1 Accessory Ultra-Violet Germicidal Lamps 40RM , 40RMQ and 40RMS Air Handler Units Installation Instructions Part Numbers: CRDBLFIX001A00, CRDBLFIX002A00, CRDBLFIX003A00, CRDBLFIX004A00, CRDBLFIX005A00, CRDBLFIX006A00 Use only specified high-output, low temperature bulbs with this accessory. Use of a lower wattage or incorrect bulb can result in damage to accessory or bulb. Correct bulbs have a blue end cap. SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform basic maintenance functions such as changing bulbs. All other operations should be performed by trained service personnel. When working on airconditioning equipment, observe precautions in the literature, tags and labels attached to the unit or accessory, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Before installing accessory or performing maintenance or service on accessory, turn off main power switch to unit. Electrical shock can cause injury or death. There may be more than one disconnect switch. Never expose eyes or skin to ultra-violet light from any source. After installation, provide an interlock to turn off germicidal lamps when access door is opened. Lamp must be off before entering HVAC unit to perform maintenance or service. Personal injury may result. Do not touch emitter glass without gloves. Damage to bulb may result. Oil from fingerprints will permanently etch glass of bulb and weaken structure. Clean bulb after handling. Bulb contains a small quantity of mercury. If a bulb breaks, clean and dispose of with care. GENERAL Carrier s commercial air handler ultra-violet germicidal lamps are designed to kill odor causing mold and fungus that may develop in the wet evaporator section of an HVAC unit. The high output, low temperature germicidal lamps are installed in the evaporator section of HVAC unit, and are pointed directly at the evaporator coil and condensate pan. The short wave length ultra-violet band light inhibits and kills mold, fungus, and microbial growth. The Carrier germicidal lamps have been specifically designed and optimized for 40 to 45 F, high-humidity operation in a moving airstream, inside an HVAC unit. The Carrier UV-C germicidal lamps have output ratings at 45 F in a 400 fpm airflow of 120 microwatts/cm 2 at a 1 meter range. Two service personnel are required for installation procedure. Germicidal lamp installation requires a separate, dedicated source of power. 40RM007, 40RM,RMQ,RMS008, 40RM,RMQ,RMS012 40RM014, 40RM,RMQ,RMS016, 40RM,RMS024 40RM028,034 AIR HANDLER UNIT PACKAGE USAGE UNIT ELECTRICAL CHARACTERISTICS FIXTURE QUANTITY PART NUMBER 115 vac, W, 50/60 Hz 2 CRDBLFIX001A00 208/230 vac, W, 50/60 Hz 2 CRDBLFIX002A vac, W, 50/60 Hz 2 CRDBLFIX003A vac, W, 50/60 Hz 2 CRDBLFIX004A00 208/230 vac, W, 50/60 Hz 2 CRDBLFIX005A vac, W, 50/60 Hz 2 CRDBLFIX006A vac, W, 50/60 Hz 3 CRDBLFIX004A00 208/230 vac, W, 50/60 Hz 3 CRDBLFIX005A vac, W, 50/60 Hz 3 CRDBLFIX006A00 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No Printed in U.S.A. Form 40RM-15SI Pg Replaces: New Tab 3c 2e
2 INSTALLATION Location The germicidal lamps are installed in the evaporator section, downstream of the cooling coil. A unit flange opposite the coil face is provided for mounting the germicidal lamps. A field-supplied junction box with a switch should be mounted to the exterior side of the corner channel of the fan section. The conduit hole in the rear of the junction box is aligned with the factory-provided knockout in the unit cabinet. Refer to Fig. 1 for lamp and junction box installation locations. See Fig. 2 for accessory dimensions. Verify site can be supplied with the necessary power requirements. Ensure that there is adequate clearance for service and bulb replacement. Installation Perform the following procedure to install the germicidal lamps: 1. Turn off all power to unit. Remove access panels to evaporator section. 2. Ultra violet light may damage certain plastics and exposed non-uvc protected wires. Wrap exposed plastic and wiring with aluminum tape or use metal conduit. A separate, dedicated, source power supply must be routed to the accessory germicidal lamp power supply per applicable codes. Unit wiring and control box connections should not be used. Refer to the Air Handler Unit Package Usage table for electrical characteristics of power supply. Power source must be a suitable fused, grounded, protected source with the correct voltage. Other voltages will permanently damage the germicidal lamp. It is recommended that the germicidal lamps be operated continuously. Wire per Table 1. Table 1 Wiring Recommendations WIRING Power Neutral Ground COLOR Black White Green 3. Place cardboard over the coils for protection. 4. Factory-supplied 90 degree, 18 gage (minimum), galvanized steel angles are required. Two angles are provided per accessory germicidal lamp. All angle dimensions and hole placements are shown in Fig. 3 and 4. Angles are required to attach germicidal lamps to unit mounting flange. 5. Install junction box. See Fig. 1. Install a 1/2-in. conduit nipple through the rear of the junction box at the knockout in the corner channel of the unit. Cut a 1/8- in. diameter hole in the unit insulation at the conduit nipple penetration for wire routing. Drill and install a no. 10 screw to provide additional support for junction box. Provide disconnect switch on junction box. Seal conduit penetration into unit at conduit nipple to prevent air intrusion. 6. Remove bulb from germicidal lamp if attached. DO NOT TOUCH GLASS ON BULB. Handle non-glass parts only. Remove cover from germicidal lamp. 7. Attach germicidal lamp to steel angle. Align top hole in rear of germicidal lamp with hole in steel angle. Bottom of germicidal lamp is the side with the UL label. Use a flat washer and no. 10 self-tapping screw to attach germicidal lamp to steel angle. See Fig. 4. Repeat to attach second angle to germicidal lamp using no. 10 self-tapping screw and washer. Two angles are used per accessory. Repeat procedure for all other germicidal lamps. 8. Using the angles attached to the germicidal lamps as a template, mark two drill holes on the unit mounting flange for the fixture furthest from the junction box. Refer to Fig. 5-7 for fixture locations specific to each unit size. Using no. 10 self-tapping screws, attach the fixture mounting angles (installed on the germicidal lamps in Step 7) to the mounting flange. Place second germicidal lamp adjacent to previously installed germicidal lamp. Verify that fixture is in correct position (conduit nipple can connect fixtures). Mark the mounting angle hole positions on flange. Drill holes and attach second germicidal lamp. Repeat procedure for remaining accessory germicidal lamps. Be careful not to drill into coil, refrigerant lines, or other objects inside the HVAC unit. Damage to unit can result. 9. Connect adjacent germicidal lamps with 1/2-in. conduit nipples and locknuts. 10. Wire germicidal lamps in series to junction box. See Fig. 8 for wiring to a single accessory. See Fig. 9 for multiple accessory applications. All field wiring external to the germicidal lamps and internal wiring within 3-in. of the germicidal lamp entrance and exit must be UV resistant, outdoor duty, 14 gage Romex wire or be jacketed in 1/2-in. conduit. Internal wiring further than 3-in. from germicidal lamp entrance or exit does not require the Romex protective sleeve. Reseal insulation hole at junction box wire penetration with a piece of aluminum tape. NOTE: Route all wiring through fixtures when possible. 11. Test all circuits. 12. Replace germicidal lamp covers and re-install bulbs. DO NOT TOUCH GLASS ON BULB. Grasp the bulb only by the bases (non-glass part). Clean the bulb using a lint free wipe and isopropyl alcohol. Fingerprints on bulb will permanently damage bulb. Push bulb into place until seated and rotate 90 degrees until two distinct clicks are heard. 13. Ensure safety equipment is being worn. WEAR SAFETY GLASSES AND COVER SKIN. Stand a safe distance away from bulb for viewing. Return power to unit. Accessory ultra-violet bulbs should glow with a blue hue. Turn off power when proper operation is verified. If bulb does not glow, check wiring, safety interlock, or replace bulb. 14. Remove cardboard placed in Step Re-install access panels. Turn on power to unit. 16. Affix the ultra-violet light hazard warning labels provided to the outside of the unit, in plain sight, on the access panels. See Fig. 10. Replace label when worn. 2
3 CORNER MOUNTED JUNCTION BOX (POSITIONED AT CONDUIT KNOCKOUT) 1/2" FLEX CONDUIT MOUNTING 90-DEGREE 90-DEGREE CONDUIT CONNECTOR Fig. 1 Germicidal Lamp Mounting Location 1.50" 2.00" A 1/2" 2.81" 1/2" FIXTURE MAY BE INSTALLED ON ANY ANGLE INLET BOTH ENDS 1 1/2" ACCESSORY PART NUMBER LENGTH (in.) DIMENSION A CRDBLFIX001A00 CRDBLFIX002A00 CRDBLFIX003A00 CRDBLFIX004A00 CRDBLFIX005A00 CRDBLFIX006A NO. 10 SELF TAPPING SCREW HOLES. TYPICAL OF /2" 1 1/2" Fig. 2 Accessory Dimensions Fig. 3 Mounting Angle 3
4 Bulb output can also be checked with a UVC radiometer. Replace bulb when output falls to 70% of initial reading. MOUNTING NO. 10 SELF-TAPPING SCREW 90 DEGREE WASHER INSTALLED INSIDE FIXTURE Use only specified high-output, low temperature bulbs with this accessory. Use of a lower wattage or incorrect bulb can result in damage to accessory or bulb. Correct bulbs have a blue end cap. The following bulbs can safely be used with this accessory: CRDBLTUB001A00 (16-in. tube, size units) CRDBLTUB002A00 (22-in. tube, size units) Other bulbs may plug into the accessory, but they should not be used. Non-approved bulbs will overheat bulb and power source. Normal operation temperature for the bulb is 80 F. Normal operation temperature for the power source is 125 F. UL LABELS AFFIXED TO BOTTOM Fig. 4 Germicidal Lamp Mounting Details MAINTENANCE Disconnect all power before performing any maintenance or service. Bulbs need periodic replacement to maintain design specifications. Replace bulbs after 6000 hours of operation or 1 year, whichever comes first. For best performance, replace bulbs at the beginning of each cooling season. OPERATION Ultra-violet lamps should be operated continuously from power source. Lamps should not be connected to indoor fan power source or any power source where lamps would be cycled more than twice per day. While lit, bulb color should be light blue. If bulb color changes to red or flickers, replace the bulb. Bulbs that are not light blue will not emit ultra-violet radiation and will not kill harmful bacteria or fungi. Fiberglass filter media are recommended for operation of HVAC when filters are exposed to ultra-violet lamps. Polyester or cotton filters are subject to ultra-violet degradation and are not recommended. 46 3/4" 4" 90 DEGREE 17 3/4" 2.81" MOUNTING ULTRAVIOLET NIPPLE 1/2" 90 DEGREE CONDUIT CONNECTOR TO JUNCTION BOX Fig. 5 Germicidal Lamp Installation 40RM,RMQ,RMS Units 4
5 86 3/4" 90 DEGREE 12" 24" 8" 2.81" MOUNTING ULTRAVIOLET 1/2" 90 DEGREE CONDUIT CONNECTOR BETWEEN S Fig. 6 Germicidal Lamp Installation 40RM,RMQ,RMS Units TO JUNCTION BOX 96 3/4" 90 DEGREE 14" 24" 2.81" MOUNTING ULTRAVIOLET NIPPLE 1/2" 90 DEGREE CONDUIT CONNECTOR Fig. 7 Germicidal Lamp Installation 40RM028 and 034 Units TO JUNCTION BOX WHITE BLACK GREEN TOP VIEW WHITE BLACK GREEN GROUND SIDE VIEW Fig. 8 Accessory Wiring 5
6 ULTRA-VIOLET FIXTURE NO. 1 ULTRA-VIOLET FIXTURE NO. 2 WHT WHT TO POWER SOURCE BLK BLK WHT TO OTHER FIXTURES BLK GROUND (GRN) GROUND (GRN) Fig. 9 Accessory Wiring Diagram for Multiple Lamp Installation! WARNING UVC EXPOSURE HAZARD Turn off power to UVC lights before servicing or repairing. This unit contains high energy ultraviolet C-band (UVC) germicidal lamps which can cause serious temporary eye and skin irritation. Never expose unprotected eyes or skin to the UVC light.! AVERTISSEMENT RISQUE D'EXPOSITION AUX UVC Couper l'alimentation des lampes UVC avant l'entretien ou les reparations. Cet appareil contient des lampes germicides haute energie a ultra-violets de bande C (UVC), qui peuvent causer l'irritation momentanee grave des yeux et de la peau. Ne jamais exposer les yeux ou la peau non proteges a la lumiere UVC. Fig. 10 Warning Label CU
7 7
8 Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No Printed in U.S.A. Form 40RM-15SI Pg Replaces: New Tab 3c 2e
Installation Instructions
N,MW03-110 Ultraviolet Germicidal Lamps Accessory Installation Instructions Part Numbers A-UVC-92000203 through A-UVC-92000265 Used in Cooling Coil Sections SAFETY CONRATIONS Installation and servicing
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Ultraviolet Single and Dual Germicidal Lamps 60 Hz Part Numbers: P103-UVLTT1LP1020A01, P103-UVLTT1LP3020A01, P103-UVLTT2LP1020A01, P103-UVLTT2LP3020A01 SAFETY CONSIDERATIONS Installation
More informationInstallation Instructions
Installation Instructions Accessory Ultraviolet (UV) Germicidal Lamp 1 & 2 Lamp Models 115-v & 208/230-v UV Lamp C03009 Fig. 1 Two Lamp Model UV Lamp NOTE: Read the entire instruction manual before starting
More informationWARNING Risk of property damage, injury, or death.
INDOOR AIR QUALITY PRODUCTS KITS AND ACCESSORIES 506412 01 10/09 Litho U.S.A. HEALTHY CLIMATE GERMICIDAL LIGHT KIT INSTALLATION & USER INSTRUCTIONS FOR HEALTHY CLIMATE GERMICIDAL LIGHT MODELS C1UVCL10B
More informationWARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
2 Please read the safety and installation instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Photo-catalytic Air Purifier. WARNING: FAILURE
More informationHARDWARE KIT INSTALLATION GLOVES
COIL MOUNT STEEL DUCT MOUNT DUCTBOARD MOUNT CLAMP PLATE Z-BRACKET PCO BRACKET SHIELDED LAMP ASSEMBLY ALSO INCLUDED BALLAST TECH MANUAL HARDWARE KIT INSTALLATION GLOVES Rev 1 Issued: 09/03/2014 SERVICE
More informationSafety, Installation and Service Manual Models 1952, 1953 & 1972
Ultraviolet Germicidal Lamps Model 1952 24 Rooftop Unit Model 1953 32 Rooftop Unit Model 1972 Rooftop Unit, Internal Mount Safety, Installation and Service Manual Models 1952, 1953 & 1972 READ AND SAVE
More informationModel: UV-16R/24 READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.
U V - AIRE AIR PURIFYING S YSTEM Model: UV-16R/24 ITEMS INCLUDED IN KIT: 1-24Volt UV-Aire Ballast Assembly 1-Mounting Base 1-Ultraviolet Lamp 6-Sheet Metal Mounting Screws 1-Instruction Sheet 1-Fiberglass
More informationUV-AIRE AIR PURIFYING SYSTEM
UV-AIRE AIR PURIFYING SYSTEM Model: UV-16/24 The UV-Aire unit is designed to emit powerful UVC Band light rays, which sterilize and reduce airborne microorganisms as they pass through a heating or air
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products 2 to 5 Tons Accessory Electric Heaters Cancels: IIK 564A-24-2 IIK 564A-24- -02 Installation Instructions Electric Heaters 5 20 kw NOTE: Read the entire instruction manual before
More informationInstallation Instructions Electric Heaters 5 20 kw
Small Packaged Products to 5 Tons Accessory Electric Heaters Cancels: IIK 564A--1 IIK 564A-- 11-01 Installation Instructions Electric Heaters 5 0 kw NOTE: Read the entire instruction manual before starting
More informationFOODSAFE IL INSTALLATION MANUAL
FOODSAFE IL INSTALLATION MANUAL STATUS UV LAMP 1 QUESTIONS ON INSTALLATION? CALL SANUVOX AT 1-888-726-8869 Version 06/2012 STATUS UV LAMP 1 2 FOODSAFE IL KIT INCLUDES E D I B C A A. High-Intensity UVC
More informationUltraviolet Systems RXIU-A02A, RXIU-A03A TREATMENT SYSTEMS
Ultraviolet Systems RXIU-A02A, RXIU-A03A TREATMENT SYSTEMS PRODUCT DATA FEATURES APPLICATION When installed in forced air heating and cooling systems, the Ultraviolet Systems kill airborne or surface micro-organism
More informationInstallation Instructions
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment
More informationBIO-FIGHTER 4Xtreme 21", 33", 45" Ultraviolet Light Systems
BIO-FIGHTER 4Xtreme 21", 33", 45" Ultraviolet Light Systems Installation & Operation Manual P/N 4Xtreme 21" #06159 4Xtreme 33" #06160 4Xtreme 45" #06168 GENERAL This product is designed to help disinfect
More informationUV100A Ultraviolet Systems UV100A1000 AND UV100A1018 AIR TREATMENT SYSTEMS UV100A1059 AND UV100A2008 SURFACE TREATMENT SYSTEMS
UV100A Ultraviolet Systems UV100A1000 AND UV100A1018 AIR TREATMENT SYSTEMS UV100A1059 AND UV100A2008 SURFACE TREATMENT SYSTEMS FEATURES PRODUCT DATA APPLICATION When installed in forced air heating and
More informationREAD AND SAVE THESE INSTRUCTIONS. ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner. Trion
READ AND SAVE THESE INSTRUCTIONS ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner Trion www.trioniaq.com Installation, Operation, & Maintenance Manual 1. Warranty 2. Safety & Warnings ComfortBreeze
More informationUNPACKING THE UNIT. Alcohol cleaning pad
MUV-403H MultiVoltage Oxidizing UVC System Installation & Maintenance Instructions UNPACKING THE UNIT Each unit is shipped with the 5 lamp installed and the germicidal lamp placed in a box with protective
More informationBIO-FIGHTER Triad FlexMount 1S and 2S Ultraviolet Light Systems
ON OFF ON OFF 250V/3 Amp Fuse Only BIO-FIGHTER Triad FlexMount 1S and 2S Ultraviolet Light Systems Installation & Operation Manual STD O3 Model 1S14 #06400 #06403 Model 1S16 #06401 #06404 Model 1S20 #06402
More informationIMPORTANT: SAFETY INSTRUCTIONS
MUV-401H GERMICIDAL AIR PURIFIER Installation & Maintenance Instructions UNPACKING THE UNIT Each MUV-401H germicidal air purifier is shipped with the germicidal lamp placed in a lamp box. Carefully remove
More informationInstallation & Maintenance of the Fresh-Aire UV Airborne Duct System for Commercial HVAC Systems. Parts Included. Optional Parts
Installation & Maintenance of the Fresh-Aire UV Airborne Duct System for Commercial HVAC Systems The Fresh-Aire UV Airborne Duct System is designed for installation into commercial HVAC system ducts for
More informationPHOTO-CATALYTIC AIR PURIFIER SYSTEMS
PHOTO-CATALYTIC AIR PURIFIER SYSTEMS Models: DUO-11/24, DUO-11/120, DUO-14/24, DUO-14/120, PCUV-16UA, DUO-16/24, DUO-16/120 *includes carbon filter ITEMS INCLUDED IN KIT: 1-24 Volt or 120 Volt UV-Aire
More informationIMPORTANT: SAFETY INSTRUCTIONS Important: Instructions de securité
MUV-401H MultiVoltage Germicidal Air Purifier Installation & Maintenance Instructions UNPACKING THE UNIT Each MUV-401H germicidal air purifier is shipped with the germicidal lamp placed in a lamp box.
More informationULTRAMAX AIR DISINFECTION SYSTEMS OWNERS GUIDE
Shown with ILS OPTION (Internal Bracket/Light Shield) Kit ULTRAMAX AIR DISINFECTION SYSTEMS OWNERS GUIDE Remote version shown Models: UMX-1224T/ UMX-1924T / UMX-12242T / UMX-19242T 24v Power Input with
More informationInstallation Instructions
8/0A,A,A,A,AJ,AK,AW,AY00-00 Power Exhaust, Barometric Relief, and Conversion Package Accessories Installation Instructions Power Exhaust Part Numbers: CRPWREXH0A00, CRPWREXH0A00, CRPWREXH0A00, CRPWREXH0A00
More informationIMPORTANT: SAFETY INSTRUCTIONS Important: Instructions de securité
MUV7-100DR MultiVoltage UVC System Installation & Maintenance Instructions UNPACKING THE UNIT Each unit is shipped with the germicidal lamps placed in a box with protective packaging. When handling lamps
More informationInstallation Instructions
30RAP010-150, 38APS05-065, 38APD05-130 Ground-Fault Interrupter Convenience Outlet Accessory Installation Instructions Part No. 30RA-900---058, 30RA-900---059 SAFETY CONSIDERATIONS Installation of this
More information21", 33", 45", & 61" Installation & Operation Manual
21", 33", 45", & 61" Installation & Operation Manual 120V 230V 277V XL 21" #06170 #06178 #06171 XL 33" #06172 #06179 #06173 XL 45" #06174 #06188 #06175 XL 61" #06176 #06189 #06177 FEATURES Reduces or prevents
More informationComplete Whole House Air Cleaning System Photronic Base Media Air Cleaner OWNERS GUIDE
Complete Whole House Air Cleaning System Photronic Base Media Air Cleaner OWNERS GUIDE Air Handler Base Models: 92-052, 92-053, 92-054 (small) 24VAC- 92-055, 92-056, 92-057 Models: 92-046, 92-047, 92-048
More informationFor safety and to ensure proper use carefully read the contents of this manual before operating or installing the unit.
NANO INDUCT Owner s Manual For use with models: NIND14, NIND9, NIND6 For safety and to ensure proper use carefully read the contents of this manual before operating or installing the unit. Thank You for
More informationUV-AIRE AIR PURIFYING SYSTEM
UV-AIRE AIR PURIFYING SYSTEM MODEL: UV-18X SAFETY CONSIDERATIONS This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or condition nor for use in the mitigation,
More informationFor safety and to ensure proper use carefully read the contents of this manual before operating or installing the unit.
NANO INDUCT Owner s Manual For use with models: NIND14, NIND9, NIND6 For safety and to ensure proper use carefully read the contents of this manual before operating or installing the unit. Thank You for
More informationInstallation Instructions
CRPWREXH08A0, CRPWREXH09A0, CRPWREXH08A00, CRPWREXH08A00 For Use With Horizontal EconoMi$er IV, EconoMi$er, or EconoMi$er X (W70) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... PACKAGE
More informationLIGHTSTICK / LIGHTSTICK PLUS Germicidal Ultraviolet Light
LIGHTSTICK / LIGHTSTICK PLUS Germicidal Ultraviolet Light Installation & Operation Manual This manual covers the following models: LightStick #19300 LightStick Plus #19301 GENERAL This product emits germicidal
More informationInstallation & Maintenance of the Fresh-Aire UV Tubular Rack System for Commercial Air Handler Systems
Installation & Maintenance of the Fresh-Aire UV Tubular Rack System for Commercial Air Handler Systems The Fresh-Aire UV Tubular Rack System is designed for installation into commercial air handling units
More informationPUREAIR AIR PURIFICATION SYSTEM PHOTOCATALYTIC OXIDATION (PCO) TECHNOLOGY
507477-01 4/2016 Supersedes 4/2015 AIR CLEANERS / FILTERS Litho U.S.A. PUREAIR AIR PURIFICATION SYSTEM PHOTOCATALYTIC OXIDATION (PCO) TECHLOGY INSTALLATION INSTRUCTIONS FOR PUREAIR AIR PURIFICATION SYSTEM
More informationCOILCARE PM. Installation Instructions and Operating Manual. CoilCare Series BioZone Scientific International, Inc.
COILCARE PM Installation Instructions and Operating Manual CoilCare Series 2017 BioZone Scientific International, Inc. 81200012B Thank you for purchasing BioZone Scientific s CoilCare ultraviolet light
More informationInstaller s Manual. PCO/UV N-Duct Model
Installer s Manual PCO/UV N-Duct Model FACTS ABOUT THE PCO/UV N-DUCT UNIT AirGorilla combines the power of two highly regarded contaminant fighting technologies - ultraviolet light and PCO (photocatalytic
More informationInstallation Instructions
265V Subbase Receptacle Accessory Kit For Use With Packaged Terminal Air Conditioner Installation Instructions INTRODUCTION These instructions cover the installation of the 265V Subbase Receptacle Accessory
More informationINSTALLATION, MAINTENANCE & OPERATION GUIDE. MODEL Sanuvair S300 WHOLE HOUSE HEPA/UV AIR PURIFIER. ITEM # Sanuvair S V EN
INSTALLATION, MAINTENANCE & OPERATION GUIDE MODEL Sanuvair S300 WHOLE HOUSE HEPA/UV AIR PURIFIER ITEM # 101275 Sanuvair S 300-120V EN SAFETY CONSIDERATIONS Installation and servicing or equipment can be
More informationInstallation Instructions
00A0, 0A0-0A0 080A00 08A00 For Use With Vertical EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY VERTICAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS TO5TON
More informationInstallation Instructions
010A00 011A00 014A00 SMALL ROOFTOP UNITS TWO POSITION OUTDOOR AIR DAMPER 2to15TONS (50/60 Hz) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS...
More informationInstallation, Start-Up and Service Instructions
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS.....................1,2 INSTALLATION................................ 2-31 Step 1 Complete Pre-Installation Checks.........................................
More informationINSTALLATION, START-UP AND SERVICE INSTRUCTIONS
INSTALLATION, START-UP AND SERVICE INSTRUCTIONS P705 Refrigeration Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................. 1 HANDLING.......................................
More informationTECHNICAL INFORMATION Puissant 30-Watt Shortwave UV Light Sources Catalog Nos. SKSUV30, SKSUV40
SIRCHIE Products Vehicles Training Copyright 2012 by SIRCHIE All Rights Reserved. TECHNICAL INFORMATION Puissant 30-Watt Shortwave UV Light Sources Catalog Nos. SKSUV30, SKSUV40 INTRODUCTION The SKSUV30
More informationEXPERIENCE THE NEW IAQ REFRESH YOUR AIR
EXPERIENCE THE NEW IAQ REFRESH YOUR AIR Indoor Air Quality The UV-C Story: Fresher, Purer Air The Bio-Fighter Germicidal UV system works 24 hours a day, 7 days a week, disinfecting cooling coils, drain
More informationInstallation Instructions
Installation Instructions Part No. 50DJ902791 48/50FP,JP,MP,NP 50FPX,FPY,JPX,JPY 50FB,JB,NB Accessory Outdoor-Air Cfm Kit CONTENTS GENERAL........................................ 1 INSTALLATION................................
More informationInstallation Instructions
08A0, 09A0, 08A00, 08A00 For Use With Horizontal EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY HORIZONTAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS
More informationInstallation Instructions
H068A00 H069A00 H070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 12.5to25TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION... 2 Power Exhaust
More informationMicroMetl INSTALLATION INSTRUCTIONS FOR 0689ZJ36EC
MicroMetl INSTALLATION INSTRUCTIONS FOR 0689ZJ36EC SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only
More informationELITE Series R-410A - Upflow / Horizontal
PRODUCT SPECIFICATIONS AIR HANDLERS CBX7UH ELITE Series R-0A - Upflow / Horizontal Bulletin No. 08 March 0 Supersedes October 0 Nominal Capacity -. to Tons Optional Electric Heat -. to kw MODEL NUMBER
More information2008 PCP COMPOUND APPLICATIONS GUIDE
2008 PCP COMPOUND APPLICATIONS GUIDE INTRODUCTION The Compound Populated Catalyst Panel (PCP Compound) is a combination of PCP Standard and Drop-In technologies. It may be used in conjunction with panels
More informationREAD AND FOLLOW ALL SAFETY INSTRUCTIONS 1. DANGER RISK OF SHOCK DISCONNECT POWER BEFORE INSTALLATION
UR Series LED Upgrade Kit Includes: 24" Linear Option IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND FOLLOW ALL
More informationInstallation Instructions
CRPWREXH068A00 CRPWREXH069A00 CRPWREXH070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 15 to 25 TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION...
More informationCRECOMZR054B00 CRECOMZR055B00. VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS WARNING TABLE OF CONTENTS
CRECOMZR05B00 CRECOMZR055B00 VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS TABLE OF CONTENTS PACKAGE USAGE...1 SAFETY CONSIDERATIONS...1 PACKAGE CONTENTS...1 GENERAL...2
More informationProduct Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm
Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA
More informationINSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS. Part Number: P DM
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Whole House Duct-Mount HEPA Air Cleaner Part Number: P102-400DM TABLE OF CONTENTS Page SAFETY CONSIDERATIONS...1 INTRODUCTION...1,2 INSTALLATION...2,3
More informationCSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440
CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440 APPLICATION SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE CSR compact fused interlocked ARKTITE
More informationIMPORTANT SAFEGUARDS
INSTRUCTION MANUAL NON-INTERRUPTIBLE AC INVERTER SYSTEM MODEL EAC FTM 350 FOR EMERGENCY LIGHTING POWER IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed,
More informationInstallation Instructions
GEMINI SELECT 38APS025-065, 38APD025-130 Air-Cooled Condensing Units with PURON Refrigerant (R-410A) 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................
More informationWiring Diagrams DIAGRAM INDEX
30HK040-060;30HL050,060;30HW018-040 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Wiring Diagrams DIAGRAM INDEX UNIT 30 VOLTAGE DIAGRAM TYPE FIGURE LABEL DIAGRAM All Component Arrangement
More informationSelf-Testing Industrial Series
Series: AS-I (Maint.-Free) Self-Testing Industrial Series Emergency Lighting Equipment Instructions for INSTALLATION OPERATION SERVICE SPECIFICATIONS 1300650 1300654 1300666 1300754 1300823 1300886 Hubbell
More informationInstallation Instructions
CRLOWAMB039A00 CRLOWAMB040A00 CRTRXKIT002A00 ACCESSORY MOTORMASTER I HEAD PRESSURE CONTROL KIT 12.5 TON HEAT PUMP Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PRODUCT USAGE... 2 SAFETY
More informationInstallation Instructions
Installation Instructions External Filter Rack KGAFR0301ALL NOTE: Read the entire instruction manual before starting the installation. INTRODUCTION The External Filter Rack is designed to fit on either
More informationIMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following:
ZR-RK Series LED Retrofit Troffer Kit Includes: ZR22RK and ZR24RK Standard and Emergency Luminaires IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed
More informationAPCO Rack System. A unique solution for the elimination of viruses, bacteria and VOC s. and saving energy FRESH-AIRE UV
FRESH-AIRE UV APCO Rack System A unique solution for the elimination of viruses, bacteria and VOC s 81cm - 117cm - 152cm UV-C lamps available and saving energy With the APCO Rack System it is also possible
More information4000 SYSTEM OPERATING MANUAL
4000 SYSTEM OPERATING MANUAL REV 1.4 COPYRIGHT 1996 Xenotech, Inc. PAGE 1 INSTRUCTIONS FOR REMOVING AND INSTALLING A TYPE XT XENON BULB IN A BL4000 FIXTURE NOTE FAMILIARIZE YOURSELF WITH THE LOCATION AND
More informationCPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h
CPC Commercial 15- & 20-Ton, Three-Phase Packaged Air Conditioner 15-Ton Cooling Capacity: 180,000 BTU/h 20-Ton Cooling Capacity: 240,000 BTU/h Contents Nomenclature...2 Product Features...3 Product Specifications...4
More informationT A A 120 S 4 D - 1 M
PRODUCT SPECIFICATIONS AIR HANDLERS TA T-CLASS SPLIT SYSTEM UNITS UPFLOW/HORIZONTAL - R-410A - 50 HZ Bulletin No. 490133 February 2013 Supersedes December 2010 180-240 Models 072-090-120-150 Models Noal
More informationMAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators
MAx-305 & MAx-38 Series MAx-405 Through MAx-49 Series Two-Position Actuators General Instructions Application For two-position operation of dampers, valves, and other equipment which require the return
More informationAdvanced PCO System. Installation Instructions & Consumer Information. Section I. Important Installer Information WARNINGS
Advanced PCO System Installation Instructions & Consumer Information Section I. Important Installer Information The Dynamic Advanced Photo Catalytic Oxidation (PCO) System utilizes the latest developments
More informationCRYSTAL-AIRE. concealed commercial air cleaners
CRYSTAL-AIRE concealed commercial air cleaners CRYSTAL-AIRE A Customized CONCEPT IN Concealed AIR CLEANING. Using a variety of accessories, Crystal-Aire can be adapted to most building configurations and
More informationACCUSTATION SUBMITTAL MATERIALS
ACCUSTATION SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE SIZE 06 = 06" DIAMETER 08 = 08" DIAMETER
More informationELITE SERIES R-410A Ready - Multi-Position
PRODUCT SPECIFICATIONS AIR HANDLERS CBXM ELITE SERIES R-0A Ready - Multi-Position Bulletin No. 0 October 07 Supersedes June 0 Nominal Capacity -. to Tons Optional Electric Heat -. to 0 kw MODEL NUMBER
More informationAir flow GUV-161. Box size is 8.25 high x 4.25 wide For service please call Germicidal UV-C Lamp. Furnace. 2.
TROUBLESHOOTING Under normal operation the LED should light when the unit has been supplied power. If the LED does not light: 1. Check to be sure there is power to the unit. 2. Be sure lamp connector is
More informationP RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS
P RO W ALL V ENTILATION H OODS INSTALLATION INSTRUCTIONS CONTACT INFORMATION Wolf Customer Service: 800-332-9513 Website: wolfappliance.com As you follow these instructions, you will notice WARNING and
More informationAsymmetrical Installation Instructions. Components: i2cove Asymmetrical LED Light Fixtures. 12 [305mm] [918mm] 48.
support@i2systems.com www.i2systems.com Electrical Specifications PARAMETER Input Power VALUE 8 Watts* / Ft Input Voltage 120-277V AC, 50/60 Hz Max. Fixture Run Length LED Color (CCT) 8 Watts: 120VAC:
More informationSpectron Industrial Series
1300650 1300654 1300666 1300754 1300823 1300886 Table B Constant Value per Voltage System Wire Size (Maximum Voltage Drop 5%) System 6 Volt 12 Volt 24 Volt Wire Size #12 #10 #8 #6 #12 #10 #8 #6 #10 #12
More informationINSTRUCTION MANUAL IMPORTANT SAFEGUARDS. When using electrical equipment, basic safety precautions should always be followed, including the following:
INSTRUCTION MANUAL IMPORTANT SAFEGUARDS SERIES D LIGHTING EQUIPMENT When using electrical equipment, basic safety precautions should always be followed, including the following: READ AND FOLLOW ALL SAFETY
More informationModel 8144NC Fresh Air Ventilator
Model 8144NC Fresh Air Ventilator Installation and Operating Instructions MOUNTING BRACKETS WIRE ENTRY LOCATION INTEGRAL PRESSURE PORTS (PORT ON INLET SIDE NOT SHOWN) OVAL OUTLET COLLAR FOR 6" DIAMETER
More informationThermoLite 110W-330W Solar Panel Installation Instructions
ThermoLite 110W-330W Solar Panel Installation Instructions INSTALL APPLICATIONS SUPPORTED BY THIS GUIDE: 1. Trailer Roof Top Mounted 2. Bus Roof Top Mounted 3. Tractor Fairing Mounted 40W and 110W Replacement
More informationInstallation Instructions
GEMINI SELECT 38APS025-050,38APD025-100 Air-Cooled Condensing Units with PURON Refrigerant (R-410A) 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................
More informationThermoLite 30W Solar Panel Installation Instructions
ThermoLite 30W Solar Panel Installation Instructions INSTALL APPLICATIONS SUPPORTED BY THIS GUIDE: 1. SB Unit (30W) 2. Precedent Unit (30W) 3. Carrier Trailer Unit (30W) 4. Test Procedure 401414-30W Solar
More informationInstallation Instructions
Motor Master ontrol Kit ancels: IIK 561A-18-1 IIK 561-18-1 11-95 Installation Instructions Part No. 32LT660004 and 005 This symbol indicates a change since last issue. INTRODUTION These instructions cover
More informationProduct Data. 40RUA 18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz
18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz Product Data 07 --- 12 C09035 Carrier s versatile packaged air-handling units satisfy design requirements with: S Multi-position design
More informationBAL3000 BAL3000. Fluorescent Emergency Ballast Lumens. Specification Sheet. Emergency Ballast 1/19/2012. Project: Catalog#: Approved by:
1/19/2012 Fluorescent 1450-3000 Lumens Works in conjunction with an AC ballast to convert new or existing fluorescent fixtures into unobtrusive emergency lighting Maintains illumination of one or two lamps
More informationThermoLite 40W Solar Panel Installation Instructions
ThermoLite 40W Solar Panel Installation Instructions INSTALL APPLICATIONS SUPPORTED BY THIS GUIDE: 1. Heat King (all models) 40W 2. Precedent Domestic Rail Container (DRC front skin mounted) 40W 3. Tractor
More informationDESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS
DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil
More informationHealthySole Plus System Owner s Manual
HealthySole Plus System Owner s Manual 1 2 DISCLAIMER DETECTO and HealthySole, LLC shall not be held liable for any improper or incorrect use of the information in the marketing material or technical documents
More informationInstallation Instructions
CAHZCOIL8A00 CAHZCOIL412A00 CAHZCOIL208A00 CAHZCOIL212A00 CAVTCOIL8A00 CAVTCOIL412A00 CAVTCOIL208A00 CAVTCOIL212A00 Installation Instructions DIRECT --- EXPANSION HORIZONTAL AND VERTICAL EVAPORATOR COILS
More informationWARRANTY. Air flow. (Please note standard off-the-shelf lamps are not compatible with this unit. Use of improper lamps will void warranty.
TROUBLESHOOTING Under normal operation the LED should light when the furnace blower is running. Both lamps operate from the same multivoltage ballast. If the LED does not light: 1. Check to be sure there
More informationA I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S
P R O D U C T S P E C I F I C AT I O N S A I R H A N D L E R S CB6UH-R MERIT Series R- - Upflow / Horizontal Bulletin No. 1067 April 01 Supersedes January 01 Nominal Capacity - 1.5 to 5 Tons Optional Electric
More informationCONGRATULATIONS. on your purchase of a Viridian Grip Laser, the most advanced sighting device available.
GRIP LASER MANUAL CONGRATULATIONS on your purchase of a Viridian Grip Laser, the most advanced sighting device available. IF YOU HAVE TECHNICAL OR SERVICE ISSUES WITH THIS LASER, DO NOT RETURN TO PRODUCT
More informationProduct Data. FNCCAB & FILCCFNC High Efficiency Fan Coil Filtration. Sizes 014, 017, 021 & 024. FNCCAB Filter Cabinet. FILCCFNC Media Filter
Product Data FNCCAB & FILCCFNC High Efficiency Fan Coil Filtration Sizes 014, 017, 021 & 024 FNCCAB Filter Cabinet FILCCFNC Media Filter Copyright 2004 Carrier Corporation Form FNCB-1PD FNCCAB Model number
More informationPro Island Ventilation Hoods
INSTALLATION GUIDE Pro Island Ventilation Hoods READ AND SAVE THESE INSTRUCTIONS Contents Wolf Pro Island Ventilation Hoods................. 3 Safety Instructions............................ 4 Installation
More informationInstructions for Mounting and Operation of the ARC Model XS Wall Xenon Light Source System
530 Main Street, Acton, MA 01720 Phone: (978)263-3584, Fax: (978)263-5086 Web Site: www.acton-research.com Instructions for Mounting and Operation of the ARC Model XS-432 75 Wall Xenon Light Source System
More informationMINISTICK TM UV Germicidal Ultraviolet Light
MINISTICK TM UV Germicidal Ultraviolet Light Installation & Operation Manual 120V - Part # 19400 230V - Part # 19401 GENERAL This product emits germicidal ultraviolet (UV-C) light to help disinfect the
More informationLED IMPORTANT SAFETY INSTRUCTIONS
LED IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION To reduce the risk of death, personal injury or property damage
More informationCP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions
CP-90 CP-90 Electronic Drives General Instructions Application The CP-90 and CP-90 electronic actuator drives process a variable input signal from a controller to provide proportional control of an electric
More informationInstallation Instruction ALG Series LED Area Light Version: 3.1
IMPORTANT SAFETY INSTRUCTIONS READ CAREFULLY BEFORE INSTALLING THE FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. To reduce the risk of death, personal injury or property damage from fire, electric
More information