section-page Table 1. Transfer switching device ratings. Conditional short circuit current

Size: px
Start display at page:

Download "section-page Table 1. Transfer switching device ratings. Conditional short circuit current"

Transcription

1 Operator s Manual 7000 Series ATS Automatic Transfer Switching Equipment D design 30 through 200 amperes TABLE OF CONTENTS section-page INSTALLATION Enclosures and Mounting Power Connections Engine Starting Contacts Functional Test , 1-4, 1 5 TESTING & SERVICE Preventive Maintenance Transfer Test Disconnecting the Controller Manual Load Transfer Trouble-Shooting INDEX... back cover An experienced licensed electrician should install the ATSE. Note: Refer to the outline and wiring drawings provided with your 7000 Series ATS for all installation and connection details and accessories. Note: Refer to Group 5 Controller User s Guide for status display messages, time delays, pickup and dropout settings, and adjustments. Nameplate / rating Label The 7000 Series Automatic Transfer Switching Equipment (ATSE) contains a nameplate / rating label which includes data for that specific ATSE. It defines the loads and fault circuit withstand/closing ratings. Refer to the labels on the Transfer Switching device for specific values and use the ATSE only within their limits. See Table 1 below. Do not exceed the values on the nameplate/ rating label. Exceeding the rating can cause personal injury or serious equipment damage. Used in this manual to warn of risk of electrical shock from high voltages capable of causing shock, burns, or death. Used in this manual to warn of possible personal injury. Automatic Transfer Switching Equipment IEC Class PC Cat No D7ATS3100J5X Ser No Ue 400 V 50 Hz AC 33A Ie 100 A 7000 Series Used in this manual to warn of possible equipment damage. Notes: Switching overvoltage not declared. The controller meets Class A limits; suitable for establishments other than domestic. Table 1. Transfer switching device ratings. Rated size in amperes 30, 70, 100, 150, 200* Rated short circuit making capacity I cm Rated short time withstand current I cw Conditional short circuit current 5000 A Short circuit protective device circuit breaker permitting I 2 tmax 4,1 x 10 5 ;I p max 7580 A Minimum clearance live metal to ground 13 mm * 200 ampere is limited to 240 volts. ASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey USA

2 SECTION 1 The ASCO Series 7000 Automatic Transfer Switching Equipment (ATS) consists of a transfer switching device, monitoring and transfer control device (controller), and controls (for door mounting). Installation requires mounting the devices into an appropriate size enclosure (Table 1 1) and connection of power conductors, engine start signal wires, and auxiliary circuits. Enclosures The Outline and Mounting Diagram furnished with the ATS shows all mounting details and instructions. Table 1 1 shows the minimum enclosure sizes required for 7000 Series ATS (suitable for IP 65 enclosures). Table 1-1. Minimum enclosure sizes required. Height (mm) Width (mm) Depth (mm) To prevent overheating and damage use a suitable enclosure with dimensions equaltoorlargerthanthese. To prevent malfunction or shortened life for the transfer switching device protect it from construction grit and metal chips. Mounting Refer to the Outline and Mounting Diagram provided with the ATS; it shows all mounting details and instructions. Mount the transfer switching device vertically in the back of the enclosure as shown on the Outline and Mounting Diagram. Level all mounting points by using flat washers behind the holes to avoid distortion of the transfer switching device. Mount the controller and the control / indicator plate on the inside of the enclosure door as shown on the Outline and Mounting Diagram. Their display, membrane controls, switches, and indicators must be accessible through cutouts in the door. An add-on DIN rail is provided for some optional accessories; it should be mounted below controller on the inside of the door. INSTALLATION Grounding Grounding (earthing) is accomplished by mounting the automatic transfer switching equipment in a metal enclosure. The controller s lower left mounting hole must be connected to equipment (enclosure or clean earth) ground via the door stud (with paint removed). Because the controller is mounted on a door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges. See Figure plugs for transfer switching device harness connect ground to lower left mounting hole Figure 1-1. Controller grounding (clean earth) and harness connections. The controller must be grounded forproperoperation. Testing Power Conductors Do not connect the power conductors to the transfer switching device until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of conductors can damage insulation and stretch or break the conductor s strands. For this reason, after the conductors are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation. De energize the conductors before making any power or auxiliary circuitry connections. Place engine generator starting control intheoffposition.makesureengine generator is not in operation. Be sure that Normal and Emergency power connections are in proper phase rotation. 1--1

3 INSTALLATION Table 1-2. Transfer switching device terminals for power conductors (use stranded type conductors). Transfer Switching Device Rating (amps) 30, 70, 100, 150, 200* Maximum Number of Conductors per Terminal Range of Al Cu Conductor Sizes ISO Cross Section (mm 2 ) 1--2 Recommended Tightening Torque 2,5 to 6 11,3 Nm one 10 to 95 use Cu only for 200 amperes 22,6 Nm *200 ampere is limited to 240 volts. Use copper conductors only for 200 amperes. Power connections A Wiring Diagram is furnished with the ASCO 7000 Series ATS. All wiring must be made in accordance with the local codes. Table 1 2 shows the range of conductor sizes and the number of conductors accepted by the transfer switching device terminals and the corresponding tightening torque recommended. Do not run cables in front of the transfer switching device. Conductors can be bundled on the right side of the transfer switching device. Maintain proper electrical clearance between the live metal parts and grounded metal: 13 mm minimum. It is not necessary to remove the barriers from the transfer switching device to install the conductors. If you do remove them, however, be sure to reinstall the barriers carefully. Connect main source and load conductors to clearly marked power terminals on the transfer switching device. Be careful when stripping insulation from the conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the terminals to the torque specified in Table 1 2. Three conductor spacers are included with 100 ampere transfer switching devices. When installing power conductors, run them through the conductor spacers as shown in Figure 1 2. Position the spacers within 38 mm of the power terminals. Three conductor spacers must be located as shown for 100, 150, & 200 amp transfer switching devices. conductor spacers 38 mm approximate conductor spacer Figure 1-2. Required conductor spacers for 100, 150, & 200 amp transfer switching devices. Engine Starting Contacts The engine control contact connections (if used) are located on the transfer switchingdevice. Connect signal wires to appropriate terminals as specified in Table 1 3 and shown in Figure 1 3. Table 1-3. Engine start connections When normal source fails contact closes contact opens ENGINE STARTING CONTACTS ( SHOWN DE ENERGIZED ) TOP STUD MIDDLE STUD BOTTOM STUD TS NR NR Terminals on transfer switching device TB1 and TB2 TB1 and TB3 TB 1 TB 3 TB 2 Figure 1-3. Engine starting contact label and location on left side of transfer switching device. Interconnecting harness Connect the plug in harness (two plugs) from the transfer switching device to left side of the controller, if not already connected. Auxiliary Circuits Connect auxiliary circuit wires (if necessary) to appropriate terminals by referring to the Wiring Diagram.

4 Functional Test INSTALLATION Position of the transfer switch is indicated here The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation. Do these checks in the order presented to avoid damaging the ATS. Read all instructions on the Wiring Diagrams and labels affixed to the ATS. Note the control features that are provided and review their operation before proceeding. weight marked N (normal) and E (emergency) maintenance handle 1 Manual Operation A detachable manual operator handle is provided on the Transfer Switching device for maintenance purposes only. Manual operation of the transfer switching device must be checked before it is operated electrically. Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers. 1. After deenergizing both power sources, open the enclosure door. Locate and the maintenance handle on the left side of the transfer switching device. See Figure Grasp the attached maintenance handle and turn it with thumb and fingers as shown to manually operate it. The maintenance handle turns the opposite direction of the weight. Turn it up or down as shown to manually operate the transfer switching device. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris. floating weight weight With ALL POWER OFF grasp maintenance handle and turn it quickly with your thumb and fingers. Figure 1-4. Maintenance handle and positions. 3. Return the transfer switching device to the N (normal) position. Now continue to 2 VoltageCheckson next page. 1--3

5 INSTALLATION Automatic Transfer Switch Transfer Switch Connected To Normal Transfer Switch Connected To Emergency Retransfer Delay Bypass Transfer Control Transfer Test HOLD FOR ( 15 SECONDS ) GREEN RED observe these lights Normal Source Accepted Emergency Source Accepted GREEN RED Figure 1-5. Standard controls and indicators. 2 VoltageChecks First check the nameplate on the transfer switching device; the rated voltage must be the same as the normal and emergency power voltages. Verify that the conductors have been correctly connected to the power terminals. Useextremecautionwhenusingameterto measure voltages. Do not touch power terminals; shock, burns, or death could result Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1 5. Black square means the light is on. Whitesquaremeansthelightisoff Close the normal source circuit breaker. The Transfer Switch Connected To Normal and the Normal Source Accepted lights should come on. Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switching device normal source terminals. Close the emergency source circuit breaker. (Start generator, if necessary.) The Transfer Switch Connected To Normal & Emergency Source Accepted lights should come on. Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switching device emergency source terminals.* * If necessary, adjust the voltage regulator on the generator according to the manufacturer s recommendations. The Automatic Transfer Switching Equipment willrespondonlytotheratedvoltagespecifiedonthe transfer switching device nameplate. Now continue to 3 Electrical Operation on next page. 5 6 Useaphaserotationmeter to check phase rotation of emergency source; it must be the same as the normal source. Shut down the engine generator, if applicable. The Emergency Source Accepted light should go off. Then put the starting control selector switch (on the generator set) in the automatic position. Close enclosure door. U V W 1--4

6 INSTALLATION Automatic Transfer Switch Transfer Switch Connected To Normal Transfer Switch Connected To Emergency Retransfer Delay Bypass Transfer Control Transfer Test HOLD FOR ( 15 SECONDS ) GREEN RED operate this switch observe these lights Normal Source Accepted Emergency Source Accepted GREEN RED Figure 1-6 Standard controls and indicators. 3 Electrical Operation This procedure will check the electrical operation of the Automatic Transfer Switching Equipment. See Figure 1 6. Close the enclosure door first. Transfer Test Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure. Perform steps 1 through 4 at the right. Observe the status lights. Black square means the light is on. Whitesquaremeansthelightisoff. NOTE: If the inphase monitor feature is enabled, then transfer may not occur immediately after the respective time delays. Transfer will only occur when the phase relationship between sources is correct. NOTE: The operating transfer time of the transfer switching device is 0,17 second maximum, which is measured from the time that power is applied to the operating coil of the transfer switching device until the main contacts close on the alternate source. This completes the Functional Test of the ATS The Transfer Switch Connected To Normal and Normal Source Accepted lights should be on. Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs (within 15 sec.). Emergency Source Accepted light should come on. Transfer switching device will operate to the Emergency position after Feature 2B time delay. The Transfer Switch Connected To Emergency light should come on and Load Connected to Normal light goes off. Transfer switching device will operate back to Normal position after Feature 3A time delay. For immediate retransfer turn Transfer Control counterclockwise to Retransfer Delay Bypass. The Transfer Switch Connected To Normal light should come on; Transfer Switch Connected to Emergency light should go off. The engine generator will stop after the Feature 2E time delay (unloaded running engine cooldown). The Emergency Source Accepted light should go off. 1--5

7 SECTION 2 TESTING & SERVICE TRANSFER TEST Operate the 7000 Series ATS at least once a month by following the five step Electrical Operation Transfer Test procedure on page 1 5. PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will ensure high reliability and long life for the 7000 Series ATS. An annual preventive maintenance program is recommended. Deenergize both Normal and Emergency power sources before performing inspections Checklist for Yearly Inspection Hazardous voltage capable of causing shock, burns, or death is used in this equipment. Deenergize both Normal & Emergency power sources before performing inspections j Clean the ATSE enclosure. Brush and vacuum away any excessive dust accumulation. Remove anymoisturewithacleancloth. j Check the transfer switching device contacts. Remove transfer switching device barriers and check the condition of the contacts. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully. j Maintain transfer switching device lubrica tion. If the equipment is subjected to severe dust or abnormal operating conditions, renew factory lubrication on all movements and linkages. Relubricate the solenoid operator if a coil is replaced. Do not use oil. Order lubrication (Castrol EndurexR 4000 lubricant). j Check all conductor connections & retighten them. REPLACEMENT PARTS Replacement parts are available. When ordering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switching device nameplate. Contact your local ASCO Power Technologies sales office. DISCONNECTING THE CONTROLLER The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps: Disconnecting the Plugs Do not unplug the controller until steps 1a or 1b is completed. 1. Observe the position of the transfer switching device. a. If the transfer switching device is in the Normal position, place the standby engine starting control in the off position. Then open the emergency source circuit breaker. b. If the transfer switching device is in the Emergency position, open the normal source circuit breaker. Place the engine starting control in the test or run position. 2. Separate the two quick disconnect plugs by squeezing the latches. Do not pull on the harness wires. Reconnecting the Plugs Do not reconnect the controller until steps 1 and 2 are completed. 1. Observe the position of the transfer switching device. a. If the transfer switching device is in the Normal position, be sure that the standby engine starting control is still in the off position. The emergency source circuit breaker still should be open. b. If the transfer switching device is in the Emergency position, normal source circuit breaker still should be open. 2. The two harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until both latches click. 3. Restore the opposite source as follows: a. If the transfer switching device is in the Normal position, place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker. b. If the transfer switching device is in the Emergency position, close the normal source circuit breaker. 2--1

8 TESTING & SERVICE MANUAL LOAD TRANSFER This procedure will manually transfer the load if the controller is disconnected. Do not manually operate the transfer switching device until both power sources are disconnected (all conductors deenergized). 1. Deenergize both the normal and emergency source conductors (remove fuses or open circuit breakers). 2. Use the maintenance handle to manually operate transfer switch to the opposite source. Then remove the handle. See Manual Operation on page If the transfer switching device is in the Emergency position manually start the engine generator and then install emergency source fuse or close the circuit breaker. TROUBLE-SHOOTING Note any optional accessories that may be furnished on the ATS and review their operation. Refer to any separate drawings and/or instructions that may be packed with the ATS. Hazardous voltage capable of causing shock, burns, or death is used in this switch. Do not touch the power or load terminals of the transfer switching device PROBLEM Engine generator set does not start when the Transfer Control is turned and held in the Transfer Test position or when normal source fails. The transfer switching device does not transfer the load to the emergency source after the engine generator set starts. The transfer switching device does not transfer the load to the normal source when normal returns or when the Transfer Control is released. Gen. does not stop after load retransfer to normal source. Table 2-1. Trouble-Shooting Checks. CHECK IN NUMERICAL SEQUENCE 1 OPERATION 2 GEN-SET 3 VOLTAGE Hold the Transfer Control in the Transfer Test position for 15 seconds, or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting. Wait for Feature 2B time delay to time out. Wait for Feature 3A time delay to time out. Wait for Feature 2E time delay to time out. Starting control must be in the automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts. Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (48Hzfora50Hzsystem.)* Starting control must be in the automatic position. * These are factory settings. Refer to Controller User s Guide. Voltmeter should read at least 90% of nominal phase to phase voltage between terminals U2 and W2 (or L2 andl6for2poleswitches)* Voltmeter should read at least 90% of nominal phase to phase voltage between terminalsv1andw1,w1and U1, and U1 and V1 (or L1 and L5 for 2 pole switches). If the problem is isolated to circuits on the controller or the transfer switching device, call your local ASCO Power Technologies sales office. Furnish the Serial No. and Catalog No. from the transfer switching device nameplate. 2--2

9 A auxiliary circuits, 1 2 B barriers, 1 2 C catalog number, inside cover CAUTION, cover cleaning, 2 1 conductor spacers, 1 2 caution, 1 2 terminals, 1 2 connections auxiliary circuits, 1 2 engine starting contacts, 1 2 power, 1 2 controller, cover, 1 1 disconnecting, 2 1 D DANGER, cover E electrical operation, 1 5 enclosures, minimum size, 1 1 engine starting contacts, 1 2 F frequency, generator, 2 2 functional test, 1 3, 1 4, 1 5 G grounding, 1 1 H harness, 1 2 disconnect plugs, 2 1 I INDEX inspection, 2 1 installation, 1 1 interconnecting harness, 1 2 L labels, engine start contacts, 1 2 rating, cover lights, 1 4, 1 5 load connected to emergency, 1 5, 2 1 load connected to normal, 1 4, 2 1 lubrication, 2 1 M maintenance, preventive, 2 1 minimum clearance, live metal to ground, cover, 1 2 minimum size enclosures, 1 1 manual load transfer, 2 2 warning, 2 2 manual operation, 1 3 illustration of, 1 3 warning, 1 3 N nameplate, cover O operation electrical, 1 5 manual, 1 3 illustration of, 1 3 warning, 1 3 sequence of, 2 1 optional accessories P parts, 2 1 phase rotation check, 1 5 power conductors terminals, 1 2 testing, 1 2 tightening torque, 1 2 power connections, 1 2 problem, 2 2 R rating label, cover ratings, cover replacement parts, 2 1 S settings short circuit conditional current, cover protective device, cover test, functional, 1 3, 1 4, 1 5 testing power conductors, 1 2 tightening torque power terminals, 1 2 time delays, 2 1 Transfer Control selector switch Retransfer Delay Bypass, 1 5 Transfer Test, 1 5 transfer test, 1 5 transfer to emergency, 1 5 transfer to normal, 1 5, 2 1 trouble shooting, 2 2 V voltage checks, 1 4 voltage, pickup and dropout settings W WARNING, cover Printed in U.S.A. E ASCO Power Technologies, L.P. 2002

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious

More information

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps Operator s Manual 7000 Series ATS Automatic Switches 600 through 1200 amps 600---1000 amp. size An experienced licensed electrician must install the ATS. DANGER is used in this manual to warn of high voltages

More information

Operator s Manual Series ATS Automatic Transfer Switches 30 through 4000 amp. Rating Label. Nameplate C TABLE OF CONTENTS

Operator s Manual Series ATS Automatic Transfer Switches 30 through 4000 amp. Rating Label. Nameplate C TABLE OF CONTENTS Operator s Manual 7000 Series ATS Automatic Switches 30 through 4000 amp. Note: Refer to the outline and wiring drawings provided with your 7000 Series ATS for all installation and connection details and

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series ATS Automatic Transfer Switches H design 600 through 1200 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches, 600 1200 amps 600---1000 amp. sizes An experienced licensed electrician must install the ADTS. DANGER is used in this manual to

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches 150 through 4000 amp. Note: Refer to the outline and wiring drawings provided with your 7000 Series ADTS for all installation and

More information

Installation Manual. E-design A Transfer Switches A

Installation Manual. E-design A Transfer Switches A ASCO 3ATS & 3NTS 3ATS & 3NTS E-design 260-400 A Transfer Switches DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury. is used in this

More information

www. ElectricalPartManuals. com Operator s Manual

www. ElectricalPartManuals. com Operator s Manual Operator s Manual TABLE OF CONTENTS section-page... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness... 1-2 Engine Starting Contacts... 1-2 Functional Test... 1-3, 1-4, 1-5, 1-6

More information

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label. Operator s Manual 7000 Series ACTS Automatic Closed Transition es 150 through 4000 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness...

More information

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label. Operator s Manual 7000 Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes TABLE OF CONTENTS Note: Refer to the outline and wiring drawings provided with your 7000 Series

More information

3ATS & 3NTS J-design 600 A 3ADTS & 3NDTS A Transfer Switches. Installation Manual. Installation A DANGER. Table of Contents WARNING

3ATS & 3NTS J-design 600 A 3ADTS & 3NDTS A Transfer Switches. Installation Manual. Installation A DANGER. Table of Contents WARNING ASCO 3ATS, 3ADTS, 3NTS, 3NDTS 3ATS & 3NTS J-design 600 A 3ADTS & 3NDTS 150-600 A Transfer Switches DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death

More information

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual Series 386 Electrically Operated Non Automatic Switches J design 600 amps DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death. WARNINGisusedinthismanualtowarn

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series ACTS Automatic Closed Transition Transfer Switches E design 150 400A, F design 600 800A, G design 1000 4000A, F design 3000 4000A, DANGER is used in this manual to warn of

More information

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators Owner s Manual Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators DANGER is used in this manual to warn of risk of electrical shock

More information

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO)

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO) Owner s Manual Series 165P Power Transfer Load Center 125 amps, 1 phase, 240 V ac, 12 or 20 load spaces for automatic 2 wire start generators DANGER is used in this manual to warn of risk of electrical

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series 7ATB Automatic Transfer & Bypass Isolation Switches G design 1000 through 4000 amp. sizes DAGR is used in this manual to warn of high voltages capable of causing shock, burns,

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series 7ADTB Automatic Delayed Transition Transfer & Bypass Isolation Switches G design 1000 through 4000 amp. sizes DAGR is used in this manual to warn of high voltages capable

More information

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches G design 1000 through 3000 amp. Rating Label B

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches G design 1000 through 3000 amp. Rating Label B Operator s Manual 7000 eries ATB Automatic Transfer & Bypass Isolation witches G design 1000 through 3000 amp. ote: Refer to the outline and wiring drawings provided with your 7000 eries ATB for all installation

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series 7ACTB Automatic Closed Transition Transfer & Bypass Isolation Switches G design 1000 through 4000 amp. sizes DAGR is used in this manual to warn of high voltages capable of

More information

Catalog Number Identification with Elements Explained

Catalog Number Identification with Elements Explained Installation Manual 920 Remote Control Switches 30 through 225 ampere sizes This Installation! Manual is for green nameplate ASCO 920s only. For black nameplate ASCO 920s refer to Owners Manual 2D4920

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual Series 300 Automatic Transfer Switches D design, 30 through 230 amp. sizes DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death. WARNINGisusedinthismanualto

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual Series 300 Automatic Transfer Switches E design, 260 and 400 amp. sizes DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death. WARNINGisusedinthismanualtowarn

More information

Accessory 44 Strip Heater. Automatic Transfer Switches. Wiring. Mounting H

Accessory 44 Strip Heater. Automatic Transfer Switches. Wiring. Mounting H Accessory 44 Strip Heater for Automatic Transfer Switches Accessory 44 Strip Heater is designed to keep humidity and/or temperature within the ATS enclosure at acceptable levels. This accessory consists

More information

Operator s Series 300 Generator Paralleling System

Operator s Series 300 Generator Paralleling System Operator s Series 300 Manual Generator Paralleling System +Before reading please note the following: DANGER is used in this manual to warn of a hazardous situation which, if not avoided, will result in

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters

More information

Transfer switch OTEC open or delayed transition

Transfer switch OTEC open or delayed transition Transfer switch OTEC open or delayed transition 40-1000 Amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets.

More information

Quick Start Guide TS 910

Quick Start Guide TS 910 Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible

More information

Transfer switch GTEC open or delayed transition

Transfer switch GTEC open or delayed transition Transfer switch GTEC open or delayed transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-338 /0 INSTALLATION INSTRUCTIONS Original Issue Date: /0 Model: Transfer Switches with Programmable Controllers Market: ATS Subject: Transformer Kits GM6369 (480 V) and GM6859 (600 V) Introduction A

More information

Transfer switch OHPC open or delayed transition

Transfer switch OHPC open or delayed transition Specification sheet Transfer switch OHPC open or delayed transition 125-800 Amp Description The Cummins Series OHPC PowerCommand automatic transfer switch monitors the primary power source, signals the

More information

Quick Start Guide TS 910 & TS 920

Quick Start Guide TS 910 & TS 920 Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R THE RELIANCE Fast/Tran IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by a qualified electrician thoroughly familiar with all

More information

Transfer switch OTEC and OTECSE open transition

Transfer switch OTEC and OTECSE open transition Specification sheet OTEC and OTECSE open transition 125-600 Amp Description OTEC transfer es are designed for operation and ing of electrical loads between primary power and standby generator sets. They

More information

Owner s Manual. For Automatic Transfer Switch. PowerPact Home Standby Generator MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

Owner s Manual. For Automatic Transfer Switch. PowerPact Home Standby Generator MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED: Owner s Manual For Automatic Transfer Switch PowerPact Home Standby Generator MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED: WWW.GENERAC.COM 1-888-GENERAC (1-888-436-3722) Para español, visita: http://www.generac.com/service-support/product-support-lookup

More information

Manual Transfer Switch

Manual Transfer Switch Manual Transfer Switch Instruction Manual 30 1200 Amp 2, 3 & 4 Pole Page 1 WARNING Before Installation READ THIS MANUAL carefully to learn how to properly install, operate and maintain this unit. Personal

More information

POWER SYSTEMS, INC. Owner s Manual. Integrated Load Center. 200 Amp, 600 Volts. This manual should remain with the unit.

POWER SYSTEMS, INC. Owner s Manual. Integrated Load Center. 200 Amp, 600 Volts. This manual should remain with the unit. POWER SYSTEMS, INC. Owner s Manual Integrated Load Center 200 Amp, 600 Volts This manual should remain with the unit. IMPORTANT SAFETY INSTRUCTIONS Read the following information carefully before attempting

More information

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE SENS part number: 101037 Document revision: A Engineering change number: 105073 Date: 1/13/2006 1840 Industrial Circle

More information

CHPC Transfer switch closed transition

CHPC Transfer switch closed transition Specification sheet CHPC Transfer switch closed transition 125-800 Amp Description The Cummins series CHPC PowerCommand automatic transfer switch monitors the primary power source, signals the generator

More information

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery

More information

OTPC-SE Service entrance transfer switch open transition

OTPC-SE Service entrance transfer switch open transition Specification sheet OTPC-SE Service entrance transfer switch open transition 40 1000 amp Description OTPC service entrance transfer switches are designed for operation and switching of electrical loads

More information

918 Remote Control Switches

918 Remote Control Switches 98 Remote Control Switches Remote Control Switches This service bulletin explains how to replace the coil, control circuit board, miniature switch, and the contact block(s) in ASCO 98 remote control switches.

More information

Operator Manual. Transfer Switch. RSS100 and RSS Cummins Inc. All rights reserved. English

Operator Manual. Transfer Switch. RSS100 and RSS Cummins Inc. All rights reserved. English Operator Manual Transfer Switch RSS100 and RSS200 English 8-2007 962 0134 Table of Contents SECTION TITLE PAGE SAFETY PRECAUTIONS................................................... ii 1. INTRODUCTION.........................................................

More information

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance / Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance / Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance / Non-Service Entrance Model Number RXSW100A3 RXSC100A3 RXSW150A3 RXSW200A3 RXSC200A3 SERIAL NUMBER: DATE PURCHASED: WWW.GENERAC.COM

More information

Owner s Manual. For Automatic Transfer Switch. 100 Amp. Model Number RTG16EZA3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

Owner s Manual. For Automatic Transfer Switch. 100 Amp. Model Number RTG16EZA3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED: Owner s Manual For Automatic Transfer Switch 100 Amp Model Number RTG16EZA3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED: Register your Generac product at: WWW.GENERAC.COM 888-436-3722 Para español, visita:

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

E.S.P. Embedded Sensing Probes for Motor Brushes

E.S.P. Embedded Sensing Probes for Motor Brushes E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com

More information

Owner's Manual 600 and 800 Amp RTS Automatic Transfer Switch

Owner's Manual 600 and 800 Amp RTS Automatic Transfer Switch Owner's Manual 600 and 800 Amp RTS Automatic Transfer Switch Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this equipment.

More information

Owner's Manual. LTS Load Shed Switch. This manual should remain with the unit.

Owner's Manual. LTS Load Shed Switch. This manual should remain with the unit. Owner's Manual LTS Load Shed Switch This manual should remain with the unit. Table of Contents SAFETY RULES SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed

More information

This Automatic Transfer Switch with built-in Load Center includes an Express Install Kit.

This Automatic Transfer Switch with built-in Load Center includes an Express Install Kit. This Automatic Transfer Switch with built-in Load Center includes an Express Install Kit. Saves on installation time and cost, in many cases up to 50% compared to traditional transfer switch installations.

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Owner's Manual. LTS Load Shed Switch. This manual should remain with the unit.

Owner's Manual. LTS Load Shed Switch. This manual should remain with the unit. Owner's Manual LTS Load Shed Switch This manual should remain with the unit. Table of Contents Safety Rules... Inside Front Cover General Information... 2 1.1 Introduction... 2 1.2 Equipment Description...

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version MD10 Engine Controller Installation and User Manual for the MD10 Engine Controller. Full Version File: MartinMD10rev1.4.doc May 16, 2002 2 READ MANUAL BEFORE INSTALLING UNIT Receipt of shipment and warranty

More information

INSTALLATION MANUAL MODEL #100947, AMP MODEL #100949, AMP RELIANCE CONTROLS ARL SERIES AUTOMATIC TRANSFER SWITCH

INSTALLATION MANUAL MODEL #100947, AMP MODEL #100949, AMP RELIANCE CONTROLS ARL SERIES AUTOMATIC TRANSFER SWITCH INSTALLATION MANUAL MODEL #100947, 100950 50 AMP MODEL #100949, 100952 100 AMP RELIANCE CONTROLS ARL SERIES AUTOMATIC TRANSFER SWITCH REGISTER YOUR PRODUCT ONLINE at championpowerequipment.com or visit

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches Instruction Leaflet IL 0106001E Contents Description Page Introduction.......................... Installation............................ Manual Operation and Thermal Magnetic Trip Unit Adjustment.......................

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

GTEC Transfer switch Open transition

GTEC Transfer switch Open transition GTE Transfer switch Open transition 40-2000 amp Description GTE transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator

More information

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance / Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance / Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance / Non-Service Entrance Model Number RXSW100A3 (Service Entrance Rated with Utility Service Circuit Breaker) RXSC100A3 RXSW150A3

More information

SERIES ASCO Valves DESCRIPTION OPERATION INSTALLATION. Positioning. Page1of5(Section1of2) I&M No.V9575R3 (Section1of2)

SERIES ASCO Valves DESCRIPTION OPERATION INSTALLATION. Positioning. Page1of5(Section1of2) I&M No.V9575R3 (Section1of2) Installation & Maintenance Instructions -- WAY DIRECT-- ACTING SOLENOID VALVES REVISION H & R NORMALLY OPEN OR NORMALLY CLOSED OPERATION BRASS OR STAINLESS STEEL CONSTRUCTION -- 1/8I, 1/4I, OR3/8I PIPE

More information

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers Cutler-Hammer Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE

More information

ASCO Low Voltage Automatic Transfer Switch Systems

ASCO Low Voltage Automatic Transfer Switch Systems ASCO Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications ASCO s experience and commitment to excellence in designing and building Emergency Power

More information

Owner s Manual. For Automatic Transfer Switch. 50 & 100 Amp. Model Number RTG10EZA1 RTG12EZA1 RTG16EZA1 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

Owner s Manual. For Automatic Transfer Switch. 50 & 100 Amp. Model Number RTG10EZA1 RTG12EZA1 RTG16EZA1 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED: Owner s Manual For Automatic Transfer Switch 50 & 100 Amp Model Number RTG10EZA1 RTG12EZA1 RTG16EZA1 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED: Register your Generac product at: WWW.GENERAC.COM 888-436-3722

More information

Transformer Installation, Operation, and Maintenance Manual

Transformer Installation, Operation, and Maintenance Manual Transformer Installation, Operation, and Maintenance Manual CONTENTS INTRODUCTION......................................... 2 INSPECTION UPON RECEIVING... 2 STORAGE...............................................

More information

Low Voltage Automatic Transfer Switch Systems

Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 2004 Specifications CSJ 2121-04-072 SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 1. Description. Furnish and install packaged engine generator system complete with transfer switch and service

More information

Transfer switch OTPC open, closed, or delayed transition

Transfer switch OTPC open, closed, or delayed transition Transfer switch OTPC open, closed, or delayed transition 40-4000 Amp Description OTPC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator

More information

ASCO 7000 Series Power Transfer Switch Technical Data and Ordering Information

ASCO 7000 Series Power Transfer Switch Technical Data and Ordering Information ASCO 7000 Series Power Transfer Switch Technical Data and Ordering Information 7000 SERIES ORDERIN INFORMATION To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number:

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Owner's/Installation Manual

Owner's/Installation Manual Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH

More information

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Cutler-Hammer Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Table of Contents Description Page 1.0 General Information......................1

More information

Battery Control Center - Diesel

Battery Control Center - Diesel Service Manual CAUTION: All servicing of the Battery Control Center should be done only by a qualified Service Technician. Inadvertent shorts inside the Battery Control Center could result in severe damage

More information

Transfer Switch. RA Series 100A (Spec B) 200A (Spec B) 400A (Spec A) English Original Instructions A056K730 (Issue 3)

Transfer Switch. RA Series 100A (Spec B) 200A (Spec B) 400A (Spec A) English Original Instructions A056K730 (Issue 3) Owner Manual Transfer Switch RA Series 100A (Spec B) 200A (Spec B) 400A (Spec A) English Original Instructions 7-2017 A056K730 (Issue 3) Table of Contents 1. IMPORTANT SAFETY INSTRUCTIONS... 1 1.1 Warning,

More information

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by

More information

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS

More information

Owner's Manual. GenReady Load Center and Transfer Switch. This manual should remain with the unit. Model Numbers. GenReady Basic Panelboard

Owner's Manual. GenReady Load Center and Transfer Switch. This manual should remain with the unit. Model Numbers. GenReady Basic Panelboard Owner's Manual GenReady Load Center and Transfer Switch 0054480 0054510 0054490 0054520 0054530 0054540 0054560 Model Numbers GenReady Basic Panelboard GenReady Advanced Panelboard with Operator GenReady

More information

Multi-Pak Group Control

Multi-Pak Group Control Multi-Pak Grouping.1 Product....................................... Application.................................... Features Enclosures........................................... V-T-2 V-T-2 V-T-2 Feeder

More information

EISHO TEK. Vacuum Circuit Breaker

EISHO TEK. Vacuum Circuit Breaker EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who

More information

Installation Manual. Transfer Switch Amps. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A)

Installation Manual. Transfer Switch Amps. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) Installation Manual Transfer Switch 40-1000 Amps OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) English - Original Instructions 4-2010 962-0617 (Issue 5) Table of Contents 1. INTRODUCTION...

More information

4000 SYSTEM OPERATING MANUAL

4000 SYSTEM OPERATING MANUAL 4000 SYSTEM OPERATING MANUAL REV 1.4 COPYRIGHT 1996 Xenotech, Inc. PAGE 1 INSTRUCTIONS FOR REMOVING AND INSTALLING A TYPE XT XENON BULB IN A BL4000 FIXTURE NOTE FAMILIARIZE YOURSELF WITH THE LOCATION AND

More information

920 Remote Control Switches

920 Remote Control Switches 920 Remote Control Switches REMOTE CONTROL SWITCHES Service Bulletin This service bulletin for ASCO 920 Remote Control Switches explains how to replace the main s, operator coil, control s, and how to

More information

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI II 1400-6 ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI ACSI 1426-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1092, REV. C INSTALLATION For C-UL Listed applications,

More information

N-frame Circuit Breaker

N-frame Circuit Breaker Bul. 140U N-Frame Circuti Breakers Instruction Leaflet for N-Frame Circuit Breakers WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN- TENANCE ON EQUIPMENT WHILE ENERGIZED. DEATH, SEVERE PERSONAL INJURY,

More information

COM Overcurrent Relay

COM Overcurrent Relay 41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3

More information

Parts Catalog. Generator Set TGHAA (Spec A C) Printed in U.S.A. Replaces (Spec A) 1 97

Parts Catalog. Generator Set TGHAA (Spec A C) Printed in U.S.A. Replaces (Spec A) 1 97 Parts Catalog TGHAA Generator Set Printed in U.S.A. 9 00 (Spec A C) 9 Replaces 9 00 (Spec A) 97 To avoid errors or delay in filling your parts order, always give the MODEL, SPEC NO. and SERIAL NO. from

More information

Prismpack V, Prismalume V, Large Prismpack, Large Prismalume

Prismpack V, Prismalume V, Large Prismpack, Large Prismalume AFTER INSTALLATION DELIVER THIS MANUAL TO OWNER Holophane Company Inc. Field Service Department IMPORTANT SAFETY INSTRUCTIONS -READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OR MAINTAIN

More information

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before

More information

Technical Manual. Nexus Smart Switch. This manual should remain with the unit.

Technical Manual. Nexus Smart Switch. This manual should remain with the unit. Technical Manual Nexus Smart Switch This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service

More information

SUPER AUTO EJECT AUTOMATIC SHORELINE DISCONNECT 3 YEARS WARRANTY. Assembled in the UK by LUDO McGURK TRANSPORT EQUIPMENT LTD WILMSLOW - U.K.

SUPER AUTO EJECT AUTOMATIC SHORELINE DISCONNECT 3 YEARS WARRANTY. Assembled in the UK by LUDO McGURK TRANSPORT EQUIPMENT LTD WILMSLOW - U.K. INSTALLATION GUIDE AND MANUAL SUPER AUTO EJECT AUTOMATIC SHORELINE DISCONNECT 3 YEARS WARRANTY Assembled in the UK by LUDO McGURK TRANSPORT EQUIPMENT LTD WILMSLOW - U.K. A KUSSMAUL ELECTRONICS CO., INC.PRODUCT

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

User Manual. Solar Charge Controller 3KW

User Manual. Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5

More information

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-8 Features: ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS Filtered/Regulated 24 Volts DC Up to Full 2 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit

More information

Bypass/Isolation Switches RTS-30 SERIES

Bypass/Isolation Switches RTS-30 SERIES Bypass/Isolation Switches RTS-0 SERIES RTS-0 Series Automatic Transfer Switches with Manual Bypass Industry s Most Comprehensive Line of UL Tested 0-Cycle Automatic Transfer Switches A Russelectric RTS-0

More information

OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

OWNER S MANUAL AND INSTALLATION INSTRUCTIONS EmerGen Switch Manual Transfer Switch OWNER S MANUAL AND INSTALLATION INSTRUCTIONS For A Series Models 6-5001, 6-7501, 10-7501, 10-12K1 PLEASE READ THIS MANUAL IN ITS ENTIRETY BEFORE INSTALLING AND/OR

More information