Breaker failure protection function block description
|
|
- Benjamin Parker
- 6 years ago
- Views:
Transcription
1 function block description Document ID: PRELIMINARY VERSION
2 User s manual version information Version Date Modification Compiled by Preliminary Preliminary version, without technical information Petri PRELIMINARY VERSION 2/10
3 CONTENTS 1 Breaker failure protection function Application Mode of operation The decision logic (Decision logic) Technical summary Technical data Summary of the parameters Summary of the generated output signals Summary of the input signals The symbol of the function block in the graphic editor PRELIMINARY VERSION 3/10
4 1 Breaker failure protection function 1.1 Application After a protection function generates a trip command, it is expected that the circuit breaker opens and/or the fault current drops below the pre-defined normal level. If not, then an additional trip command must be generated for all backup circuit breakers to clear the fault. At the same time, if required, a repeated trip command can be generated to the circuit breaker(s) which are expected to open. The breaker failure protection function can be applied to perform this task. 1.2 Mode of operation The starting signal of the breaker failure protection function is usually the trip command of any other protection function. The user has the task to define these starting signals using the graphic equation editor as the General Start (BRF50_GenSt_GrO_), or if the operation of the individual phases is needed, then the start signals for the phases individually. The phase start signals are: Start L1 (BRF50_StL1_GrO_), Start L2 (BRF50_StL2_GrO_) and Start L3 (BRF50_StL3_GrO_). Dedicated timers start at the rising edge of the start signals, one for the backup trip command and one for the repeated trip command, separately for operation in the individual phases. During the running time of the timers the function optionally monitors the currents, the closed state of the circuit breakers or both, according to the user s choice. The selection is made using the enumerated parameter BRF50_Oper_EPar_ (Operation). If this parameter setting is Current, the current limit values BRF50_StCurrPh_IPar_ (Start current Ph) and BRF50_StCurrN_IPar_ (Start current N) must be set correctly. The binary inputs indicating the status of the circuit breaker poles have no meaning. If this parameter setting is Contact, the current limit values BRF50_StCurrPh_IPar_ (Start current Ph) and BRF50_StCurrN_IPar_ (Start current N) have no meaning. The binary inputs indicating the status of the circuit breaker poles must be programmed correctly using the graphic equation editor. The input variables to be programmed are: BRF50_CBClL1_GrO_ (CB closed L1), BRF50_CBClL2_GrO_ (CB closed L2) and BRF50_CBClL3_GrO_ (CB closed L3). If this parameter setting is Current/Contact, the current parameters and the status signals must be set correctly. The breaker failure protection function resets only if all conditions for faultless state are fulfilled. If at the end of the running time of the backup timer the currents do not drop below the predefined level, and/or the monitored circuit breaker is still in closed position, then a backup trip command is generated in the phase(s) where the timer(s) run off. The time delay is defined using the parameter BRF50_BUDel_TPar_ (Backup Time Delay). If repeated trip command is to be generated for the circuit breakers that are expected to open, then the enumerated parameter BRF50_ReTr_EPar_ (Retrip) must be set to On. In this case, at the end of the timer(s) the delay of which is set by the timer parameter BRF50_TrDel_TPar_ (Retrip Time Delay), a repeated trip command is also generated. The pulse duration of the trip command is not shorter than the time defined by setting the parameter BRF50_Pulse_TPar_ (Pulse length). The breaker failure protection function can be enabled or disabled by setting the parameter BRF50_Oper_EPar_ (Operation) to Off. PRELIMINARY VERSION 4/10
5 Dynamic blocking is possible using the binary input BRF50_Blk_GrO_ (Block). The conditions are to be programmed by the user, using the graphic equation editor. 1.3 The decision logic (Decision logic) The decision logic module combines status signals, binary and enumerated parameters to generate the dead line or live line status signals. Binary status signals The breaker failure protection function has binary input signals. The conditions are defined by the user, applying the graphic equation editor. The binary input status signals of the breaker failure protection function are listed in Table 1-1. Binary status signal Title Explanation BRF50_Blk_GrO_ Block Blocking of the breaker failure protection function BRF50_CBClL1_GrO_ CB closed L1 Signal indicating the closed state of the circuit breaker in phase L1 BRF50_CBClL2_GrO_ CB closed L2 Signal indicating the closed state of the circuit breaker in phase L2 BRF50_CBClL3_GrO_ CB closed L3 Signal indicating the closed state of the circuit breaker in phase L3 BRF50_GenSt_GrO_ General Start General starting signal BRF50_StL1_GrO_ Start L1 Starting signal in phase L1 BRF50_StL2_GrO_ Start L2 Starting signal in phase L2 BRF50_IoSt_GrO_ Start Io Starting signal for the residual current Internal signal: IL1> Current in phase L1 is above the preset parameter value Internal signal: IL2> Current in phase L2 is above the preset parameter value Internal signal: IL3> Current in phase L3 is above the preset parameter value Internal signal: Io> Current 3Io is above the preset parameter value Enumerated parameter Current/Contact The monitored condition is current, contact or both Enumerated parameter Retrip On/Off The retrip command must be enabled (On) Table 1-1 The binary input status signals of the decision logic PRELIMINARY VERSION 5/10
6 General Start IL1> Start L1 t RETRIP PULSE Retrip L1 IL2> Start L2 t RETRIP PULSE Retrip L2 IL3> Start L3 Start Io Current t RETRIP PULSE Retrip L3 Contact Io> CB closed L1 t BACKUP TRIP PULSE Backup Trip CB closed L2 CB closed L3 Retrip Figure 1-1 The logic scheme of the decision logic PRELIMINARY VERSION 6/10
7 The binary output status signals of the breaker failure protection function are listed in Table 1-2. Binary status signal Title Explanation BRF50_BuTr_GrI_ Backup Trip Trip command generated for the backup circuit breakers BRF50_TrL1_GrI_ Retrip L1 Repeated trip command in phase L1 BRF50_TrL2_GrI_ Retrip L2 Repeated trip command in phase L2 BRF50_TrL3_GrI_ Retrip L3 Repeated trip command in phase L3 Table 1-2 The binary output status signals of the decision logic PRELIMINARY VERSION 7/10
8 1.4 Technical summary Technical data Function Effective range* Accuracy* *To be defined by types tests Table 1-3 Technical data of the breaker failure protection function Summary of the parameters Enumerated parameters Parameter name Title Selection range Default Selection of the operating mode BRF50_Oper_EPar_ Operation Off,Current,Contact,Current/Contact Current Switching on or off of the repeated trip command BRF50_ReTr_EPar_ Retrip Off,On On Tables 1-4 Enumerated parameters of the breaker failure protection function Integer parameters Parameter name Title Unit Min Max Step Default Phase current setting BRF50_StCurrPh_IPar_ Start current Ph % Neutral current setting BRF50_StCurrN_IPar_ Start current N % Table 1-5 Integer parameters of the breaker failure protection function Timer parameters Parameter name Title Unit Min Max Step Default Time delay for repeated trip command generation BRF50_TrDel_TPar_ Retrip Time Delay msec Time delay for trip command generation for the backup circuit breaker(s) BRF50_BUDel_TPar_ Backup Time Delay msec Trip command impulse duration BRF50_Pulse_TPar_ Pulse lenght msec Table 1-6 Timer parameters of the breaker failure protection function PRELIMINARY VERSION 8/10
9 1.4.3 Summary of the generated output signals The binary output status signals of the breaker failure protection function are listed in Table 1-7. Binary status signal Title Explanation BRF50_BuTr_GrI_ Backup Trip Trip command generated for the backup circuit breakers BRF50_TrL1_GrI_ Retrip L1 Repeated trip command in phase L1 BRF50_TrL2_GrI_ Retrip L2 Repeated trip command in phase L2 BRF50_TrL3_GrI_ Retrip L3 Repeated trip command in phase L3 Table 1-7 Binary output status signals of the breaker failure protection function Summary of the input signals Binary status signals The breaker failure protection function has binary input status signals. The conditions are defined by the user, applying the graphic equation editor. The binary input status signals of the breaker failure protection function are listed intable 1-8. Binary status signal Title Explanation BRF50_Blk_GrO_ Block Blocking of the breaker failure protection function BRF50_CBClL1_GrO_ CB closed L1 Signal indicating the closed state of the circuit breaker in phase L1 BRF50_CBClL2_GrO_ CB closed L2 Signal indicating the closed state of the circuit breaker in phase L2 BRF50_CBClL3_GrO_ CB closed L3 Signal indicating the closed state of the circuit breaker in phase L3 BRF50_GenSt_GrO_ General Start General starting signal BRF50_StL1_GrO_ Start L1 Starting signal in phase L1 BRF50_StL2_GrO_ Start L2 Starting signal in phase L2 BRF50_StL3_GrO_ Start L3 Starting signal in phase L3 BRF50_IoSt_GrO_ Start Io Starting signal for the residual current Table 1-8 Binary input signals of the breaker failure protection function PRELIMINARY VERSION 9/10
10 1.4.5 The symbol of the function block in the graphic editor The names of the input and output signals are parts of the Binary status signal names listed in Table 1-7 andtable 1-8 PRELIMINARY VERSION 10/10
Circuit breaker wear monitoring function block description for railway application
Circuit breaker wear monitoring function block description for railway application Document ID: PP-13-21313 Budapest, September 2016 CONTENTS Circuit breaker wear monitoring function...3 Technical data...5
More informationCat/DCG-6D1I/07-08/03/Ver 1 Page 2/10
Cat/DCG-6D1I/07-08/03/Ver 1 Page 2/10 Index 1.1 Introduction 1.2 Salient Feature of the DGC-6D 1.2.1 Protection & Supervision 1.2.2 Measurement & Display 1.2.3 LED Indications 1.2.4 Timer 1.3 Function
More informationBreaker-failure protection RAICA
Breaker-failure protection RAICA Features Provides local back-up protection when the primary breaker fails to operate Initiates tripping of adjacent back-up breakers for disconnection of the fault, thus
More informationExtracting Valuable Information from HV Circuit Breaker Testing. Charles Sweetser - OMICRON MIPSYCON 2014
Extracting Valuable Information from HV Circuit Breaker Testing Charles Sweetser - OMICRON MIPSYCON 2014 5 November 2014 FINEPOINT 2 Agenda Topics SF6 and Oil Breaker Types (Info) Timing and Travel Power
More informationBreaker failure relay REB 010
Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970138) Features Local redundant protection when the circuit breaker does not operate The technique with microprocessors
More informationBackup Generation Application
Backup Generation Application For connection of non-parallel generation between Menard Electric Cooperative s Electric system and standby generation that will operate with a manual or automatic transfer
More informationApplication Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS
Application Note GET-8558 RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS REVISION 01 March 17 th, 2016 1 INDEX 1. INTRODUCTION 4 2. RELAY ORDER CODE 5 3. RELAY IO CONNECTIONS
More informationOPERATING INSTRUCTION: DGC-6D/6D1I
OPERATING INSTRUCTION: DGC-6D/6D1I GCB Auto Man Stop Fail - PROCOM Pvt Ltd MRM PROCOM Plot No. : 20-21, Industrial Estate, Sector - 59, Phase-II, Faridabad (Haryana) Ph.: 0129-4700400(10 Lines) Email:
More informationOPERATING INSTRUCTIONS ECON-M
OPERATING INSTRUCTIONS ECON-M INDEX 1.0 Introduction 2.0 Salient features, Protection & Supervision 3.0 Display/ Front Panel 4.0 Switches Description 5.0 LED Annunciations Description 6.0 Lamp Test 7.0
More informationASPIRO & GUARDIAN BATTERY MANAGEMENT WITH ACC EXTENDED CONTROLLER
DESCRIPTION Battery management is implemented in the Aspiro and Guardian DC Power Systems using the ACC Extended (ACX) controller. ASPIRO & GUARDIAN BATTERY MANAGEMENT WITH ACC EXTENDED CONTROLLER The
More informationCat N 3. OVERALL DIMENSIONS
Cat N Motor driven remote control module 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat N : : 4 062 91 CONTENTS PAGE 1. Description - Use...1 2. Product range...1
More informationDSEULTRA DSE6000 Quick Start Guide Document Number
n DSEULTRA DSE6000 Quick Start Guide Document Number 057-102 Author : John Ruddock Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales
More informationTRIPS AND FAULT FINDING
WWW.SDS.LTD.UK 0117 9381800 Trips and Fault Finding Chapter 6 6-1 TRIPS AND FAULT FINDING Trips What Happens when a Trip Occurs When a trip occurs, the drive s power stage is immediately disabled causing
More informationCase Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI
Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising
More informationHIDRA CRONO Controller VVVF Control Techniques Unidrive SP (Asynchronous motors)
VVVF CT Unidrive SP / Asynchronous Rev. 1 19/05/2014 HIDRA CRONO Controller VVVF Control Techniques Unidrive SP (Asynchronous motors) It is essential to carry out the autotuning procedure of the inverter-motor
More informationClose-Open (Short-Circuit) Time Results Interpretation
Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection
More informationVission 20/20 micro-controller. Operation and service manual
Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1
More informationBTB TYPE AUTOMATIC TRANSFER SWITCH (ATS)
BTB TYPE AUTOMATIC TRANSFER SWITCH (ATS) Programmable Automatic Transfer Switch Operation Manual Main Switch Rated Current 2P/3P/4P 250Amp 2P 400 Amp Main Switch Rated Voltage 690 Vac Taiwan Patent Number
More informationXM1 - Motor protection relay
XM1 - Motor protection relay Contents 1 Applications and features 1 Applications and features 2 Design 3 Working principle 3.1 Overload protection 3.2 Stalling protection 3.3 Earth fault protection 3.4
More information4100C BOSS AC Shovel Drive System Overview. WMEA Edmonton - June 2008
4100C BOSS AC Shovel Drive System Overview WMEA Edmonton - June 2008 Overview Drives Partnership with ABB Deck Plan / One-Line Schematic ISU (IGBT Supply Unit) Shovel Motion Inverters Cabling / Grounding
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationMANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450
MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION
More informationOperating manual and installation instructions ENGLISH. Electronic engine remote control. Copyright 2001 Vetus den Ouden n.v.
Operating manual and installation instructions ENGLISH Electronic engine remote control Copyright 00 Vetus den Ouden n.v. Schiedam Holland Contents Introduction... General conditions of use... Operating....
More informationNew range of reclosing systems
Protection and Control RECmax New range of reclosing systems Earth leakage and circuit breaker protection with automatic earth leakage reclosing system. Manage its installation remotely Energy efficiency
More informationMoulded case circuit breakers
Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded
More informationSummary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers
Summary of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection of Power Circuit Breakers Kevin Donahoe GE Grid Solutions 2018 Texas A&M Protective Relaying Conference Agenda Introduction
More informationTesting Breaker Failure Schemes
Hands-On Relay School Testing Breaker Failure Schemes Valence Electrical Training Services Chris Werstiuk Table of Contents 1. Introduction... 4 2. What Should Happen When a Fault is Detected... 5 3. Basic
More informationHGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL
HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL SMARTGEN ELECTRONICS Smartgen Electronic Equipment Co., Ltd No.12 Dongqing Street Zhengzhou Henan Province P.R.China Tel : (0086)-371-67992951
More informationBattery & Energy Meter Quick Guide
Battery & Energy Meter Quick Guide Issue: 01 Date: 2017-12-07 1 Preparing Cables Copyright Huawei Technologies Co., Ltd. 2017. All rights reserved. The battery output voltage should always be lower than
More informationHPA603 (>7-cell Li-ion/LiFePO4 battery charger) evaluation
HPA603 (>7-cell Li-ion/LiFePO4 battery charger) evaluation 1. Introduction... 2 EVM Features... 2 General Description... 2 I/O Description... 2 Controls and Key Parameters Setting... 3 2. Schematic...
More informationPARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR
PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR VPC-AA The VPC-AA Parking Lot Controller is an easily installed device designed for mid-sized parking lot installations. The weather proof design is ideal
More information1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.
1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse
More informationController over electromechanical fuel dispensers for petrol stations
Controller over electromechanical fuel dispensers for petrol stations TECHNICAL GUIDE Review date: 05 Jan 2013 Revision number: 1.02 TECHNOTRADE LTD CONTENT REVISION HISTORY... 3 PURPOSE OF THE DOCUMENT...
More informationAPPLICATION NOTES. Industrial Wall Control (IWC10) (English) (IWC10)
APPLICATION NOTES Industrial Wall Control (IWC0) (English) (IWC0) The Breezair Industrial Wall Control (IWC0) is designed to provide both local and external Evaporative Air cooler control for all Breezair
More informationISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT
ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT By Girija Shankar Sharma, M.Tech (Power System), DGM (O&M-Opn), NTPC-Rihand, E-mail: gssharma@ntpc.co.in Presentation Points System Description and Grid
More informationPowerCommand 2100 digital generator set control
Specification sheet PowerCommand 2100 digital generator set control Description The PowerCommand 2100 control is a microprocessor-based generator set monitoring, metering and control system. The control
More informationIndoor air quality sensor.
Indoor air quality sensor. Options and Accessories, Installation manual Ref.: N-40175_EN 1107 Index Index 1 Indoor air quality sensor... 1 1.1 General Information... 2 1.2 General measurements... 2 1.3
More informationSeries 905-IV16(E) CAN/CANopen Input Modules Installation and Operating Manual
Series 905-IV16(E) CAN/CANopen Input Modules Installation and Operating Manual Model 905 IV16 DC Input Module. Page 2 Operations Manual Table of Contents Table of Contents...2 Module Installation Procedure...3
More informationSolid Dielectric, Three Phase Reclosers CATALOG VS11
Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance
More informationatalog Welcome to ATO.com! Contact us... Tel: (Toll-free) Website:
atalog Welcome to.com! Contact us... Email: sales@ato.com Tel: +1 800-585-1519 (Toll-free) Website: ZMQ2E Series Dual Power Automatic Transfer Switch (ATS) Applications ZMQ2E dual auto transfer switch
More informationFusesaver specification form
Fusesaver specification form Please send this sheet attached to your inquiry / order to: Customer Support Center Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail:
More information1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.
RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to
More informationLS200 Series Instruction Manual
LS200 Series Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage may lead to an electrical shock, damage to the unit
More informationTE2010-GE Instructions manual
TE2010-GE Instructions manual Hardware: 3.1-4.0 Software: 3.7 PREFACE Thanking you for preference, TECNOELETTRA SRL hopes that the use of this equipment could be a reason of satisfaction. This manual is
More informationMagnetek DSD 412 Drive
DRIVE STARTUP MANUAL Magnetek DSD 412 Drive Induction Motor Installation www.smartrise.us 2601 Fair Oaks Blvd., Sacramento, CA 95864 916.457.5129 Magnetek DSD 412 Drive EQUIPMENT/SETTINGS VERIFICATION
More informationDEEP SEA ELECTRONICS PLC
COMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS PLC DSE704 AUTOSTART CONTROL MODULE OPERATING MANUAL 057-042 704 Operating Instructions Issue 2.1 18/06/2007 11:27:00 JR - 1 - Deep Sea Electronics Plc
More informationCABINET REEL OPERATING INSTRUCTIONS
CABINET REEL OPERATING INSTRUCTIONS MODELS 15, 25, 40 & 60 SERIES RAPID-AIR CORPORATION 4601 KISHWAUKEE ST. ROCKFORD, IL 61109-2925 Phone: (815) 397-2578 Fax: (815) 398-3887 Web Site: www.rapidair.com
More informationCSP Circuit Breaker Three Phase
General Information : LR Breaker SQR Breaker LQR Breaker, HQR Breaker Wall-Mounting Type CSP Circuit Breaker Three Phase Three Phase CSP Circuit Breaker For Distribution Transformers General Information
More informationICL Three Pump Controller
ICL Three Pump Controller Pump Operation The number of pumps that the program controls can be selected by enabling only the ones that are currently installed and in service. The enable/disable setting
More informationParalleling Equipment
Paralleling Equipment PowerCommand Model 300 Digital Master Control Description The PowerCommand TM Digital MasterControl is a microprocessor-based paralleling system component, designed to directly interface
More informationDKG-114 MANUAL AND REMOTE START UNIT
DKG-114 MANUAL AND REMOTE START UNIT FEATURES Both manual and remote controlled engine starting and stopping, Automatic shutdown on fault condition, Optional cooldown cycle on remote start operation, Optional
More informationTime scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal)
86 Timer modules 86 Timer modules for use in conjunction with relay & socket. 86.00T - Multi-function & multi-voltage timer module 86.30T - Bi-function & multi-voltage timer module Complies with EN 45545-2:2013
More informationGuide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C
s Guide for Primary Injection Testing WL Circuit Breakers Document No. : 11-C-9036-00 Before Beginning... Qualified Person Siemens type WL circuit breakers should only be only be operated, inspected, and
More informationInduction Power Supplies
Induction Power Supplies 7.5kW; 135 400kHz 480V version (Integral Heat Station) User s Guide Model 7.5-135/400-3-480 SMD Control Brds Rev. D 5/08 Table of Contents 1. Specifications and features...3 2.
More information2 pole, 10 A AC/DC supply non polarized Plug-in for use with 94 series sockets
Miniature plug-in timers 7-10 A Plug-in timer.02-2 Pole 10 A.03-3 Pole 10 A.04-4 Pole 7 A Multifunctions Seven time scales, from 0.05 s to 100 h 94 series sockets for 35 mm rail (EN 60715) mount with push-in
More informationApplication Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.
Application Guide 575-012 Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1 Carlyle Controller Part No. 2BSB000928 1 General Description The PCM is part of Paragon Compressor
More informationNHP SAFETY REFERENCE GUIDE
4 NHP SAFETY REFERENCE GUIDE CONTENTS SAFETY TECHNOLOGY Risk Reduction Options Permanent Fixed Guard 4-02 Interlocked Guard: 4-03 Limit Switches 4-08 Presence Sensing Technology 4-09 Safety Laser Scanners
More information( DOC No. HX8678-A-DS ) HX8678-A
( DOC No. HX8678-A-DS ) HX8678-A Preliminary version 01 July, 2006 Preliminary Version 01 July, 2006 1. General Description The HX8678-A is a 480/320 channels output gate driver used for driving the gate
More informationKEWTECH. KT56 digital multi function tester. Instruction manual
KEWTECH KT56 digital multi function tester Instruction manual Contents 1 Safety Notice 1 2 Features and Principles of Measurement 3 3 Introduction 6 4 Specifications 7 5 Instrument layout 9 6 Operating
More informationATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A
ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat
More informationMaxxForce 11 and 13 ( )
MaxxForce 11 and 13 (2007-2009) Overview: TABLE OF CONTENTS General Overview:... 1 Description and Operation... 1 OPERATION...1 Programmable Parameters... 2 Parameter Setup... 3 Frequently Asked Questions...
More information01 Spectra Plus - Introduction
01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from
More informationINSTRUCTION INVERTER COMPACT FOR SLIDING GATES /R0 10/11/2017
INSTRUCTI INVERTER COMPACT FOR SLIDING GATES 6-1622616 /R0 10/11/2017 2 / 20 3 / 20 1. INTRO The control unit INVERTER COMPACT is integrated in the motor KALOS XL. It is a device suitable for operating
More informationBB-LEISGER International GmbH
Manual Display C6 BB-LEISGER International GmbH Function Display NORMAL OPERATION Section 4 4.1 PAS level selection 4.2 Error code indicator 4.3 SET operation Section 3 3.1 Speed indicator 3.2 KM/H & MPH
More informationINSTALLER MANUAL USER MANUAL. Contents
Installation & user manual two way Contents INSTALLER MANUAL Important information General 1. Technical data 2. Description Installation: 1. Positioning the unit 2. Connection. 3. Parts description. 4.
More informationPD-Series Ground Fault Circuit Protection
PD-Series Ground Fault Circuit Protection SmartGuard is an equipment ground fault protection device that functions as a standard high-quality Carling hydraulic/ magnetic circuit breaker, offering customized
More informationINTRODUCTION. AC motor operations, most widely used motor is three phase induction motor. This type of motor does not require any starting device
Modular Application (AC Motors) Engineering and Technical Teaching Equipment AEL-AI12 INTRODUCTION An electrical motor is such an electromechanical device which converts electrical energy into a mechanical
More informationPOWER SUPPLY aps-412_en 06/16
APS-412 POWER SUPPLY aps-412_en 06/16 The APS-412 switching power supply has been designed for use with 12 V DC electrical devices. It comes with a dedicated connector allowing for integration with Satel's
More informationExplanation 1 Input External Switch 2 Input Hipot Safety Switch
on the 1100H+ The 1100H+ has capability, which allows you to set up the tester to control external devices with tester functions. You can also use an input on the tester to start a test. For example, the
More informationSECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.
SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products
More informationWelcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.
Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the
More informationFT-10 Network Digital I/O Module Kits and
Instruction Sheet 10-2004 FT-10 Network Digital I/O Module Kits 541 0771 and 541 0772 PURPOSE OF KIT The Digital I/O Module (DIM) makes provisions for a group of relay contact outputs and discrete inputs
More information( DOC No. HX8678-B-DS )
( DOC No. HX8678-B-DS ) Preliminary version 01 1. General Description The HX8678-B is a 480-channel outputs gate driver, which is used for driving the gate line of TFT LCD panel. It is designed for 2-level
More informationInterface I-300 / I-300 Pro Technical data sheet
Interface I-300 / I-300 Pro Technical data sheet The Interface I-300 or I-300 Pro are the central control unit for all process parameters of a Rotavapor R-300 system: rotation speed, temperature (heating
More informationDEEP SEA ELECTRONICS PLC
COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE4120 AUTO MAINS FAILURE MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel:
More informationEmergency lighting units EM converterled. EM converterled PRO 50 V PRO series
PRO 50 V PRO series Product description lighting Driver with DAI interface and automatic test function For self-contained emergency lighting For modules with a forward voltage of 10 52 V SEV for output
More informationBBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER
BBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER Important The BBC -3140 must be used according to the local safety standards with the particular application. All wiring and connections
More informationDeep Sea Electronics Plc
Deep Sea Electronics Plc 5120 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL Author: Anthony Manton Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH England Tel: +44 (0) 1723
More informationPneumatic Timer. TECHNICAL DATA Display digit roll s, s or s, depending on version Operating pressure 2...
Type 499 Pneumatic Timer Low-cost DIN dimensions Requires little space for installation Pressure-independent No continuous air supply equired Stationary preset value TECHNICAL DATA Display digit roll Time
More informationEUP8075/8079. Preliminary. USB-Compliant Li-Ion Battery Charger Integrated with System Power-Path Management FEATURES DESCRIPTION APPLICATION
Preliminary EUP8075/8079 USB-Compliant Li-Ion Battery Charger Integrated with System Power-Path Management DESCRIPTION The EUP807X series of devices are highly integrated Li-ion linear chargers and system
More informationTranZformer 2 nd Gen Shift Kit Installation
TranZformer 2 nd Gen Shift Kit Installation For Firmware Version 2.0.0-061214 The TranZformer Shift Kit is an electronic shift enhancer for 2011-2014 Dodge Charger and Chrysler 300 vehicles. The TranZformer
More informationProduct manual Oil Streak Sensor INTRODUCTION CONSTRUCTION. Master Sensor
Product manual Oil Streak Sensor INTRODUCTION Oil streak sensors are designed to detect traces of oil travelling through air tubes, down to flows as low as 5mm 3 /min. The product utilizes a master and
More informationHGM6410/6420. Automatic Generator Module. With J1939 Interface OPERATING MANUAL. Smartgen Electronics
HGM6410/6420 Automatic Generator Module With J1939 Interface OPERATING MANUAL Smartgen Electronics Smartgen Electronic Equipment Co,.Ltd No.12 Dongqing Street Zhengzhou Henan Province P.R.China Tel : (0086)-371-67992951
More informationInstruction Manual. Q Series 2 Motor Control Modules - OEM
A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230
More informationDEEP SEA ELECTRONICS PLC DSE3210 Configuration Suite Software Manual
DEEP SEA ELECTRONICS PLC DSE3210 Configuration Suite Software Manual Document Number 057-152 Author : Paul Gibbons DSE3210 Configuration Suite Software Manual Issue 1 DSE3210 Configuration Suite Software
More informationFrame size R2, IP20 / NEMA 1
Dimension drawings 395 Frame size R2, IP20 / NEMA 1 1) 1) Extension modules add 26 mm (1.02 in) to the depth measure. 3AUA0000067783-A Frame size R2, IP20 / NEMA 1 396 Dimension drawings Frame size R3,
More informationApplication Description
-14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....
More informationArc flash hazard mitigation
Low Voltage Products Arc flash hazard mitigation Each year more than 2,000 people are treated in burn centers with severe arc flash injuries. ABB designs and manufactures products and solutions to provide
More informationPhillips Permalogic Trailer Dome Lamp Controller Technical Bulletin
SERVICE BULLETIN NO. SB-17-014 Issue Date: 07/05/06 SUBJECT: Phillips Permalogic Trailer Dome Lamp Controller Technical Bulletin Phillips Industries has released a technical bulletin related to installation
More informationPower Distribution System User s Manual. Model: PDS-100
Power Distribution System User s Manual Model: PDS-0 Section Page Product Overview... 1 I) General Information... 2 II) Important Safety Information... 2 III) Installation... 3 A) Materials Provided...
More informationFlow and check valves Logic valves Pneumatic counters. Brochure
Flow and check valves Logic valves Pneumatic counters Brochure 2 Flow and check valves Logic valves Pneumatic counters Pneumatic presetting counter (add) 5-digit, digits Compressed air connection input:
More informationSK-10. Features. Solar Charge Controller User Manual. Important Safety Information
SK-10 Solar Charge Controller User Manual 12V/24V 10Amp Dear Users: Thank you for selecting our product. Please read this manual carefully before you use this product. This product is of cutting edge design,
More informationUSER MANUAL FOR GC500 GENSET CONTROLLER SEDEMAC ABSTRACT
ABSTRACT This manual is intended as an information guide for operating SEDEMAC's GC500 genset controller. USER MANUAL FOR Doc #SED-MAN-GC500-002 Date: 01-Aug-2016 GC500 GENSET CONTROLLER Product Manual
More informationDesigned for ease of integration with automation systems
BAS, 200 ~ 600V, 1/2-30HP BUILDING AUTOMATION STARTER SMARTER AND MORE VERSATILE THAN EVER Smartstart Equipped with advanced I/O including Fireman s Override and damper control, the BAS was designed from
More informationBIDIRECTIONAL DC/DC CONVERTER
Features: Description: The 3,500 Watt 48S14.250BC Bidirectional non-isolated DC/DC converter provides a complete solution for invehicle power distribution in 12V/48V battery configurations for a variety
More informationVersa II SLR Lubricator
Versa II SLR Lubricator With Controller General The Versa II SLR Lubricator is an automatic, robust and durable pump that can handle oil. Its compact size is designed to fit your space requirements and
More informationDG SYNCHRONIZING &AMF PANEL
A 80, Sector 80, Phase 2, Noida 201305, Utter Pradesh, India DG SYNCHRONIZING &AMF PANEL Clients Bharat Petroleum Corp.Ltd PROJECT- DG Synchronization panel with AMF function. Design BY:- Errection By
More informationThe information in this chapter will enable you to: 90VAC to 50/60 Hz
C H A P T E R ➃ Hardware Reference The information in this chapter will enable you to: Use this chapter as a quick-reference tool for most system specifications (dimensions and performance) Use this chapter
More informationQUICK START GUIDE FOR DEMONSTRATION CIRCUIT DC1259A BATTERY BACKUP MANAGER BOARD
DESCRIPTION Demonstration circuit DC1259A is a single-battery battery-backup controller featuring the LTC4110. The LTC4110 controller provides all the features and functions to offer a complete standalone
More informationEC328 Power Control System
1 Key Features Battery Charger / Power Supply Incorporates an air cooled 300 Watt multi-stage power converter unit that charges the batteries and provides 12V DC power. Built-in dual Solar Regulator -
More information