER SIDE ECONOMIZER FOR CSV060B VERTICAL R-410A STYLE B R-410A

WATER COOLED AIR CONDITIONING UNITS MODEL CVWSEK-060 WATER SIDE ECONOMIZER FOR CSV060B VERTICAL R-410A STYLE B R-410A WATER COOLED AIR CONDITIONING UNITS INSTALLATION, OPERATION, & MAINTENANCE SUPERSEDES 145.15-IOM1 (612) Form 145.15-IOM1 (514) MODEL CVWSEK-060 WATER SIDE ECONOMIZER FOR CSV060B VERTICAL R-410A STYLE B

More information

TK-6024, TK-6124, TK-8024, TK-8124

TK-6024, TK-6124, TK-8024, TK-8124 TK-6024, TK-6124, TK-8024, TK-8124 Pneumatic Bulb Thermostats General Instructions APPLICATION For proportional temperature control of pneumatic valves and actuators to maintain air or liquid temperatures

More information

G600 Series Replacement Intermittent Pilot Ignition Controls

G600 Series Replacement Intermittent Pilot Ignition Controls Installation Instructions G600 Issue Date 0601 G600 Series ment Intermittent Pilot Ignition Controls Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

Q35 Series Automatic Vent Damper System

Q35 Series Automatic Vent Damper System Installation Sheets Manual 121 Energy Conservation and Miscellaneous Kits Section Q Technical Bulletin Q35 Issue Date 0999 Q35 Series Automatic Vent Damper System Figure 1: Q35 Automatic Vent Damper System

More information

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician: START-UP INSTRUCTION OPTIMUM 36000 To 72000 BTU S PACKAGE UNITS 3 To 6 Ton START-UP CHECKLIST Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

More information

SetPoint 501 and 501s Controllers Installation and Operation Manual

SetPoint 501 and 501s Controllers Installation and Operation Manual SetPoint 501 and 501s Controllers and Operation Manual SetPoint 501s SetPoint 501 Setpoint 501 and 501s Controllers and Operation Manual is published by Uponor Wirsbo, Inc. 5925 148th Street West Apple

More information

BLOWER VACUUM SWITCH FAILED OPEN

BLOWER VACUUM SWITCH FAILED OPEN F1 F1 AC BLOWER VACUUM SWITCH FAILED CLOSED AC BLOWER VACUUM SWITCH FAILED CLOSED UHS If the blower vacuum switch is closed before blower start-up, the control module will not start the blower. Pre-check

More information

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician: START-UP INSTRUCTION START-UP CHECKLIST SERIES 5 36000 To 72000 BTU S PACKAGE UNITS 3 To 6 Ton Date: _ Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up

More information

Installation Instructions

Installation Instructions 00A0, 0A0-0A0 080A00 08A00 For Use With Vertical EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY VERTICAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS TO5TON

More information

A11 Series Low Temperature Cutout Control

A11 Series Low Temperature Cutout Control A11 Series Low Temperature Cutout Control Installation Instructions Part No. 997-358, Rev. F Issued March 2016 Applications IMPORTANT: All Series A11 temperature controls are designed for use only as operating

More information

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators Installation D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators IMPORTANT: The D- Series actuators are intended to control equipment under normal operating conditions. Where failure

More information

G76x Direct Spark Ignition Controls

G76x Direct Spark Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G76x Issue Date 0400 G76x Direct Spark Ignition Controls Figure 1: G76x Direct Spark Ignition

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS MiniCOREVentilator ENERGY RECOVERY CORE INSTALLATION INSTRUCTIONS MC500-1ERV JANUARY 10, 2018 SUPERSEDES: NONE INSTALLATION INSTRUCTIONS FOR MINICORE VENTILATOR (MCV) WITH FACTORY INSTALLED OPTIONS USED

More information

80 PLUS A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES

80 PLUS A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES FORM NO. G66-478 REV. 5 Supersedes Form No. G66-478 Rev. 4 80PJ SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] 80 PLUS A.F.U.E. UPF/HORIZONTAL GAS FURNACES Features The WeatherKing

More information

General Description. Product Specification. Document Digital Temperature Interlock

General Description. Product Specification. Document Digital Temperature Interlock Document 474751 Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the

More information

LF24-ECON-R03(-R10) US Operation, Installation and Wiring

LF24-ECON-R03(-R10) US Operation, Installation and Wiring LF24-ECON-R03(-R0) US Operation, Installation and Wiring Operation LF24-ECON-R03(-R0) US The LF24-ECON-R03(-R0) US provides a direct coupling solution for RoofTop Unit(RTU) economizer dampers. Control

More information

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Engineering Bulletin IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Issued By: Clarksville Marketing and Sales Support Order No. UN-PRB001-EN

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8120A & 8126A Digital Ventilation Controller Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Safety Instructions... 3 Specifications... 4 Overview... 4 Mounting

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2005 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CB29M & CB30M Elite Series Units MULTI POSITION BLOWER COILS 504,79M 09/05 Supersedes 04/05 Litho U.S.A. RETAIN THESE INSTRUCTIONS

More information

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual The IAQ50 Air Damper/Monitor Installation and Maintenance Manual RUSKIN MANUFACTURING 3900 Dr. Greaves Road Kansas City, Missouri 64030-1183 U.S.A. ! WARNING DO NOT TAMPER WITH (REMOVE, REPLACE, RELOCATE

More information

E Series CE Approved Intermittent Pilot Ignition Control

E Series CE Approved Intermittent Pilot Ignition Control Installation Instructions Issue Date January 11, 2013 E Series CE Approved Intermittent Pilot Ignition Control Application The E Series CE Approved Intermittent Pilot Ignition Control is a safety control

More information

Remote Temperature Controllers. Quick Selection Guide

Remote Temperature Controllers. Quick Selection Guide Remote Temperature Controllers Quick Selection Guide A Complete Selection For A Wide Range Of Applications Electronic Standalone Controllers T775 Provide on/off, modulating, or reset control in applications

More information

Warm. DFC Direct Fired Gas Heating System. Applied Air. Keeps You. Technical Guide for: Outdoor Mounted Units To 100,000 CFM And 14M BTUH

Warm. DFC Direct Fired Gas Heating System. Applied Air. Keeps You. Technical Guide for: Outdoor Mounted Units To 100,000 CFM And 14M BTUH TGDFC-6 DFC Direct Fired Gas Heating System Technical Guide for: Outdoor Mounted Units To 0,000 CFM And 14M BTUH Applied Air Keeps You Warm Featuring the Patented AdaptAire controlled Circulation System

More information

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1 Series Bulk Flow Monitor Specifications - Installation and Operating Instructions Bulletin FL-1-4x 3/4 CONDUIT KNOCKOUTS BFS 1A FUSE RED LED RELAY 5-9/64 [130.45] TRANSFORMER 3[76.20] GREEN LED 7 [177.80]

More information

Modulating Furnace Information. Warning on Meter Setting - Read First!

Modulating Furnace Information. Warning on Meter Setting - Read First! Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS MANUAL TRANSFER SWITCHES FROM 0 Residential Wattage Requirements Appliance Running Watts Add watts for starting Furnace blower, gas or fuel 1/8 hp 300 500 1/8 hp

More information

Installation Instructions

Installation Instructions 010A00 011A00 014A00 SMALL ROOFTOP UNITS TWO POSITION OUTDOOR AIR DAMPER 2to15TONS (50/60 Hz) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS...

More information

Table of Contents GF801U Series

Table of Contents GF801U Series FORM NO. GSC-520 GF801U SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] 80% A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES The Sure Comfort line of upflow/horizontal gas furnaces are designed

More information

Installation Instructions

Installation Instructions Outdoor plit Flow Center Kit FCP11BDO (1 pump) FCP21BDO (2 pumps) For plit Geothermal Heat Pump models GZ & H Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

Model 8144NC Fresh Air Ventilator

Model 8144NC Fresh Air Ventilator Model 8144NC Fresh Air Ventilator Installation and Operating Instructions MOUNTING BRACKETS WIRE ENTRY LOCATION INTEGRAL PRESSURE PORTS (PORT ON INLET SIDE NOT SHOWN) OVAL OUTLET COLLAR FOR 6" DIAMETER

More information

Motor. Document # Vari-Green Motor and Controls. Table of Contents. Features, Operation, Wiring and Troubleshooting

Motor. Document # Vari-Green Motor and Controls. Table of Contents. Features, Operation, Wiring and Troubleshooting Document #473681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Document 483514 SMOKE DAMPERS SMD-XXX and SMDR-XXX Series Leakage Rated Smoke Dampers Vertical and Horizontal Mount Please read and save these instructions

More information

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S P R O D U C T S P E C I F I C AT I O N S A I R H A N D L E R S CB6UH-R MERIT Series R- - Upflow / Horizontal Bulletin No. 1067 April 01 Supersedes January 01 Nominal Capacity - 1.5 to 5 Tons Optional Electric

More information

General Information... 2

General Information... 2 VAV Flow Controller-Actuators CSP 5001/5002 Applications Guide General Information... 2 CSP 5001/5002 Overview...2 Controller, Sensor, and Thermostat Functions...3 Wiring...4 Air Flow Sensor Connection...4

More information

IMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS

IMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS DIFFERENTIAL TEMPERATURE CONTROLLERS MAIN FEATURES - Microprocessor programed specifically for optimal performance of WARM AIR systems - Large easy-to-read 40 character (x0) backlit LCD display showing

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR011A00 & CPECOMZR012A00 Installation Instructions Read these instructions completely before attempting to install the Horizontal Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for (NPECOMZR006A00) ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR010A00 Read these instructions completely before attempting to install the Vertical Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2 ACCESSORIES LIST...2 INSTALLATION...2-6

More information

Electric. PN April Series Electric Oven

Electric. PN April Series Electric Oven Electric PN April 2013 Series Electric Oven E NOTICE: This Owner s Operating and Installation Manual should be given to the user. The operator of the oven should be familiar with the operation of the oven.

More information

Installation Instructions

Installation Instructions Part Number: CPECOMZR008A00 & CPECOMZR009A00 Installation Instructions Read these instructions completely before attempting to install the Vertical Accessory. CONTENTS SAFETY CONSIDERATIONS...1 GENERAL...1,2

More information

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

Blank-off. HVAC unit screws. Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for NPECOMZR00A00 ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Corp L3 Revised CB17/CBH17 SERIES UNITS SPECIFICATIONS CB17-95V CBH17-95V

Corp L3 Revised CB17/CBH17 SERIES UNITS SPECIFICATIONS CB17-95V CBH17-95V Service Literature Corp. 0002 L3 Revised 08 2004 CB17/CBH17 SERIES UNITS CB17 Lennox CB17 and CBH17 model blower coil units, designed for indoor applications only, are available in two models; CB17 series

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw MicroMetl INSTALLATION INSTRUCTIONS for 0637-0311 (CPECOMZR006A00) MicroMetl's 0637 economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions

More information

80 PLUS A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES

80 PLUS A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES FORM NO. G66-478 REV. 1 Supersedes Form No. G66-478 Rev. 0 80 PLUS A.F.U.E. UPF/HORIZONTAL GAS FURNACES Features The WeatherKing line of upflow/horizontal gas furnaces are designed for utility rooms, closets,

More information

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600 MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard C**H Series 2 & 2½ Ton 2-Stage Wall Mount Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard C**H Series 2 & 2½ Ton 2-Stage Wall Mount Heat Pumps INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-3 For Use with Bard C**H Series 2 & 2½ Ton 2-Stage Wall Mount Heat Pumps NOTE: CHCRV-3 Models must be installed with TCURB

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS INSTALLATION OPERATION & MAINTENANCE New Release Form 130.13-NOM4 (908) In conjunction with the use of these instructions, obtain and refer to the construction,

More information

Technical Manual. DLM Module. This manual should remain with the unit.

Technical Manual. DLM Module. This manual should remain with the unit. Technical Manual DLM Module This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this

More information

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ZIP Economizer Fault Detection and Diagnostics (FDD) Table Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns

More information

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it. RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

Installation, Operation and Maintenance Instructions. ERV1500e ERV2000e ERV3000e

Installation, Operation and Maintenance Instructions. ERV1500e ERV2000e ERV3000e Installation, Operation and Maintenance Instructions ERV500e ERV000e ERV000e ERV000e ERV500e ERV000e Table of Contents Safety Considerations..................................................................

More information

M9216 Series Electric Spring Return Actuators

M9216 Series Electric Spring Return Actuators *34636461G* 34-636-461, Rev. J Installation Instructions M9216 Issue Date October 217 M9216 Series Electric Spring Return Actuators Installation IMPORTANT: The M9216 Series actuator is intended to control

More information

T500 Series. Applications. Features. Applicable Literature. Non-Digital, On/Off Thermostat General Instructions

T500 Series. Applications. Features. Applicable Literature. Non-Digital, On/Off Thermostat General Instructions T500 Series Non-Digital, On/Off Thermostat General Instructions Applications The T500 series thermostats are available in four basic models for low and line voltage control of valves, relays, and fan motors

More information

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350R Electronic Temperature Reset Control (with Relay) FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date April 8, 2014 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is

More information

WATER-COOLED SELF-CONTAINED UNITS MODEL CVWSEK-060BK/DP WATERSIDE ECONOMIZER FOR CSV060B LEFT-HAND VERTICAL R-410A STYLE B

WATER-COOLED SELF-CONTAINED UNITS MODEL CVWSEK-060BK/DP WATERSIDE ECONOMIZER FOR CSV060B LEFT-HAND VERTICAL R-410A STYLE B WATER-COOLED SELF-CONTAINED UNITS INSTALLATION, OPERATION, & MAINTENANCE Supersedes: 145.15-IOM1 (514) Form 145.15-IOM1 (817) MODEL CVWSEK-060BK/DP WATERSIDE ECONOMIZER FOR CSV060B LEFT-HAND VERTICAL R-410A

More information

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR 24 Volt AC input Built in 15 second low fire start timer 0-24 Volt DC modulating output Remote temperature selection Calibration trim pot Rated for -40 F (-40 C) DFC-1 STANDARD TEMPERATURE CONTROL DFC-2

More information

Installation Instructions

Installation Instructions KALA0601AAA KALA0701AAA MotorMasterR Low Ambient Controller for Residential plit ystem Applications Installation Instructions Fig. 1 - MotorMasterr Low Ambient Controller A93157 NOTE: Read the entire instruction

More information

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS BY JOHNSON CONTROLS INSTALLATION OPERATION & MAINTENANCE MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS New Release Form ET130.13-NOM4 (908) In conjunction with the use of these instructions, obtain

More information