1 DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc
2 ASHARE 110 A Method of Testing Three components Face velocity measurements Smoke visualization Tracer gas testing Owner sets acceptance levels The problem What do you do when the results are unacceptable?
3 General Approach Operational Problems Tracer gas leakage Reentry Hood problems Aerodynamics Operations Room Conditions Other Considerations
4 Gas Delivery System Leakage Symptoms Steady increase No reduction when gas is turned off Analysis Use meter as a leak meter Solution Stop leak Place cylinder inside hood
5 Cylinder Inside the Hood
6 Reentry Tracer gas released inside the hood Characteristics Delayed onset Tracer gas in the room Often slow decay
7 Potential Reentry
8 Room Concentration
9 Repeat with Different Wind
10 Smoke Visualization ASHRAE 110 Failure Smoke spills out Diagnostic testing Lazy air Reverse air flow Interior roll
11 Reverse Flow Reverse flow
12 Lazy Flow Lazy Flow
13 Good sweeping flow Good Sweeping Action
14 Roll in top of hood Smoke Showing the Hood Roll
15 Summary Poor flow characteristic can pass but can contribute to poor performance Repeat somke tests with mannequin Vortex formed by mannequin interacts with the weak airflow in the hood Can show spillage where not seen without the mannequin
16 Equipment in the Hood
17 Other Issues Equipment in hood Sash Position Mandates other than left, right, center Difference between use and design Heat sources or disturbances in hood Work position Operator position
18 Room Air Supply The supply ventilation design is as important (or more important than) the exhaust ventilation design Rule of thumb: Room air currents in the laboratory near the hood should be less than half, preferably less than one third, of the face velocity
19 Room Air Currents Cross Draft Grid & Probe Orientation Top View Horizontal Draft Vertical Perpendicular Horizontal Left Center Right Vertical Draft Stand Perpendicular Draft High Midpoint Low Front View Side View
20 Minor Room Air Currents Hood 628, Position A, 52.5 inches 100 Velocity, fpm Vertical Perpendicular Horizontal Time, Seconds
21 Significant Room Air Currents Hood 628, Position AB, 52.5 inches 100 Velocity, fpm Vertical Perpendicular Horizontal Time, seconds
22 Case History New 12-foot bench top hoods Acceptance level AI 0.05 Preliminary tests not acceptable Diagnostic testing Reverse flow at work surface High Turbulence in laboratory High Cross drafts near hood Temperature variable in laboratory
23 Original Design
24 Approach Change diffusers to reduce room air turbulence Modify airfoil on laboratory hoods Modify room temperature control Recalibrate CV supply and exhaust boxes Rewire part of Building Management System Readout matched boxes
25 Diffuser Replacement
26 Original Diffuser and Hood Hood Rating 0.45
27 Change Diffuser Hood Rating 0.03
28 Changed Diffuser Modified Airfoil Hood Rating <0.01
29 Conclusions In many instances ASHRAE 110 can be used diagnostically to determine the probable cause of poor hood performance
30 Other Test Dynamic tests Human as a mannequin Artificial clutter Walk by tests Large apparatus (walk in hoods) Floor mounted fans
31 Philosophy Provides additional information relative to robustness Often no correlation to safety Interpretation is difficult
32 Caution Hoods are designed for specific strength Some hood manufacturers modifies the hood to provide strength in the top of the hood Reduce roll Airfoil that tends to lift the air up Some manufacturers provide a strong base Exceptional turning action by airfoil Piston flow in lower portion of the hood Many manufactures design for general flow
33 Manufacture Recommended Tests Higher release rate is better controlled by a hood strong at the top A lower diffuser is better controlled by a hood strong along the work surface Boxes and induced flow may work bit the geometry may be critical Some tests can be self serving
34 Conclusion Special tests are useful and provide additional information concerning the robustness of the hood Often suggested by user but have no comparative basis Hood manufactures recommend tests that favor their hoods
Lab Safety & Energy Optimization. Introduction & Agenda
Lab Safety & Energy Optimization Determining Appropriate Airflow Specifications for VAV Fume Hoods Thomas C. Smith tcsmith@labhoodpro.com Introduction & Agenda Thomas C. Smith President, BSME (NCSU), MSEE
More informationDEPAUL UNIVERSITY. Fume Hoods Manual. Environmental Health & Safety. April 2017
DEPAUL UNIVERSITY Fume Hoods Manual Environmental Health & Safety April 2017 1 TABLE OF CONTENTS SECTION PAGE NO. 1. INTRODUCTION 2 2. TYPES OF FUME HOODS 2 2.1 CONVENTIONAL FUME HOODS 2 2.2 HIGH PERFORMANCE
More informationSupreme AirLV- FUME HOODS. KEWAUNEE encouraging new discovery LOW CONSTANT VOLUME
Supreme AirLV- LOW CONSTANT VOLUME FUME HOODS KEWAUNEE encouraging new discovery Supreme Air LV Fume Hood Low Velocity Low Volume Full Access Hold-Open Catch for set-up sash position Flush Mounted Convergent
More informationVOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes
Stainless Steel Pitot Airflow Traverse Probes The VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probe is ideally suited for new installations or retrofit applications requiring accurate airflow
More informationFume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall:
Fume Hood Standard A fume hood is an enclosed working chamber fitted with an exhaust ventilation system. It is one component of an exposure control system which is designed to contain, dilute and disperse
More informationDesign Standard - Fume Hoods & Fume Hood Exhausts
Design Standard - Fume Hoods & Fume Hood Exhausts 1.0 Introduction The fume hood is the primary control device in most laboratories for protecting employees and students from exposure to hazardous chemicals.
More informationFUME HOOD SELECTION GUIDE
FUME HOOD SELECTION GUIDE FUME HOOD SELECTION GUIDE Laboratory fume hoods are one of the most vital pieces of safety equipment in a working laboratory. Fume hoods are designed to safely exhaust dangerous
More informationUSER'S GUIDE TO FUME HOODS. Procedures for Increasing the Effectiveness of Laboratory Hoods. Revised December, Hood Basics
USER'S GUIDE TO FUME HOODS Procedures for Increasing the Effectiveness of Laboratory Hoods Revised December, 1998 A laboratory fume hood system is designed to protect the operator from undesirable substances
More informationProtector XStream Laboratory Hood is shown with SpillStopper Work Surface , Protector Acid Storage Cabinet and Protector
Protector XStream Laboratory Hood 9840600 is shown with SpillStopper Work Surface 9849800, Protector Acid Storage Cabinet 9901100 and Protector Standard Storage Cabinet 9900100. Protector XStream Laboratory
More informationRequires Ductwork and Blower
6' Protector XStream Laboratory Hood 9840600 is shown with SpillStopper Work Surface 9849800, Protector Acid Storage Cabinet 9901100 and Protector Standard Storage Cabinet 9900100. Requires Ductwork and
More information3.5 Exposure Control Measures
3.5 Exposure Control Measures 3.5.1 Chemical Fume Hoods Chemical fume hoods are the most reliable and primary engineering control used in the laboratory to protect against the inhalation of hazardous vapors
More informationHow to Use a Chemical Fume Hood Safely
Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) How to Use a Chemical Fume Hood Safely SafetyNet #: 35 A chemical fume hood is designed to protect the worker from volatile and
More informationASHRAE 110 Test Report Cover Sheet
SHRE 110 Test Report over Sheet lient: mgen orporation One mgen center rive Thousand Oaks 91320-3424 Ray Russell Test Report # : 1 Test ate # : 1/6/2005 Lead Technician: Joe Tech Test Report Scope and
More information---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2
Environmental Health & Safety RADIATION PROCEDURES MANUAL Procedure Cover Sheet Procedure Title: Fume Hoods Procedure Number: EHS-08-03-REV 2 Effective Date: 18 September, 2018 ---:...-- Approved By_-=--------::.--...l~---
More informationIntroducing NJK Precision Airflow Measuring Stations
Introducing Precision Airflow Measuring Stations A new and unique airflow measuring station that accurately measures airflows at very low flow rates and can operate in physically restrictive applications
More informationSpring Air Systems FN-B-MB-10/4.5-VE Wall-Mounted Canopy Exhaust Hood Performance Report
Spring Air Systems FN-B-MB-10/4.5-VE Wall-Mounted Canopy Exhaust Hood Performance Report Application of ASTM Standard Test Method F1704-09 FSTC Report 501311275 Food Service Technology Center Prepared
More informationTable of Contents. Page 2 Page 2 Page 2 Page 2 Page 3 Page 3 Page 3 Page 3 Page 3 Page 4 Page 4 Page 4 Page 5 Page 5 Page 5
-02 - Location and Mounting: AirflowMonitoringStation Table of Contents #1 - Right Angle wo/turning Vanes Mounting #2 - Right Angle w/turning Vanes Mounting #3 - Right Angle w/rounded Elbow Mounting #4
More informationTABLE OF CONTENTS STANDARDS FOR THE DESIGN, CONSTRUCTION, MAINTENANCE AND USE OF LABORATORY FUME HOODS. Effective August 2010
TABLE OF CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 2 BACKGROUND... 2 FUME HOOD DESIGN AND CONSTRUCTION... 3 VARIABLE AIR VOLUME FUME HOODS... 3 RECIRCULATING HOODS... 3 SPECIAL LABORATORY FUME HOODS...
More informationSECTION LABORATORY FUME HOODS UNIFLOW LE SERIES
SECTION 11610.1 LABORATORY LE FUME HOODS UNIFLOW LE SERIES REVISED AUGUST 2, 2013 LABORATORY FUME HOODS UNIFLOW LE SERIES PART 1 GENERAL 1.00 SUMMARY A. Section Includes: 1. Laboratory Fume Hoods B. Related
More informationDaikin Steam Coils. Installation and Maintenance Manual IM 901. Types HI-F5, HI-F8, & E-F5. Group: Applied Air. Part Number: IM 901
Installation and Maintenance Manual IM 901 Daikin Steam Coils Group: Applied Air Part Number: IM 901 Date: February 2008 Types HI-F5, HI-F8, & E-F5 2008 Daikin Applied Contents Introduction... 3 General
More informationSECTION LABORATORY FUME HOODS
SECTION 115313 LABORATORY FUME HOODS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes Laboratory Fume Hoods: B. Related Sections include the following: 1. [Division 12 Section Painted Steel Laboratory
More informationGeneral Purpose Walk-In Fume Hood
General Purpose Walk-In Fume Hood with Vertical Rising Sash Available Models: Open By-Pass Restricted By-Pass Auxiliary Air Available Option: Adjustable Baffles Air Flow and Static Pressure Alarms Service
More information2.6. Air Flow Control Valve Type PRD
2.6. Air Flow Control Valve Type PRD Page 1/10 Air Flow Control Valve, Type PRD Page 2/10 Air Flow Control Valve Type PRD Description and Design The PRD remains the air valve of choice for critical heating,
More informationScope and Application of ASTM 1704, Standard Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems
Scope and Application of ASTM 1704, Standard Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems The capture and containment exhaust air flow rates for
More informationAUDIO-VISUAL EQUIPMENT
11 52 00 AUDIO-VISUAL EQUIPMENT 1. GENERAL A. Related sections: i. 00 00 13 Designing Learning Environments ii. 11 52 13 Projection Screens iii. 12 56 52 Audio-Visual Equipment iv. 72 41 00 General Audio-Visual
More informationBench fume hood with horizontal sash - 14" working sash height. Bench fume hood with vertical sliding doors 14" working gap between doors
UNIVERSITY OF HOUSTON ENVIRONMENTAL HEALTH AND SAFETY POLICIES AND PROCEDURES SECTION: SUBJECT: ENVIRONMENTAL HEALTH AND SAFETY LABORATORY FUME HOODS I. PURPOSE These laboratory fume hood survey procedures
More informationGeneral Purpose Walk-In Fume Hood
General Purpose Walk-In Fume Hood with Vertical Rising Sash Available Models: Open By-Pass Restricted By-Pass Auxiliary Air Available Option: Adjustable Baffles Air Flow and Static Pressure Alarms Service
More informationPennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume
PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing
More informationStudy on Flow Fields in Variable Area Nozzles for Radial Turbines
Vol. 4 No. 2 August 27 Study on Fields in Variable Area Nozzles for Radial Turbines TAMAKI Hideaki : Doctor of Engineering, P. E. Jp, Manager, Turbo Machinery Department, Product Development Center, Corporate
More informationDesign Requirements The system shall be designed, manufactured, tested and installed in compliance with the current versions or issuance of:
SECTION 15877 FUME HOODS 1. General 1.1. Summary These specifications provide a performance specification for a chemical laboratory Fume Hood (herein referred to as FH). The intent of the specification
More informationLFBC - LATERAL FLOW BIO CONTAINMENT FOR HPAPI PROCESSING FLOW SCIENCES, INC.
LFBC - LATERAL FLOW BIO CONTAINMENT FOR HPAPI PROCESSING FLOW SCIENCES, INC. LFBC THE FLOW SCIENCES GLOVEBOX WORKSTATION SERIES safety. The Glovebox Workstation series provides provides containment containment
More informationSTATE UNIVERSITY CONSTRUCTION FUND
DIRECTIVE 15H-8 Issue date: June 2016 1. General Design Criteria LABORATORY DESIGN a. Design a Pressure Independent Variable Volume system that satisfies the airflow demand of the fume hoods, minimum air
More informationGaylord 30-inch Tall ELX-ND-BDL-54 Wall-Mounted Canopy Exhaust Hood Performance Report
Gaylord 30-inch Tall ELX-ND-BDL-54 Wall-Mounted Canopy Exhaust Hood Performance Report Application of ASTM Standard Method F1704-09 FSTC Report 5011.09.06-R1 Food Service Technology Center Prepared by:
More informationFume cupboards and extraction devices
Fume cupboards and extraction devices Energy efficiency, maximum ergonomics and a larger internal workspace make working with our new fume cupboards even safer and more convenient. A new design together
More informationLaboratory Fume Hood. Operation & Maintenance Manual APR 2005
Laboratory Fume Hood Operation & Maintenance Manual APR 2005 TABLE OF CONTENTS I. Introduction p. 3 II. Fume Hood Services p. 4 III. Operation Recommendations p. 4 IV. General Fume Hood Maintenance p.
More informationLaboratory Demonstration Space Located at Price Research Center North Winnipeg. Fume Hoods. ehpricesales.com
Laboratory Demonstration Space Located at Price Research Center North Winnipeg Fume Hoods ehpricesales.com 2 www.ehpricesales.com FUME HOODS Contents Dynamic Bench Fume Hood Features High Performance Fume
More information.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section )
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying Laboratory Fume Hoods. These standards are not intended to restrict or replace professional judgment..2
More informationFVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description
TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2100/2200 FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER MODEL 2100: Constant face velocity, variable volume MODEL 2200: Constant face velocity, variable volume
More informationVentilated Balance Enclosures
Ventilated Balance Enclosures by PLAS n LABS Meets and exceeds ANSI/ASHRAE 110:2016 standard for containment & performance PLAS n LABS, INC. www.plas-labs.com PLI@PLAS-LABS.com 517-372-7177 Ventilated
More informationAir Sentry High Performance Fume Hood Operation & Maintenance Manual
Air Sentry High Performance Fume Hood Operation & Maintenance Manual Revision 8 TABLE OF CONTENTS I. Introduction p. 3 II. High Performance Fume Hoods p. 4 III. Vortex Control System p. 5 IV. Uncrating
More informationFOR USE IN SOLUTION AIR HANDLING UNITS
AMS-60 AIRFLOW MONITORING DEVICE APPLICATION GUIDE Supersedes: NOTHING Form 102.20-AG1 (303) FOR USE IN SOLUTION AIR HANDLING UNITS GENERAL The YORK AMS-60 is an airflow monitoring device which combines
More informationAlarge portion of kitchen ventilation planning is dedicated to
By Richard T. Swierczyna, Associate Member ASHRAE, & Paul A. Sobiski, Associate Member ASHRAE Alarge portion of kitchen ventilation planning is dedicated to properly exhausting cooking effluent. Appliance
More informationElement D Services Heating Ventilating and Air Conditioning ODG010107
Element D Services Heating Ventilating and Air Conditioning ODG010107 D304202 Laboratory Exhaust and Ventilation Part 1. General 1. This section supplements Design Guideline Element D3042 on air handling
More informationFacts, Fun and Fallacies about Fin-less Model Rocket Design
Facts, Fun and Fallacies about Fin-less Model Rocket Design Introduction Fin-less model rocket design has long been a subject of debate among rocketeers wishing to build and fly true scale models of space
More informationPre-lab Questions: Please review chapters 19 and 20 of your textbook
Introduction Magnetism and electricity are closely related. Moving charges make magnetic fields. Wires carrying electrical current in a part of space where there is a magnetic field experience a force.
More informationAir Flow Factors. Alnor Model 6070, 6000, 2220, or 2220-A Probe Orientation
ir Flow Factors Model: TDC irflow Measurements Procedure 1. Record diffuser velocities with lnor probe in the locations and orientation shown the velocity Measurement Location Chart. Note: Each diagram
More informationJanuary, 2014 Page 1 of 6
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying chemical fume hood modifications or installations. These standards are not intended to restrict or replace
More informationDemand Based Static Pressure Reset Control for Laboratories
Accutrol, LLC Product Sheet Demand Based Static Pressure Reset Control for Laboratories Accutrol, LLC 21 Commerce Drive, Danbury, CT 06810 203-445-9991 www.accutrolllc.com Contents and specifications are
More informationFume Hood Operation & Maintenance Manual
Fume Hood Operation & Maintenance Manual Fume Hood Operation & Maintenance Manual TABLE OF CONTENTS Fume Hood Applications 2 Safety 3 Aerodynamic Principles & Safety 4 Fume Hood Cleaning 7 Basic Maintenance
More informationGround Effect and Turbulence Simulation at the Pininfarina Wind Tunnel. Giuseppe Carlino Aerodynamic and Aeroacoustic Research Center
Ground Effect and Turbulence Simulation at the Pininfarina Wind Tunnel Giuseppe Carlino Aerodynamic and Aeroacoustic Research Center The Aerodynamic and Aeroacoustic Research Center The Full Scale Automotive
More informationCompressor Noise Control
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1972 Compressor Noise Control G. M. Diehl Ingersoll-Rand Research Follow this and additional
More informationAUTOMOTIVE TESTING AND OPTIMIZATION. Tools for designing tomorrow's vehicles
AUTOMOTIVE TESTING AND OPTIMIZATION Tools for designing tomorrow's vehicles 2 Measurement of flow around the side mirror by Particle Image Velocimetry (PIV). Courtesy of Visteon Deutschland GmbH Our advanced
More informationLive Wire Owner s Manual
Live Wire Owner s Manual Battery Replacement Introduction Features Precautions Tool Description Purpose Using the Tool Model MB0414L, MB0414H www.origocorp.com Operating the Tool How it Works Quick Summary
More informationEnergy Recovery Laboratory Exhaust
Energy Recovery Laboratory Exhaust Model Vektor -ERS For Vektor-M, MH and MS Systems January 2018 Model Vektor -ERS Greenheck s Vektor -ERS is a pre-engineered laboratory exhaust energy recovery system.
More informationnew fume hoods providing performance and protection
new fume hoods providing performance and protection five questions to get us started 1. Will the use of your hood require a special application hood? 2. How high of a priority is energy conservation? 3.
More informationFaraday s Electromagnetic Lab
Name Section Date CONCEPTUAL PHYSICS Electromagnetic Induction: Generators and Alternating Current Tech Lab Electromagnetism Sim Faraday s Electromagnetic Lab Purpose To manipulate simulated magnets, compasses,
More informationFume Hoods Overview OVERVIEW
OVERVIEW What Is A Fume Hood - A laboratory chemical fume hood is first and foremost a safety device. Users need to be able to rely on their fume hood as a primary containment device to protect them from
More informationThe A4 Paper Test Page 1 of (C)
The A4 Paper Test Page 1 of 5 2010-10-25 (C) A4 Paper Test_R1.doc Version: R1 The A4 Paper Test Without access to suitable measuring equipment, the most effective method to correctly calibrate the oven
More informationChapter 11: Flow over bodies. Lift and drag
Chapter 11: Flow over bodies. Lift and drag Objectives Have an intuitive understanding of the various physical phenomena such as drag, friction and pressure drag, drag reduction, and lift. Calculate the
More informationComputer-Assisted Induction Aluminum
Home Computer-Assisted Induction Aluminum Brazing November 11, 2003 Coupled electromagnetic and thermal computer simulation provides a sufficient basis for process optimization and quality improvement
More informationGaylord Company, Model EL-ND-BDL-54 Wall-Mounted Canopy Exhaust Hood Performance Report
Gaylord Company, Model EL-ND-BDL-54 Wall-Mounted Canopy Exhaust Hood Performance Report Application of ASTM Standard Test Method F 1704-05 Food Service Technology Center (www.fishnick.com) -R1 Prepared
More informationLABORATORY FUME HOODS
Fume Hoods Fume Hood Applications Laboratory professionals and students across the country, and all over the world, depend on the safety of our hoods. Your protection is our first concern and the fume
More informationProtector XStream Laboratory Hoods
High Performance Hood offers enhanced containment combined with energy savings. With its unsurpassed containment and substantial energy savings potential, the patented* Protector XStream Fume Hood delivers
More informationABSTRACT INTRODUCTION
Wind tunnel investigation of waste air re-entry with wall ventilation P. Broas Technical Research Centre of Finland, Ship Laboratory, Tekniikantie 12, SF-02150, Espoo, Finland ABSTRACT A wind tunnel investigation
More informationA. Perform a vacuum gauge test to determine engine condition and performance.
ENGINE REPAIR UNIT 2: ENGINE DIAGNOSIS, REMOVAL, AND INSTALLATION LESSON 2: ENGINE DIAGNOSTIC TESTS NOTE: Testing the engine s mechanical condition is required when the cause of a problem is not located
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with specific criteria for projects involving design of Laboratory Exhaust and Systems.
More informationThe Influence of the Phase Difference between the Crank Angle of the Pilot and that of the Stoker on the Drag Acting on a Tandem Bike
Proceedings The Influence of the Phase Difference between the Crank Angle of the Pilot and that of the Stoker on the Drag Acting on a Tandem Bike Kazuya Seo * and Satoshi Eda Department of Education, Art
More informationUNIVERSITY OF ROCHESTER DESIGN STANDARDS JANUARY 2012 SECTION FUME HOODS AND LOCAL EXHAUST SYSTEMS
SECTION 15860 - FUME HOODS AND LOCAL EXHAUST SYSTEMS This standard describes fundamental good practices relating to the design, selection, installation, commissioning, and testing of local exhaust systems
More informationEngine Performance Troubleshooting Tree - Signature and ISX CM870
File: 70-t02-1001 Page 1 of 64 Engine Performance Troubleshooting Tree - Signature and ISX CM870 This troubleshooting procedure should be followed for the following symptoms: Engine Acceleration or Response
More informationChapter 1: Introduction to Automobile Aerodynamics...1
Preface...xv Acknowledgments...xix Chapter 1: Introduction to Automobile Aerodynamics...1 1.1 Scope... 1 1.1.1 The Role of Aerodynamics in Vehicle Design... 1 1.1.2 The Character of Vehicle Aerodynamics...
More informationAUDIO-VISUAL EQUIPMENT
11 52 00 AUDIO-VISUAL EQUIPMENT 1. GENERAL A. Related sections: i. 00 00 13 Designing Learning Environments ii. 11 52 13 Projection Screens iii. 12 56 52 Audio-Visual Equipment iv. 72 41 00 General Audio-Visual
More informationThermo Scientific Hamilton Horizon Fume Hoods. Operation, Maintenance and Installation Instructions
Thermo Scientific Hamilton Horizon Fume Hoods Operation, Maintenance and Installation Instructions Thermo Scientific Horizon Fume Hood Table of Contents Introduction.............................................................
More informationVOLU-probe. Pitot Airflow Traverse Probes. amca. Accurate airflow measurement for demanding applications. CERTIFIED RATInGS
amca CERTIFIED RATInGS VOLU-probe Pitot Airflow Traverse Probes FLOW MEASUREMENT STATION PERFORMANCE MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. Accurate airflow measurement for demanding applications
More informationContent - Silencers. Silencers for spiral systems. Silencers for rectangular systems
Silencer Catalog Content - Silencers General information on noise... 3 General information on sound attenuation... 4 Silencer specification... 7 2 Silencers for spiral systems Silencers for rectangular
More informationA. Each cabinet must be constructed and installed in accordance with EN12469:2000.
BIOLOGICAL SAFETY CABINETS Class II, Biological Safety Cabinet PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this section to the extent referenced. The publications are referred
More informationAD-1250 Airflow Measuring Station
AD-1250 Airflow Measuring Station Product Bulletin Code No. LIT-12011472 Issued March 2016 Refer to the QuickLIT website for the most up-to-date version of this document. The AD-1250 Airflow Measuring
More informationProtector XStream Laboratory Fume Hoods
User s Manual Protector XStream Laboratory Fume Hoods Models 9840400, 9840401, 9840402, 9840403, 9840500, 9840501, 9840502, 9840503, 9840600, 9840601, 9840602, 9840603, 9840800, 9840801, 9840802, 9840803
More informationGeneral Purpose Permanent Magnet Motor Drive without Speed and Position Sensor
General Purpose Permanent Magnet Motor Drive without Speed and Position Sensor Jun Kang, PhD Yaskawa Electric America, Inc. 1. Power consumption by electric motors Fig.1 Yaskawa V1000 Drive and a PM motor
More informationFan Efficiency Grades and System Effect and Their Effects on HVAC Systems
Fan Efficiency Grades and System Effect and Their Effects on HVAC Systems Matt Spink, P.E. Greenheck Fan Corporation Learning Objectives Understanding Fan Efficiency Grades (FEG) Selection of fans within
More informationBRAKE SYSTEM DESIGN AND THEORY
RAKE SYSTEM DESIGN AND THEORY Aircraft brake systems perform multiple functions. They must be able to hold the aircraft back at full static engine run-up, provide adequate control during ground taxi operations,
More informationModeling, Structural & CFD Analysis and Optimization of UAV
Modeling, Structural & CFD Analysis and Optimization of UAV Dr Lazaros Tsioraklidis Department of Unified Engineering InterFEA Engineering, Tantalou 7 Thessaloniki GREECE Next Generation tools for UAV
More informationSECTION DUCTWORK ACCESSORIES
SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference
More informationVIBRATION OF AUTOMOBILE SIDE VIEW MIRROR DUE TO AERODYNAMIC INPUTS
Proceedings of the International Conference on Mechanical Engineering 25 (ICME25) 28-3 December 25, Dhaka, Bangladesh ICME5- VIBRATION OF AUTOMOBILE SIDE VIEW MIRROR DUE TO AERODYNAMIC INPUTS Rajneesh
More informationLABORATORY HOOD MANUAL
LABORATORY HOOD MANUAL DRAKE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY November 2015 TABLE OF CONTENTS I. INTRODUCTION... 1 II. FUME HOOD SERVICE... 2 Fume Hood Service Provided by EH&S... 2 Fume Hood Service
More informationAerodynamics and its application for vehicles / Járműáramlástan DIRECTIONAL STABILITY SIDE WIND EFFECT
Aerodynamics and its application for vehicles / Járműáramlástan DIRECTIONAL STABILITY SIDE WIND EFFECT Aerodynamics and its application for vehicles SIDE WIND EFFECT FORCES: LIFT force: L = c L (1/2rv
More informationEnergy Recovery Laboratory Exhaust
Energy Recovery Laboratory Exhaust Model Vektor ERS-M For Vektor-M Fan Systems September 2012 Model Page Header Vektor ERS-M Greenheck s Vektor -ERS is a pre-engineered laboratory exhaust energy recovery
More informationBoilers, Steam Generators, and Process Heaters (Oxides of Nitrogen) - Adopted 10/13/94, Amended 4/6/95, 7/10/97
RULE 425.2 Boilers, Steam Generators, and Process Heaters (Oxides of Nitrogen) - Adopted 10/13/94, Amended 4/6/95, 7/10/97 I. Purpose The purpose of this Rule is to limit oxides of nitrogen (NOx) emissions
More informationAlmost 200 years ago, Faraday looked for evidence that a magnetic field would induce an electric current with this apparatus:
Chapter 21 Electromagnetic Induction and Faraday s Law Chapter 21 Induced EMF Faraday s Law of Induction; Lenz s Law EMF Induced in a Moving Conductor Changing Magnetic Flux Produces an E Field Inductance
More informationPart 1 of this series discussed optimizing outdoor
Many methods await when it comes to reducing exhaust rates. Fortunately, engineers can avail themselves of multiple tactics, from the hood specification to proper commissioning and air balance. By Doug
More informationSTUDY OF THE AERODYNAMIC NOISE CHARACTERISTICS OF BLUFF BODIES AS A PANTOGRAPH MEMBER
STUDY OF THE AERODYNAMIC NOISE CHARACTERISTICS OF BLUFF BODIES AS A PANTOGRAPH MEMBER PACS REFERENCE: 43.5.Lj IKEDA Mitsuru Railway Technical Research Institute -8-38, Hikari-cho, Kokubunji-shi, Tokyo,
More informationA Study of EGR Stratification in an Engine Cylinder
A Study of EGR Stratification in an Engine Cylinder Bassem Ramadan Kettering University ABSTRACT One strategy to decrease the amount of oxides of nitrogen formed and emitted from certain combustion devices,
More informationPre-lab Questions: Please review chapters 19 and 20 of your textbook
Introduction Magnetism and electricity are closely related. Moving charges make magnetic fields. Wires carrying electrical current in a part of space where there is a magnetic field experience a force.
More informationINSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS
INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS CONTENTS Introduction Safety Operating Principle System Installation Initial Startup System Operations Troubleshooting Maintenance
More informationNJK Precision Product NJK-02 Sensor Installation Guide
Precision -02 Sensor 2017 Product Line Precision Product Table of Contents Precision Company Overview - Page 2-02 Installation Guidelines - Page 3-02 Recommended Installations - Page 5-02 Non-Recommended
More informationRULE BOILERS, STEAM GENERATORS, AND PROCESS HEATERS (Adopted 5/11/93, Revised 6/13/95, 6/13/00, 9/11/12)
VENTURA COUNTY AIR POLLUTION CONTROL DISTRICT RULE 74.15.1 - BOILERS, STEAM GENERATORS, AND PROCESS HEATERS (Adopted 5/11/93, Revised 6/13/95, 6/13/00, 9/11/12) A. Applicability The provisions of this
More informationSpecial edition paper
Development of a Brake System for Shinkansen Speed Increase Hiroshi Arai* Satoru Kanno* Kenji Fujino* Hiroyuki Kato* Koji Asano* In efforts to increase Shinkansen speeds toward a 360 km/h operating speed,
More informationHYDRAULIC ACTUATOR REPLACEMENT USING ELECTROMECHANICAL TECHNOLOGY
HYDRAULIC ACTUATOR REPLACEMENT USING ELECTROMECHANICAL TECHNOLOGY SCOPE This white paper discusses several issues encountered by Lee Air with past projects that involved the replacement of Hydraulic Actuators
More informationUser s Manual. LabShield. Laboratory Fume Hoods. Air Foil By-Pass Models: 6714, 6716, ADA Models: 8796, 8798, Demonstration Hood 6725G
User s Manual LabShield By CampbellRhea Laboratory Fume Hoods Air Foil By-Pass Models: 6714, 6716, 6718 ADA Models: 8796, 8798, 8800 Demonstration Hood 6725G CampbellRhea 1865 North Market Street Paris
More informationFLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES
FLS F6.60 MAGMETER FLOW SENSOR The new F6.60 and F6.63 are flow meters without moving mechanical parts which can be applied for the measurement of dirty liquids so long as they are conductive and homogeneous.
More informationApplication Guidelines
Grilles and Registers Application Guidelines Introduction Overview It is the intent of this section to give some basic application guidelines for the use of supply and return grilles and registers in a
More information