STANDBY EMERGENCY CNG/LPG GENERATOR

Size: px
Start display at page:

Download "STANDBY EMERGENCY CNG/LPG GENERATOR"

Transcription

1 SECTION STANDBY EMERGENCY CNG/LPG GENERATOR PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Compressed natural gas (CNG) or liquefied petroleum gas (LPG) powered standby emergency generators. B. Related Sections: Concrete. 2. Division 15 - Mechanical Ductwork Automatic Transfer Switch Overcurrent Protective Devices SYSTEM DESCRIPTION A. Use of fuel oil system is not allowed SUBMITTALS A. Submit for review, properly identified product data material. B. Provide operating and maintenance manuals complete with replacement parts data for standby emergency generator system. C. Submit sample of written warranty with product data. D. Contract Closeout Submittal: Furnish the Board with manufacturer's certification and warranty assuring each item of equipment is complete and in good condition, free from damage, properly installed, connected, adjusted, and tested as to full power rating, stability, and voltage and frequency regulation QUALITY ASSURANCE A. Qualifications: Single source generator supplier and installer, acceptable to the standby emergency generator manufacturer, capable of providing, but not limited to, the following services: 1. Generator and electrical apparatus pertinent to the generator including the automatic transfer switches. 2. Complete fuel tank system. Project No. SPECIFICATION GUIDELINES

2 3. Sheet metal shrouding. 4. Plumbing pertinent to the fuel system and generator. 5. Exhaust system and piping. 6. Insulation of exhaust system. 7. Control wiring between generator and transfer switch, water heater, battery charging, and annunciator wiring. 8. Required warranty. 9. Other work required for a complete and operable system. B. The Board will not accept 2 or more subcontractors to do the Standby Emergency Generator work. C. Performance Requirements: Materials shall bear Underwriters Laboratories (UL) labels WARRANTY A. Furnish standby emergency generator set completely by manufacturer and warranted for a period of 5 years from date of substantial completion. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Standby Electric Generator System: 1. Caterpillar. 2. Kohler. 3. Onan EQUIPMENT NOTE TO SPECIFIER: In the following sentence, specify the voltage requirements to suit project conditions. A. Standby Emergency Generator: Include an electric generator set rated for continuous standby service. B. Emergency Generator Fuel Tanks: Pressurized with uninterrupted, on-site, local fuel, such as CNG or LPG tanks. C. System shall be a package of new and current equipment consisting of: 1. A natural gas or electric engine driven generating set Project No. SPECIFICATION GUIDELINES

3 to provide standby power. 2. An engine start-stop control system. 3. An automatic load transfer control to provide automatic starting and stopping of the engine and switching of the load as specified in Section Mounted accessories as specified. D. The system shall be built, tested, and shipped by the manufacturer of the alternator so there is one source of supply and responsibility. The performance of this generating set series shall be certified by an independent testing laboratory as to the set's full power rating, stability and voltage and frequency regulation. NOTE TO SPECIFIER: The A/E shall provide the project specific information regarding engine performance requirements to suit project conditions. E. Engine: F. Engine Instrument Panel: G. Engine Controls: H. Alternator: Provide overcurrent protection on generator. I. Unit Performance: J. Alternator Instrument Panel: Wire, test, and shock mount on the generating set by the manufacturers of the alternator. It shall contain panel lighting, manual reset circuit breaker, frequency meter, running time meter, voltage adjusting rheostat, AC voltmeter (dual range, indicates all voltages), AC ammeter (dual range, indicates current in each phase), meter switch, voltmeter-ammeter phase selector with OFF position. K. Generator Mounting: 1. Concrete Pad: Provide a 6 inch high concrete pad under each emergency generator. 2. Equip with vibration isolators and mount on a welded steel base that shall provide suitable mounting to any level surface. L. Automatic Load Transfer Control: Complete automatic transfer switch shall be supplied by manufacturer of alternator. It shall include necessary relays and component Project No. SPECIFICATION GUIDELINES

4 parts, with electrically and mechanically interlocked switches. See Section M. Accessories: Furnish accessories needed for the proper operation of the generating set. These shall include but not be limited to an exhaust muffler, flexible exhaust connection, starting batteries, battery cables, battery charger, battery rack, fuel oil day tank, and fuel lines. 1. Exhaust Muffler: All-welded design, constructed of sheet and plate steel. Provide with all necessary flexible exhaust connections as indicated on mechanical drawings for installation by mechanical contractor. Exhaust muffler manufacture: Maxim M-41 with side inlet or accepted equivalent. 2. Insulation: The muffler and all indoor exhaust piping shall be properly lagged using Kaylo 1800 degree F. insulation. Insulation will be furnished and installed under the insulation section. 3. Jacket water heater shall be installed inline with engine cooling system. Jacket water heater to be rated at 2 KW, at application voltage, single phase. PART 3 EXECUTION 3.01 INSTALLATION A. Install standby emergency generator according to the manufacturer's recommendations and according to the requirements of NFPA 70 - National Electrical Code (NEC). 1. The following items of work relating to the emergency generators will be provided under other sections by different trades. a. Fuel System including main fuel oil storage tank, (day tanks), and piping, as specified. b. Cooling air intake and exhaust louvers. c. Sheetmetal ductwork interconnection between radiator and exhaust air louvers. d. Installation of mufflers and exhaust pipes and insulation of same. 2. The Installer shall be responsible for coordinating all trades to ensure the proper functioning of the entire systems including but not limited to fuel supply, exhaust equipment and air transfer system. This coordination shall include furnishing all required Project No. SPECIFICATION GUIDELINES

5 information to other subcontractors regarding fuel, exhaust and cooling system dimensions, pipe and duct sizes, etc. The Installer shall furnish a dimensioned plan layout indicating all generator dimensions, roughing dimensions, piping layout, duct layout, tank locations and elevations and all required electrical wiring and interconnections TESTS AND START-UP A. Tests: 1. The electric generator set shall receive the manufacturer's standard testing. 2. Before acceptance of the installation, the equipment shall be tested to show it will start automatically, subjected to full load test or that load available at the job-site, shut down and reset as required in these Specifications. 3. Before acceptance, any defects that become evident during this test shall be corrected at no additional cost to the Board. B. Start-up and Instructions: 1. On completion of the installation, perform the initial start-up by a factory-trained representative of the engine supplier. 2. At the time of start-up, operating instructions and maintenance procedures shall be thoroughly explained to operating personnel. 3. Two copies of operating and maintenance instruction books shall be supplied for the electric set and such auxiliary equipment as may require same. END OF SECTION Project No. SPECIFICATION GUIDELINES

************************************************************************************************************* PART 1 GENERAL 1.

************************************************************************************************************* PART 1 GENERAL 1. 16620 STANDBY EMERGENCY ELECTRICAL GENERATOR (CNG/LPG) ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number:

More information

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates Issued 2005/06/01 Section 16239 Power Generation to 30 kw Page 1 of 7 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01355 Waste Management and Disposal..2 Section 01810 Commissioning..3 Section 03100 Concrete

More information

EMERGENCY GENERATOR SET

EMERGENCY GENERATOR SET PART 8.1: EMERGENCY GENERATOR SET PART 1 - GENERAL I SCOPE A. This specification covers the design, furnishing, installation and start up of a factory built, production tested, operable, liquid cooled

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 263213 - ENGINE GENERATORS PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 2004 Specifications CSJ 2121-04-072 SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 1. Description. Furnish and install packaged engine generator system complete with transfer switch and service

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

1510 GENERATOR AND TRANSFER SWITCHES

1510 GENERATOR AND TRANSFER SWITCHES SECTION 263216-GENERATOR AND TRANSFER SWITCHES PART 1 GENERAL 1.1 RELATED DOCUMENTS 1.2 INTENT 1.3 STANDBY A. Drawings and provisions of the "General Conditions" and "Special Requirements" and other Division

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section SECTION 15910 DUCT ACCESSORIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division-1 Specification Sections,

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

Product Specification Guide Expansion and Deflection Couplings. SECTION Raceway and Boxes for Electrical Systems

Product Specification Guide Expansion and Deflection Couplings. SECTION Raceway and Boxes for Electrical Systems Product Specification Guide Expansion and Deflection Couplings SECTION 26 05 33 Raceway and Boxes for Electrical Systems Specifier Notes: Delete any information below in Parts 1, 2 or 3 which is not required

More information

A. Equipment shall comply with applicable sections of the latest edition of the following standards:

A. Equipment shall comply with applicable sections of the latest edition of the following standards: SECTION 26 32 13 STANDBY GENERATOR SETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section Operation and Maintenance Data, include the following: SECTION 16211 - ELECTRICITY METERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

VERTICAL LIFT FIRE/BLAST DOORS

VERTICAL LIFT FIRE/BLAST DOORS International Door, Inc. 8001 Ronda Drive Canton, MI 48187 (800) 231-9521 Website: www.international-door.com Sales Dept. E-Mail: sales@international-door.com Engineering Dept. E-Mail: engineering@international-door.com

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ENGINEERING MANUAL PRESSURE STEAM HUMIDIFIERS

ENGINEERING MANUAL PRESSURE STEAM HUMIDIFIERS Ogdensburg, New York, U.S.A. 1-866-NORTEC-1 Ottawa, Ontario, Canada 1-866-NORTEC-1 ENGINEERING MANUAL PRESSURE STEAM HUMIDIFIERS The LS Series is a cost effective way to provide precise humidity control,

More information

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes: SECTION 15970 HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Thermostats, temperature transmitters, controllers, automatic valves, dampers, damper operators, pneumatic/ electric

More information

SECTION WELDING FUME EXHAUST SYSTEM

SECTION WELDING FUME EXHAUST SYSTEM SECTION 233500 WELDING FUME EXHAUST SYSTEM PART 1 - GENERAL 1.1 WORK INCLUDES Welding fume exhaust system and controls Accessories Additional System Equipment Engineering Support Commissioning 1.2 RELATED

More information

LINCOLN COUNTY STANDARD SPECIFICATIONS SECTION PACKAGED ENGINE GENERATORS, DIESEL

LINCOLN COUNTY STANDARD SPECIFICATIONS SECTION PACKAGED ENGINE GENERATORS, DIESEL LINCOLN COUNTY STANDARD SPECIFICATIONS SECTION 16231 PACKAGED ENGINE GENERATORS, DIESEL 1.1 General Requirements It is the intent of this specification to secure emergency standby generators that have

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL 13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,

More information

SECTION ENGINE GENERATORS

SECTION ENGINE GENERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 32 13 ENGINE GENERATORS A. This section specifies the furnishing, installation, connection, and testing of the 480v, 3 phase, 3 wire, 125eKW, 156KVA engine standby

More information

ATTACHMENT A PRINCE EDWARD COUNTY INVITATION FOR BIDS # MOBILE DIESEL PACKAGED ENGINE GENERATOR SPECIFICATIONS

ATTACHMENT A PRINCE EDWARD COUNTY INVITATION FOR BIDS # MOBILE DIESEL PACKAGED ENGINE GENERATOR SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

MEDIUM-VOLTAGE SWITCHGEAR

MEDIUM-VOLTAGE SWITCHGEAR REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.

More information

SECTION ENGINE GENERATORS

SECTION ENGINE GENERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 32 13 ENGINE GENERATORS SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

SECTION EMERGENCY STANDBY POWER SYSTEM

SECTION EMERGENCY STANDBY POWER SYSTEM PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall provide, install, and acceptance test a complete and operable emergency standby electric generating system, including all devices and equipment

More information

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems.

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems. SECTION 220523 - PLUMBING VALVES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball valves. 2. Butterfly valves. 3. Swing check valves. 4. Spring loaded check valves. 5. Water pressure reducing

More information

SPECIAL SPECIFICATION 8334 Packaged Engine Generator

SPECIAL SPECIFICATION 8334 Packaged Engine Generator 2004 Specifications CSJ 0196-07-027 SPECIAL SPECIFICATION 8334 Packaged Engine Generator 1. Description. Furnish and install packaged engine-generator of the types and ratings shown on the plans. Where

More information

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS SECTION 22 11 23.13 (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Packaged Domestic Water Booster Pumps B. Related Sections: 1.02 REFERENCES 1. Section

More information

BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR

BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR Bid Specifications for 300 kw Standby Generator Compliance CITY OF GENEVA PUBLIC WORKS DEPARTMENT ENGINE In-Line Six Cylinder, turbocharged ATAAC aspirated,

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

Note: All items shown in red require review, and possible input, for information required that is specific to the generator system being specified.

Note: All items shown in red require review, and possible input, for information required that is specific to the generator system being specified. DIVISON 16 ELECTRICAL Section 16620A Diesel Engine Generator Set Note: All items shown in red require review, and possible input, for information required that is specific to the generator system being

More information

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY SECTION 230533 - PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pressure gages. 2. Pressure gage taps. 3. Thermometers. 4. Thermometer supports. 5. Test plugs. 6. Static pressure

More information

SECTION ENGINE GENERATORS

SECTION ENGINE GENERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 32 13 SPEC WRITER NOTE: Use this section lonely for NCA projects. Delete between //----// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL 13686.00 GENERAL SERVICE AIR COMPRESSOR 221519-1 SECTION 22 1519 - GENERAL-SERVICE AIR COMPRESSOR 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract, including General

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

STANDBY 200 ekw 250 kva

STANDBY 200 ekw 250 kva DIESEL GENERATOR SET STANDBY 200 ekw 250 kva Image shown may not reflect actual package. Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility,

More information

STATEMENT OF WORK. Sinnemahoning State Park Cameron County, Pennsylvania

STATEMENT OF WORK. Sinnemahoning State Park Cameron County, Pennsylvania STATEMENT OF WORK Purchase of One (1) LP Gas (Propane) Standby Generator Set and One (1) Service Entrance Rated Automatic Transfer Switch For Delivery to Visitors Center Sinnemahoning State Park Cameron

More information

SOUND-RETARDANT- VERTICAL LIFT DOORS

SOUND-RETARDANT- VERTICAL LIFT DOORS International Door, Inc. 8001 Ronda Drive Canton, MI 48187 (800) 231-9521 Website: www.international-door.com Sales Dept. E-Mail: sales@international-door.com Engineering Dept. E-Mail: engineering@international-door.com

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

PROJ. NO SECTION HYDRONIC PUMPS

PROJ. NO SECTION HYDRONIC PUMPS SECTION 23 21 23 HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 2123 - PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Optimizing Emergency Power Systems for Health Care Applications

Optimizing Emergency Power Systems for Health Care Applications 2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan

More information

Rotary Disconnect Switches, Bulletin 194R

Rotary Disconnect Switches, Bulletin 194R ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION Rotary Disconnect Switches Bulletin 194R NOTICE: The specification guidelines in this document are intended to aid in the specification

More information

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

City of Storm Lake Fire Department Heavy Rescue Specifications

City of Storm Lake Fire Department Heavy Rescue Specifications INTENT OF SPECIFICATIONS City of Storm Lake Fire Department Heavy Rescue Specifications It shall be the intent of these specifications to provide a complete apparatus equipped as hereinafter specified.

More information

STANDBY 40 ekw 40 kva PRIME 36 ekw 36 kva

STANDBY 40 ekw 40 kva PRIME 36 ekw 36 kva DIESEL GENERATOR SET FEATURES Image shown may not reflect actual package. STANDBY 40 ekw 40 kva PRIME 36 ekw 36 kva Caterpillar is leading the power generation marketplace with Power Solutions engineered

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

STANDBY 80 ekw 100 kva PRIME 72 ekw 90 kva

STANDBY 80 ekw 100 kva PRIME 72 ekw 90 kva DIESEL GENERATOR SET FEATURES Image shown may not reflect actual package. STANDBY 80 ekw 100 kva PRIME 72 ekw 90 kva Caterpillar is leading the power generation marketplace with Power Solutions engineered

More information

SECTION STANDBY GENERATOR

SECTION STANDBY GENERATOR SECTION 26 32 13 STANDBY GENERATOR PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections,

More information

STANDBY 200 ekw 250 kva

STANDBY 200 ekw 250 kva DIESEL GENERATOR SET STANDBY 200 ekw 250 kva Caterpillar is leading the power generation marketplace with Power Solutions engineered Image shown may not reflect actual package reliability, and cost-effectiveness.

More information

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS SECTION 08350 HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1

More information

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,

More information

East Central College

East Central College SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Wall switches. b. Receptacles c. Device plates and decorative box covers. 1.2 RELATED

More information

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES Page 226113-1 SECTION 226113 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Standby Power Systems

Standby Power Systems Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to

More information

Low Voltage Automatic Transfer Switch Systems

Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

RPS Station. Solutions for the North American Solar Market

RPS Station. Solutions for the North American Solar Market RPS Station Solutions for the North American Solar Market 2013/2014 Power, control and green solutions 3 RPS Station s RPS Station is a fully integrated photovoltaic power conversion system that is designed

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

SECTION PACKAGED ENGINE GENERATOR SYSTEMS

SECTION PACKAGED ENGINE GENERATOR SYSTEMS PROJECT: SECTION 16620 PACKAGED ENGINE GENERATOR SYSTEMS PART 1 GENERAL 1.1 SUMMARY: A. This Section includes packaged engine-generator systems for emergency power supply with the following features: 1.

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

3. Customer shall provide space for metering equipment and meter base as per Springville City Power requirements.

3. Customer shall provide space for metering equipment and meter base as per Springville City Power requirements. A. General This Customer-Owned Generation Standards for Customer-Owned Grid Connected Electric Generating Systems sets forth the requirements and conditions for interconnected non-utility-owned electric

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

This Manu-Spec specifies automatic swinging gate operators and accessories for residential, commercial, and industrial use GATE OPERATORS

This Manu-Spec specifies automatic swinging gate operators and accessories for residential, commercial, and industrial use GATE OPERATORS 7820 Gloria Avenue Van Nuys, California, 91406 Phone: (818) 787-1988 FAX: (818) 787-2214 Email: info@allomatic.net Website: allomatic.net This Manu-Spec utilizes the Construction Specifications Institute

More information

CLIENT: PROJECT: PO#: ESTIMATOR:

CLIENT: PROJECT: PO#: ESTIMATOR: GENERATOR CONTROL DATA SHEET CLIENT: PROJECT: PO#: ESTIMATOR: PRIME MOVER FUEL: RPM: GOVERNOR SPEED ADJUST RHEOSTAT SUPPLIED WITH GOVERNOR: LOAD SHARING: REMOTE: PRIME MOVER PROTECTION LOW OIL PRESSURE

More information

1500 or 1800 RPM. Engine Specifications C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel 145 mm (5.71 in) 183 mm (7.2 in) Compression Ratio 14.

1500 or 1800 RPM. Engine Specifications C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel 145 mm (5.71 in) 183 mm (7.2 in) Compression Ratio 14. Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness. Specifications Generator Set

More information