Medium Voltage 400A Contactor - Series E and F

Size: px
Start display at page:

Download "Medium Voltage 400A Contactor - Series E and F"

Transcription

1 User Manual Original Instructions Medium Voltage 400A Contactor - Series E and F Catalog Number 1502

2 Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

3 Table of Contents Preface Summary of Changes About This Publication What This Manual Contains Additional Resources Chapter 1 Product Description Contactor Description Series Letter Details Vacuum Bottle Description Electrically Held Contactor Operation IntelliVAC and IntelliVAC Plus Controlled Contactors Electromechanical Relay Controlled Contactors Mechanically Latched Contactor Operation IntelliVAC and IntelliVAC Plus Controlled Contactor Electromechanical Relay Controlled Contactor Contactor Identification Catalog Number Explanation Contactor Dropout Times Specifications Product Approvals Chapter 2 Receiving and Handling Receiving Preliminary Inspection Handling Pre-energization Inspection Storage Vacuum Bottle Integrity Test Insulation Resistance Test Chapter 3 Installation Mounting Electrical Connections Wiring and Schematic Diagrams Chapter 4 Maintenance Tool Requirements Recommended Torque Values Routine Maintenance Cleaning Main Contact Inspection HiPot and Insulation Resistance Test Lubrication Rockwell Automation Publication 1502-UM052J-EN-P - December

4 Table of Contents Vacuum Bottle Replacement Coil Replacement Procedure Auxiliary Contact Setup Procedure Mechanically Latched Contactor Trip Coil Replacement Procedure 44 Parts Procedure Mechanically Latched Contactor Setup Procedure Altitude Adjustment Chapter 5 Troubleshooting Troubleshooting and Contactor Coil Resistance Chapter 6 Spare Parts Bulletin 1502 Spare Parts Diagrams and Chart Index Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

5 Preface Summary of Changes This table contains the changes made to this revision. Topic Page Updated procedure for replacing the vacuum bottles 38 About This Publication This manual pertains to the Allen-Bradley Bulletin 1502, Series E and F version 400 A vacuum contactors. For earlier product series letters, contact your local Rockwell Automation representative. Series E and F vacuum contactors are intended for use with electromechanical (relay) control circuits and with IntelliVAC and IntelliVAC Plus control modules. See publications 1503-UM053 and 1503-UM054 respectively. This manual is intended for engineers or technicians that are directly involved in the installation, connection, energizing, and maintenance of the Medium Voltage 400 A Contactor. What This Manual Contains This manual contains the following sections: Contactor description, including dropout times and specifications Information on how to receive, handle, and store the contactor How to mount the contactor, which includes typical electrical and wiring diagrams Tools that are required to maintain the contactor, recommended torque values, and how to perform routine maintenance tasks Troubleshooting section that outlines symptoms, possible causes, and how to remedy them Spare Parts list Rockwell Automation Publication 1502-UM052J-EN-P - December

6 Preface Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Medium Voltage Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure, publication 1512A- UM100 Medium Voltage Controllers, 200/400A Two-High Cabinet, Standard and Arc-Resistant Enclosure, publication UM055 IntelliVAC Contactor Control Module User Manual, publication 1503-UM053 IntelliVAC Plus Contactor Control Module User Manual, publication 1503-UM054 Industrial Automation Wiring and Grounding Guidelines, publication Product Certifications website, overview.page Description Provides information on installation, maintenance, and spare parts for standard and arc resistant enclosures Provides information on installation, maintenance, and spare parts for standard and arc resistant enclosures Provides information on receiving and storage, installation, setup, monitoring, and spare parts for the IntelliVAC Contactor Control Module Provides information on receiving and storage, installation, wiring, programming, and troubleshooting for the IntelliVAC Plus Contactor Control Module Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. 6 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

7 Chapter 1 Product Description Contactor Description The Allen-Bradley Bulletin A vacuum contactors are designed for applications in the V AC range. The contactor is suitable for all types of loads, for example: three-phase motors, transformers, power capacitors, and resistive heat loads. The contactor uses three interrupters (referred to as vacuum bottles) operated by an electromagnet assembly through a mechanical linkage. They are resistant to most adverse atmospheric conditions and provide long mechanical and electrical life. The contactors are used in various motor control and drive configurations, such as full-voltage non-reversing, full-voltage reversing, two-speed, reduced voltage, synchronous, drive input/output, and bypass applications. They are fixed-mounted within the structures and the line and load terminations are made at the rear of the device. In most configurations, the main contactor is mechanically interlocked with the external operating handle and isolation switch. Bulletin 1502 vacuum contactors are designed for use with the IntelliVAC and IntelliVAC Plus control modules (see publications 1503-UM053 and 1503-UM054). Certain contactor models are configured for use with electromechanical (relay) control panels. There are physical differences between contactors that are designed for IntelliVAC and IntelliVAC Plus control versus those intended to be operated using electromechanical relay controls (see Catalog Number Explanation on page 12). Series Letter Details The series letter of the Bulletin 1502 contactor is shown on the label that is located on the front of the armature plate (Figure 4). The catalog number, along with the series letter, define the product s electrical and mechanical configuration. This information must be used to select the appropriate repair or replacement parts. Electromechanical relay controlled, electrically held contactors moved from Series D to Series E with the inclusion of mechanical vacuum bottle braces. Electromechanical relay controlled, mechanical-latch contactors were moved from Series E to Series F with the inclusion of mechanical vacuum bottle braces. Rockwell Automation Publication 1502-UM052J-EN-P - December

8 Chapter 1 Product Description IntelliVAC and IntelliVAC Plus controlled electrically held and mechanically latched contactors were moved from Series E to Series F with the inclusion of mechanical vacuum bottle braces. Figure A Contactor Vacuum Bottle Description Each vacuum bottle (Figure 2) consists of two contacts that are enclosed in a ceramic housing: an upper contact that is mounted to a fixed shaft, and a lower contact that is mounted to a movable shaft. A stainless steel bellow helps the vacuum integrity of the bottle, while letting the lower contact move towards and away from the fixed contact. Figure 2 - Vacuum Bottle Cross Section Fixed Shaft Ceramic Arc Shield Contacts Bellows Contact Wear Indicator Line Bearing Movable Shaft 8 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

9 Product Description Chapter 1 Electrically Held Contactor Operation IntelliVAC and IntelliVAC Plus Controlled Contactors The electrically held contactor consists of three vacuum bottles. An electromagnet assembly and a mechanical linkage are used to close the contacts. When the IntelliVAC or IntelliVAC Plus control module receives a close command, the contactor coils (two connected in series) are energized, and the current creates an electromagnet with the coils. The electromagnet pulls the armature plate towards the core of the coils, which rotates the shaft and causes the actuator plate to move upwards. As the actuator plate moves, it pushes the insulator and each vacuum interrupter s movable shaft up, which closes the contacts in the vacuum bottle. The IntelliVAC or IntelliVAC Plus control module supplies the current required to close the coils for approximately 200 milliseconds. Afterward, the coil current is reduced to a lower hold-in value. When the close command is removed from the IntelliVAC or IntelliVAC Plus control module (Open), the coils are de-energized, which opens the contactor. Electromechanical Relay Controlled Contactors When the main pilot relay (CR1) in the control circuit is energized, the circuit energizes an electromagnet in the closing coil and in the hold-in coil (Figure 18). The electromagnet pulls the armature plate towards the core of the coils, which rotates the shaft and causes the actuator plate to move upwards. As the actuator plate moves, it pushes the insulator and each vacuum interrupter s movable shaft up, which closes the contacts in the vacuum bottle. The control circuit economizing auxiliary contacts, on the left side of the contactor, change from the normally closed state to the normally open state as the contactor closes, which de-energizes the closing coil. The hold-in coil remains energized and keeps the contactor closed. Deenergizing the hold-in coil opens the contactor. IMPORTANT The standard electrically held contactor requires an external 120V AC or 240V AC control relay and rectification circuit to control the standard DC closing and hold-in coils on the contactor (see Figure 19). Rockwell Automation Publication 1502-UM052J-EN-P - December

10 Chapter 1 Product Description Figure 3 - Electrically Held Vacuum Contactor Operation Control Transformer Fuse Clip Insulator Armature Plate and Shaft Auxiliary Actuator Control Wire Plug Armature Stop Bracket Line Terminal Vacuum Bottle Load Terminal Flexible Bus Return Spring Actuator Plate Gap Adjustment Screw Magnet Coil Assembly Mechanically Latched Contactor Operation The mechanically latched contactor operates in much the same way as the electrically held (Figure 3) with only a few exceptions. IntelliVAC and IntelliVAC Plus Controlled Contactor Once the contactor is fully closed, a spring-loaded mechanism moves a roller against the armature plate to hold it against the electromagnetic core. The contactor can be opened electrically by energizing a trip coil (via IntelliVAC or IntelliVAC Plus open [TCO] output) which pulls the latch away from the armature, or by a push button that mechanically releases the contactor. The push button is mounted on the power cell door. Electromechanical Relay Controlled Contactor Once the contactor is fully closed, a spring-loaded mechanism moves a roller against the armature plate to hold it against the electromagnetic core. The control circuit auxiliary contact, on the left side of the contactor, changes from the normally closed state to the normally open state as the contactor closes. This action de-energizes the relay that controls the closing coils (see Figure 18). The contactor can be opened electrically by energizing a trip coil that pulls the latch away from the armature, or by a push button that mechanically releases the contactor. The push button is mounted on the power cell door. 10 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

11 Product Description Chapter 1 The electromechanical relay controlled mechanical latch contactor requires external 120V AC or 230V AC control relays and rectification circuit to control the standard DC closing and trip coils on the contactor (when IntelliVAC or IntelliVAC Plus is not used). See Figure 19. WARNING: The Rockwell Automation relay control panel (1503C-XXX or 1503E-CXXX) is required for reliable operation of the contactor within its published specifications. The relays break the DC current that is drawn by the closing coil, holding coil, and trip coil. The relays make sure the pick-up and drop out voltages are coordinated with the pick-up and drop out voltages of the contactor. This provides reliable operation of the circuit in undervoltage conditions. The use of alternative control relays is not supported or recommended. Alternative relays do not provide the necessary control timings necessary to provide reliable operation and coordination with all power fuses used in combination with the contactors. Contactor Identification Each contactor is identified with a rating label (Figure 4) attached to the armature plate at the front of the contactor. The rating label information includes the Catalog Number (Cat.) Series Letter (Ser.) Voltage Rating, Non- Enclosed Current Rating, Interrupting Capacity, Altitude Range (in meters), CSA, UL, and CE markings. Figure 4 - Contactor Rating Label (400 A) Rockwell Automation Publication 1502-UM052J-EN-P - December

12 Chapter 1 Product Description Catalog Number Explanation The following catalog number explanation is used to identify the contactor and must be used when contacting your local Rockwell Automation sales office for assistance. Position V 4 D B D A a b c d e f g Contactor Type and Interlock V Vacuum, electromechanical relay controlled VC Vacuum, optimized for IntelliVAC control Contactor Size A Nominal Line Voltage D 7200V a b c d Control Circuit or Voltage Transformer Primary Fuse Mounting Provisions B 5000V C 7200V Coil Voltage D 110V DC E 207V DC e A f Function 3-pole, electrically held contactor B 3-pole, mechanically latched contactor with electrical and mechanical release C 3-pole, electrically held contactor with fast drop-out (1) (1) Controlled by electromechanical relay. Altitude Code (m) (1) (1) Only with VC contactor type (Position 1 in Catalog Number). g Contactor Dropout Times The IntelliVAC or IntelliVAC Plus contactor control module (publications 1503-UM053 and 1503-UM054) varies the speed at which the electrically held vacuum contactor opens. When electromechanical relays are used to control the electrically held contactor, there are two speeds available: normal dropout time and fast dropout time. The opening speed is controlled by changes to the onboard contactor control circuity (see Figure 13 through Figure 16). Contactors that are configured for faster dropout times are used for specific applications if faster uncoordinated action is required. 12 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

13 Product Description Chapter 1 Contactors with normal dropout times must be used in coordination with medium voltage power fuses. The dropout time must be longer than the Total Clearing Time of the medium voltage power fuses being applied in combination with the vacuum contactor. Damage to the contactor can occur if this coordination is not addressed appropriately. All mechanically latched contactors are designed with the fast dropout time. Specifications Table 1 - Voltage Rating (1) Maximum Rated Voltage 7200 System Voltages 2400, 3300, 4160, 4800, 6600, 6900 Dielectric Voltage Withstand Rating For 60 seconds (kv) 18.2/20 (IEC) Basic Impulse Level (B.I.L.) Withstand Phase to Ground, Phase to Phase (kv) Frequency Ratings Hertz 50/60 (1) The voltage ratings listed are valid up to 1000 m (3300 ft). See Table 8 for ratings above this altitude. 60 Table 2 - Current Ratings (1) Rated Continuous Current (A) 400 Maximum interrupting current rating 2400V (RMS Sym A) V (RMS Sym A) V (RMS Sym A) (2) 6000 Maximum interrupting MVA rating 2400V (Sym MVA) V (Sym MVA) V (Sym MVA) (2) 75 Short circuit withstand at rated voltage Current Peak ½ cycle (ka) 55 Short time current rating capability For 1 second (ka) 6.0 For 30 seconds (ka) 2.4 Chop current (average rms amperes) 0.5 Make and Break Capability at Rated Voltage (ka) 4.0 Ambient Temperature C 40 (1) The current ratings that are listed are valid up to 1000 m (3300 ft). See Table 8 for ratings above this altitude. (2) The IEC rating at 7200V (RMS Sym.) is 5300 A / 66 MVA. Rockwell Automation Publication 1502-UM052J-EN-P - December

14 Chapter 1 Product Description Table 3 - Contactor Coil Data Control Voltage (V CTL ) Coil Voltage (V CL ) Electromechanical Relay Controlled (Mechanical Latch) 120V AC 110V DC Close current inrush (A DC ) 5.6 Pilot Relay (CR1) pick-up voltage 102 Minimum trip coil voltage (VAC) 84 Trip coil current (A) 6 Electromechanical Relay Controlled (Electrically Held) 120V AC 110V DC Close current inrush (A DC ) 7.3 Economized holding current (A DC ) 0.13 Minimum CR1 coil pick-up voltage (VAC) 102 CR1 coil drop-out voltage (VAC) 75 Electromechanical Relay Controlled (Mechanical Latch) 230V AC 210V DC Not available at this control voltage Electromechanical Relay Controlled (Electrically Held) 230V AC 210V DC Close current inrush (A DC ) 8.3 Economized holding current (A DC ) 0.11 Minimum CR1 coil pick-up voltage (V AC) 190 CR1 coil drop-out voltage (V AC) 140 IntelliVAC and IntelliVAC Plus Control (Electrically Held & Mechanical Latch) V AC or V DC (1) V AC: V CL = 2 V DC: V CL = V CTL x V CTL (max.) Close current (A DC, 200 milliseconds) 4.3 Hold current (A DC ) 0.48 Pick-up voltage (1) 95 Drop-out voltage (1) 75 Trip current (A DC, 200 milliseconds) 5.5 Trip voltage (1) 70 (1) Control voltage, as measured at the input of the IntelliVAC or IntelliVAC Plus control module or the primary voltage to the pilot relay control circuit. Table 4 - Operational Characteristics Mechanical life (operations) x 1000 (1) Electrically held 2500 Mechanical latch 100 Electrical life (operations) x 1000 (1) 1000 Switching frequency (operations per hour) Electrically held 600 Mechanical latch 150 (1) Provided that regular maintenance is performed, as detailed in this manual. 14 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

15 Product Description Chapter 1 Table 5 - Opening and Closing Times Maximum closing time (120V AC) (1) Maximum opening time (120V AC) (2) Maximum opening time (120V AC) (3) Electromechanical (Relay) Controlled 50 Hz or 60 Hz (ms) 160 (1) Control/Pilot relay, other than the standard Rockwell Automation Control Panel assembly (1503C-E4_ or 1503C-M4D), must provide a constant closing signal for at least this period of time. The use of control components other than Rockwell Automation products is not recommended and may pose reliability concerns. (2) Mechanical latched. 50 Hz or 60 Hz (ms) Hz or 60 Hz (ms) 160 IntelliVAC and IntelliVAC Plus Control (Electrically Held & Mechanical Latch) Maximum closing time (50 60 Hz) 120 / 240V AC (ms) 100/70 Maximum opening time (without delay, for Hz) (4) 120 / 240V AC (ms) 60 (3) Electrically held, normal dropout. (4) A contactor drop-out delay may be configured with the IntelliVAC or IntelliVAC Plus control module (refer to publications 1503-UM053 and 1503-UM054). Table 6 - Capacitor Switching (max. kvar) System Voltage 2400V V V 2000 Table 7 - General Standard Altitude Capability (1) (2) Contactor Weight Auxiliary Contact Rating Auxiliary Contacts on the Vacuum Contactor (max.) (3) m ( ,500 ft) 21.8 kg (48 lb) A600 3 N.O., 3 N. C. (1) The voltage and current ratings that are listed are valid up to 1000 m (3300 ft). See Table 8 for ratings above this altitude. (2) The full altitude range is available with the IntelliVAC or IntelliVAC Plus control module only, and the IntelliVAC or IntelliVAC Plus is to be configured accordingly (refer to publications 1503-UM053 and 1503-UM054). The standard mechanical latch contactors, if used with electromechanical control, are designed for m ( ft). Higher altitudes are possible by changing the contactor return springs (refer to Catalog Number Explanation for suitable catalog numbers). (3) The number of contactor auxiliary contacts depends on the contactor type. Some of the contacts are used in the typical control schemes used. Rockwell Automation Publication 1502-UM052J-EN-P - December

16 Chapter 1 Product Description Table 8 - Altitude Derating Altitude Rating Max. Continuous Current Rating (2) Reduce B.I.L. Withstand Rating by: m ( ft) (1) m ( ft) m ( ft) m ( ft) m ( ,200 ft) m (13,201 16,500 ft) 400 A 400 A 390 A 6.0 kv 380 A 12.0 kv 370 A 18.0 kv 360 A 24.0 kv (1) Only supported with IntelliVAC or IntelliVAC Plus controlled contactors (2) Open rating. When enclosed in a controller, see the appropriate controller manual for enclosed contactor derating values. Product Approvals UL347 CSA22.2 No. 14 and T.I.L. D-21 IEC CE Marked 16 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

17 Chapter 2 Receiving and Handling Receiving The contactors have been tested both mechanically and electrically before leaving the factory. Immediately upon receiving the contactor, remove the packing material and check the contactor for possible damage from shipping. If damage is found, do not discard the packaging materials and, if possible, note the damage on the Bill of Lading before accepting the shipment. Report any damage immediately to the claims office of the common carrier. Provide a description of the damage and as much identification as possible. Preliminary Inspection Check for any cracks or breaks that were caused by impact. Push armature plate to verify that the mechanisms are functional. Use a HiPot tester to test vacuum bottle integrity (refer to Vacuum Bottle Integrity Test on page 18) Handling The contactor weighs approximately 21.8 kg (48 lb). When transporting the contactor over longer distances or for sustained lifting, use a forklift. When a forklift is used to handle the equipment, adhere to the following precautions: Keep the contactor in an upright position. Carefully balance the contactor on the forks. Use a safety strap to steady the contactor and avoid shifting or being tipped. Avoid excessive speeds and sudden starts, stops, and turns. Never lift a contactor above an area where personnel are located. Rockwell Automation Publication 1502-UM052J-EN-P - December

18 Chapter 2 Receiving and Handling Pre-energization Inspection Before placing the contactor in service, inspect for possible damage sustained in transit or maintenance:. Check housing for any cracks or breaks. Push the armature plate and rotating shaft to verify that the mechanism is in good working order. Inspect the contactor for dirt, stray or loose hardware, tools, or metal chips. Vacuum if necessary. Storage To store the contactor before it is in service, store it in a clean, dry area, free from dust and condensation. Do not store contactor outdoors. Storage temperature must be between C ( F). If storage temperature fluctuates or if humidity exceeds 85%, use space heaters to prevent condensation. Vacuum Bottle Integrity Test The internal dielectric condition and vacuum integrity of the vacuum bottles is determined by this test. ATTENTION: Do not apply a voltage higher than 25,000V across the open contacts of a vacuum bottle. Dangerous x-ray emissions can be produced. ATTENTION: Vacuum bottles are thoroughly tested at the factory; however, damage during shipment can occur. It is important to perform the vacuum bottle integrity test before energizing the contactor for the first time, and before it is returned to service after maintenance or repair. The test may result in personal injury or damage to the equipment if the vacuum bottle integrity fails. ATTENTION: A high-voltage test is potentially hazardous. Use caution when performing the Hi-pot test. Failure to do so may result in severe burns, injury, or death. High-potential test instruments can be purchased to perform the vacuum bottle integrity test. An insulation resistance tester cannot be used to measure vacuum integrity because the voltage is too low. One of the following AC Hipot testers is recommended as a test instrument. Manufacturer Mitsubishi Type VI #4U17 Jennings Model JHP-70A Hipotronics Model 7BT 60A Address Chicago, Ill., USA San Jose, CA., USA Brewster, NY, USA 1. Clean the outside of the vacuum bottles with a lint-free cloth or industrial wipe before performing the test. 18 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

19 Receiving and Handling Chapter 2 2. The contactor can be tested while it is in the power cell. The line connection of the contactor must be disconnected and the ground lead from the Hi-pot tester must be connected to the load side of the contactor. Any fuses in the top of the contactor must be removed. 3. With the contactor in the open position, connect the test leads to the contactor power terminals as shown in Figure 5. It is recommended that an AC Hi-pot tester be used. Apply 16 kv for 60 seconds and monitor the leakage current. It must not exceed 5 ma. Test each vacuum bottle individually. 4. If no breakdown occurs, the vacuum bottle is in an acceptable condition. If a breakdown occurs, repeat the test once more. If the vacuum bottle fails a second time, it must be replaced. If no breakdown occurs in the second test, the vacuum bottle is in an acceptable condition. ATTENTION: If one vacuum bottle fails, Rockwell Automation recommends replacing all three vacuum bottles, if the unit has been in service. 5. After the high potential voltage is removed from the vacuum bottles, the metal end caps of the vacuum bottles must be discharged with a grounding rod. Figure 5 - Vacuum Bottle Integrity Test Circuit Vacuum Checker Vacuum Contactor in Open Position The allowable leakage current value of 5 ma is exclusive of leakage due to test equipment leads. The test setup leakage can be determined by running the dielectric test with test leads not connected to the contactor and noting the maximum leakage current. If this value is more than 2 ma, it must be added to the 5 ma limit when testing the vacuum bottles. Rockwell Automation Publication 1502-UM052J-EN-P - December

20 Chapter 2 Receiving and Handling Rockwell Automation does not recommend a DC Hi-pot test. The values that are obtained during the test are not a reliable indication of vacuum bottle integrity. Some specific DC GO-NO GO testers may provide suitable defective readings. A DC Hi-pot test is unreliable because of Cathode Ray Tube Effect. This phenomenon occurs when one contact of the vacuum bottle has a deformity, such as a burr or deposit, while the other contact remains flat and true. This deformity creates leakage currents, which flow from a small surface to a large surface in one direction and vice versa when the polarity of the tester is changed. The resultant current is large in one direction, which would incorrectly indicate a faulty vacuum bottle. A DC test can verify some degree of vacuum integrity. It does not give any indication of the degree of vacuum, since the contact surface can change with each operation of the vacuum contactor. However, an AC test provides a reliable vacuum integrity indication. Additionally, the degree of vacuum within the bottle can be determined by comparing initial test results to the present readings. Increases in leakage current indicate a reduction in vacuum within the vacuum bottle. For these reasons, Rockwell Automation recommends an AC test as the preferred method of a vacuum bottle test. A suitable GO-NO GO DC test unit is: Manufacturer Programma, Model VIDAR Address Santa Rosa, CA, USA Insulation Resistance Test Use a 1000V insulation resistance tester to verify that the resistance from phase-to-phase or from phase-to-ground is greater than 500 megohms. 20 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

21 Chapter 3 Installation Mounting The electrically held and the mechanically latched contactors are fixedmounted in the cabinet. Two retaining tabs at the rear of the molded base can be used for mounting. The two mounting slots at the front of the molded base secure the contactor with 1/4 in. bolts. The appropriate mounting configuration is provided inside the power cells of Allen-Bradley controllers. If the contactor is supplied as an OEM component for installation in a custom application, refer to the dimensional information in Figure 6. If the contactor is mounted in an enclosure designed by an OEM, there must be a minimum of 3 in. (76 mm) of air space between live parts (terminals and vacuum bottles) and the enclosure. Figure 6 - Contactor Mounting Details (dimensions are in inches [millimeters]) 0.75 [19] [336] 8.64 [219] 4.96 [126] [438] 8.53 [217] 5.00 [127] 3.15 [80] 4.25 [108] 4.25 [108] Front View Cutaway View 0.37 [9] 0.91 [23] 1.36 [35] [267] 0.37 [9] [7] wide slots 7.87 [200] 2.12 [54] 8.00 [203] 0.98 [25] Bottom View Rockwell Automation Publication 1502-UM052J-EN-P - December

22 Chapter 3 Installation Figure 7 - Mechanical Latch Dimensions (Optional) Contactor Electrical Connections A wire harness connects the control wiring to the contactor from the low voltage control panel. The harness connects to a wire plug on the lower left side of the contactor. If the contactor is supplied as an OEM component for installation in a custom application, the following two control options and a connecting wire harness are available from Rockwell Automation. IntelliVAC and IntelliVAC Plus control modules Electromechanical control panel Connect incoming power to the line side terminals at the top, rear of the contactor near the control fuse clips. Use 3/8 in. (10 mm) bolts torqued to 20 lb ft (292 N m) to secure the connection. Connect outgoing power to the load side terminals halfway down the rear of the contactor. Use 3/8 in. (10 mm) bolts torqued to 20 lb ft (292 N m) to secure the connection. For mechanically latched contactors, the manual trip button in the cabinet door must be in line with the trip lever on the contactor. 22 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

23 Installation Chapter 3 Figure 8 - Electrical Connections (Rear View) Control Circuit Transformer Primary Fuse Clips Line Side Terminals Load Side Terminals Control Wire Plug Rockwell Automation Publication 1502-UM052J-EN-P - December

24 Chapter 3 Installation Wiring and Schematic Diagrams Figure 9 - Wiring Diagram - Electrically Held Contactor (for use with IntelliVAC and IntelliVAC Plus Control Modules Only) Yellow Black Yellow Black 120V Contactor Plug Power Wiring Control Transformer Primary Fuse Holders A - N - Pins D, P - No Connections Schematic 400 A Vacuum Contactor Auxiliary Contacts 24 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

25 Installation Chapter 3 Figure 10 - Wiring Diagram - Mechanical Latch Contactor (for use with IntelliVAC and IntelliVAC Plus Control Modules Only) Yellow Black Yellow Black White Blue Auxiliary Contacts Power Circuit Control Transformer Primary Fuse Holders A, B, C, D, I - Sockets All Others - Pins Auxiliary Contacts Contactor Shown in Open (Tripped) Condition CC - Closing Coil TC - Trip Coil Rockwell Automation Publication 1502-UM052J-EN-P - December

26 Chapter 3 Installation Figure 11 - Wiring Diagram - Mechanical Latch Contactor (for use with Electromechanical Control Panel Only) Yellow Black Yellow Black White Blue Auxiliary Contacts Power Circuit Control Transformer Primary Fuse Holders C, D, I - Sockets All Others - Pins Auxiliary Contacts Contactor Shown in Open (Tripped) Condition CC - Closing Coil TC - Trip Coil 26 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

27 Installation Chapter 3 Figure 12 - Wiring Diagram - Electrically Held Contactor, 120V AC, Normal Dropout Time, (for use with Electromechanical Control Panel Only) Yellow Black Yellow Blue Auxiliary Contacts Power Circuit Control Transformer Primary Fuse Holders A - N - Pins Schematic 400 A Vacuum Contactor 120V Coil, Normal Dropout Auxiliary Contacts CC - Closing Coil HC - Holding Coil Rockwell Automation Publication 1502-UM052J-EN-P - December

28 Chapter 3 Installation Figure 13 - Wiring Diagram - Electrically Held Contactor, 230V AC, Normal Dropout Time, (for use with Electromechanical Control Panel Only) Yellow Black Yellow Blue Auxiliary Contacts Power Circuit Control Transformer Primary Fuse Holders B, C, D, E, F, G, H, I, J, K, N - Pins A, L, M - Sockets P - Not used Schematic 400 A Vacuum Contactor 230V Coil, Normal Dropout Auxiliary Contacts CC - Closing Coil HC - Holding Coil 28 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

29 Installation Chapter 3 Figure 14 - Wiring Diagram - Electrically Held Contactor, 120V AC, Fast Dropout Time, (for use with Electromechanical Control Panel Only) Yellow Black Yellow Blue Auxiliary Contacts Power Circuit Control Transformer Primary Fuse Holders A - N - Pins Schematic 400 A Vacuum Contactor 230V Coil, Fast Dropout Auxiliary Contacts CC - Closing Coil HC - Holding Coil Rockwell Automation Publication 1502-UM052J-EN-P - December

30 Chapter 3 Installation Figure 15 - Wiring Diagram - Electrically Held Contactor, 230V AC, Fast Dropout Time, (For Use with Electromechanical Control Panel Only) Yellow Black Yellow Blue Auxiliary Contacts Power Circuit Control Transformer Primary Fuse Holders B, C, D, E, F, G, H, I, J, K, N - Pins A, L, M - Sockets P - Not used Schematic 400 A Vacuum Contactor 230V Coil, Fast Dropout Auxiliary Contacts CC - Closing Coil HC - Holding Coil 30 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

31 Installation Chapter 3 Figure 16 - Typical Schematic Diagram for 400 A Full-Voltage Non-Reversing (FVNR) Controller With IntelliVAC Control and Electrically Held Contactor L1 L2 L3 GRD M CT1 CT2 CT3 T1 T2 T3 2400V-6900V 3Ø, 50/60Hz POWER BUS GRD BUS ISOLATING SWITCH DOOR INTERLOCK CURRENT LIMITING POWER FUSES H1 CPT 500VA ISa 5 7 X1 H2 X2 CURRENT LIMITING PRIMARY FUSES OL OVERLOAD X (5) (6) ISb A 2.0A E M F I M J 35 EXTRA AUXILIARY CONTACTS 32 G M H K M L STOP STOP 1 # MOV D NOTE: NORMAL X OFF TEST (1) (2) (7) (8) X TEST SUPPLY POINT 10 TS V 50/60Hz (3) (4) X A M B EC M-IV TCO 11 6 AUX CCO N MAIN CONTACTOR MOV M M C L1 G L2/N START START D D 1A M-IV CLOSE OL M-IV CONTACTOR STATUS D RUN 12 D OFF INTELLIVAC NOTES: OUTPUT RELAY CONTACTS SHOWN WITHOUT CONTROL POWER APPLIED. THE FOLLOWING FACTORY INSTALLED CONFIGURATION/POWER-UP STATES ARE IN EFFECT: CONTACTOR STATUS - FAIL SAFE MODULE STATUS - FAIL SAFE INTELLIVAC TO BE PROGRAMMED/CONFIGURED BY THE CUSTOMER BEFORE START-UP. REMOVE JUMPER WHEN CONNECTING REMOTE EQUIPMENT. REMOTE EQUIPMENT LOW VOLTAGE DOOR MOUNTED DEVICE "IEEE" NUMBER FOR PROTECTIVE DEVICE METAL OXIDE VARISTOR CUSTOMER WIRING REFER TO DIMENSION DRAWING FOR COMPONENT SIZING NOT - Rockwell Automation Publication 1502-UM052J-EN-P - December

32 Chapter 3 Installation Figure 17 - Typical Schematic Diagram for 400 A Full-Voltage Non-Reversing (FVNR) Controller With IntelliVAC Control and Mechanical Latch Contactor L1 L2 L3 GRD M CT1 CT2 CT3 T1 T2 T3 2400V-6900V 3Ø, 50/60Hz POWER BUS GRD BUS ISOLATING SWITCH DOOR INTERLOCK CURRENT LIMITING POWER FUSES H1 CPT 500VA X1 5 H2 X2 CURRENT LIMITING PRIMARY FUSES MANUAL TRIP 42 OL OVERLOAD ISa 7 6 X (5) (6) ISb 9 4.0A 2.0A 14 1A 32 G M H 33 M L 37 EXTRA AUXILIARY CONTACT 30 E M F 31 M J N M P 34A NORMAL X OFF (1) (2) (7) (8) X TEST SUPPLY POINT 10 TS V 50/60Hz (3) (4) 15 M K EC M-IV TCO 11 6 AUX CCO D 17 C MAIN CONTACTOR M MOV TC MOV CC M B A G L1 L2/N OL ON 1B D 2 OFF D 3 OL 1 M-IV CLOSE 1 M-IV OPEN D RUN D OFF 1 INTELLIVAC NOTES: OUTPUT RELAY CONTACTS SHOWN WITHOUT CONTROL POWER APPLIED. THE FOLLOWING FACTORY INSTALLED CONFIGURATION/POWER-UP STATES ARE IN EFFECT: CONTACTOR STATUS - FAIL SAFE MODULE STATUS - FAIL SAFE CC TC MOV NOTE: D # INTELLIVAC TO BE PROGRAMMED/CONFIGURED BY THE CUSTOMER BEFORE START-UP. CLOSING COIL TC-TRIP COIL LOW VOLTAGE DOOR MOUNTED DEVICE "IEEE" NUMBER FOR PROTECTIVE DEVICE METAL OXIDE VARISTOR CUSTOMER WIRING REFER TO DIMENSION DRAWING FOR COMPONENT SIZING NOT TEST X I - 32 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

33 Installation Chapter 3 Figure 18 - Typical Schematic Diagram for 400 A Full-Voltage Non-Reversing (FVNR) Controller With Electro-Mechanical Control and Mechanical Latch Contactor (1) L1 L2 L3 GRD M CT1 CT2 T1 T2 CT3 T3 2400V-6900V 3Ø, 50/60Hz POWER BUS GRD BUS ISOLATING SWITCH DOOR INTERLOCK CURRENT LIMITING POWER FUSES H1 CPT 500VA ISa X1 5 H2 X2 CURRENT LIMITING PRIMARY FUSES MANUAL TRIP OL OVERLOAD X (5) (6) ISb A E M J 30 1 M F G M H 32 1 M L EXTRA AUXILIARY CONTACTS 34 N M P 34A 36 I M K 36A OFF NORMAL TEST X (1) (2) (7) (8) X TEST SUPPLY POINT 10 TS V 50/60Hz (3) (4) X REC/MOV RECTIFIER + MOV 15 CR1 CR1 CR1 CR1 17A 17B MAIN CONTACTOR 17C 17 C M T D1 CC M A 20 CR2 CR2 D B 19 TC 15A R 35 OL ON 2A D 2 CR1 MAIN CONTACTOR LATCH RELAY 31 OFF OL D 3 CR2 MAIN CONTACTOR UNLATCH RELAY 33 D RUN 37 D OFF CC TC MOV NOTE: D # CLOSING COIL TC-TRIP COIL LOW VOLTAGE DOOR MOUNTED DEVICE "IEEE" NUMBER FOR PROTECTIVE DEVICE METAL OXIDE VARISTOR CUSTOMER WIRING REFER TO DIMENSION DRAWING FOR COMPONENT SIZING NOT (1) CR1 and CR2 and the wiring of their contacts into the control circuit are part of the Rockwell Automation relay control panel (1503C-XXX or 1503E-CXXX). This control panel provides reliable operation of the contactor within its published specification. Rockwell Automation Publication 1502-UM052J-EN-P - December

34 Chapter 3 Installation Figure 19 - Typical Electrical Diagram for 400 A Full-voltage Non-reversing (FVNR) Controller with Electrically Held Contactor, 120V AC (Normal Drop-out Time) (1) (1) CR1 and CR2 and the wiring of their contacts into the control circuit are part of the Rockwell Automation relay control panel (1503C-XXX or 1503E-CXXX). This control panel provides reliable operation of the contactor within its published specification. 34 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

35 Chapter 4 Maintenance Tool Requirements IMPORTANT Some components of this product incorporate imperial hardware. Rockwell Automation recommends the use of the appropriate tools to complete the maintenance procedure on these components. If you cannot obtain such tools, contact your Rockwell Automation sales office. When maintenance is performed on the vacuum contactor, the following tools are required: 3/8 in. drive ratchet wrench with extension 3/8 in. drive torque wrench Standard 3/8 in. drive sockets; 7/16 in., 1/2 in. Open-end wrenches; 7/16 in., 1/2 in., 5/8 in. Slot head screwdrivers; 1/8 in. wide, 1/4 in. wide External retaining ring pliers (STANLEY-PROTO #393 or equivalent) Feeler gauge set (0.030 in. [0.76 mm] and in. [1.91 mm]) Feeler gauge set (0.010 in. [0.25 mm]) Mechanical Latch 2 in. C-Clamp Armature clamping fixture (Allen-Bradley Part No ) Digital caliper capable of depth measurement High potential tester Rockwell Automation Publication 1502-UM052J-EN-P - December

36 Chapter 4 Maintenance Recommended Torque Values Part of the contactor may have to be disassembled for maintenance or replacement. There are appropriate torque requirements for particular bolt sizes when reassembling the contactor. Use the torque values that are specified in Table 9. Table 9 - Torque Values #10 in. Hardware 2.7 lb ft (3.6 N m) 1/4 in. Hardware 6 lb ft (8 N m) 5/16 in. Hardware (Grade 2) (1) 11 lb ft (15 N m) 5/16 in. Hardware (Grade 5) (2) 18 lb ft (24 N m) 3/8 in. Hardware 20 lb ft (27 N m) (1) All 5/16 hardware is Grade 2 unless otherwise specified. (2) See Figure 22. Routine Maintenance ATTENTION: Before performing any maintenance on the contactor, refer to the User Manual of the starter configuration. Failure to do so can result in injury to personnel or damage to the controller or contactor. ATTENTION: To avoid shock hazards, lockout incoming power and disconnect the control plug from the contactor before working on the unit. Verify with a hot stick or meter that all circuits are voltage free. Failure to do so can result in severe burns, injury, or death. The following must be performed annually or whenever a contactor is serviced: Cleaning 1. Clean all metal chips or filings from around the electromagnet assembly (coil core pole face and mating armature plate) as they can affect proper operation of the contactor. Vacuum clean if necessary. IMPORTANT Do not use compressed air to clean or remove dirt from surfaces or the enclosure. 2. If the vacuum bottles are dirty, clean the white ceramic area with a clean lint-free cloth. 36 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

37 Maintenance Chapter 4 Main Contact Inspection Visually inspect the wear of the main contacts with the contactor energized. When any part of the wear indicator line, located on the front side of the shaft, moves up into the bearing, replace all three vacuum bottles (Figure 20). Figure 20 - Vacuum Bottle Wear Indicator Vacuum Bottle Bearing Wear indicator line on operating shaft HiPot and Insulation Resistance Test The internal dielectric condition and vacuum integrity of the vacuum bottles is determined by this test. See page 18 to check the vacuum bottle integrity. See page 20 to check the insulation resistance. Lubrication Using AeroShell No. 7 (1 oz tube, Part No ), grease the actuator plate where the overtravel springs and washers make contact (Figure 21). Rockwell Automation Publication 1502-UM052J-EN-P - December

38 Chapter 4 Maintenance Figure 21 - Grease Locations Insulator Grease Actuator Plates Grease IMPORTANT Do not grease the armature shaft plastic bearings. These bearings are selflubricating and do not require grease. Vacuum Bottle Replacement Do not replace the vacuum bottles in the field. If the vacuum bottles need to be replaced, remove and return the vacuum contactor to Rockwell Automation for refurbishment. Coil Replacement Procedure See Spare Parts on page 54 for the part numbers that are required for this procedure. 1. Remove the auxiliary actuator, front stop bracket, and armature plate as shown in Figure 22. Do not remove the bolts that secure the stop bracket. Loosen them and slide out the bracket. 38 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

39 Maintenance Chapter 4 Figure 22 - Access to Coils Grade 5 (5/16 in. Hardware) to mount return spring actuator plate Grade 5 (5/16 in. Hardware) to mount armature plate Auxiliary Actuator Armature Plate Armature Stop Bracket Stop Bracket Bolts Return Spring Actuator Plate 2. Remove the retaining ring from the core of the coil you wish to replace as shown in Figure Loosen the auxiliary assembly retaining bolt and slide the assembly and the coils forward and out of the contactor as shown in Figure 23. Figure 23 - Coil Removal Operating Coil Operating Coil Retaining Ring Auxiliary Assembly Retaining Bolt Auxiliary Assembly 4. Disconnect the coil leads (take note of their location). Connect the leads of the new coil making sure that all metal-oxide varistors (MOVs) and/ or diodes are secure. See the appropriate wiring diagram in this manual for further control wiring details (page 24). 5. Slide the new coil into position and install the retaining ring on the core. Install the auxiliary assembly leaving the retaining bolt loose for adjustment later. See the Auxiliary Contact Setup Procedure (page 40) for determining the position of the auxiliary assembly. Rockwell Automation Publication 1502-UM052J-EN-P - December

40 Chapter 4 Maintenance 6. Install the armature plate, auxiliary actuator and stop bracket. Position the stop bracket by resting it lightly against the armature plate. IMPORTANT This procedure applies to adjustment of existing auxiliaries and installation of new auxiliaries. Under normal conditions, auxiliaries last at least 1,000,000 operations. If auxiliary contacts must be replaced, discard the entire assembly and install a new assembly. Discarding the entire assembly is easier than replacing one contact block. Auxiliary Contact Setup Procedure See Spare Parts on page 54 for part numbers required for this procedure. To facilitate the set-up procedure, the contactor is held closed mechanically with a clamping fixture (Figure 24). It is important that the contactor is held closed tightly with the armature plate against the magnet cores when gauging the overtravel and auxiliary positioning. To aid in closing the contactor mechanically, a clamping fixture is required. Allen-Bradley part number is recommended. Figure 24 - Contactor Components Auxiliary Actuator Armature Plate Armature Stop Bracket 1. Loosen the nuts on auxiliary assembly retaining bolt. This requires loosening and removal of the first nut that secures a ground wire at this location. Leave the nut loosened enough to permit the assembly to slide along the adjustment slot as shown in Figure Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

41 Maintenance Chapter 4 Figure 25 - Auxiliary Contact Adjustment Auxiliary Assembly Retaining Bolt 2. Slide the clamping fixture (part number ) over the top of the armature stop bracket (Figure 26). Finger-tighten the two outside fixture mounting bolts against the armature stop bracket. You might have to push the armature plate a little to the rear to put the clamp in place. Figure 26 - Clamping Contactor Closed Contactor Clamping Fixture 3. Place a 5/8 in. wrench on the main shaft of the contactor, pull-down and close the contactor (Figure 27) while finger-tightening the top middle screw on the clamping fixture. ATTENTION: Do not bend the actuator stop plate. Rockwell Automation Publication 1502-UM052J-EN-P - December

42 Chapter 4 Maintenance Figure 27 - Closing the Contactor 4. After the top screw is finger tight, continue to tighten this screw with a hand tool. The armature stop bracket flexes a little, which is acceptable, but do not overtighten and bend the armature stop plate. It is important that the armature plate is held tightly against the magnet cores. The contactor must be fully closed. 5. Place a wide blade in. (0.76 mm) feeler gauge between the plastic auxiliary actuator tips and the steel actuator plate. To aid the installation of the feeler gauge, the gauge can be put in place as the clamping block screw is being finger-tightened (Step 3). See Figure 28 and Figure 29. Figure 28 - Gauging the Contacts 42 Rockwell Automation Publication 1502-UM052J-EN-P - December 2017

Medium Voltage 400A Contactor - Series E and F Allen-Bradley Parts

Medium Voltage 400A Contactor - Series E and F Allen-Bradley Parts User Manual Medium Voltage 400A Contactor - Series E and F Catalog Number 1502 Allen-Bradley Parts Important User Information Read this document and the documents listed in the additional resources section

More information

Electrically Held to Mechanically Latched Contactor

Electrically Held to Mechanically Latched Contactor Electrically Held to Mechanically Latched Contactor Bulletin 1502 Series E or later Retrofit Instructions Important User Information Read this document and the documents listed in the Additional Resources

More information

Medium Voltage Contactor

Medium Voltage Contactor Medium Voltage Contactor (Series D) Bulletin 1502 400A 2400 to 7200 volts User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch Installation Instructions Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch Catalog Numbers 2193FZ Topic Page About This Publication 1 Required Tools 1 Important User Information 2

More information

Battery Replacement. Installation Instructions. Summary of Changes. Catalog Number 2711P-RY2032. Original Instructions

Battery Replacement. Installation Instructions. Summary of Changes. Catalog Number 2711P-RY2032. Original Instructions Installation Instructions Original Instructions Battery Replacement Catalog Number 2711P-RY2032 Topic Page Summary of Changes 1 Important User Information 2 Precautions 3 About This Publication 2 Replace

More information

USER MANUAL Bulletin 1512A 400A One-High Cabinet Standard and Arc-Resistant Enclosure

USER MANUAL Bulletin 1512A 400A One-High Cabinet Standard and Arc-Resistant Enclosure Medium Voltage CONTROLLERS USER MANUAL Bulletin 1512A 400A One-High Cabinet Standard and Arc-Resistant Enclosure Important User Information Solid-state equipment has operational characteristics differing

More information

Allen-Bradley Parts. CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns. Installation Instructions. Catalog Number 2500

Allen-Bradley Parts. CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns. Installation Instructions. Catalog Number 2500 Installation Instructions CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns Catalog Number 2500 Topic Page Important User Information 2 Location Planning 3 Environment 3 Removal

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

Installation Instructions. PowerFlex 700 Drive - Frame 8 Components Replacement

Installation Instructions. PowerFlex 700 Drive - Frame 8 Components Replacement Installation Instructions PowerFlex 700 Drive - Frame 8 Components Replacement Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical

More information

505 Size 5 Series A Construction

505 Size 5 Series A Construction 505 Size 5 Series A Construction With Overload Relays Without Overload Relays Item Part Description Left-Hand Contactor Right-Hand Contactor Both Contactors No. Part Number Part Number Part Number 1 Stationary

More information

Installation Instructions. Y-Series Brushless Servo Motor

Installation Instructions. Y-Series Brushless Servo Motor Installation Instructions Y-Series Brushless Servo Motor Catalog Number Y-1002-1, Y-1002-2, Y-1003-1, Y-1003-2, Y-2006-1, Y-2006-2, Y-2012-1, Y-2012-2, and Y-3023-2 These installation instructions describe

More information

Series A Construction

Series A Construction Page 1 of 7 Knowledgebase Technote ID # Q18363 9/2/2003 505 Series A Construction 505 505 1495-F1 (1 N.O. auxiliary contact) 1495-G5 (1 N.C. early break auxiliary contact) 1495-H0 ( 1 N.C. late break auxiliary

More information

Spare Allen-Bradle. Battery Replacement. Installation Instructions. About This Publication. Catalog Number 2711P-RY2032

Spare Allen-Bradle. Battery Replacement. Installation Instructions. About This Publication. Catalog Number 2711P-RY2032 Installation Instructions Battery Replacement Catalog Number 2711P-RY2032 Topic Page Important User Information 2 Precautions 3 Replace the Battery in PanelView Plus Terminals 3 Replace the Battery in

More information

Kinetix 350 Single-axis EtherNet/IP Servo Drives

Kinetix 350 Single-axis EtherNet/IP Servo Drives Installation Instructions Kinetix 350 Single-axis EtherNet/IP Servo Drives Catalog Numbers 2097-V31PR0-LM, 2097-V31PR2-LM, 2097-V32PR0-LM, 2097-V32PR2-LM, 2097-V32PR4-LM, 2097-V33PR1-LM, 2097-V33PR3-LM,

More information

IEC Starter Approximate Dimensions

IEC Starter Approximate Dimensions Technical Data IEC Starter Approximate Dimensions Bulletin Numbers 103H/107H/140M, 103-C/107/C, 105, 109, 106, 112, 113, 190E/191E, 190S/191S, 103S/107S, 103T/107T Topic Page Enclosed Starters and Motor

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Control and Load Switch Specifications Bulletin Number 194E, 194L

Control and Load Switch Specifications Bulletin Number 194E, 194L Technical Data Control and Load Switch Specifications Bulletin Number 194E, 194L Topic Page Product Line Overview 2 194E General Specifications 3 194E Approximate Dimensions 5 194L Circuit Diagrams 13

More information

Application Description

Application Description -14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

S&C Type FVR Substation Circuit Breaker

S&C Type FVR Substation Circuit Breaker S&C Type FVR Substation Circuit Breaker 15 kv to 38 kv, 200 kv BIL, 1200 A, Class 6065 Instructions for Installation 60553014 S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE Document: VF00W103 Rev. 8 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-5HA 7.2kV, 400A-7.0kA (4.5kA@7.2kV) HCV-5HAL 7.2kV, 400A-7.0kA (4.5kA@7.2kV) Manufactured in the USA AUGUST 2013

More information

PowerFlex 7000 AC Drive with Direct-to-Drive Technology. Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions

PowerFlex 7000 AC Drive with Direct-to-Drive Technology. Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions PowerFlex 7000 AC Drive with Direct-to-Drive Technology Re-installing a Common Mode Choke Bulletin 7000 Installation Instructions Important User Information Solid-state equipment has operational characteristics

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

700 Type P & PK DC Relays Timer Units Latch Units Series A and B Construction. Renewal Parts

700 Type P & PK DC Relays Timer Units Latch Units Series A and B Construction. Renewal Parts Page 1 of 5 Knowledgebase Technote ID # Q19373 3/10/2004 700 Type P & PK DC Relays Timer Units Latch Units Series A and B Construction Renewal Parts Figure 1 Page 2 of 5 Knowledgebase Technote ID # Q19373

More information

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA Document: VF00W103 Rev. 7 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-5HA 7.2kV, 400A-7.0kA (4.5kA@7.2kV) HCV-5HAL 7.2kV, 400A-7.0kA (4.5kA@7.2kV) Manufactured in the USA MAY 2008 MAY

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number)

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number) POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 480 Volts, 60Hz April 15, 2010: updated capacitor UL File number) Page 1 of 14 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Advantage

More information

1489-M Circuit Breakers

1489-M Circuit Breakers Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

Bulletin 1494M Fixed Depth Remote Operated Disconnect Switches Renewal Parts

Bulletin 1494M Fixed Depth Remote Operated Disconnect Switches Renewal Parts Page 1 of 8 Knowledgebase Technote ID # Q37160174 5/13/2005 Repair Parts for the Handle/Mechanism and Fusible Disconnect Switch Assembly (See Figure 1 on next page for exploded view of parts.) Catalog

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

Kinetix 350 Single-axis EtherNet/IP Servo Drives

Kinetix 350 Single-axis EtherNet/IP Servo Drives Installation Instructions Kinetix 350 Single-axis EtherNet/IP Servo Drives Catalog Numbers 2097-V31PR0-LM, 2097-V31PR2-LM, 2097-V32PR0-LM, 2097-V32PR2-LM, 2097-V32PR4-LM, 2097-V33PR1-LM, 2097-V33PR3-LM,

More information

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model User's Manual High Voltage Megohmmeter Analog Insulation Tester plus AC Voltage and Continuity Tests Model 380353 Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

Industrial Control Transformers

Industrial Control Transformers 6 Industrial Control Transformers Section 6 Industrial Control Transformers provide a low and safe control voltage for the operation of electromagnetic devices, such as motor starters, contactors, solenoids

More information

Page 1 of 9 Knowledgebase Technote ID # Q /24/2006

Page 1 of 9 Knowledgebase Technote ID # Q /24/2006 Page 1 of 9 Knowledgebase Technote ID # Q18356 3/24/2006 Bulletin 520F/520G Multi-Speed NEMA Starters with Eutectic Alloy or Solid-State Overload Relays Sizes 0 through 4 (all series), Size 5 (series L)

More information

SG-B1 SERIES / SG-A1 SERIES

SG-B1 SERIES / SG-A1 SERIES 643 Door with Solenoid Interlock / Door Ultra-slim SG-B1 SERIES / SG-A1 SERIES Related Information General terms and conditions... F-7 General precautions... P.1501 PHOTO PHOTO Conforming to Machine &

More information

PowerFlex 700 Drive - Frame 8 Components Replacement

PowerFlex 700 Drive - Frame 8 Components Replacement Installation Instructions PowerFlex 700 Drive - Frame 8 Components Replacement Catalog Numbers 20B Important User Information Read this document and the documents listed in the additional resources section

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 080920 2008 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic mitigation

More information

HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA

HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA Document: VF010H08A INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA Issued: 12/05 Manufactured in the

More information

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers User manual W-VACi W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers 65A7355H01 Rev.04 January 2013 www.eaton.com 2 Table of contents 1 Safety... 5 1.1 Safety precautions...5 1.2 Safety practices...5

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Bulletin 509 Three Phase Full Voltage NEMA Starters Size 00 (all series) Renewal Parts

Bulletin 509 Three Phase Full Voltage NEMA Starters Size 00 (all series) Renewal Parts Page 1 of 7 Knowledgebase Technote ID # Q18318 3/28/2006 Renewal Parts The 509 Three phase starter consists of three switching poles, a fourth pole to be used as a control circuit hold-in contact and overload

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Transfer switch OTEC and OTECSE open transition

Transfer switch OTEC and OTECSE open transition Specification sheet OTEC and OTECSE open transition 125-600 Amp Description OTEC transfer es are designed for operation and ing of electrical loads between primary power and standby generator sets. They

More information

Installation Instructions. PowerFlex 700 Drive - Frame 7 Components Replacement

Installation Instructions. PowerFlex 700 Drive - Frame 7 Components Replacement Installation Instructions PowerFlex 700 Drive - Frame 7 Components Replacement Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

Direct Communication Module

Direct Communication Module Installation Instructions Direct Communication Module (Catalog Number 1747-DCM) Inside...................................... page For More Information.............................. 3 Hazardous Location

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Manual Transfer Switch

Manual Transfer Switch Manual Transfer Switch Instruction Manual 30 1200 Amp 2, 3 & 4 Pole Page 1 WARNING Before Installation READ THIS MANUAL carefully to learn how to properly install, operate and maintain this unit. Personal

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

MOTORTRONICS Solid State AC Motor Control

MOTORTRONICS Solid State AC Motor Control Solid State AC Motor Control MWH Series Solid State Motor Winding Heater 10 to 80 Amps INSTALLATION & START-UP MANUAL REV 4 6091101MN Table of Contents Chapter 1: General Information... 1 1.1 Introduction

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

CENTERLINE 1500 Medium Voltage Motor Control Centers

CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide CENTERLINE 1500 edium Voltage otor Control Centers Designed for Intelligence, Safety, and Reliability CENTERLINE 1500 otor Control Centers edium Voltage otor Control Centers... 3 Standard

More information

Installation Instructions

Installation Instructions Smart Start Assist Kit For use with Single-Phase Residential Geothermal Heat Pumps 8-733-934-497 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY

More information

EISHO TEK. Vacuum Circuit Breaker

EISHO TEK. Vacuum Circuit Breaker EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who

More information

WARRANTY INFORMATION...

WARRANTY INFORMATION... Table of contents 1 General Information... 3 1.1 Description... 3 1.2 Features... 3 1.3 Specifications... 4 1.4 Receiving and Unpacking... 4 1.5 Dimensions... 4 2 Installation... 5 2.1 Wiring... 5 3 Operation...

More information

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION 505 z 509 FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION The movable contacts are carried in stainless steel cages which in turn are mounted in cavities in the molded portion of the cross bar. This

More information

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Descriptive Bulletin R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG TM is truly the next generation in medium voltage vacuum circuit breaker

More information

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Descriptive Bulletin R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG is truly the next generation in medium voltage vacuum circuit breaker technology.

More information

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release)

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release) Document: GF07Z304 Rev. 2 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release) Issued: 10/2006

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

Pump Panel Specifications

Pump Panel Specifications Technical Data Pump Panel Specifications Bulletin Numbers 13 and 133 Topic Page Specifications Electrical Ratings (Bulletins 13, 13X, 133, 133X) Mechanical Ratings (Bulletins 13, 13X, 133, 133X) 3 Construction

More information

Rotary Disconnect Switches, Bulletin 194R

Rotary Disconnect Switches, Bulletin 194R ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION Rotary Disconnect Switches Bulletin 194R NOTICE: The specification guidelines in this document are intended to aid in the specification

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity.

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity. INSTALLATION, OPERATION and MAINTENANCE MANUAL MODEL SCPF1 15, 25, 40 & 65 AMP SCR POWER CONTROLS UL/cUL FILE NUMBER E151547 CE See last page of manual for CE Declaration of Conformity. AMETEK HDR POWER

More information

MV SMC-Flex OEM Components

MV SMC-Flex OEM Components MV SMC-Flex OEM Components Bulletin 1503E Installation Instructions Important User Information Read this document and the documents listed in the Additional Resources section about installation, configuration,

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Installation Operation Maintenance ADDENDUM

Installation Operation Maintenance ADDENDUM Installation Operation Maintenance ADDENDUM Bulletin #: PS-IOM-HYPO2-0111-A FACTORY SERVICE POLICY If you are experiencing a problem with your Pulsafeeder pump, first review the IOM, and consult the troubleshooting

More information

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls P-269-89-0408 Installation Installation & Operating Instructions Contents Introduction........................... 2 Specifications.........................

More information

Control Relays Overview

Control Relays Overview Control Relays Overview DESIGN FEATURES Among the advances Agastat Control Relays offer over existing designs is a unique contact operating mechanism. An articulated arm assembly amplifies the movement

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 120628 REV. 007 2012 MTE Corporation Matrix Series D User s Manual 600VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

NHP SAFETY REFERENCE GUIDE

NHP SAFETY REFERENCE GUIDE NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS Door Monitoring Trojan 5 Interlock Switch, Guardmaster Safety Relay, PowerFlex 525 Drive with Safe Torque-off Table of Contents: Introduction 6-122

More information

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation MATRIX FILTER SERIES D 480 Volts, 60HZ USER MANUAL PART NO. INSTR 024 REL. 120628 REV. 012 2012 MTE Corporation Matrix Series D User s Manual 480VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Model C230 Pump Controller

Model C230 Pump Controller MANUAL Model C230 Earthsafe Systems, Inc. 7553 S. Madison Willowbrook, IL 60527 T: (630) 794-5100 F: (630) 794-5106 info@earthsafe.com www.earthsafe.com March 1, 2010 The information contained herein is

More information

General information about motor protection

General information about motor protection Application guide General information about motor protection Typical construction of a motor starter Disconnect Switch UL 98 - UL489 CSA C22.2 # 4 CSA C22.2 # 5 Fuses SIRCO Non-Fusible Disconnect Switch

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

Auxiliary Contact Rating Induction Motor 1750 HP 2250 HP 3000 HP 4500 HP Voltage (Max)

Auxiliary Contact Rating Induction Motor 1750 HP 2250 HP 3000 HP 4500 HP Voltage (Max) Cutler-Hammer Instructions for 26" Wide Vacuum-Break Starters Rated 200 and 400 Amperes, 7200 Volts, Stab-Connected with SL Contactor DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS MANUAL IN ITS EN-

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

HS1E Series Full Size Interlock Switch with Locking Solenoid

HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Series HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Key features include: Basic unit and solenoid unit in one housing Plastic Housing: Light weight Ease of Wiring: All the terminal

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information