SynergEX Panelboards. Installation & Maintenance Information IF Panelboards for Hazardous Locations SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

Size: px
Start display at page:

Download "SynergEX Panelboards. Installation & Maintenance Information IF Panelboards for Hazardous Locations SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE"

Transcription

1 SynergEX Panelboards Panelboards for Hazardous Locations Installation & Maintenance Information IF 1659 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE CAUTION Read these operating instructions and all other information sheets before wiring and use (300mm) Do not alter this product in any way. Doing so may lead to serious injury or death. To avoid dangerous overheating, do not use aluminum wiring. Use copper wire only (950mm) To avoid electrical shock, electrical power must be OFF before and during installation, inspection, and maintenance. Observe the national safety rules and regulations (775mm) TABLE OF CONTENTS Dimensional Drawings: SynergEX Panelboards Breakers Circuit (300mm) 1. Technical Data Complete Distribution Technical Data Busbar System Busbar System Connectors Rated Current of Connectors/Wires Clearance and Creepage Dimensions of Busbar System Connection Busbar System Hazardous Location Technical Data for Breakers Mechanical Data /480V Circuit Breakers /240V Circuit Breakers Aux./Signal Contact Safety Instructions Conformity with Standards Field of Application Application/Properties Installation Transport/Storage Before Installation Transport Mounting/Installation Opening SynergEX Panelboards Electrical Connection General Busbar System Electrical Connection Busbar System Busbar Connectors Cable Entries, Blanking Plugs Drilling for Additional Cable Entries Flanges, Metal Plates, and External Earth Connection Closing Apparatus Putting Into Operation Maintenance/Servicing Repairs/Modifications Disposal/Recycling Dimensional Drawings, Breakers Tripping Characteristic Derating Table for Breakers Certificate of Conformity enclosed separately. 24 Circuit 42 Circuit (950mm) (950mm) (1900mm) (1280mm) (300mm) (1600mm) (1100mm) (300mm) 60 Circuit Figure 1. Dimension Drawings IF /13 Copyright 2013, Cooper Industries, Inc. Page 1

2 1. TECHNICAL DATA 1.1 Complete Distribution Master Contract Explosion Category: -20 C or -20 C to -40 C with heater For USL AEx de IIC T4 For CNL Ex de IIC T4; Ex tb IIIC T100 C Db Certifications and Compliances: Class I, Zones 1 & 2 For USL Zone 1 & 2 For CNL Rated Voltage to 600VAC / 60 Hz 1.2 Technical Data Busbar System Class I, Division 2, Groups A, B, C, D; Class II, Division 1, Groups E, F, G Class I, Division 2, Groups A, B, C, D; Class II, Division 1, Groups E, F, G, Extb IIIC T100 C Db Rated Current Max. 225A Up to 40 C 40 C to 55 C Size A (12 cct) up to 100A up to 85A Size B (24 cct) up to 150A up to 125A Size C (42 cct) up to 225A up to 190A Size D (60 cct) up to 225A up to 190A Ambient Temperature -40 C to +55 C (varies with configuration) Perm. Storage Temperature in Original Packing -40 C to +55 C Degree of Protection to EN/IEC IP66 (standard version); Type 4X Insulation Class to EN/IEC I Maximum Number of Breakers (Single Pole) Size A 12 Size B 24 Size C 42 Size D 60 Connectors Quantity - acc. to number of breakers (poles) Cable Entries Acc. to customer s specification and as certified Terminal Cross-section Max. AWG 4/0 / 120mm 2 Incoming Wires 75 C Outgoing Wires 75 C Enclosure Material Stainless steel -20 C to -40 C without heater AEx de IIB T4 Ex de IIB T4; Ex tb IIIC T100 C Db Busbar Rail System Rated Voltage Rated Current Rated Short Time Current Rated Short Circuit Current Support Spacing for Is to 10kA Test Torques: Fixing Screws Busbar System 1 x 12mm x 5mm 600V / 60 Hz 225A (40 C) 4kA 10kA 300mm 2.5 N-m Figure 2. Connectors Busbar System Connectors (phase X/Y/Z, neutral N, ground ) Cross Section/AWG Solid Stranded Number of d/ a/ b/ c/ Test Torque/ Connectors Min. Max. Min. Max. Connectors mm / inch mm / inch mm / inch mm / inch N-m grck / / / / grck / / / / grck / / / / grck / / / / / grck / / / / / IF /13 Copyright 2013, Cooper Industries, Inc. Page 2

3 1.2.2 Rated Current of Connectors/Wires Ambient Temperature Range Rated Current of Busbar 40 C 225A Cross-section of Cables Max. Rated Current of Connecting Cables /0 4/0 15A 20A 30A 40A 50A 60A 100A 150A 225A Clearance and Creepage Dimensions of Busbar System 120V/240V 277V/480V Minimum Spacing Through Air A between phases >= 19.0mm >= 25.0mm Minimum Spacing Through Air B between phases and ground >= 12.5mm >= 12.5mm Minimum Spacing Over Surface C between opposition phases >= 31.0mm >= 50.0mm Minimum Spacing Over Surface D between phases and ground >= 31.0mm >= 50.0mm Cross Section / AWG Connectors Stranded Min. Max. Stripping Length grck grck grck grck /0 22 grck /0 25 Figure 3. Stripping Length Connection Busbar System 1 Phase 120/240V 3 Phase 277/480V IF /13 Copyright 2013, Cooper Industries, Inc. Page 3

4 1.3 Hazardous Location Technical Data for Breakers Master Contract Explosion Category: For USL AEx de IIB/IIC For CNL Ex de IIB/IIC Certifications and Compliances: Class I, Zone 1 For USL Class I, Division 2, Groups A, B, C, D Zone 1 For CNL Class I, Division 2, Groups A, B, C, D Ambient Temperature Range: IIC: -20 C to +55 C (GHG62-1/2/3/4...R...) IIB: -45 C to +55 C (GHG62-1/2...R...) Permissible Service Temperature Range: IIC: -20 C to +110 C (GHG62-1/2/3/4...R...) IIB: -45 C to +110 C (GHG62-1/2...R...) Other temperatures possible with special versions. Perm. Ambient Temperature in Original Packing -45 C to 60 C Figure 4. Contact Arrangement/ Circuit Breaker Mechanical Data Terminal Cross Section: Stripping Length Main Terminal Module Size 1-3 Current 15A or less AWG 14 11mm / A AWG 12 11mm / A AWG 10 11mm / A AWG 10 11mm / A AWG 8 11mm / 0.4 Aux. Terminals AWG 14 11mm / 0.4 Quantity Terminals for the Module Size: Main Terminals Aux. Terminals Test Torques: Main Contacts 3.5 N-m Aux. Contacts 1.0 N-m Mounting Screws 2.5 N-m Enclosure Material Polyamide /480V Circuit Breakers Figure 5. Contact Arrangement/ Additional Devices Rated Voltage Main contact to 277/480VAC; 60 Hz Rated Current Main contact 10A-40A Types 1-pole GHG R... 2-pole GHG R... 3-pole GHG R... Rated Switching Capacity 10kA Non-ambient Compensated Temperature 25 C Component Size Weight ca kg 0.90 kg 1.20 kg 1-pole* 2-pole* 3-pole* Tripping characteristic of circuit breaker, see last page. *Circuit breakers with additional devices are built into larger component enclosures /240V Circuit Breakers Rated Voltage Main contact to 120/240VAC; 60 Hz Rated Current Main contact 10A to 40A Types 1-pole GHG R... 2-pole GHG R... Rated Switching Capacity 10kA Non-ambient Compensated Temperature 40 C Component Size 1 2 Weight ca kg 1.20 kg 1-pole* 2-pole* Tripping characteristic of circuit breaker, see last page. *Circuit breakers with additional devices are built into larger component enclosures in bigger size Aux./Signal Contact The technical data relates to standard built-in apparatus. If other built-in apparatus is used, the technical data sheets or the data on the type label shall be observed. Rated Voltage to 230VAC 277VAC 480VAC Rated Current 2A 2A 1A Minimum Switching Capacity 5 ma at 24V IF /13 Copyright 2013, Cooper Industries, Inc. Page 4

5 2. SAFETY INSTRUCTIONS For installation only by a qualified electrician in accordance with the National Electric Code, the Canadian Electric Code, applicable local codes, and these instructions. SynergEX Panelboards are not suitable for Zone 0 or Zone 20 hazardous areas. The temperature class and explosion group marked on the distributions shall be observed. The permissible ambient temperature, the terminal cross-section, and the self-heating of the apparatus, which is mainly caused by the power dissipation, are to be observed to ensure that the temperature class stated on the type label of the apparatus is maintained. (Test criterion for the selfheating is an overload of 10%). The apparatus shall be used for the intended purpose and shall be in a perfect and clean state. Check to see that the rating label on the device is correct for the installation. Only original parts from the manufacturer may be used as replacements and for repairs. Repairs that affect the explosion protection may only be carried out by Cooper Crouse-Hinds / CEAG or by a qualified electrician in compliance with the respective national regulations. Modifications to the distributions or design changes are not permitted. Prior to being put into operation, the distributions shall be checked in accordance with the instructions given in Section 6. Before initial operation, any foreign matter shall be removed from the distribution enclosures. Before opening the enclosure dead front, it is necessary to ensure that the distributions are isolated from the voltage supply or take the appropriate protective measures. The minimum terminal cross-sections of the flameproof components shall be observed during connection in accordance with CSA C22.2 No. 29 / UL67. Maximum continuous load on all circuit breakers (including main and subfeeder breakers) not to exceed 80% of rating. The national safety rules and regulations for the prevention of accidents, as well as the safety instructions included in these operating instructions, shall be observed. 3. CONFORMITY WITH STANDARDS SynergEX Panelboards have been designed, manufactured, and tested according to the following standards: CSA C CSA C (R2003) CSA C CSA C CSA C22.2 No M85 CSA C22.2 No CSA C22.2 No. 213-M1987 CAN/CSA C22.2 No :11 CAN/CSA C22.2 No : 11 CAN/CSA C22.2 No :12 CAN/CSA C22.2 No :12 4. FIELD OF APPLICATION ANSI/ISA ( ): 2009 ANSI/ISA ( ): 2009 ANSI/ISA ( ): 2008 ANSI/ISA ( ): 2009 UL67, 12 th Ed., 2009 UL50, 12 th Ed., 2007 UL50E, 1 st Ed., 2007 The distributions are suitable for use in hazardous areas in Class I, Division 2; Class II, Division 1; Zone 1; Zone 2; Zone 21; or Zone 22 in accordance with IEC , CAN/CSA The materials used for the enclosures, including the exterior metal parts, are high quality materials that ensure an appropriate corrosion protection and resistance to chemical substances according to the requirements for use in a normal industrial atmosphere : - Stainless steel AISI 316L - Stainless steel AISI Safety glass In case of use in an extremely aggressive atmosphere, please refer to manufacturer. 5. APPLICATION/PROPERTIES SynergEX Panelboards are used for distributing electric power (e.g. main, lighting, heating, control and intrinsically safe circuits, etc.). (See Technical Data for temperature classes, explosion groups, and permissible ambient temperatures). The function of MCB circuit breakers and ELCBs (RCDs) with circuit breakers shall be checked after several short circuits. An ELCB (RCD) does not prevent the sensation caused by an electric shock, but it limits the duration of the current flow through the human body to such a short time that the probability of a fatal effect is reduced to a negligible amount. Once the cause for the tripping of the ELCB (RCD) has been eliminated, it is reset by switching the toggle to the ON position. Details of the electric contacts are given on the base of the component or in these operating instructions. If not specified in these operating instructions, information on the safe use of third-party products shall be requested from the respective manufacturer of the equipment. 6. INSTALLATION The relevant national regulations and the generally recognized rules of engineering apply for the installation and operation. 6.1 Transport/Storage Before Installation SynergEX Panelboards shall be inspected on receipt to verify that they are complete and undamaged. If the delivery is not complete, an inventory shall be drawn up immediately together with the transport company. Any damages shall be documented accordingly. To store, SynergEX Panelboards shall be placed on a clean, dry, and flat surface, whereby the position shall be maintained. SynergEX Panelboards shall be protected against adverse weather conditions Transport To transport SynergEX Panelboards, use the suitable transport aids that are put at your disposal. Depending on the size of the SynergEX Panelboards, a transport beam might have to be used. 6.2 Mounting/Installation The data according to Sections 3 and 4 shall be taken into account during use. Applications other than those described are not permissible without a written declaration of consent from the manufacturer. During operation, the instructions stated in Section 7 of the operating instructions shall be observed. These operating instructions also apply as instructions for the replacement or addition to individual flameproof components. The sole responsibility with respect to the suitable and proper use of these panels lies with the operator. The mounting and installation of SynergEX Panelboards must only be carried out by skilled electricians. SynergEX Panelboards can be mounted without opening the cover. When SynergEX Panelboards are mounted directly onto the wall, they shall rest evenly only on the fastening points provided for this purpose, and they shall be fixed in such a way that they cannot twist or turn. The screws used shall match the fixing holes (see dimension drawings) and must not damage the openings (e.g. use of washers). All fixing points shall be used when screwing SynergEX Panelboards to the wall or floor. Excessive tightening can result in damage to SynergEX Panelboards. IF /13 Copyright 2013, Cooper Industries, Inc. Page 5

6 SynergEX Panelboards must not be left near heat sources. The correct position of the openings for power supply access must be checked before installation. The connections for the incoming and outgoing leads of the busbar systems shall be fitted in such a way that the current load of the copper rails is distributed evenly. 6.3 Opening SynergEX Panelboards Use the relevant key for the locking device (see Figure 6). To maintain the explosion protection, conductors shall be connected with special care. The insulation shall reach to the terminal (see Figure 8). The conductor itself must not be damaged. Cross Section / AWG Connectors Stranded Min. Max. Stripping Length grck grck grck grck /0 22 grck /0 25 Figure 8. Stripping Length The minimum and maximum connectable conductor cross-sections are to be observed. All screws and/or nuts of the connection terminals, including those not in use, shall be tightened down securely. The circuit diagram for the built-in components is either shown on the components, or in the operating instructions. In the case of wired SynergEX Panelboards, the connection diagram included with the apparatus is to be observed. Figure 6. Locking Devices If a flameproof component is disassembled before it is connected to the electric power supply, it is necessary to ensure that the components are put back into the distribution enclosure correctly. Overtightening can damage the enclosure or impair the sealing effect. After opening the lid of the SynergEX Panelboard, you can open the protective covers by unscrewing the screws (see Figure 7). Before opening the dead front in the SynergEX Panelboard, it is necessary to ensure that the SynergEX Panelboard is isolated from the voltage supply or to take suitable protective measures. 6.5 Busbar System The maximum rated current of the busbar system, specified in the Technical Data, have to be observed Electrical Connection Busbar System The electrical connection of the apparatus may only be carried out by skilled staff. In order to maintain the mode of protection, special care shall be taken when connecting the conductors. The minimum and maximum connectable conductor cross-sections are to be observed (see Table 1.2.1). Figure 7. Protective Cover, Open 6.4 Electrical Connection General The electrical connection of the apparatus may only be carried out by trained staff. The properly bared conductors of cables shall be connected with due regard to the respective regulations. The incoming and outgoing wires shall be identified as sized for 75C. IF /13 Copyright 2013, Cooper Industries, Inc. Page 6

7 6.5.2 Busbar Connectors When positioning the connectors, the required clearances D in Figure ( Connection Busbar System ) shall be observed. The possible combinations of connectors and terminal cross-sections can be seen in Table Place the connectors and wiring as shown in Figures 8 and ( Connection Busbar System ). The stripping of the cable depends on the used busbar terminal. The stripped wire should not protrude above the busbar terminal. The insulation must reach up to the terminal (see Figure 8). The busbar terminal attract at least with the test torque specified in Table Excessive tightening will damage the threads. Figure 10. High Torque Screw ø 6mm Test Torque 2.8 N-m Before putting the apparatus into operation, the tests specified in the individual national regulations shall be performed. Improper validation and operation can lead to loss of warranty. 6.6 Cable Entries (KLE); Blanking Plugs Generally only certified cable entries and blanking plugs may be used. The relevant mounting directives for the built-in cable entries shall be observed. When using cable entries for the connection to or into the apparatus, where applicable, the relevant special conditions for safe use given in the individual certificates shall be considered. In order to ensure the minimum degree of protection, any unused entry holes shall be sealed with certified blanking plugs. Overtightening can impair the degree of protection Drilling for Additional Cable Entries Additional holes for cable entries can be drilled into the metal flange. Observe the dimensions of drilling surface, shown in Figure Flanges, Metal Plates, and External Earth Connection If flange plates have to be removed, in order to maintain the minimum protection category, attention shall be paid to the proper fit of the flange plates when remounting them (see Figure 9). Figure 11. Drilling Surface of Metal Flanges Flange plates for SynergEX Panelboards shall be fitted in such a way that the IP protection is maintained. Pay attention to the proper fit of the sealing. Ground conductors fed from outside are to be connected to the ground terminal provided on the SynergEX Panelboard enclosure. The maximum cross-section is 50mm 2. Metal flanges, metal plates, and metal cable entries shall be included in the equipotential earth connection. 6.8 Closing Apparatus Any foreign matter shall be removed from the SynergEX Panelboard. To ensure the minimum protection category, the lids of SynergEX Panelboards shall be closed correctly. 6.9 Putting Into Operation Before putting SynergEX Panelboards into operation, the tests specified in the individual national regulations shall be performed. In addition to this, before being put into operation, the correct functioning of the SynergEX Panelboards and of the built-in components shall be checked in accordance with these operating instructions and other applicable regulations. The incorrect installation and operation of SynergEX Panelboards can result in the invalidation of the guarantee. Figure 9. Cable Entries/Flanges To fix the flange plates, use the high torque screws (ø 6mm, length 6mm) (see Figure 10). Please observe the respective torques given in Figure 10. IF /13 Copyright 2013, Cooper Industries, Inc. Page 7

8 7. MAINTENANCE/SERVICING The valid regulations IEC for the servicing/maintenance of electrical apparatus for use in potentially explosive atmospheres shall be observed. Prior to opening SynergEX dead front, it is necessary to ensure that the voltage supply has been isolated or to take suitable protective measures. The user is responsible for stipulating the necessary maintenance intervals specific to the application depending on the conditions of use, national directives, and standards. Should the maintenance interval for the function test of an RCD (ELCB) not be defined, the manufacturer of the RCD (ELCB) recommends testing the function by actuating the test button twice yearly. The RCD (ELCB) shall release when the test button is actuated. If this is not the case, the protective function is no longer guaranteed and the RCD (ELCB) shall be replaced. During servicing, above all, the correct working order of parts on which the explosion protection depends (e.g. intactness and efficiency of the flameproof components, the enclosure, the seals, and cable entries shall be checked). If, in the course of servicing, it is ascertained that repairs are necessary, Section 8 of these operating instructions shall be observed. 8. REPAIRS/MODIFICATIONS Only original Cooper Crouse-Hinds / CEAG parts shall be used for carrying out repairs. In the event of damage to the flameproof encapsulation, replacement of the respective components is mandatory. In case of doubt, the respective apparatus shall be sent back to the manufacturer for repair. Repairs that affect the explosion protection may only be carried out by Cooper Crouse-Hinds / CEAG or by a qualified electrician in compliance with the respective national regulations (IEC ). Ex-d components in SynergEX Panelboards may only be replaced by components of the same type (electrical ratings and mechanical size). When replacing these individual built-in components, Section 6.2 ( Opening Apparatus / Electrical Connection ) shall be observed. Apparatus modifications or design changes are not permitted; excluded from this are the fitting of additional cable entries, additional RCD (ELCB), and the installation of connection terminals within the scope of the approvals for the respective apparatus, or according to details laid down by the manufacturer. 9. DISPOSAL/RECYCLING The respective valid national regulations for waste disposal shall be observed when disposing of apparatus. To facilitate recycling of individual parts, parts made of molded plastic shall bear the marking for the type of plastic used. The product range is subject to changes and additions. IF /13 Copyright 2013, Cooper Industries, Inc. Page 8

9 10. DIMENSIONAL DRAWINGS, BREAKERS X 0.98 (25mm) X 1.69 (43mm) 0.22 (ø5.5mm) 0.22 (ø5.5mm) 1.42 (36mm) 2.13 (54mm) X 2.40 (61mm) 0.22 (5.5mm) 2.83 (72mm) X 1.69 (43mm) X 2.40 (61mm) 0.22 (5.5mm) 0.22 (5.5mm) 2.13 (54mm) 2.83 (72mm) X 3.82 (97mm) 0.22 (5.5mm) 4.25 (108mm) IF /13 Copyright 2013, Cooper Industries, Inc. Page 9

10 10.1 Tripping Characteristic of Breakers K - Characteristic 277/480V 10-25A 277/480V 30-40A 120/240V 10-40A 10.2 Derating Table for Breakers 120/240VAC Ambient Temperature T ( C) In (A) /480VAC Ambient Temperature T ( C) In (A) GHG P0001 (-) All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith. Cooper Industries Inc. IF 1659 Crouse-Hinds Division Revision 1 PO Box 4999, Syracuse, New York U.S.A. New 04/13 Copyright 2013, Cooper Industries, Inc.

SynergEX Panelboards for Hazardous Locations

SynergEX Panelboards for Hazardous Locations SynergEX Panelboards for Hazardous Locations Installation & Maintenance Information 1. APPLICATION SynergEX panelboards provide short circuit protection for feeder or branch circuits to control lighting,

More information

Explosion protected terminal boxes type, GHG 72.

Explosion protected terminal boxes type, GHG 72. 1 Technical data 1.1 Plastic terminal boxes GHG 721... ATX type examination certificate BVS 13 ATX 013 X Marking acc. to 94/9/G and standard ATX x (d e mb) II T5* -55 T amb +55 Gb x (d e mb) II T6* -55

More information

Operating Instructions

Operating Instructions Important Information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect

More information

EVZ Series (Small body) Explosion protected luminaire Operating Instructions

EVZ Series (Small body) Explosion protected luminaire Operating Instructions EVZ Series (Small body) Explosion protected luminaire Operating Instructions Cooper Crouse-H i n d s Cooper E l ec t ron i c T ec h n ol og i es ( S h a n g h a i ) Co., L t d. No. 955 Shengli Road, East

More information

Operating Instructions

Operating Instructions Operating Instructions Terminal Box > 8150/1 > 8150/2 Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2 2.2 Operating Instructions Information...2 3 Intended Use...2 4 Safety

More information

9.6 Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

9.6 Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax , E X - C O N T R O L S T A T I O N S Moulded plastic Version for Zone 1 and Zone 21 Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS RTECK terminal boxes RTKB series IEC Ex EX010 TECHNICAL FILES CONTENTS: 1) Contents 2) General information 3) Safety information 4) Conformity to standards 5) Function 6) Technical

More information

A good connection. International approvals.

A good connection. International approvals. E X - P L U G S A N D R E C E P T A C L E S 0 A to 25 A plugs and receptacles plastic version for zone, 2, 2 and 22 A good connection Providing electrical energy there, where it is most needed even in

More information

Operating Instructions

Operating Instructions Operating Instructions Ex UPS Combination of > 8265/5 GUBox control panel > 8316 battery box Contents 1 Contents 1 Contents 2 2 General Information 2 3 Safety Instructions 2 4 Conformity to standards 3

More information

Unused flameproof threads for cable glands have to be closed with certified plugs.

Unused flameproof threads for cable glands have to be closed with certified plugs. E X - P L U G A N D R E C E P T A C L E 1 A Metallic Design for Zone 1 The explosion-protected light metal plug and receptacle devices can be used in the areas of Zone 1 and Zone 2 at no risk of explosion.

More information

EX-REPAIR AND MAINTENANCE RECEPTACLES

EX-REPAIR AND MAINTENANCE RECEPTACLES EX-REPAIR AND MAINTENANCE RECEPTACLES A 3 A plugs and receptacles plastic version for zones, 2, 2 and 22 For maintenance, repair and upgrading work, appliances such as drills, welding transformers, hand

More information

ILED Aquarius Illuminated Windsock. User Manual

ILED Aquarius Illuminated Windsock. User Manual Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 3.1 The light fitting has a type plate:... 4 3.2 The junction box has a type plate:... 5 4. Product Description...

More information

International approvals.

International approvals. E X - P L U G A N D R E C E P T A C L E A to 25 A plugs and receptacles plastic version for Zone 2 A good connection Providing electrical energy there, where it is most needed even in hazardous areas for

More information

5.1. GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A A

5.1. GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A A .1 GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A - 630 A Safety for your protection CEAG safety switches can be protected against inadvertent switching on by our integrated locking facility

More information

Operating Instructions

Operating Instructions Operating Instructions Load and Motor Switch, Load-Break Switch > 8544/1 Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Designated Use...4 5 Technical

More information

EPLX and D2LX lighting panelboards Installation & maintenance information IF 1813 APPLICATION D2LX/EPLX IF SHEET TABLE OF CONTENTS WEIGHTS

EPLX and D2LX lighting panelboards Installation & maintenance information IF 1813 APPLICATION D2LX/EPLX IF SHEET TABLE OF CONTENTS WEIGHTS EPLX and D2LX lighting panelboards Installation & maintenance information APPLICATION EPLX and D2LX panelboards provide a centrally controlled switching system and short circuit protection for feeder or

More information

ILED Dorado. User Manual

ILED Dorado. User Manual 10NM U-code Medium Intensity Obstruction Light Helideck Status Light 15NM U-code Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description...

More information

EStrong-series Emergency Stop

EStrong-series Emergency Stop Original instructions EStrong-series Emergency Stop ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand

More information

Lighting Panelboards EPLU and D2LU Series IF Installation & Maintenance Information APPLICATION

Lighting Panelboards EPLU and D2LU Series IF Installation & Maintenance Information APPLICATION Lighting Panelboards EPLU and D2LU Series Installation & Maintenance Information APPLICATION EPLU and D2LU Series panelboards provide a centrally controlled switching system and short circuit protection

More information

HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL

HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL Subject to change without prior notice TUM5461 REV. B 20.07.2017 IMPORTANT Read this instruction carefully before installing the product

More information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS Champ Fluorescent Luminaires DMVFB Auxiliary Series - 52, 64, & 84 Watt Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE IF 1713 IMPORTANT SAFEGUARDS READ AND FOLLOW

More information

Internationally approved.

Internationally approved. E X - M A N U A L M O T O R S T A R T E R S Up to 2 A Motors have to be protected against over loads, phase failures and overheating: CEAG s power circuit breaker and manual motor starter features phase-failure

More information

Ex m Solenoid Operator Type 0519

Ex m Solenoid Operator Type 0519 nass magnet GmbH Eckenerstrasse 4-6 D-30179 Hannover Doc. No. 113-720-0002 Revision No. 2 01.06.2015 Ex m Solenoid Operator Type 0519 Operating Instructions Dear Customer! To ensure the function and for

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) BExBGL2D LED BEACON For use in Flammable Gas and Dust Atmospheres BExBGL2D 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGIZED POTENTIAL

More information

Operating Instructions

Operating Instructions Operating Instructions Pendant Light Fitting > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Conformity to Standards...3 5 Intended Field of Application...3

More information

EX-D ENCLOSURES AND DISTRIBUTIONS

EX-D ENCLOSURES AND DISTRIBUTIONS EX-D ENCLOSURES AND DISTRIBUTIONS Series GHG made of metal for gases of explosion group IIC To use MCBs, fuses, contactors etc. which give off arcs in potentially hazardous areas, they must be integrated

More information

ATX DPD Series Distribution Panelboards Flameproof

ATX DPD Series Distribution Panelboards Flameproof ATX DPD Series Distribution Panelboards Applications Protection and control of electrical equipment in hazardous areas where ignitable vapors, gases or highly combustible dusts are present. For installation

More information

Load and Motor Switches, Load-Break Switches Series 8549

Load and Motor Switches, Load-Break Switches Series 8549 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Pick-off terminal block Auxiliary

More information

The cover screws and all other external metal parts are made of stainless steel (AISI 316L). International approvals

The cover screws and all other external metal parts are made of stainless steel (AISI 316L). International approvals E X - J U N C T I O N B O X Plastic version for Zone 1,, 1 and The robust junction boxes made of plastic and light alloy are featured by their simple mounting and installation capability and their design.

More information

Operating Instructions Mechanical Temperature Switches ML1H,MT1H,L2H,T2H,L1X/L1X-EX,T1X/T1X-EX,T2X/T2X-EX

Operating Instructions Mechanical Temperature Switches ML1H,MT1H,L2H,T2H,L1X/L1X-EX,T1X/T1X-EX,T2X/T2X-EX ATEX Type Certification marking for type L1X-EX, T1X-EX, T2X-EX Type of protection "d" explosion-proof enclosure Operating Instructions Mechanical Temperature Switches ML1H,MT1H,L2H,T2H,L1X/L1X-EX,T1X/T1X-EX,T2X/T2X-EX

More information

A good connection. International approvals.

A good connection. International approvals. E X - P L U G S A N D R E C E P T A C L E S A to A Plastic version for Zone and Zone A good connection Providing electrical energy there, where it is most needed even in hazardous areas for the Zones,,

More information

VALIADIS S.A. HELLENIC MOTORS

VALIADIS S.A. HELLENIC MOTORS Explosion proof motors MAK 56-250 (MAKe 63-250) series Groups IIB and IIC Ex db / Ex db e (EPL) executions Gb or Ex tb IIIC (EPL) Db II 2 G, II 2D, 2GD SAFETY INSTRUCTIONS Safety Instructions MAK and MAKe

More information

Operating Instructions

Operating Instructions DuroSite & SafeSite Area Light with Adapters Important Information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury,

More information

BMRX Series ROTARY LEVEL CONTROL

BMRX Series ROTARY LEVEL CONTROL BMRX Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0292 Rev C TABLE OF CONTENTS GENERAL SPECIFICATIONS... 3 SAFETY SUMMARY... 4 1.0 INTRODUCTION... 5 2.0 INSTALLATION...

More information

Innovation in soft start technology HFE-2 USER MANUAL. MAN-HFE-002. Version 01

Innovation in soft start technology HFE-2 USER MANUAL. MAN-HFE-002. Version 01 Innovation in soft start technology HFE-2 USER MANUAL MAN-HFE-002. Version 01 HFE-2 user guide Fairford Electronics Ltd Bristow House Gillard Way, Ivybridge PL21 9GG UK www.fairford.com 2016 by Fairford

More information

VSQ SERIES 30 AMP INTERLOCKED SWITCHED RECEPTACLES

VSQ SERIES 30 AMP INTERLOCKED SWITCHED RECEPTACLES INSTALLATION, OPERATION & MAINTENANCE DATA SHEET VSQ SERIES 30 AMP INTERLOCKED SWITCHED RECEPTACLES CLASS I, GROUPS B, C, D; CLASS I ZONE 1, GROUPS IIB, IIA +H2; CLASS II, GROUPS F & G; & CLASS III HAZARDOUS

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) BExBG10D-P and BExBG15D-P Flameproof Xenon Beacons For use in Flammable Gas and Dust Atmospheres BExBG10D-P / BExBG15D-P 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE

More information

Main current switches >180 A are realized in metal enclosures. Internationally approved.

Main current switches >180 A are realized in metal enclosures. Internationally approved. E X - M A I N C U R R E N T S W I T C H E S 10 A - 80 A (up to 630 A) CEAG main current switches in a number of versions can be protected against inadvertent switching on by our integrated locking facility

More information

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489 MINIATURE CIRCUIT BREAKERS SU200M Datasheet Branch protection acc. to CSA C22.2 No.5 / UL 489 The miniature circuit breaker SU200 M is ABB s solution for UL 489 branch circuit protection up to 480 Y/277

More information

Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600

Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600 Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600 Installation Guide WBP-Box-IEN103320 IMEN-WBP-BOX Version 2.0 EN SMA Solar Technology AG Table of Contents Table of Contents

More information

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3

EN Operating manual. Motorised zone valve. Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3 EN Operating manual Motorised zone valve Three-way, 22 mm & 28 mm 3PV2, 3PV8 & VRMH3 This manual ensures safe and efficient use of the 3PV2 or 3PV8 force-actuated three-way valve with spring-loaded return

More information

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions Segurança TC RU C-DE.ГБ06.B.00230 OCP 0004 Compulsório INMETRO Operation Manual and Installation Instructions Segurança PSB Heating System Cold applied connection technology Compulsório Type 27-1680-...0/...

More information

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10. BATTERY MODULE Long Life Battery: 10 to 12 Years According to EUROBAT Small Mounting Footprint Easy Access to the Terminals and the Fuse Heavy Duty Fuse Holder and Spare Fuse Included 3 Year Warranty,

More information

Load and Motor Switches, Load-Break Switches Series 8544

Load and Motor Switches, Load-Break Switches Series 8544 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: alligator clip auxiliary

More information

Zone 1 Linear Range - Installation Guide

Zone 1 Linear Range - Installation Guide Zone 1 Linear Range - Installation Guide CML14ATEX3119 & IEC Ex CML15.0001 This installation guide provides instructions for installing SPARTAN series of explosion protected Zone 1 Linear luminaires. Text

More information

EPS 16 ATEX 1072 X, IECEx EPS X. Operating Instructions. Solenoid coil Type AC19 Magnetspule Typ AC19 Bobine magnétique Type AC19

EPS 16 ATEX 1072 X, IECEx EPS X. Operating Instructions. Solenoid coil Type AC19 Magnetspule Typ AC19 Bobine magnétique Type AC19 , IECEx EPS 16.0030X Solenoid coil Type AC19 Magnetspule Typ AC19 Bobine magnétique Type AC19 Device with II 2G/D Ex approval Geräte mit II 2G/D Ex Zulassung Appareils avec mode de protection II 2G/D Ex

More information

Technical Data. Dimensions

Technical Data. Dimensions Model Number Features 40 mm flush 4-wire DC ATEX-approval for zone 2 and zone 22 S Technical Data specifications Switching element function PNP NO/NC Rated operating distance s n 40 mm Installation flush

More information

Control Panels, Distribution Panels and Components

Control Panels, Distribution Panels and Components 11 Control Panels, Distribution Panels and Components EEx d Enclosures in Light Metal or stainless steel Flexible modular design for combining enclosures Can be used in Zone 1 and Zone 2 in Zone 21 and

More information

Load disconnect switch Series 8146/5-V11

Load disconnect switch Series 8146/5-V11 www.stahl.de Load disconnect switch > Motor switching capacity AC-3 and AC-23 acc. to DIN VDE 0660 part 107 IEC/EN 60947-3 > Isolating characteristics acc. to IEC/EN 60947-3 > Positive opening operation

More information

Linear Luminaire for Fluorescent Lamps

Linear Luminaire for Fluorescent Lamps Linear Luminaire for Fluorescent Lamps Operating instructions Additional languages www.stahl-ex.com General Information Contents 1 General Information...2 1.1 Manufacturer...2 1.2 Information regarding

More information

I Ex-Safety switches I

I Ex-Safety switches I 3-pole, 20 A Technical data Ex-Safety switch 20 A for variable-speed three-phase drives Marking to 94/9/EC II 2 G Ex ed ia IIC T6 / II 2 D Ex td A21 IP66 T80 C EC-Type Examination Certificate PTB 99 ATEX

More information

Dimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 162, S2, SF*2, S2L, SF*2L = 170, S3, SF*3 = 250,

Dimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 162, S2, SF*2, S2L, SF*2L = 170, S3, SF*3 = 250, Assembly Instructions for junction boxes type: Assembly Instructions for: S1 to S / SFI1 to SFI / SFE1 to SFE S1 to S Junction Boxes MS1 to MS Junction Boxes IMPORTANT: This document should be read carefully

More information

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN Electropneumatic Converters i/p Converters Type 6111 Fig. 1 Type 6111 in standard version Fig. Type 6111 mounted on a supply air manifold Fig. 3 Type 6111 in field enclosure Mounting and Operating Instructions

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440

CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440 CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440 APPLICATION SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE CSR compact fused interlocked ARKTITE

More information

I 16A 2-pole up to 50 V I I 16A 3-pole up to 50 V I

I 16A 2-pole up to 50 V I I 16A 3-pole up to 50 V I I 6A 2-pole up to 50 V I I 6A 3-pole up to 50 V I Flange socket Coupler Technical data Ex-plugs and receptacles for low voltage, 2- and 3-pole acc. to IEC 60309-/2 Marking accd. to 94/9/EC II 2 G Ex de

More information

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE 24V, 7Ah Battery Capacity (2x 12V Batteries in Series) Small Mounting Footprint 2m Power Leads Included PT1000 Sensor for Battery Module Temperature Included Includes a Center-tap Terminal

More information

Load and Motor Switches, Load-Break Switches Series 8544

Load and Motor Switches, Load-Break Switches Series 8544 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Alligator clip Auxiliary

More information

PTB 14 ATEX 2023 X, IECEx PTB X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10

PTB 14 ATEX 2023 X, IECEx PTB X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10 , IECEx PTB 14.0049X Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10 Device with II 2G/D Ex approval Geräte mit II 2G/D Ex Zulassung Appareils avec mode de protection II 2G/D Ex

More information

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T**

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T** Assembly Instructions for: S1 Assembly to S Junction Instructions Boxes for: MS1 to MS Junction Boxes Boxes MS1 to MS Junction Boxes IMPORTANT: This document should be read carefully before commencing

More information

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax , E X - M A N U A L M O T O R S T A R T E R S Up to A Motors have to be protected against over loads, phase failures and overheating: CEAG's power circuit breaker and manual motor starter features phase-failure

More information

Control Buttons / Switches for Panel Mounting Series 8003

Control Buttons / Switches for Panel Mounting Series 8003 www.stahl.de > Different actuators pushbutton mushroom pushbutton mushroom stay-put button mushroom stay-put button with key lock key-operated button key-operated switch > 2 contact elements > Spring clamp

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Type 5404 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation Contents 1 Operating instructions...2 2 Intended use...3 3

More information

10 Load and Motor Switchgear

10 Load and Motor Switchgear 10 Load and Motor gear Safety es 01941E00 Safety switches ensure the obligatory isolation of electrical power under condition of equipment cleaning, maintenance and repair. Other methods of isolation,

More information

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401 > As wall, ceiling and pendant light fitting or pole mounted light fitting > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp

More information

I Ex-safety switches I

I Ex-safety switches I 3-pole, 20 A Technical data Ex-safety switches 20 A for controlled three-phase drives Marking accd. to 94/9/EC II 2 G Ex ed ia IIC T6 / II 2 D Ex td A21 IP66 T80 C EC-Type Examination Certificate PTB 99

More information

EX Series User Manual

EX Series User Manual MODELS: EX90L T4 IIB 720 DS, EX90L T4 IIB 1440 SS, EX90L T4 IIC 720 SS EXIN LIGHT EX & INDUSTRIAL LIGHTING EX Series EX90L T4 IIB 720 DS, EX90L T4 IIB 1440 SS, EX90L T4 IIC 720 SS Contents 0. Introduction

More information

Power distribution SynergEX panelboards. SynergEX. Class I, Division 2 panelboards

Power distribution SynergEX panelboards. SynergEX. Class I, Division 2 panelboards Power distribution SynergEX panelboards SynergEX Class I, Division 2 panelboards SynergEX panelboards for hazardous rated areas Maximum safety. Easy access, lower risk and less downtime. One of the biggest

More information

Safety Switches Series 8537

Safety Switches Series 8537 Safety Switches www.stahl.de > 3- and 6-pole switches 12 / 16, 25, 40, 63 / 80, 125 / 160, 250, 315, 400, 500 A > Motor switching capacity AC-3 and AC-23 acc. to IEC 60947-3, EN 60947, DIN VDE 0660 part

More information

I Ex-control stations I

I Ex-control stations I Type 11 83 Type 11 82 Type 11 81 Technical data Ex-control stations Type 11 81 I Type 11 82 I Type 11 83 Marking accd. to 9/9/EC II 2 G Ex ed ib m IIC T6 II 2 D Ex td A21 IP66 T80 C EC-Type Examination

More information

I Ex-safety switches I

I Ex-safety switches I EMERGENCY STOP EMERGENCY STOP Technical data Ex-safety switches 12 A Marking accd. to 94/9/EC II 2 G Ex de IIC T6 / II 2 D Ex td A21 IP66 T80 C EC-Type Examination Certificate PTB 99 ATEX 1164 PTB 00 ATEX

More information

Emergency Light Fitting for Fluorescent Lamps Series 6009

Emergency Light Fitting for Fluorescent Lamps Series 6009 > As wall, ceiling and pendant light fitting or pole mounted light fitting > Version with 2 lamps: 18 W and 36 W > Central locking > All-pole disconnection via N/C switch when opening light fitting or

More information

NEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH

NEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH NEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH INSTALLATION AND OPERATION MANUAL PN 610-0006 Rev E WARNING CAUTION SPECIAL CONDITIONS FOR SAFE USE NOTE Manual No. 610-0006 Rev

More information

P SERIES POWERPLEX DISTRIBUTION PANELBOARDS SAFETY MADE SIMPLE

P SERIES POWERPLEX DISTRIBUTION PANELBOARDS SAFETY MADE SIMPLE P SERIES POWERPLEX DISTRIBUTION PANELBOARDS SAFETY MADE SIMPLE A BREAKER PROTECTION BREAKTHROUGH Simplify flameproof protection for lighting, heat trace and power circuit distribution with the new generation

More information

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch

More information

IQL Helios Area-/Streetlight. User Manual

IQL Helios Area-/Streetlight. User Manual Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description... 5 5. Specifications... 6 5.1 General... 6 5.2 Dimensions... 6 6. Installation...

More information

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

Light Fitting for Fluorescent Lamps Series ECOLUX 6600 > 1- or 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series

More information

Position Switches Series 8060/2

Position Switches Series 8060/2 www.stahl.de > Ex e plastic enclosure > Operating temperature range -60 to +60 C > Dimensions and characteristic values according to EN 50047 > Degree of protection IP66 / IP67 > Extensive assortment of

More information

CCAI, CCAIF, CCAIF..H

CCAI, CCAIF, CCAIF..H CCAI, CCAIF, CCAIF..H - Zone 1, 2, 21, 22 - Group IIC - Stainless steel junction boxes - Choice of 4 sizes - IP66 AISI 316L stainless steel Grub screws for opening lid Lid opening system Detail of inside

More information

US CATALOG. ProLine Panelboard and breakers

US CATALOG. ProLine Panelboard and breakers US CATALOG ProLine Panelboard and breakers 2 PROLINE PANELBOARD AND BREAKERS PROLINE PANELBOARD AND BREAKERS 3 Table of contents 004 006 Description and features 007 008 Guides: and breaker placement 009

More information

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW) Product datasheet Characteristics ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/400...440V(45kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

Operating / Assembly Instructions Type A and CS Coupling

Operating / Assembly Instructions Type A and CS Coupling Page: 1 of 14 Subject Index 1. Technical Data 2. Hints 2.1. General Hints 2.2. Warning and Safety Hints. 2.3. General Hints to Danger. 2.4. Proper use. 3. Storage. 4. Assembly. 4.1. Coupling components.

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Operating Instructions

Operating Instructions Operating Instructions Pendant Light Fitting > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Notes Regarding Safety...3 4 Intended Area of Application...4 5 Technical Data...5

More information

Solenoid Valves Type 3963

Solenoid Valves Type 3963 Mounting and Operating Instructions Solenoid Valves Type 3963 Fig. 1 General Assembly, commissioning and operation of these devices may only be performed by experienced personnel. Proper shipping and appropriate

More information

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600 > 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series 6600

More information

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581 www.stahl.de > Various versions Extra-low voltage up to 16 A 16, 32, 125 A > Large handle, can be locked in position 0 and I > Clear switch position indication > Optimal contact by means of self-cleaning

More information

Assembly instruction. Pendant Light Toccata GENERAL REMARKS ON SAFETY: Technical data: BOM

Assembly instruction. Pendant Light Toccata GENERAL REMARKS ON SAFETY: Technical data: BOM GENERAL REMARKS ON SAFETY: Read all of these instructions before installing fixtures. Keep all of the instructions for future reference. Turn off power before installing fixture. Installation is to be

More information

Linear Luminaire with LED

Linear Luminaire with LED Linear Luminaire with LED Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3 1.3

More information

USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE /..

USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE /.. d.o.o. tel. 049 222 900, fax 049 426 450 e-mail: tepex@tepex.hr www.tepex.hr USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE 0403.24/.. No: TEPEx.RS.077 Rev : 0 Date: 02.2016. CONTENT 1. Manufacturer

More information

Switching DC Power Supply

Switching DC Power Supply 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Model 1693, 1694 Switching DC Power Supply INSTRUCTION MANUAL 1 Safety Summary

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

Installation Accessories

Installation Accessories Installation Accessories Elektrostatische Aufladung vermeiden. Nur mit feuchtem Tuch säubern. Evitez lez charges electrotetiques Nettoyer unkjuement avec un chifion humide. Avold electrostatic charge.

More information

CEAG Products Main Catalogue Part 1 Chapter 3. Emergency and safety light fittings. EATON 1.3.1

CEAG Products Main Catalogue Part 1 Chapter 3. Emergency and safety light fittings.  EATON 1.3.1 CEAG Products Main Catalogue Part 1 Chapter Emergency and safety light fittings www.crouse-hinds.de EATON 1..1 .1..2.1..2 EATON'S CROUSE-HINDS BUSINESS EATON Ex-Signal- and Rettungszeichenleuchten www.crouse-hinds.de

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

APPLICATION MANUAL. Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin

APPLICATION MANUAL. Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin Updated 09.11.16 APPLICATION MANUAL Universal Explosionproof Two-Compartments Instrument Housing Type: XD-ID100, XD-ID100win, XD-ID100H, XD-ID100Hwin Contents: 1. Destination. 2. Flameproof joints, process

More information

Control Stations & Switches: Control Stations Increased Safety Unicode 2 Series: Pre-drilled Control Stations

Control Stations & Switches: Control Stations Increased Safety Unicode 2 Series: Pre-drilled Control Stations Unicode 2 Series: Pre-drilled Control Stations Polamide U43W211 Polyester U23W211 Compliance Data: ATEX IEC and IECEx (Polyester): Stainless Steel U62W229 Aluminum U83W211 ATEX IEC / IECEx CE Ex de IIC

More information

Position Switches Series 8074/2

Position Switches Series 8074/2 www.stahl.de > Ex e metal enclosure > Operating temperature range -40 C... +70 C > Dimensions and characteristic values according to EN 50041 > Degree of protection IP66 > Extensive assortment of actuators,

More information

Floodlight Range Installation Guide

Floodlight Range Installation Guide SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information